FACULTAD DE INGENIERÍA
INGENIERÍA ELÉCTRICA

MATERIA
SUBESTACIONES

CATEDRÁTICO
Ing. Edwin Ponce Minaya, MG

NIVEL
Décimo Semestre

AUTORES
Paredes Morillo George
Barona Posligua Héctor
García Palma Douglas
Holguín Cedeño Edison

PERÍODO LECTIVO
2020 período 1
CONTENIDO
VIRTUDES DE CONTAR CON UN LABORATORIO DE POTENCIA ................ 1

Introducción .................................................................................................................... 1

Desarrollo del informe.................................................................................................... 1

Sistema de Potencia de Transmisión y Distribución ................................................... 1

1. N-ALI01. Fuente de alimentación principal industrial........................................ 2

2. N-BUS04. Barra Bus de transporte (Emisor). ...................................................... 3

3. N-BUS05. Barra Bus de transporte (Receptor). ................................................... 4

Conclusión ....................................................................................................................... 8

Recomendaciones ............................................................................................................ 9

Anexo ............................................................................................................................... 9

Bibliografía ...................................................................................................................... 9
www.uleam.edu.ec
Facultad de Ingeniería

VIRTUDES DE CONTAR CON UN LABORATORIO DE POTENCIA

Introducción
La Universidad Laica Eloy Alfaro de Manabí es una Institución de Educación Superior,
que se ha esforzado por llevar a cabo su finalidad en la formación de profesionales con los
mejores niveles de conocimiento tanto teórico como práctico, por esto, la Universidad, en
especial la carrera de Ingeniería Eléctrica (actualmente Carrera de Ingeniería en Electricidad)
con sede en Manta, cuenta con un laboratorio completo de potencia en el cual los estudiantes
de Pregrado puedan enriquecer sus conocimientos teóricos en el área de Electricidad de
media Tensión.
La necesidad de implementar el Laboratorio en la Universidad fue inminente por lo que
este proyecto de diseño aportó a la eficacia dentro del componente práctico necesario para
complementar los conocimientos adquiridos, además contribuir en los esfuerzos de cambio
y mejoramientos socioeconómicos del país, respetando el derecho a la vida y preservando el
medio ambiente, esto justificó totalmente la implementación de un laboratorio para realizar
las prácticas necesarias en Media Tensión, y de esta manera obtener una completa
preparación en la materia (Cañadas & Velásquez, 2016).

Desarrollo del informe


Sistema de Potencia de Transmisión y Distribución
El sistema de potencia de transmisión y distribución con transformador regulable y relés
de protección (AEL-T-P-01S) es un sistema modular con tecnología Smart Grid desarrollada
para estudiar los sistemas de energía de Transporte y Distribución.

Este sistema nos permite adquirir los conocimientos más importantes sobre cómo se
transporta la energía eléctrica, elevación de voltaje hasta ciertos niveles, cuál es la función
de los transformadores con regulador de voltaje, etc. Además, sabremos cómo se realizan
las maniobras básicas en sistemas de doble barra colectora, cuál es la secuencia correcta de
actuación entre los interruptores aisladores y el disyuntor y muchas otras preguntas.

El sistema AEL-T-P-01S consta de una serie de módulos que nos permiten simular las
operaciones más importantes de control, regulación y supervisión realizado en subestaciones
emisoras y receptoras unidas con una línea de transmisión aérea.
www.uleam.edu.ec
Facultad de Ingeniería

Para poner en práctica todos estos conocimientos, en la aplicación AEL-T-P-01S se


incluyen ciertos dispositivos que hacen de nuestra aplicación una verdadera red inteligente:

➢ Incluye un relé de protección de distancia. Este relé controla, en tiempo real, los
parámetros de impedancia de la línea de transmisión.
➢ Incluye un sofisticado módulo de inyección de fallas para analizar la evolución de
los transitorios y observar la solicitud de los relés de protección utilizados en l.
➢ Incluye analizadores de red que nos muestran en tiempo real los parámetros eléctricos
en la línea de transmisión para estudiar las pérdidas de energía, voltajes caídos, línea,
corrientes, etc.
➢ Incluye un regulador de voltaje TAP en el transformador de distribución para
compensar el voltaje de caída de la línea de transmisión.

AEL-T-P-01S

A continuación, se detallarán los elementos incluidos en el módulo de


transmisión/distribución:

1. N-ALI01. Fuente de alimentación principal industrial


Es una fuente de alimentación trifásica industrial de 400 VAC con capacidad de conexión
tanto trifásica como monofásica en sus terminales; como protección tiene un disyuntor
diferencial de 30mA y un pulsador de emergencia en caso de que ocurra alguna falla en el
módulo.
www.uleam.edu.ec
Facultad de Ingeniería

También lleva su respectiva llave de seguridad para encender el módulo y conector de 7


pines para alimentarlo.

N-ALI01

2. N-BUS04. Barra Bus de transporte (Emisor).


Este módulo de busbar consta con conmutadores giratorios para la conexión o
desconexión de seccionadores y disyuntor que representan las barras de una subestación de
transporte.

Tiene consigo un interruptor para funcionamiento local o remoto, luces indicadoras de


estado del módulo (On/Off), conectores de comunicación y una fuente de alimentación de
230 VAC.

