Análisis de Sistemas de
Protección empleando
DIgSILENT PowerFactory

Copyright © 2009. http:www.fglongatt.org.ve


Francisco M. Gonzalez-Longatt, PhD
Jairo H. Quiros Tortos. Ph.D. Researcher
Manchester, UK, Enero, 2011
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 1/23
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Análisis de Sistemas de Protección
empleando
DIgSILENT PowerFactory

Copyright © 2009. http:www.fglongatt.org.ve


Mostrar los aspectos teoricos del analisis de sistemas de
proteccion empleando la herramienta DigSILENT
PowerFactory
Francisco M. Gonzalez-Longatt, PhD,
Jairo H. Quiros Tortos. Ph.D. Researcher
fglogatt@fglongatt.org.ve, jquiros@eie.ucr.ac.cr
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 2/23
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
Protección
1. Introducción a los Sistemas de

3/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Objetivos de los Sistemas de Protección
• Prevenir lesiones a las personas.

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Minimizar el daño en los componentes del
sistema.

• Limitar la duración y minimizar las


interrupciones del servicio.

Copyright © 2009. http:www.fglongatt.org.ve


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 4/23
Aspectos de Sistemas de Protección
• Confiabilidad

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
– Propiedad de garantizar un funcionamiento correcto de la
protección. Incluye operar cuando se requiere
(dependebilidad) y no operar incorrectamente (seguridad).
• Selectividad
– Eliminar la falla o anomalía mediante la desconexión del
menor número de elementos.
• Velocidad de Operación
– Desconexión de la falla en el menor tiempo posible.
• Simplicidad
– Mínimo de dispositivo de protección y circuitería asociados

Copyright © 2009. http:www.fglongatt.org.ve


para lograr los objetivos de protección.
• Sensibilidad
– Detección de fallas o condiciones anormales que
provoquen variaciones pequeñas en el sistema.
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 5/23
Anormalidades en SP
• Las anormalidades en sistemas de

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
potencia son miles, pero pueden ser
agrupadas en:
– Cortocircuitos
– Sobrecargas
– Contactos a tierra
– Interrupción de conductores

Copyright © 2009. http:www.fglongatt.org.ve


– Déficit de potencia activa
– Poleslip (Perdida de estabilidad)

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 6/23


Criterio de deteccion de falla
Criterio de Detección de falla:

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Sobrecorriente (cortocircuito, sobrecarga)

• Corriente diferencial (cortocircuito).

• Sobre voltaje/Bajo voltaje (cortocircuito, estabilidad de voltaje)

• Dirección de potencia (cortocircuito, contacto a tierra)

• Desbalance (interrupción de conductor, desbalance de


carga).

Copyright © 2009. http:www.fglongatt.org.ve


• Impedancia (cortocircuito, perdida de estabilidad).

• Frecuencia (déficit de potencia activa)

• Temperatura (sobrecarga)
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 7/23
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
Transformador de Potencial (TP)
2. Transformadores de Corriente (TC) y

8/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Clasificación de los TC
Clases de predicción por IEC:

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
ejemplo: 15VA Clase 10 P 20

 15VA : Burden in VA
 10 : Clase de precisión
P : Aplicación: P para “Protección”
 20 : Accuracy Limit Factor (factor limite de precisión)
(hasta 10% de error a 20 veces la corriente nominal o

Copyright © 2009. http:www.fglongatt.org.ve


burden)

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 9/23


Clasificación de los transformadores
• Definición según ANSI/IEEE:

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Ejemplo: T100 o C 100
 ‘T‘ indica que el desempeno del TC ha sido probado:
Fabricantes pueden proveer pruebas y datos medidos.
 ‘C‘ indica que el desempeno ha sido calculado.
 Numero que define el maximo voltaje en el secundario a
el cual el error es menor a 10%, para corrientes entre 1-
Number defines the maximum secondary voltage at
which the error is less than 10%, for currents between 1-

Copyright © 2009. http:www.fglongatt.org.ve


20 veces la corriente secundaria.

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 10/23


Saturación del Transformador de Corriente
 Los transformadores de corriente (TC) se pueden

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
saturar si:
 Voltaje AC secundario es mas alto que el voltaje del codo
(kneepoint).
 Corriente primaria contiene componentes DC.

