OPCIÓN 1 :

D= 0.3 m

ΔL (m) ϒ (g/cm3) Presión efectiva (Kg/cm2) Perímetro*ΔL (cm2) φ (°) C (kg/cm2) Ko k 𝜹 (°) f (kg/cm2) s (kg/cm2) Qs (KN)
1.200 1.660 0.792 0.079
0.800 1.830 1.456 0.146 7539.822 32.000 0.000 0.470 0.385 27.200 0.022 1.647
0.500 1.830 1.871 0.187 4712.389 33.000 0.000 0.455 0.373 28.050 0.033 1.530
4.100 1.870 5.438 0.544 38641.590 0.000 0.255 0.000 0.000 0.000 0.204 77.283
5.400 Qs= 80.460

FS= 3.000
e= 0.700
Wpilote= 0 KN
Ap= 0.071 m2
c= 25.000 KN/m2

Qp= 15.904 KN

196.200 KN Carga total al grupo de pilotes


8.726 Nro de pilotes ENTONCES SE NECESITARÍA 9 PILOTES
196.200 KN

OPCIÓN 2 :
D= 0.3 m

ΔL (m) ϒ (g/cm3) Presión efectiva (Kg/cm2) Perímetro*ΔL (cm2) φ (°) C (kg/cm2) Ko k 𝜹 (°) f (kg/cm2) s (kg/cm2) Qs (KN)
1.200 0.000 0.000 0.000
0.800 1.830 0.664 0.066 7539.822 32.000 0.000 0.470 0.385 27.200 0.007 0.486
0.500 1.830 1.079 0.108 4712.389 33.000 0.000 0.455 0.373 28.050 0.017 0.802
4.100 1.870 4.646 0.465 38641.590 0.000 0.255 0.000 0.000 0.000 0.204 77.283
5.400 Qs= 78.571

FS= 3.000
e= 0.700
Wpilote= 0 KN
Ap= 0.071 m2
c= 25.000 KN/m2

Qp= 15.904 KN

196.200 KN Carga total al grupo de pilotes


8.900 Nro de pilotes ENTONCES SE NECESITARÍA 9 PILOTES
196.200 KN
DATOS DEL PROYECTO
Centro Comercial (Edificio Tipo C), ubicado en Chimbote.

Edificio tipo C
FSL Mínimo 1
Lat: -9.3-° y LONG: -78.49°

Mw (Magnitud Momento) = 8

Pa (kg/cm2) 1.033

NF = 0.9m de la superficie

1. Calcular el potencial de licuefacción por los métodos determinístico.

Aceleración máxima obtenida del mapa de isoaceleraciones


PGA= 0.45 g

Factor de escala de magnitud


MSF= 0.98 ≤ 1.13

CRR M= 7.5 M=8

Presión VERIFICAMOS SI CUMPLE


Prof. representativa Presión total CRR
Profundidad de ensayo (m) SUCS CF% Nspt efectiva CN CR N1 (60) rd CSReq alpha beta N160cs CRR sin corregir a/g FS EL FSL TABLA 13A
(m) (REAL) Kg/cm2 corregido
Kg/cm2 Norma - E050
1.00 - 1.45 1.3 SM 15 6 0.1867 0.2267 1.7 0.7500 7.6500 0.9901 0.3516 2.4982 1.0481 10.5161 0.1277 0.1251 0.1570 0.3557 No Cumple
2.00 - 2.45 2.3 SM 15 6 0.2687 0.4087 1.7 0.7500 7.6500 0.9824 0.4371 2.4982 1.0481 10.5161 0.1277 0.1251 0.1263 0.2862 No Cumple
3.00 - 3.45 3.3 SP 4 8 0.3516 0.5916 1.7 0.8000 10.8800 0.9748 0.4797 0.0000 1.0000 10.8800 0.1310 0.1283 0.1180 0.2674 No Cumple
4.00 - 4.45 4.3 SP 4 12 0.4366 0.7766 1.5382 0.8500 15.6895 0.9671 0.5032 0.0000 1.0000 15.6895 0.1771 0.1734 0.1522 0.3447 No Cumple
H1= 0.577 m x1= 0.150 m Sección Fvertical (KN) Fhorizontal (kN) Brazo (m) Momento f. estabilizantes (KN.m) Momento f. destabilizantes (KN.m)
H2= 6.000 m x2= 0.500 m 1.00 21.222 0.925 19.630
H3= 0.600 m x3= 0.500 m 2.00 24.759 0.733 18.157
H= 7.177 m x4= 2.500 m 3.00 49.518 1.750 86.657
B= 3.500 m Df= 1.400 m 4.00 315.000 2.250 708.750
ϒ concreto= 23.580 KN/m3 5.00 15.146 2.667 40.390
𝜹= 17.000 ° 6.00 44.037 3.500 154.129
6.00 190.744 2.392 456.324
Presión efectiva en la base
ΔL (m) ϒ (KN/m3) φ (°) C (kN/m2) β (°) k (KN/m2) P (kN) Ph (kN) Pv (kN) 469.682 190.744 1027.712 456.324
LADO ACTIVO 0 21.000 30.000 13.000 0.362 0.000
7.177 21.000 30.000 13.000 0.362 54.553 195.762 190.744 44.037
LADO PASIVO 0.000 21.000 20.000 40.000 2.040 0.000 ∑ Fzas resistentes= 310.950 KN 269.596 KN
1.400 21.000 20.000 40.000 2.040 0.000 0.000

FS (volcamiento)= 2.252 ˃ 2 CUMPLE


FS (deslizamiento)= 1.413 ˃ 1.5 NO CUMPLE

TAMBIÉN SE PUDO HABER CONSIDERADO EL PESO DEL SUELO EN EL LADO ACTIVO, PERO POR NO TENER EFECTO CONSIDERABLE TAMBIÉN SE DESPRECIÓ,
SIMILAR AL EMPUJE ACTIVO