N-BUS04
www.uleam.edu.ec
Facultad de Ingeniería

3. N-BUS05. Barra Bus de transporte (Receptor).


Es un módulo de doble busbar que consta con conmutadores giratorios para la conexión
o desconexión de seccionadores y disyuntor, que representan las barras de una subestación
distribución.

Tiene consigo un interruptor para funcionamiento local o remoto, luces indicadoras de


estado del módulo (On/Off) y un conector de comunicaciones SUB-D 62 pines para SCADA

N-BUS05

4. N-EALD. Unidad de analizador de red con adquisición de datos por computadora.

Es un display analizador de redes, con capacidad de mostrar: potencia (activa, reactiva y


aparente), energía (activa, reactiva y aparente), corrientes de fase y línea, tensiones de fase
y línea, frecuencias y factor de potencia. A continuación, se mostrarán las características
técnicas del analizador:

• Terminales de entrada: Terminales de entrada de medición trifásica con


neutro, 400VAC.
• Terminales de salida: Terminales de salida de medición trifásica con neutro,
400VAC.
• Puerto de comunicación Rs485.
• Terminales de alimentación: Voltaje nominal: 230VAC.
• Fusibles: fusibles de línea 3x10A.
• Salidas digitales: Tres salidas digitales para pulsos o alarmas, o para combinar
cualquiera.
www.uleam.edu.ec
Facultad de Ingeniería

N-EALD

5. N-REG15. Modulo regulador TAP

Este módulo regulador de voltaje TAP tiene una fuente de alimentación monofásica a
230VAC y rengos de selección de TAP desde +7,5% hasta -7,5%, que regularan el voltaje a
nivel de distribución en caso que se lo requiera.

Tiene consigo un interruptor para funcionamiento local o remoto, luces indicadoras de


estado del módulo y conmutador (On/Off), luces indicadoras del porcentaje de regulación
seleccionado, y un conector de comunicaciones SUB-D 62 pines para SCADA

N-REG15
www.uleam.edu.ec
Facultad de Ingeniería

6. N-AE1CD. Unidad digital simulador de líneas de transmisión.

Este modulo es usado para la simulación de valores de reactancia en las líneas de


transmisión a 400VAC, así también, la simulación de perdida de fases (R, S y/o T).

Tiene consigo un interruptor para funcionamiento local o remoto, conmutadores para la


simulación y luces indicadoras de estado del módulo (On/Off).

N-AE1CD

7. N-ERP-PD01. Módulo de relé de protección de distancia.

Este módulo es utilizado para realizar investigaciones sobre protección y monitoreo de


líneas aéreas de transmisión y cables subterráneos. Permite una amplia gama de pruebas e
investigaciones y demuestra la última tecnología en relés.

La conexión al circuito experimental es a través de transformadores de corriente (TC) con


relación de transformación adaptadas a las entradas del relé. Tiene las siguientes
características técnicas:

• Precisión: + - 10%.
• Corriente: 5 A (AC).
• Frecuencia: 50 o 60 Hz.
• Tiempo de funcionamiento: típicamente de 10 ms a 25 ms.
www.uleam.edu.ec
Facultad de Ingeniería

N-ERP-PD01

8. N-ERP-MF01. Módulo simulador digital de fallas.

Este modulo nos permite simular fallas de cortocircuito en el sistema, la cuales las
siguientes que podemos preseleccionar:

• Cortocircuito trifásico.
• Cortocircuito bifásico.
• Cortocircuito bifásico a tierra.
• Cortocircuito monofásico.

Tiene consigo un interruptor para funcionamiento local o remoto, interruptor para


cambiar el estado del módulo (On/Off), conectores para terminales y un conector de
comunicaciones SUB-D 62 pines para SCADA

N-ERP-MF01
www.uleam.edu.ec
Facultad de Ingeniería

9. TRANS3/5KR. Transformador reductor de 5KW con regulador de voltaje.

Es un transformador de potencia de 5KVA trifásico usado para la simulación de la etapa


de transformación de voltaje. Está configurado con conexión delta a 400VAC regulable
desde -7,5% hasta +7,5% en el primario, y configurado con conexión estrella a 400VAC en
el secundario

TRANS3/5KR

Conclusión
• Se ha verificado la instrumentación que se encuentra dentro de un laboratorio de este
tipo, cumpliendo con la normativa IEEE 4-995: Standard Techniques for High-Voltage
Testing. Y el adendum de la norma IEEE 4a – 2001: Standard Techniques for High-
Voltage Testing, con lo cual se obtendrá una alta confiabilidad en los resultados
obtenidos en los procesos a realizarse dentro del Laboratorio, pudiendo de esta manera
obtener una certificación externa y con esto servir a la comunidad eléctrica del país.
www.uleam.edu.ec
Facultad de Ingeniería

• Además de haber realizado prácticas acordes a los requerimientos de las mallas de


estudio de la Universidad, este laboratorio es de gran ayuda a para la sustentación de la
parte teórica del aprendizaje, siendo la mejor forma de practicar y desarrollar criterios
que nos van a permitir tomar decisiones en el campo laboral.