 La corriente secundaria de un TC saturado es


distorcionada y mas pequena de la corriente no
saturada.
 TC especiales con caracteristicas dinamicas mejorasas

Copyright © 2009. http:www.fglongatt.org.ve


son clasificados segun la norma IEC como TPX,TPY o
TPZ

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 11/23


CT Saturacion

DIgSILENT
1200.0

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
800.00

400.00

0.000

-400.00

-800.00

-1200.0
-0.1000 0.000 0.100 .. 0.200
Stromwandler: Mag.-Fluss L1 in V

1200.0

800.00

400.00

0.000

-400.00

-800.00

-1200.0
-0.1000 0.000 0.100 .. 0.200
Stromwandler: Mag.-Fluss L2 in V

Copyright © 2009. http:www.fglongatt.org.ve


1200.0

800.00

400.00

0.000

-400.00

-800.00

-1200.0
-0.1000 0.000 0.100 .. 0.200
Stromwandler: Mag.-Fluss L3 in V

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 12/23


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
3. Proteccion contra Sobrecorrientes

13/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Característica de tiempo definido

DIgS ILE NT
10

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
I>

• Tiempo total de limpieza de


[s]
falla (Tcf):
Tfc = Trelay + Tbrk
1
I>> Trelay: tiempo de disparo del rele
Tbrk : Tiempo de disparo del interruptor
• Tiempo de disparo del rele
(Trelay):
Tfct=Trelay+Tbrk

0.1

Trelay = Ts + Tset

Copyright © 2009. http:www.fglongatt.org.ve


Ts: tiempo de arranque
Tfct=Trelay+Tbrk Tset: tiempo ajustado
• Ajuste de corriente
0.01
1000
I>/I>>
10000 [pri.A] 100000 I > und I >> Ajuste de corriente de
arranque
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 14/23
Característica de tiempo inverso

DIgSILENT
10
• Tiempo total de limpieza de

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Imin
Ipset falla (Tcf):
[s]

Tfc = Trelay + Tbrk


1
Trelay: tiempo de disparo del rele
Tbrk : Tiempo de disparo del interruptor
• Tiempo de disparo del rele
Tpset (Trelay):
0.1 Trelay = Ts + Tset
Ts: tiempo de arranque

Copyright © 2009. http:www.fglongatt.org.ve


Tfct=Trelay+Tbrk Tset: tiempo ajustado
• Ajuste de corriente
0.01
Ipset: rango de corriente ajustada
1000 10000 [pri.A] 100000
AMZ
Imin: Corriente de arranque

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 15/23


Características - IEC
• Normalmente Inverso: 0.14
t = Tpset ⋅

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
( I / I pset ) 0.02 − 1
13.5
• Muy Inverso: t = Tpset ⋅
( I / I pset ) − 1

80
• Extremadamente Inverso: t = Tpset ⋅
( I / I pset ) 2 − 1

Copyright © 2009. http:www.fglongatt.org.ve


120
• Inverso Largo: t = Tpset ⋅
( I / I pset ) − 1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 16/23


Características - ANSI / IEEE

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
 8.9341 
t = Tpset ⋅  + 0.17966 
• Normalmente inversa  ( I / I ) 2,0938 − 1
 pset


 0.2663 
t = Tpset ⋅  + 
• Inverso corto  ( I / I )1.2969 − 1
 pset
0 . 03393


 5.64143 
• Largamente inversa t = Tpset ⋅  + 2.18592 
 (I / I ) −1 
 pset 
 
• Moderadamente inversa t = Tpset ⋅ 
0.0103
 (I / I ) −10 . 02
+ 0.0228 

 pset 
 3.922 
• Muy inversa t = Tpset ⋅ 
 (I / I )2 −1
+ 0 . 0982 

 pset 
 
• Extremadamente inversa t = Tpset ⋅ 
5.64
 (I / I )2 −1
+ 0.0243

 pset 
• Inversa definidad  0.4797 
t = Tpset ⋅  

Copyright © 2009. http:www.fglongatt.org.ve


+ 0 .21359
 ( I / I )1.5625 − 1 
 pset 
• Corriente cuadrada t=
50.7 ⋅ Tpset + 10.14
( I / I pset ) 2

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 17/23


Infeed
t
A

A-B
t=1.2 s

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009


B
t= 0.8 s

B-C
Coordinacion por Tiempo

C
t= 0.4 s

C-D

D
18/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Infeed
t
A

A-B

lmax(0.8*LAB)

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009


B

lmax(0.8*LBC)
B-C

C
C-D

lmax(0.8*LCD)
Coordinación Tiempo/Corriente

D
19/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Fusibles

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Máximo tiempo de
liberación de falla
Max. Melt Curve

