Documentos de Académico
Documentos de Profesional
Documentos de Cultura
PROPIETARIO
______________________________________________________________________________________________________________________
MEMORIAS DE CALCULO
______________________________________________________________________________________________________________________
TABLA DE CONTENIDO
DOCUMENTO DE I – MEMORIA
1. INTRODUCCION-----------------------------------------------------------------------------------------------------------------------4
2 OBJETO------------------------------------------------------------------------------------------------------------------- ---------------4
3 LOCALIZACION------------------------------------------------------------------------------------------------------------------------4
4 PROMTOR AO CLIENTE------------------------------------------------------------------------------------------------------------4
5 PROYECTISTA-------------------------------------------------------------------------------------------------------------------------5
6 DESCRIPCION DEL PROYECTO-------------------------------------------------------------------------------------------------5
6.1 RED DE MEDIA TENSION-------------------------------------------------------------------------------------------------------6
6.2 RED DE BAJA TENSION-------------------------------------------------------------------------------------------------------6
6.2 CENTROS DE TRANSFORMACION----------------------------------------------------------------------------------------6
7 CALCULOS ELECTRICOS-----------------------------------------------------------------------------------------------------------6
9. CONCLUSION-------------------------------------------------------------------------------------------------------------------------18
10. ANEXOS---------------------------------------------------------------------------------------------------------------------------------
10.1 PLANOS
______________________________________________________________________________________________________________________
MEMORIAS DE CÁLCULO DEL POLIDEPORTIVO LOS PALMITOS
1. INTRODUCCIÓN.
Cabe anotar que se tendrá en cuenta el cumplimiento del Reglamento técnico de instalaciones Eléctricas RETIE
que se rige en Colombia como ley, en cuanto a distancias de seguridad y homologación de productos.
2. OBJETO.
Se pretende INSTALAR UN TRANSFORMADOR DE 37.5 KVA BIFÁSICO con la finalidad de mejorar el servicio
de energía eléctrica del proyecto en referencia, supervisado y dirigido por mi persona, Ingeniero Electricista
Daniel Gastelbondo Mogollón con tarjeta profesional N° CN 205-30575 DE ACIEM
El objeto del presente documento es la tramitación oficial de la obra descrita, en cuanto a la consecución de las
correspondientes autorizaciones administrativas.
Este diseño eléctrico se basa en disponibilidad otorgada por mi persona, Ingeniero Electricista Daniel
Gastelbondo Mogollón.
Se plantea el diseño cambiando una estructura ubicada en el punto de conexión en donde se ubicará el
transformador el cual irá conectado a la línea con conectores tipo AMPACT y estribos. Se pretende eliminar un
tramo de línea que cruza por el polideportivo y se instalará subterránea con cable XLPE MONOPOLAR.
Se utilizarán crucetas estandarizadas y aisladores tipo line-post, el transformador será de 37.5KVA 2F e irá en
una estructura en alineación.
3. LOCALIZACIÓN.
______________________________________________________________________________________________________________________
NOMBRE POLIDEPORTIVO LOS PALMITOS
DIRECCIÓN POLIDEPORTIVO LOS PALMITOS
BARRIO / VEREDA / CORREGIMIENTO LOS PALMITOS
MUNICIPIO: LOS PALMITOS
DEPARTAMENTO: SUCRE
NIVEL DE ELECTRIFICACION (RURAL / URBANO) URBANO
4. PROMOTOR O CLIENTE.
5. PROYECTISTA.
Se describe el proyecto como se mencionó en los objetivos, adicionalmente se hace referencia a la parte
constructiva del mismo, con todos los cálculos pertinentes que hagan referencia.
______________________________________________________________________________________________________________________
No. DE CT EN POSTE 1
No. DE CT INTERIOR 0
No DE CT PEDESTAL (PAD MOUNTED) 0
No. TOTAL DE CT 1
No de CT TRIFÁSICOS 0
No. DE CT MONOFÁSICOS 1
KVA CT’S TRIFÁSICOS 0
KVA CT’S MONOFÁSICOS 37.5
KVA TOTAL INSTALADOS 37.5
7. CALCULOS ELÉCTRICOS.
Todos los cálculos eléctricos relativos al presente PROYECTO han sido realizados de acuerdo con los “Criterios
de Diseño y de Construcción de Redes Aéreas de Distribución” de ELECTRICARIBE.