Recomendaciones
• Se recomienda se utilice esta implementación del Laboratorio de Media Tensión de la
Universidad Laica Eloy Alfaro de Manabí, ya que el mismo se ha realizado pensando
en las necesidades académicas, técnicas, y económicas tanto de los alumnos de la
Universidad como de la comunidad eléctrica que podría servirse del mismo para los
ensayos de laboratorio pertinente luego de la certificación correspondiente.
• Además, la revisión de las prácticas a realizarse será un aporte a los estudios, ya que
como egresado de la Universidad aportarían de gran ayuda al estudio de la Media
Tensión local, tanto académica como profesionalmente.

Anexo
ANEXO 1: Modular Smart Grid Power Systems Simulators (Utilities) – AEL-MPSS
(AL FINAL DEL TRABAJO SE ANEXARÁ)

Bibliografía
Cañadas, S. A., & Velásquez, N. D. (2016). Desarrollo de un software para realizar el
análisis termodinámico del ciclo Brayton de la Turbina de Gas de Doble Eje (Edibon
TGDEC) del Laboratorio de Termodinámica de la Facultad de Ingeniería Mecánica
de la Escuela Politécnica Nacional. Recuperado el 30 de 7 de 2020, de
http://bibdigital.epn.edu.ec/bitstream/15000/15250/1/cd-7024.pdf

Tovar, L., & Maria, A. (2015). SUPERVISIÓN Y CONTROL ON-OFF DE LA PLANTA DE


PROCESOS T5552 CON SISTEMA EDIBON DE ADQUISICIÓN DE DATOS Y
LABVIEW. Recuperado el 30 de 7 de 2020, de
http://repository.udistrital.edu.co/bitstream/11349/2222/2/lemustovaranamaria2015
pdf
Modular Smart Grid Power Systems Simulators
(Utilities)
AEL-MPSS
Technical Teaching Equipment

SCADA

Key features:
Several Utilities and Final User options.

Modular and scalable applications (from simple to advance complexity).

Scalable and expandable applications.

Possibility to work either with individual applications or combined applications to


form simulators (Generation + Transmission/Distribution + Loads).

Use of real devices as substations protection relays, generators management


devices, frequency controllers, etc. www.edibon.com
Products
Products range
EDIBON SCADA System (Supervision, Control and Data Acquisition) always included. Units
5.-Energy
Smart Grid devices.

Micro-Grids.

ISO 9000: Quality Management European Union Certificate Certificates ISO 14000 and Worlddidac Quality Charter
(for Design, Manufacturing, (total safety) ECO-Management and Audit Scheme Certificate and
Commercialization and After-sales service) (environmental management) Worlddidac Member
Page 1
AEL-MPSS

2. TRANSMISSION/DISTRIBUTION
1. GENERATION SYSTEMS 3. LOADS SYSTEMS
SYSTEMS

+ +

AEL-GCA- Automatic Control Generation AEL-T- Transmission and Distribution Power AEL-C- Conventional Loads options.
Systems options. Systems options. AEL-CS- Special Loads options.
AEL-GCM- Manual Control Generation
Systems options.
AEL-GAD- Additional Generation Systems
options.

EDIBON SCADA System

OPEN CONTROL
+ Control
MULTICONTROL Interface
+
REAL TIME CONTROL
SCADA Software

Page 2 www.edibon.com
ALL AVAILABLE OPTIONS
1. GENERATION SYSTEMS
AEL-GCA- AEL-GCM- AEL-GAD-
Automatic Control Generation Systems Manual Control Generation Systems Additional Generation Systems
options options options
Applications Applications Applications
Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCM-P-02S. Generation System with SCADA.
AEL-GCA-P-02S. Generation System with
Manual Control of AEL-GAD-02S. Auto-Start Diesel Generator
Automatic Control of
Synchronous Generator, Trainer for Recovery of the
Synchronous Generator,
Synchronization and Energy System due to Black-
Synchronization and
Protection Relays, with Outs, with SCADA.
Protection Relays, with
SCADA.
SCADA. AEL-GAD-03S. A u t o m a t i c G e n e r a t i o n
AEL-GCM-02S. Generation System with System with Two Parallel
AEL-GCA-02S. Generation System with Manual Control of Generators, with SCADA.
Automatic Control of Synchronous Generator and
Synchronous Generator and Synchronization, with AEL-GAD-04S. Hydroelectric Power Plant,
Synchronization, with SCADA. with SCADA.
SCADA.
AEL-GCM-P-03S. Manual Synchronization
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous These applications can be complemented with AEL-
System of Synchronous Generator with Servomotor GCA and AEL-GCM applications.
Generator with Servomotor and Protection Relays, with
and Protection Relays, with SCADA.
SCADA. AEL-GCM-03S. Manual Synchronization
AEL-GCA-03S. Automatic Synchronization System of Synchronous
System of Synchronous Generator with Servomotor,
Generator with Servomotor, with SCADA.
with SCADA. Isolated Grid Studies
Isolated Grid Studies AEL-GCM-P-01S. Generation System with
Manual Control of
AEL-GCA-P-01S. Generation System with Synchronous Generator in
Automatic Control of an Isolated Grid and
Synchronous Generator in an Protection Relays, with
Isolated Grid and Protection SCADA.
Relays, with SCADA.
AEL-GCM-01S. Generation System with
AEL-GCA-01S. Generation System with Manual Control of
Automatic Control of Synchronous Generator in
Synchronous Generator in an an Isolated Grid, with
Isolated Grid, with SCADA. SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS
AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA.
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)


AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. L o a d s S y s t e m s w i t h A u t o m a t i c Po w e r F a c t o r AEL-C-03S. Complex Loads, Power Consumption Measurement and


Compensation and Protection Relays, with SCADA. Peak Load Monitoring, with SCADA.
AEL-C-02S. L o a d s S y s t e m s w i t h A u t o m a t i c Po w e r F a c t o r
Compensation, with SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation
and Protection Relays, with SCADA.
AEL-C-01S. L o a d s S y s t e m s w i t h M a n u a l Po w e r F a c t o r
Compensation, with SCADA.