Mínimo tiempo de
liberación de falla

Min. Melt Curve

Copyright © 2009. http:www.fglongatt.org.ve


Average Melt Curve

Fuse 1 Fuse 2

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 20/23


Interruptores de Bajo Voltaje

DIgSILENT

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Ir Tiempo largo de
retardo por
1000 proteccion de • Tiempo largo con retardo
tr sobrecarga
por protección de
[s] sobrecarga
Tiempo corto con
Im retardo por cortocircuito

10
• Tiempo corto con retardo
tm
por cortocircuito – con o
I²t on/off
sin característica I²t
0.1
Protección instantánea I

Copyright © 2009. http:www.fglongatt.org.ve


contra cortocircuito
• Protección instantánea
contra cortocircuito

0.001
1000 10000 [pri.A] 100000
LV-Breaker

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 21/23


Caracteristicas de Arranque de Motores

DIgSILENT
100

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
[s]
• Característica de
tcold Sn
arranque I n =
10
3 ⋅U n
thot
I a Corriente nominal
tstart t startCorriente de arranque
1
I p Corriente de magnetización (Inrush)
In tinrush Duración de la corriente de Inrush

Limite térmico
Ip tcold bajo condiciones frías

Copyright © 2009. http:www.fglongatt.org.ve


0.1
t hot bajo condiciones calientes
tinrush
Ia
0
1000 [pri.A] 10000
M otor - 1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 22/23


Curva Limite de Cables

DIgSILENT
10

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Capabilidad térmica
[s]
Ithr Tkr
I th < I thr con 0.01s ≤ Tk ≤ 10s
Tk
Tkr I thr Corriente de cortocircuito
1

Tkr Periodo nominal(1s)

Tk Tiempo de liberación de falla

• Corriente de
Ip magnetización
0.1

Ip
Corriente de magnetizacion

Copyright © 2009. http:www.fglongatt.org.ve


tinrush (Inrush)
tinrush Duración de la corriente de
Inrush

0.01
100 10000 [pri.A] 100000
Cable-1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 23/23


Curva limite de cales/ Parámetros de líneas

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
IEC/VDE ANSI/IEEE
k⋅A k⋅A
=I th < I thr Fac con 0.01s ≤ Tk ≤ 10s =I th < I thr Fac con 0.01s ≤ Tk ≤ 10s
Tk Tk

 ϑ f − ϑi  ϑ f + 234
k =226 ⋅ ln 1 +  para Cu =k 0.0297 ⋅ log10 para Cu
 234.5 + ϑi  ϑi + 234

 ϑ f − ϑi  ϑ f + 228
k=
148 ⋅ ln 1 +  para Al =k 0.0125 ⋅ log10 para Al
 228 + ϑi  ϑi + 228

k k constante de aislamiento
constante de aislamiento
ϑi Temperatura inicial ϑi Temperatura inicial
ϑf Max. Temperatura alcanzable ϑf Max. Temperatura alcanzable

Copyright © 2009. http:www.fglongatt.org.ve


A Área transversal in mm² A Área transversal in mm²
Tk Tiempo de liberación de falla Tk Tiempo de liberación de falla
Fac Relación del efecto piel Fac Relación del efecto piel

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 24/23


Curva de Sobrecarga de Cables

DIgSILENT
10000
In

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Sobrecarga (for t > 10s )
[s]
2
 I 0  − tτb
1−   e
I < In  Ib  para corta operacion
tb
1000 −
1− e τ

In Corriente nominal en A
I0 Corriente de prefalla en A
100 tb Tiempo de sobrecarga en s
τ Mínimo constante de tiempo

Copyright © 2009. http:www.fglongatt.org.ve


del cable

10
100 1000 [pri.A] 10000
Cable-1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 25/23


Curva de Transformadores ANSI/IEEE - Cat. I/II

DIgSILENT
10000

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
[s]
Sn = 1MVA (10kV)
• Curva de limite térmico
1000
– Categoría I (0.15 - 0.5
MVA)
100
térmica – Categoría II (0.501 - 5
MVA)
• Curva de limite mecánico
mecánica
10
– Categoría II (0.501 - 5
MVA)
Ip

Copyright © 2009. http:www.fglongatt.org.ve


12 10 8 7 5 4 uk in %
1 • Corriente de
tinrush
Sn = 0,1 MVA (10kV)
magnetización
Ip Corriente de magnetización
0.1
10 100 1000 [pri.A] 10000
tinrush Duración de la corriente de
Category I Category II
magnetización