TABLA 7.1.1 - RED DE MEDIA TENSION - REGULACION Y PERDIDAS (CALCULO POR ALIMENTADOR)
TABLA 7.1.2 – RED DE BAJA TENSION – RESUMEN REGULACIÓN Y PERDIDAS POR CIRCUITO DE BT
MÁXIMA CAIDA DE TENSION CALCULADA (%) 0,00000
MÁXIMA PERDIDA DE POTENCIA CALCULADA(%) 0,000001
______________________________________________________________________________________________________________________
CUADRO DE AREAS TD-1
F1 F2
ALUMBRADO EN
4x400 w 1 5
POSTE SUR
CANCHA AUXILIAR
ORNAMENTALES
4x400 w 2 6 SUR
ALUMBRADOA EN
2x400 w 3 7
POSTE - NORTE
JUEGOS INFANTILES
ORNAMENTALES
2x400 w 4 8 NORTE
RESERVA RESERVA
RESERVA RESERVA
______________________________________________________________________________________________________________________
TABLERO DE DISTRIBUCIÓN N° 1= 8350W
CONTIENE:
8 REFLECTORES X 400W = 3200W PARA CANCHA PRINCIPAL
4 REFLECTORES X 400W = 1600W PARA JUEGOS INFANTILES
10 LUMINARIAS DE 70W = 700W PARA POSTES SUR.
24 LUMINARIAS DE 70W = 1680W PARA ORNAMENTALES SUR
10 LUMINARIAS DE 70W = 700W PARA POSTES NORTE.
16 LUMINARIAS DE 70W = 1120W PARA ORNAMENTALES NORTE
Diseño Transformador
KVAs instalados = 27.65
Factor de potencia = 0.9
KVAs Tot = 30.72
Fac de Demanda = 1
KVAs Diseño = 30.72
KVAs transformador 2ø = 37.5
37,5KVA
Lado de media tensión:
13,2 KV
Lado de media tensión: 2.84 Amp.
1.97Amp x 1.25 = 3.55
Se escogen fusibles de 3 Amp. Tipo D a 15 KV.
37500VA
Lado de baja tensión:
240V
Lado de baja tensión: 156.25 Amp.
Se escoge un breaker termomagnético de 150 Amp. A 600 V, variable
______________________________________________________________________________________________________________________
La impedancia del transformador Zt = 4,0%
Ipc
Icc( SIM ) 100
Zt
143,79
Icc ( SIM ) 100
4,0
Icc(SIM ) 3.594,79 Amp.
Icc( ASIM ) 1,7 Icc(SIM )
Icc( ASIM ) 1,7 3.594,79
Icc( ASIM ) 6.111,14 Amp.
2 I L
v
56 S
S: Sección del conductor en milímetros cuadrados
I: Corriente en amperios
L: Longitud de la acometida en metros
56: Corriente de resistividad del cobre
v: Caída de voltaje para la condición máxima del 3%
______________________________________________________________________________________________________________________
L = 32 Mts
2 156.25 32
v
56 67.44
v 2,64V
2,64
% Re g 100 1,11% 3%
240
Para la puesta a tierra de la subestación, se construirá en el terreno circundante al poste una malla con cable de
cobre desnudo nº 2 AWG, enterrado a una profundidad de 0,60 mts, usando soldadura exotérmica de 90 gramos
para conexiones. Se instalará 1 varilla de Cu de 2.4mts x 5/8.
Para los cálculos, se efectuaron mediciones de resistividad aparente, aplicando el método tetraelectrodico de
WENNER y se obtuvo un valor p= 21 ohm-mts en las condiciones mas desfavorables.
Para la selección de conductor de puesta a tierra, se tomo como base el especificado en la TABLA 250-94 dela
NTC2050.
CONDUCTOR:
Cobre nº 2 AWG.
Longitud = 9 mts
Diámetro del conductor= 0,00742 mts
Sección del conductor = 33,63mm^2
VARILLA DE COBRE:
Longitud = 2,40 mts
______________________________________________________________________________________________________________________
Diámetro = 5/8” = 0,016 mts
Cantidad= 3
Con estos parámetros se obtuvieron los siguientes valores de resistencia:
Cumpliendo con lo exigido por la norma técnica IEC- 60360, ANSI/ IEEE80, NTC2050, NTC4552 y lo especificado
en la TABLE 24 del RETIE.
Posteriormente, antes de la puesta en servicio de la subestación, se medirá físicamente la resistencia de puesta a
tierra, como parte de la rutina de mantenimiento, aplicando el método de caída de potencial, según lo descrito en
el articulo 15 apartado 5.2 del RETIE.
Esta malla se interconectara a través del neutro de la acometida con las puestas a tierra del tablero de
distribución general de la edificación, lo cual equipotencializara y mejorara notablemente la conductividad y
seguridad del sistema de puesta a tierra en toda la edificación.
13. CIMENTACIONES
14. PARALELISMOS
15. SERVIDUMBRES.
______________________________________________________________________________________________________________________
16. CONCLUSIONES.
Expuestas en este Proyecto las razones que justifican la necesidad de la instalación y sus características, se
solicita la aprobación y la autorización para su construcción y posterior puesta en servicio.
Cordialmente
_________________________________
DANIEL ANDRES GASTELBONDO MOGOLLON
ING ELECTRICISTA
MAT PROF: AN205-47973
______________________________________________________________________________________________________________________
ANEXOS.
B. PLANOS
______________________________________________________________________________________________________________________