* Each application can work individually or combined with other applications to form systems simulators (Generation + Transmission/Distribution + Loads).
Page 3 www.edibon.com
INTRODUCTION
Due to the growth and development of electric power systems it has been required to design increasingly sophisticated devices to manage electric
power in a safer and more efficient way.

Nowadays, protection and monitoring devices, which allow to know the electrical parameters in real time, such as voltage level in the nodes of the
grid, current level in the lines, active and reactive power level, frequency values, etc., are essential in the electrical grids. Protection systems play an
important role in power systems, since they can control in a practically independent way the safety and continuity of the power supply, as well as the
quality of the energy the final consumer gets.

The Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS”, with more than 285 control variables, have been designed to make
and use the same technology employed in power systems available in the industrial world, easy to use by experts and inexperienced people. We
included the safety conditions required to perform different short-circuit tests and experiments.

The AEL-MPSS systems simulators are specially designed and aimed at technical professional training, vocational training, for higher education
and even applied research, as well as the improvement in all fields through advanced systems.

The Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS” can be configured from three great areas formed by several options and
applications as:

1. Generation systems applications.

2. Transmission/Distribution systems applications.

3. Loads systems applications.

The objective of each area is to study a field of the electric power systems. All the options available in these three great areas have been designed
to be able to work either independently or combining with several options and applications in order to configure systems simulators (generation +
trasmission/ distribution + loads).

Due to the flexibility of our modular applications, it is possible to begin with easy applications for students with basic knowledge of power systems
and/or to combine several applications for intermediate or advanced levels. Thus, a system simulator consisting of applications of generation,
transmission/ distribution and loads will be created. Optionally, all of them including cutting edge protection relays to test their efficiency and
reliability against any electrical fault.

All applications on this catalogue include the SCADA (Supervision, Control and Data Acquisition), which allows to study the operation of today's
power systems in depth. This software enables the student to control the devices that make up the power systems remotely, observe in real time how
the typical operations of an electrical substation work, which are the voltage and current values at different points of the transport networks, how
much energy is generated and what occurs when the excitation current of our generator is increased or decreased.

Main features of Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS”:

-Several Utilities and Final User options.

-Modular and scalable applications (from simple to advance complexity).

-Scalable and expandable applications.

-Possibility to work either with individual applications or combined applications to form simulators (Generation + Transmission/Distribution +
Loads).

-Use of real devices as substations protection relays, generators management devices, frequency controllers, etc.

-EDIBON SCADA System (Supervision, Control and Data Acquisition) always included.

-Smart Grid devices.

-Micro-Grids.

Page 4 www.edibon.com
SOME CONTROL VARIABLES USED WITH AEL-MPSS MODULAR SMART GRID POWER SYSTEMS
The AEL-MPSS Modular Power Systems is one of the most advanced and complete modular power systems of the market. In the following pages
the most important variables which allow the control of the system both in local and remote through the included SCADA are indicated.

The following are the most important 285 control variables that make the AEL-MPSS a forefront system able to interact with the user thanks to the
cutting-edge included devices.

The AEL-MPSS has been designed to show any electric phenomenon that are present in real power systems, such as short circuits, over currents,
over voltages, over frequencies, reverse power, generator runaway, etc.

A variable is any element or symbol of our system susceptible to be modified directly or indirectly by the user and the control system.

All power systems are formed by three fundamental parts:

1. Generation System.

2. Transmission/Distribution System.

3. Load System.

1. Generation System:

Power generation is the point where all power systems born, where transmission lines emerge up to distribution lines and finally, to give
electrical service to the final consumer. It is necessary a great quantity of control variables for a power system reliable, safe and optimal
because of these variables depend the electrical energy quality. This is the reason why the generation systems of the AEL-MPSS includes the
145 control variables most important that will allow user to interact with a sophisticated, real and intelligent generation system, which is
able to respond automatically against energy demand, it is able to protect automatically against short circuits, with light indicators and
alarms that will allow us to understand at all time the generation system state.

See the 145 control variables in next page.

2. Transmission/Distribution System:

After power generation, transmission and distribution systems are required to give power to the final consumer. These systems are highways of
aluminum and steel which transport great quantities of power up to strategic points of the country and even other countries. In the
transmission systems is very important to know variables such as transported energy, length transmission lines, capacitive effect, energy losses
produced along kilometers and kilometers, etc. Besides, in a transmission line system is not enough a conventional protection system. For
these systems are required distance protection relays able to detect changes in the line impedances and to sense undetectable anomalies for
other conventional protection relays.

Distribution substations adapt the transmission lines voltage levels up to lower voltage levels for energy distribution. On this point take
importance the distribution transformer with voltage regulator, which are able to compensate the transmission liens drop voltages.

The transmission/distribution power system of AEL-MPSS allows to study all these control variables and much more. In the following page the
most important 76 control variables that allow the user to interact with the transmission/distribution system are listed.

