MEMORIA DESCRIPTIVA
1. GENERALIDADES
2. AGUA POTABLE
2.1.2. DESAGUE
1
V ACI ASUMIDO = 79.70 m3
Entonces:
Por Hazen-Williams
S= 0.146
Hf = 6.27 m.
2
2.4.1. CALCULO HIDRAULICO DEL ALIMENTADOR DE AGUA
UH Q Diametro V Longitudes Equivalentes por accesorio Long.Tub Long. Tot. S HF Diferencia de Cotas Presion (m)
PISO UH
Acum. (lps) (pulg) (m/s) CODO hf TEE hf VALV hf (m) (m) (m) inicio final inicial final
Piso 7 157 157 2.12 1 1/2 1.86 1 1.554 0 0 1 0.328 1.00 2.88 0.091 0.26 18.30 17.70 10.00 10.86
Piso 6 93 250 2.84 2 1.40 0 0 1 4.091 0 0 2.70 6.79 0.039 0.26 17.70 15.00 10.86 13.82
Piso 5 93 343 3.53 2 1.74 0 0 1 4.091 0 0 2.70 6.79 0.058 0.39 15.00 12.30 13.82 16.91
Piso 4 118 461 4.48 2 1/2 1.41 0 0 1 5.154 0 0 2.70 7.85 0.030 0.24 12.30 9.60 16.91 19.85
Piso 3 93 554 5.05 2 1/2 1.59 0 0 1 5.154 0 0 2.70 7.85 0.038 0.30 9.60 2.90 19.85 26.85
Piso 2 118 672 5.89 2 1/2 1.86 0 0 1 5.154 0 0 2.70 7.85 0.050 0.39 2.90 4.20 26.85 25.94
Piso 1 81 753 6.22 3 1.37 0 0 1 6.136 0 0 2.70 8.84 0.023 0.20 4.20 1.50 25.94 28.84
Semisotano 81 834 6.81 3 1.49 0 0 1 6.136 0 0 3.00 9.14 0.027 0.25 1.50 -1.50 28.84 32.09
SOTANO 1 0 834 6.81 3 1.49 5 15.34 0 0 0 0 8.15 23.49 0.027 0.63 -1.50 -4.25 32.09 35.47
SOTANO 2 0 834 6.81 3 1.49 0 0 0 0 0 0 2.75 2.75 0.027 0.07 -4.25 -7.00 35.47 38.29
BOMBAS 0 834 6.81 3 1.49 5 15.34 3 18.408 1 0.648 8.30 42.70 0.027 1.15 -7.00 -9.75 38.29 42.19
Hf total= 4.14
3
2.4.2. Sistema de Bombas de Presion contante y Velocidad Variable
Qtotal = 6.8 lps
Qbombeo = 3.4 lps Hdt= 42.19 m. Pot.Aprox.= 3.146 HP
Impulsion = 3 plg Eficiencia = 60 %
Hg = 28.05 m
Hsalida = 10.00 m.
Hf = 4.14 m.
agua y equipos de bombeo en los cuadros 2.4.1 y 2.4.2:
medidores de agua (contometros) (uno por departamento).
Para el abastecimiento de agua de toda la edificación, se ha considerado el
4
De acuerdo con la tabla 2.6.1, se muestran las capacidades mínimas de
los calentadores para los departamentos, por razones prácticas hemos
considerado calentadores de 80 lts para cada departamento.