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 26/23


Curva de Transformadores ANSI/IEEE Cat. III/IV

DIgSIL ENT
10000

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
[s] Sn = 10 MVA (110kV) • Curva de limite térmico
thermal – Categoría III (5.001 - 30
1000 MVA)
Sn = 50MVA (110kV)
– Categoría IV ( > 30 MVA)

100
mechanical • Curva de limite mecánico
– Categoría III (5.001 - 30
MVA)
10 – Categoría IV ( > 30 MVA)

Copyright © 2009. http:www.fglongatt.org.ve


uk in % 12 10 8 7 5 4 12 10 8 7 5 4
• Curvas de cambio de fase
1
100 1000 [pri.A] 10000
ANSI
Category III Category IV

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 27/23


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
4. Protección de Distancia

28/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Relés de Impedancia: Principio de Operación

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
I
Arranque/ Elementos
Medición/ Zonas de
Detección Auslöse- Tempo-
Auslöse-
filtración disparo
Auslöse- Auslöse-
U falla zonen rizados
zonen
zonen zonen

Disparo
Logica de salida

Copyright © 2009. http:www.fglongatt.org.ve


1/10/2011

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 29/23


Medición de Impedancia
• Lazo de falla Línea - Línea

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Z L I L1 − Z L I L 2 = U L1− L 2
U L1− L 2
ZL =
I L1 − I L 2

ZL

IL 2 ZL

Copyright © 2009. http:www.fglongatt.org.ve


UL1−L2 IL 1 ZL

ZE

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 30/23


Medición de Impedancia
• Lazo de falla Línea - Tierra ZL

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Z L I L1 − Z E I E = U L1− E ZL

U L1− E IL 1 ZL
ZL =
ZE
I L1 − ⋅IE UL1−E IE ZE
ZL
• K0 es independiente de la posición de la falla:
ZE
k0 =

Copyright © 2009. http:www.fglongatt.org.ve


ZL

1/10/2011

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 31/23


Elemento Direccional/Polarizacion

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
X

vorwärts inductivo
induktiv
adelante
Z

R
α

Copyright © 2009. http:www.fglongatt.org.ve


atras
rückwärts
capacitivo
kapazitiv

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 32/23


G1
ZG1

ZG1
S1
F2

F1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009


Relais

R
ZL+ZG2
F1

ZL

F2
ZG1
X

ZL+ZG2

S2
Elemento Direccional/Polarizacion

R
ZG2
G2

33/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Coordinación Impedancia Tiempo

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
DIgSILENT
A B C D

Z1 = (0.8...0.9)*ZAB

Copyright © 2009. http:www.fglongatt.org.ve


Z2 = 0.8*(ZAB + (0.8...0.9)*ZBC)

Z3 = 0.8*(ZAB + 0.8*(ZBC+ (0.8...0.9)*ZCD))

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 34/23


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
5. Esquemas de teleprotección

35/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
R1
R1
Lógica

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009


Comparación de Senales

R2
Lógica
R2

36/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
PUTT con detección de falla
(Permisivo de bajo alcance)

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
R1:S

R1:Z1
R1

R2
R2:Z1

Copyright © 2009. http:www.fglongatt.org.ve


R2:S
R1 dispara si (R1:Z1 o R1:S y R2:Z1)
R2 dispara si (R2:Z1 o R2:S y R1:Z1)

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 37/23


PUTT con aceleración por Z1B

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
R1:S

R1:Z1 R1:Z1B
R1

R2
R2:Z1B R2:Z1

Copyright © 2009. http:www.fglongatt.org.ve


R2:S

R1 dispara si (R1:Z1 o R1:Z1B y R2:Z1)


R2 dispara si (R2:Z1 o R2:Z1B y R1:Z1)
1/10/2011

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 38/23


POTT con Zona Z1B

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
R1:Z1 R1:Z1B
R1

R2
R2:Z1B R2:Z1

R1 dispara si (R1:Z1 o R1:Z1B y R2:Z1B)


R2 dispara si (R2:Z1 o R2:Z1B y R1:Z1B)

Copyright © 2009. http:www.fglongatt.org.ve


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 39/23
Comparación direccional de bloqueo
(Blocking)

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
R1:R R1:Z1
R1

R2
R2:Z1 R2:R

R1 dispara si (R1:Z1 y no R2:R)


R2 dispara si (R2:Z1 y no R1:R)