See the 76 control variables in next page.

3. Load System:

Once the energy is transported, this has to be carried to the consumption points through distribution lines. Final consumer provokes changes
in the power balance of the system from generation up to distribution. On this way, all machinery of the system (generation, transmission and
distribution) works in real time in order to the electrical parameters remain constants in the consumption points.

In the consumption points is very important to ensure the electrical energy quality through reactive energy compensation devices. Besides, on
this point are essential the feeders management protection relays, which are installed in strategic points of the distribution lines giving to the
grid the required reliability, safety and efficiency. These protection relays monitor electrical variables such as frequency, voltage, current,
power factor, etc. in order to protect the grid.

In the following page the most important 64 control variables which allow user to interact with the load system are listed.

See the 64 control variables in next page.


Continue...
Page 5 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

The most important 285 control variables which allow user to interact with the load system are listed below:

1. Generation System: the most important and used 145 physical variables in the industrial power systems.

1.1. Some general control variables of the Turbine-Generator group.  Manual Control Variable for 52G breaker open/close.
 Manual Control Variable for emergency stop of the Turbine- - Load Sharing/Parallel Grid Mode:
Generator group.  Manual Control Variable for synchronization the generator and
 Control Variable for starting order of the Turbine-Generator in the grid.
automatic mode.  Manual Control Variable for Active Power given to the grid.
 Permission Variable for synchronization in automatic mode.  Manual Control Variable for Reactive Power given to the grid.
 Manual Control Variable for 52G breaker open/close.
1.2. Local Control Mode of Turbine-Generator group.
1.2.1. Local Control of the group in manual mode. 1.3.2. Automatic Remote Control (SCADA) of Turbine-Generator
- Island mode: group.
 Manual Control Variable for turbine frequency/speed - Island Mode:
control with analog potentiometer.  Automatic Control Variable for turbine frequency/speed control
 Manual Control Variable for synchronous generator through AVR (Automatic Voltage Regulator).
excitation with analog potentiometer.  Automatic Control Variable for synchronous generator
 Manual Control Variable for 52G breaker open/close. excitation/voltage control through AVR (Automatic Voltage
- “ Load sharing/parallel grid” mode: Regulator).
 Automatic Control Variable for line and phase voltages.
 Manual Control Variable for synchronization the generator and
the grid.  Automatic Control Variable for Reactive Power given to the grid.

 Manual Control Variable for Active Power given to the grid.  Automatic Control Variable for maximum line current.

 Manual Control Variable for Reactive Power given to the grid.  Automatic Control Variable for 52G breaker open/close.

 Manual Control Variable for 52G breaker open/close. - Load Sharing/Parallel Grid Mode:
 Automatic Control Variable for synchronization the synchronous
generator with the grid.
1.2.2. Local Control of the group in automatic mode.
 Automatic Control Variable for Active Power given to the grid.
- Island mode:
 Automatic Control Variable for Active Power maximum limit.
 Automatic Control Variable for turbine frequency/speed
control through AVR (Automatic Voltage Regulator).  Automatic Control Variable for Reactive Power given to the grid.

 Automatic Control Variable for synchronous generator  Automatic Control Variable for Reactive Power maximum limit.
excitation/voltage control through AVR (Automatic Voltage  Automatic Control Variable for adjusting the synchronous
Regulator). generator optimum power factor.
 Automatic Control Variable for line and phase voltages.  Automatic Control Variable for 52G breaker open/close.
 Automatic Control Variable for Reactive Power given to the grid.  Automatic Control Variable for line and phase voltages.
 Automatic Control Variable for maximum line current.  Automatic Control Variable for maximum line current.
 Automatic Control Variable for 52G breaker open/close.
- “ Load sharing/parallel grid” mode: 1.4. Control Variables for protection system.
 Automatic Control Variable for synchronization the synchronous 1.4.1.Over Current and Earth fault protection relay.
generator with the grid.  Configuration variable for the current transformer relationship.
 Automatic Control Variable for Active Power given to the grid.  Configuration variable for the voltage transformer relationship.
 Automatic Control Variable for Active Power maximum limit.  Configuration variable for the removing fault time (TRIP duration).
 Automatic Control Variable for Reactive Power given to the grid.  Configuration variable for Level 1 instantaneous overcurrent
 Automatic Control Variable for Reactive Power maximum limit. 50P1P.
 Automatic Control Variable for adjusting the synchronous  Configuration variable for Level 2 instantaneous overcurrent
generator optimum power factor. 50P2P.
 Automatic Control Variable for 52G breaker open/close.  Configuration variable for Level 3 instantaneous overcurrent
 Automatic Control Variable for line and phase voltages. 50P3P.
 Automatic Control Variable for maximum line current.  Configuration variable for Level 4 instantaneous overcurrent
50P4P.
 Configuration variable for Level 5 instantaneous overcurrent
1.3. Remote Control (SCADA) of Turbine-Generator group 50P5P.
1.3.1. Manual Remote Control (SCADA) of Turbine-Generator group.  Configuration variable for Level 6 instantaneous overcurrent
- Island Mode: 50P6P.
 Manual Control Variable for turbine frequency/speed control  Configuration variable for the inverse time overcurrent
with analog potentiometer. parameter threshold.
 Manual Control Variable for synchronous generator excitation  Configuration variable for inverse time curve type 51P1T: U1,
with analog potentiometer. U2, U3, U4, U5, C1, C2, C3, C4, C5.
Continue...
Page 6 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