5
3.3.1. CALCULO HIDRAULICO DE LA MONTANTE ACI
Q Q Diametro V Longitudes Equivalentes por accesorio Long.Tub Long. Tot. S HF Diferencia de Cotas Presion (m)
PISO
(GPM) (lps) (pulg) (m/s) CODO hf TEE hf VALV hf (m) (m) m/m (m) inicio final inicial final
PISO 7 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 20.50 19.00 46.00 48.42
PISO 6 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 19.00 16.30 48.42 52.04
PISO 5 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 16.30 13.60 52.04 55.66
PISO 4 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 13.60 10.90 55.66 59.28
PISO 3 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 10.90 8.20 59.28 62.90
PISO 2 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 8.20 5.50 62.90 66.52
PISO 1 250 15.8 4 1.95 0 0 2 16.364 0 0 2.70 19.06 0.05 0.92 5.50 2.80 66.52 70.14
SOTANO 1 250 15.8 6 0.86 0 0 2 24.546 0 0 2.70 27.25 0.01 0.19 2.80 0.10 70.14 73.03
SOTANO 2 475 30.0 6 1.64 0 0 2 24.546 0 0 2.70 27.25 0.02 0.60 0.10 -2.70 73.03 76.43
SOTANO 3 475 30.0 6 1.64 2 12.276 3 36.819 0 0 2.70 51.80 0.02 1.14 -2.70 7.00 76.43 67.87
BOMBA ACI 475 30.0 6 1.64 4 24.552 5 61.365 2 2.59 24.50 113.01 0.02 2.49 7.00 -9.75 67.87 87.11
Hf total= 10.86
6
Qtotal = 475 GPM
volumen de reserva de 79.7 m3.
acuerdo con NFPA 13 y NFPA 14, con lo cual el volumen mínimo requerido
de ACI vienen en rangos (Ver NFPA 20 – Edificio 2019) tendremos que
# ROCIADORES Q Diametro V Longitudes Equivalentes por accesorio Long.Tub Long. Tot. S HF Dif. de Nivel Presion (m)
TRAMO
SIMULTANEOS (lps) (gpm) (pulg) (mm) (m/s) CODO hf TEE hf VALV hf (m) (m) (m/m) (m) inicio final inicial final
1-2 1 1.23 19.50 1 25 2.43 1 1.023 1 2.045 0 0 2.00 5.07 0.362 1.84 0.75 0.75 4.95 6.79
7
2-3 3 3.69 58.50 1 1/4 32 4.66 0 0 2 5.236 0 0 3.50 8.736 0.932 8.14 0.75 0.75 6.79 14.93
3-4 5 6.15 97.50 1 1/2 40 5.40 0 0 2 6.218 0 0 3.50 9.718 0.988 9.60 0.75 0.75 14.93 24.53
3.4. Calculo del sistema de Rociadores
4-5 7 8.61 136.50 2 50 4.25 0 0 2 8.182 0 0 3.50 11.682 0.454 5.30 0.75 0.75 24.53 29.83
5-6 9 11.07 175.50 2 50 5.46 0 0 2 8.182 0 0 3.42 11.604 0.723 8.39 0.75 0.75 29.83 38.22
6-7 12 14.76 234 2 80 7.29 0 0 2 8.182 0 0 2.20 10.382 1.231 12.78 0.75 0.75 38.22 51.00
7-8 12 14.76 234 2 80 7.29 0 0 1 4.091 0 0 6.36 10.451 1.231 12.87 0.75 0.75 51.00 63.87
8-9 12 14.76 234 2 80 7.29 0 0 2 8.182 0 0 3.03 11.211 1.231 13.80 0.75 0.75 63.87 77.67
9-10 12 14.76 234 3 80 3.24 0 0 1 6.136 0 0 2.07 8.205 0.171 1.40 0.75 0.75 77.67 79.07
10-11 12 14.76 234 3 80 3.24 0 0 1 6.136 0 0 2.38 8.511 0.171 1.46 0.75 0.75 79.07 80.53
11-12 12 14.76 234 4 100 1.82 0 0 2 16.364 2 1.728 1.30 19.391 0.042 0.81 0.75 0.75 80.53 81.34
12-13 12+Mangueras 30.00 475 6 150 1.65 0 0 1 12.273 0 0 1.13 13.398 0.022 0.29 0.75 0.75 81.34 81.63
13-14 12+Mangueras 30.00 475 6 150 1.65 0 0 1 12.273 0 0 2.80 15.073 0.022 0.33 0.75 -2.70 81.63 85.41
14-15 12+Mangueras 30.00 475 6 150 1.65 0 0 1 12.273 0 0 1.13 13.398 0.022 0.29 -2.70 -7.00 85.41 90.00
3.4.Descripción del Sistema de ACI y Componentes del Sistema de ACI
1. Cabe resaltar que para las tuberías de ACI que pasen bajo vigas o
colgadas bajo la losa, la distancia mínima entre la clave de la tubería y
el nivel de fondo de viga o losa, será de 1”.