Copyright © 2009. http:www.fglongatt.org.ve


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 40/23
A
Entrada

B1

B3
I1

ZM

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009


L3
L1

B
I2

B2
ZM =
L2

I1

Z M = Z1 + Z 2 + Z 2
I1
I2
Z1 I1 + Z 2 ( I1 + I 2 )

DIgSILENT
41/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
DIgSILENT PowerFactory
5. Modelando Relés de Protección en

42/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Estructura General

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Estructura
Rangos
Diagrama de bloque

Tipo
Rele

Librería

Red
Voltaje
Elemento VT

Copyright © 2009. http:www.fglongatt.org.ve


Disparo

T1

T2
Del
relé
Corriente
CT
G G
Ajustes ~
G1
~
G2

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 43/23


Modelando Relés de Sobrecorriente
• No hay limites en termino de complejidad de los

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
modelos
• Caracteristicas Disponibles:
– Todos los tipos ANSI / IEEE
– Todos los tipos IEC
– Ecuaciones Matematicas
– Tablas
• Interruptores de bajo voltaje
• Elementos Direccionales

Copyright © 2009. http:www.fglongatt.org.ve


• Fusibles
• Curvas limite de Transformador y de Cable
• Caracteristicas de arranque de motores

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 44/23


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
Ejemplo: I-t Time-grading Diagram

45/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
Modelado de Rele de Distancia
• No hay limites en la complejidad de los modelos

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
• Soporta reles modenos, digitales, multi-funcionales
• Caracteristicas
– MHO
– Quadrilateral
– X constante, R constante
– Z constante (circulo)
• Varios elementos direccionales estan disponibles
• Es posible el uso de operaciones logicas complejas

Copyright © 2009. http:www.fglongatt.org.ve


• Es posible la comparacion entre senales.

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 46/23


Ejemplo: Digrama de Impedancia R-X

DIgSILENT

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
[pri.Ohm]

100.

90.0

80.0

70.0

60.0 R3-Mho-1
Zl A 131.086 pri.Ohm 4.31 deg
Zl B 26.306 pri.Ohm 81.25 deg
50.0
Zl C 129.771 pri.Ohm 161.03 deg
Faulttype: BC
40.0 Tripping Time: 0.19 s
Zone:2
30.0 Ph-Ph 2: 0.19 s
Zone:3
Ph-Ph 3: 0.29 s
20.0 Zone:4
Ph-Ph 4: 0.44 s
10.0

-110. -100... -90.0 -80.0 -70.0 -60.0 -50.0 -40.0 -30.0 -20.0 -10.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100. 110. 120. 130. [pri.Ohm]
-10.0..

Copyright © 2009. http:www.fglongatt.org.ve


R1-Dist
-20.0 Zl A 141.551 pri.Ohm 17.88 deg
Zl B 60.135 pri.Ohm 82.35 deg
Zl C 140.851 pri.Ohm 147.44 deg
-30.0 Faulttype: BC
Tripping Time: 0.37 s
-40.0 Zone3
ZPHPH3: 0.37 s
-50.0

-60.0

R1-Dist
R3-Mho-1

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 47/23


Ejemplo: Z-t Time-grading Diagram

DIgSILENT
0.46

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
[s]
0.37

0.28
R4-Mho-2
Ph-Ph 3
Zone 3

0.18
R8-Dist
ZPHPH1
Zone 1
0.09

0.00
0.0 21.0 42.0 63.1 84.1 [pri.Ohm] 105.
HV-UT2 SS-D3 SS-D2 SS-D1 HV-Infeed

HV-UT2 SS-D3 SS-D2 SS-D1 HV-Infeed

105. [pri.Ohm] 84.1 63.1 42.0 21.0 0.0


0.00

0.09

0.18

Copyright © 2009. http:www.fglongatt.org.ve


0.28

0.37
[s]
0.46
x-Achse: Reaktanz Cub_2\Rel-U1 Cub_2\Rel-L2-1 Cub_3\R1-Dist
Cub_1\R2-D1 Cub_2\R3-Mho-1 Cub_1\R4-Mho-2 Cub_2\R5-Mho-4
Cub_1\R6-Mho-5 Cub_2\R7-Mho-6 Cub_2\R8-Dist

Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009 48/23


Dr. Francisco M. Gonzalez-Longatt, fglongatt@ieee.org .Copyright © 2009
Preguntas

49/23

All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.
Copyright © 2009. http:www.fglongatt.org.ve
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author.