1.4.1. Over Current and Earth fault protection relay. (continuation)  Configuration variable for 2º harmonic restriction percentage.
 Configuration variable for the 51P1T Time-Dial of the inverse  Configuration variable for 4º harmonic restriction percentage.
time overcurrent protection curve parameter.
 Configuration variable for 5º harmonic restriction percentage.
 Configuration variable for the 51P2T inverse time curve
 Configuration variable for 50P1P instantaneous overcurrent
threshold.
level of the primary winding power transformer.
 Configuration variable for inverse time curve type 51P2T: U1,
 Configuration variable for 51P1D define time instantaneous
U2, U3, U4, U5, C1, C2, C3, C4, C5.
overcurrent level of the primary winding power transformer.
 Configuration variable for the 51P2P Time-Dial of the inverse
 Configuration variable for 51P1P inverse time overcurrent
time overcurrent protection curve parameter.
threshold of the power transformer primary winding.
 Configuration variable for 50N1 neutral instantaneous
 Configuration variable for inverse time curve type 51P1P: U1,
overcurrent threshold.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 50N2 neutral instantaneous
 Configuration variable for the 51P1P Time-Dial of the inverse
overcurrent threshold.
time overcurrent protection curve parameter.
 Configuration variable for 51N1T inverse time neutral
 Configuration variable for 50Q1P negative sequence
overcurrent parameter threshold.
instantaneous overcurrent threshold of the power transformer
 Configuration variable for inverse time curve type 51N1T: U1, primary winding.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q1P negative sequence inverse
 Configuration variable for the 51N1T Time-Dial of the inverse time overcurrent threshold of the power transformer primary
time overcurrent protection curve parameter. winding.
 Configuration variable for 50G1 instantaneous residual  Configuration variable for inverse time curve type 51Q1P: U1,
overcurrent parameter threshold. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 50G2 instantaneous residual  Configuration variable for 51Q1P Time-Dial of the inverse time
overcurrent parameter threshold. overcurrent protection curve parameter.
 Configuration variable for 50G1T inverse time residual  Configuration variable for 50N1P instantaneous residual
overcurrent parameter threshold. overcurrent threshold of the power transformer primary winding.
 Configuration variable for inverse time curve type 51G1T: U1,  Configuration variable for 50N1P inverse time residual
U2, U3, U4, U5, C1, C2, C3, C4, C5. overcurrent threshold of the power transformer primary winding.
 Configuration variable for the 51G1T Time-Dial of the inverse  Configuration variable for inverse time curve type 51N1P: U1,
time overcurrent protection curve parameter. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q1P negative sequence  Configuration variable for 51N1P Time-Dial of the inverse time
instantaneous overcurrent parameter threshold. overcurrent protection curve parameter.
 Configuration variable for 51Q2P negative sequence  Configuration variable for 50P2P instantaneous overcurrent
instantaneous overcurrent parameter threshold. level of the power transformer secondary winding.
 Configuration variable for 51Q1T inverse time overcurrent  Configuration variable for 50P2D define time instantaneous
parameter threshold. overcurrent level of the power transformer secondary winding.
 Configuration variable for inverse time curve type 51Q1T: U1,  Configuration variable 51P2P inverse time overcurrent threshold
U2, U3, U4, U5, C1, C2, C3, C4, C5. of the power transformer secondary winding.
 Configuration variable for the 51Q1T Time-Dial of the inverse  Configuration variable for inverse time curve type 51P2P: U1,
time overcurrent protection curve parameter. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q2T inverse time overcurrent  Configuration variable for 51P2P Time-Dial of the inverse time
parameter threshold. overcurrent protection curve parameter.
 Configuration variable for inverse time curve type 51Q2T: U1,  Configuration variable for 50Q2P negative sequence
U2, U3, U4, U5, C1, C2, C3, C4, C5. instantaneous overcurrent threshold of the power transformer
 Configuration variable for the 51Q2T Time-Dial of the inverse secondary winding.
time overcurrent protection curve parameter.  Configuration variable for 51Q2P negative sequence inverse
time overcurrent threshold of the power transformer secondary
winding.
1.4.2. Differential Protection Relay of Step-Up power transformer
 Configuration variable for inverse time curve type 51Q2P: U1,
 Configuration variable for the current transformer relationship.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for the voltage transformer relationship.
 Configuration variable for 51Q2P Time-Dial of the inverse time
 Configuration variable for the removing fault time (TRIP overcurrent protection curve parameter.
duration).
 Configuration variable for 50N2P instantaneous residual
 Configuration variable for power transformer connection type. overcurrent threshold of the power transformer secondary
 Configuration variable for measurement transformer connection winding.
type.  Configuration variable for 50N2P inverse time residual
 Configuration variable for 87P differential protection element. overcurrent threshold of the power transformer primary winding.
 Configuration variable for SLP1 restriction percentage of 87P  Configuration variable for inverse time curve type 51N2P: U1,
differential element. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for SLP2 restriction percentage of 87P  Configuration variable for 51N2P Time-Dial of the inverse time
differential element. overcurrent protection curve parameter.
Continue...
Page 7 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

1.4.3. Protection Relay of Turbine-Generator Group.


 Configuration variable of synchronous generator nominal
power.
 Configuration variable of synchronous generator poles number.
 Configuration variable of instantaneous overcurrent protection
threshold.
 Configuration variable of inverse time overcurrent protection
threshold.
 Configuration variable of overvoltage protection threshold.
 Configuration variable of undervoltage protection threshold.
 Configuration variable of overfrequency protection threshold.
 Configuration variable of subfrequency protection threshold.
 Configuration variable of reverse power level.
 Configuration variable of Proportional, Integral and Derivative
(PID) for Turbine-Generator group control and regulation.

