Está en la página 1de 3

REPUBLICA BOLIVARIANA DE VENEZUELA

UNIVERSIDAD RAFAEL URDANETA

FACULTAD DE INGENIERIA

CATEDRA: ACONDICIONAMIENTO AMBIENTAL

SECCION: A

PROFESOR: ELISEO GOVEA

CARGA TERMICA

Alumna:

María Claudia Fuentes CI: 28.000.015

Maracaibo, 01 de Noviembre del 2020


PRACTICA 1
CARGA TERMICA 2020C
Tabla 9.15. CARGA TERMICA
DESCRIPCION Btu/hr

INFILTRACION
HABITACION PRINCIPAL

1 OASHinf = 12.76 x (3.30 x 3.27 x 2.7) mt3 x 1 camb/ hr 371.77Btu/hr


2 OALHinf = 32.02 x(3.30 x 3.27 x 2.7)mt3 x 1 camb/hr 932.93Btu/hr
HABITACION 1

1 OASHinf = 12.76 x (3.30 x 3.30 x 2.7) mt3 x 1 camb/ hr 375.18Btu/hr


2 OALHinf = 32.02 x(3.30 x 3.30 x 2.7)mt3 x 1 camb/hr 941.48Btu/hr
HABITACION 2
1 OASHinf = 12.76 x ( ( (3 x 3.27)- 1) x 2.7) mt3 x 1 camb/ hr 303.52Btu/hr
2 OALHinf = 32.02 x ( ( (3 x 3.27)- 1) x 2.7) mt3 x 1 camb/hr 761.65Btu/hr
PASILLO
1 OASHinf = 12.76 x ( ( (3 x 0.9)+ 1) x 2.7) mt3 x 0.5 camb/ hr 63.74Btu/hr
2 OALHinf = 32.02 x ( ( (3 x 0.9)+ 1) x 2.7) mt3 x 0.5 camb/hr 159.94Btu/hr
COCINA/SALA
1 OASHinf = 12.76 x ( 6.7 x 3 x 2.7) mt3 x 1.5 camb/ hr 1038.73Btu/hr
2 OALHinf = 32.02 x ( 6.7 x 3 x 2.7) mt3 x 1.5 camb/hr 2606.59Btu/hr
LAVADERO
1 OASHinf = 12.76 x ( 3.27 x 1.40 x 2.7) mt3 x 1 camb/ hr 157.72Btu/hr
2 OALHinf = 32.02 x ( 3.27 x 1.40 x 2.7) mt3 x 1 camb/hr 395.78Btu/hr
VENTILACION
5 OASHven = 21.60 x 10CFM/Pers x 15 pers 3240Btu/hr
6 OALHven = 54.41 x 10CFM/Pers x 15 pers 8161.5Btu/hr
VIDRIO (CONDUCCION+CONVECCION)Q= AREA x U x T
7 Q sensible = (1.23x 1.2) x 0.54 x 215.28)x6 1029.54Btu/hr
VIDRIO(RADIACION)Q= AREA x Fs x SHGF
9 Qne= (1.23 x 1.2 x 2) x 0.81 x 251.23 600.72Btu/hr
11 Qse= (1.23 x 1.2) x 0.81 x 251.23 300.36Btu/hr
13 Qsw= (1.23 x 1.2 x 2) x 0.81 x 1457.97 3486.18Btu/hr
15 Qnw= (1.23 x 1.2) x 0.81 x 1888.96 2258.37Btu/hr
CARGA TERMICA PAREDES Q= AREA x U x T
17 Qne= 4.2 x 2.7 x 0.232 x 258.55 680.21Btu/hr
19 Qse= 8.76 x 2.7 0.232 x 258.55 1418.73Btu/hr
21 Qsw= 4.2 x 2.7 x 0.232 x 466.62 1227.62Btu/hr
23 Qnw= 8.58 x 2.7 x 0.232 x 540.99 2907.58Btu/hr
CARGA TERMICA TECHO Q= AREA x U x T
24 Q= 69 x 0.271 x 372.96 6973.98Btu/hr
PRACTICA 1
CARGA TERMICA 2020C

CARGA TERMICA TABIQUE Q= AREA x U x T


25 Q= 60 x 0.232 x 107.64 1498.35Btu/hr
CARGA TERMICA PUERTAS DE MADERA Q= AREA x U x T
26 Qint= (0.7 x 2.1) x 2 x 0.116 x 107.64 36.71Btu/hr
27 Qext=(0.9 x 2.1) x 1 x 0.430 x 215.28 174.96Btu/hr
CARGA TERMICA PISO Q= AREA x U x T
28 Qpiso= 69 x 0.213 x 157.20 2310.37Btu/hr
CARGA TERMICA PERSONAS
29 Qsensible= 200 x 15pers 3000Btu/hr
30 Qlatente= 250 x 15pers 3750Btu/hr
CARGA TERMICA LUCES
31 Qincandescente= 180+100+100+60 vatios x 3.41 1500.4Btu/hr
32 Qfluorescente= 180+100+100+60 vatios x 4.09 1799.6Btu/hr
33 Qnorma= 14 vatios/m2 x 69m2 x 3.41 3294.06Btu/hr
CARGA TERMICA EQUIPOS
34 Qs equipos= 4.250+(3100 x 4 + 8100) x 0.40 + 1075 14155Btu/hr
35 Ql equipos= (1700x4 +4000) x 0.40 4320Btu/hr
36 Qartefactos= 500 vatios x 3.41 Btu/hr-vatio 1075Btu/hr
CALOR TOTAL EN BTU/HR GTH
41 1+2+3+4+5……..+36 78308.27Btu/hr
CALOR TOTAL EN TON DE REFRIGERACION
42 78308.27/12000 6.53=7ton
43 Mt2/ton = 69/7 9.86

También podría gustarte