2. El Hueco o pase dejado en la losa para la instalación de las montantes
de agua contra incendio, será de 6” para la montante de 4”, de esta
manera, la separación entre el pase y la tubería será de 1” y el espacio
vacío podrá rellenarse con masilla especial.
3. La Válvula de alivio de presión de cierre, deberá graduarse para abrirse
antes que la bomba llegue a presión de caudal 0, (presión de cierre) para
evitar que la bomba se dañe.
8
4. DESAGÜE
Q = 0.318 lps
S= 0.010 (10 %o)
D= 150 mm (6”)
Q Vpreliminar S Y
( mm ) ( lps ) ( m/s) ( o/oo) ( mm )
150 0.318 0.417 10.00 13.20
Entonces
9
4.2.1. Calculo del Caudal de bombeo
hallando K
K=Qmax.c/Qmin.c = 3.33
periodos de retencion asumidos al inicio (para que no se tenga un comportamiento de tanque septico se recomienda)
Pretension maximo = 14.00 min entonces a = Prmax/Prmin = 2.80
Pretension minimo = 5.00 min
hallamos los valores de K1
apartir de resolver la siguiente ecuacion
(k-a)K1^2+(a-K^2)K1+k(k-1)(a+1)=0
0.533 K1^2 + -8.311 k1 + 29.56 = 0.00
k1 = 10.092
k1" = 5.491
comprobacion de la respuesta 1 = 0.00
comprobacion de la respuesta 1" = 0.00
Qb = K1"xQmin.c = 8 lps
Qb = 7.79 lps
Vutil=Prmax(min)x60x(k-k1)xQmin.c(lps)/((k-k1-1)x1000) = 0.815 m3
V util = 0.80 m3
Error = 5.00 %
Pr.max= 13.75 minutos. Si cumple lo asumido en un inicio
Pr.min = 4.91 minutos. Si cumple lo asumido en un inicio
10
4.2.2. Calculo de la Tubería de Impulsión y Hdt
DATOS
Qtotal (lps) = 7.79 lps Hdt (m)= 17.73 m
Qb (lps) = 7.79 lps #.Bombas= 2 und
C.Llegada= 0.3 m Pot.Aprox. = 3.07 HP
C.Inicio = -11.45 m Efici.%= 60%
Hg = 11.75 m
Hf = 0.98 m
Ps(m) = 2.00 mca
c(coef )= 150
Long.Imp 32.00 m.
VERIFICAMOS VELOCIDADES
sabemos :
V = 1.974 xQb/(D^2)
D(pul) = 2.5 D(mm) = 63
D(pulg) D(mm) V(m/s) Q(lps) coef. long (km) hf (m) Ps (m) Hg (m) Hdt (m)
2 1/2 63.5 2.46 7.794 150 0.032 2.68 2.00 11.75 16.43
3 76.2 1.71 7.794 150 0.032 1.10 2.00 11.75 14.85
4 101.6 0.96 7.794 150 0.032 0.27 2.00 11.75 14.02
D(pulg) D(mm) V(m/s) Q(lps) coef. long (km) hf (m) Ps (m) Hg (m) Hdt (m)
2 1/2 63.5 4.92 15.588 150 0.032 9.67 2.00 11.75 23.42
3 76.2 3.42 15.588 150 0.032 3.98 2.00 11.75 17.73
4 101.6 1.92 15.588 150 0.032 0.98 2.00 11.75 14.73
11
electrobombas para drenaje sumergibles, con capacidad para Q = 4 lps. y
HDT= 15 m., cuya línea de impulsión de 3” descargará al sistema de
desagüe, cabe mencionar que el funcionamiento de las bombas será,
alternado y simultaneo en caso extremo (cuando se llega a 0.10 m. del nivel
máximo de desagüe).
Las cotas, dimensiones, ubicación de los elementos del sistema, así como
los demás detalles, se muestran en los planos correspondientes.