1.5. Control variables of double bus bar generation substation


switchgear. Local and remote control possibility (SCADA).
 Control variable of open/close 89GC1-1 coupling
disconnector.
 Control variable of open/close 89GC1-2 coupling
disconnector.
 Control variable of open/close 52GC1-1 coupling breaker.
 Control variable of open/close 89GT1-1 transformer
disconnector.
 Control variable of open/close 89GT1-2 transformer
disconnector.
 Control variable of open/close 89GT1-3 transformer
disconnector.
 Control variable of open/close 52GT1-1 transformer breaker.
 Control variable of open/close 52NET grid breaker.
 Control variable of open/close 52G1 generation breaker.

1.6. Control variables for faults selection.


1.6.1. Local/Remote control (SCADA):
 Control variable for direct single phase short preselection.
 Control variable for single phase short circuit with fault
impedance.
 Control variable for direct two phases to ground short circuit
preselection.
 Control variable for two phases to ground short circuit
preselection with fault impedance.
 Control variable for direct two phase short circuit preselection.
 Control variable for two phase short circuit preselection with
fault impedance.
 Control variable for direct three-phase phase short circuit
preselection.
 Control variable for three-phase phase short circuit preselection
with fault impedance.
 Control variable for fault injection.

Continue...
Page 8 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

2. Transmission/Distribution System: the most important and used 76 physical variables in the industrial power systems.
2.1. Control variables of double bus bar emitter substation - Configuration variable for Z2MG ground impedance element
switchgear. Possibility to control both local and remote modes of zone 2.
(SCADA). - Configuration variable for Z3MG ground impedance element
 Control variable of open/close 89T1-1 disconnector. of zone 3.
 Control variable of open/close 89T1-2 disconnector. - Configuration variable for Z4MG ground impedance element
 Control variable of open/close 89T1-3 disconnector. of zone 4.
 Control variable of open/close 52T1-1 breaker. - Configuration variable for Z1D time distance element of zone
1.
2.2. Control variables of double bus bar receptor substation - Configuration variable for Z2D time distance element of zone
switchgear. Possibility to control both local and remote modes 2.
(SCADA). - Configuration variable for Z3D time distance element of zone
 Control variable of open/close 89L1-1 disconnector. 3.
 Control variable of open/close 89L1-2 disconnector. - Configuration variable for Z4D time distance element of zone
4.
 Control variable of open/close 89L1-3 disconnector.
 Configuration variable for 50P1P instantaneous overcurrent
 Control variable of open/close 52T2-1 breaker.
element of level 1.
 Configuration variable for 50P2P instantaneous overcurrent
2.3. Control variables of distribution transformer voltage regulator. element of level 2.
Possibility to control both local and remote modes (SCADA).
 Configuration variable for 50P3P instantaneous overcurrent
 Control variable for voltage regulation at 0 %.
element of level 3.
 Control variable for voltage regulation at 2, 5 %.
 Configuration variable for 50P4P instantaneous overcurrent
 Control variable for voltage regulation at 5 %. element of level 4.
 Control variable for voltage regulation at 7, 5 %.  Configuration variable for 67P1D define time overcurrent
 Control variable for voltage regulation at -2, 5 %. element of level 1.
 Control variable for voltage regulation at -5 %.  Configuration variable for 67P2D define time overcurrent
 Control variable for voltage regulation at -7,5 %. element of level 2.
 Configuration variable for 67P3D define time overcurrent
2.4. Control variables of transmission line parameters. Local and element of level 3.
remote control possibility (SCADA).  Configuration variable for 67P4D define time overcurrent
 Variable control for line resistor. element of level 4.
 Variable control for line inductance.  Configuration variable for 50G1P residual instantaneous
 Variable control for line capacitance.
overcurrent element of level 1.
 Configuration variable for 50G2P residual instantaneous
 Variable control for breaking line 1.
overcurrent element of level 2.
 Variable control for breaking line 1 and line 2.
 Configuration variable for 50G3P residual instantaneous
 Variable control for breaking line 1, line 2 and line 3.
overcurrent element of level 3.
 Configuration variable for 50G4P residual instantaneous
2.5. Control variables of distance protection relay. overcurrent element of level 4.
 Configuration variable for current transformer relationship.  Configuration variable for 67G1P residual define time
 Configuration variable for voltage transformer relationship. overcurrent element of level 1.
 Configuration variable for remove fault duration.  Configuration variable for 67G2P residual define time
 Configuration variable for line impedance. overcurrent element of level 2.
 Configuration variable for length line.  Configuration variable for 67G3P residual define time
 Configuration variables for Mho distance elements. overcurrent element of level 3.
- Configuration variable for Z1P instantaneous distance  Configuration variable for 67G4P residual define time
element of zone 1. overcurrent element of level 4.
- Configuration variable for Z2P instantaneous distance  Configuration variable for 50Q1P negative sequence
element of zone 2. instantaneous overcurrent element of level 1.
- Configuration variable for Z3P instantaneous distance  Configuration variable for 50Q2P negative sequence
element of zone 3. instantaneous overcurrent element of level 2.
- Configuration variable for Z4P instantaneous distance  Configuration variable for 50Q3P negative sequence
element of zone 4. instantaneous overcurrent element of level 3.
- Configuration variable for 50PP1 instantaneous overcurrent  Configuration variable for 50Q4P negative sequence
element of zone 1. instantaneous overcurrent element of level 4.
- Configuration variable for 50PP2 instantaneous overcurrent  Configuration variable for 67Q1D negative sequence define
element of zone 2. time overcurrent element of level 1.
- Configuration variable for 50PP3 instantaneous overcurrent  Configuration variable for 67Q2D negative sequence define
element of zone 3. time overcurrent element of level 2.
- Configuration variable for 50PP4 instantaneous overcurrent  Configuration variable for 67Q3D negative sequence define
element of zone 4. time overcurrent element of level 3.
- Configuration variable for Z1MG ground impedance element  Configuration variable for 67Q4D negative sequence define
of zone 1. time overcurrent element of level 4.
Continue...
Page 9 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems
2.5. Control variables of distance protection relay. (continuation)
 Configuration variable for 51PP inverse time overcurrent
element of level 1.
 Configuration variable for 51PP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51PP “Time Dial”.
 Configuration variable for 51GP inverse time residual
overcurrent element.
 Configuration variable for 51GP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51GP “Time Dial”.
 Configuration variable for 51QP inverse time negative
sequence overcurrent element.
 Configuration variable for 51QP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51QP “Time Dial”.
 Configuration variable for directional element.

Continue...
Page 10 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

3. Load System: the most important and used 64 physical variables in the industrial power systems.
3.1. Control variables of double bus bar emitter distribution  Configuration variable for 50N2P instantaneous to neutral
substation switchgear. Local and remote control possibility overcurrent of element 2.
(SCADA).  Configuration variable for 50N2D define time neutral
 Control variable of open/close 89T2-1 disconnector. overcurrent of element 2.
 Control variable of open/close 89T2-2 disconnector.  Configuration variable for 50N3P instantaneous to neutral
 Control variable of open/close 89T2-3 disconnector.
overcurrent of element 3.
Configuration variable for 50N3D define time neutral
 Control variable of open/close 52T2-1 breaker.
overcurrent of element 3.
 Control variable of open/close 89T1-1 disconnector.
 Configuration variable for 50N4P instantaneous to neutral
 Control variable of open/close 89T1-2 disconnector. overcurrent of element 4.
 Control variable of open/close 89T1-3 disconnector.  Configuration variable for 50N4D define time neutral
 Control variable of open/close 52T1-1 breaker. overcurrent of element 4.
 Configuration variable for 50G1P instantaneous residual
overcurrent of level 1.
3.2. Control variables for the connected type load. Possibility to
control both local and remote modes (SCADA).  Configuration variable for 50G1D define time residual
overcurrent of element 1.
 Control variable for minimum resistive load.
 Configuration variable for 50G2P instantaneous residual
 Control variable for medium resistive load.
overcurrent of level 2.
 Control variable for maximum resistive load.
 Configuration variable for 50G2D define time residual
 Control variable for minimum inductive load. overcurrent of element 2.
 Control variable for medium inductive load.  Configuration variable for 50G3P instantaneous residual
 Control variable for maximum inductive load. overcurrent of level 3.
 Control variable for minimum capacitive load. Configuration variable for 50G3D define time residual
overcurrent of element 3.
 Control variable for medium capacitive load.
 Configuration variable for 50G4P instantaneous residual
 Control variable for maximum capacitive load.
overcurrent of level 4.
Configuration variable for 50G4D define time residual
3.3. Control variables for load power factor compensation. overcurrent of element 4.
Possibility to control both local and remote modes (SCADA).
 Configuration variable for 50Q1P instantaneous negative
The load system has an automatic power factor controller able to sequence of element 1.
remain constant the load power factor according to the set point
 Configuration variable for 50Q1D define time negative
previously adjusted by the user. Six capacitor steps give more or
sequence overcurrent of element 1.
less reactive power in function of the connected load.
 Configuration variable for 50Q2P instantaneous negative
sequence of element 2.
3.4. Control variables of feeder management protection relay
 Configuration variable for 50Q2D define time negative
 Configuration variable for current transformer relationship. sequence overcurrent of element 2.
 Configuration variable for voltage transformer relationship.  Configuration variable for 50Q3P instantaneous negative
 Configuration variable for remove fault duration. sequence of element 3.
 Configuration variable for 50P1P instantaneous overcurrent of  Configuration variable for 50Q3D define time negative
element 1. sequence overcurrent of element 3.
 Configuration variable for 50P1D define time overcurrent of  Configuration variable for 50Q4P instantaneous negative
element 1. sequence of element 4.
 Configuration variable for 50P2P instantaneous overcurrent of  Configuration variable for 50Q4D define time negative
element 2. sequence overcurrent of element 4.
 Configuration variable for 50P2D define time overcurrent of  Configuration variable for 55 power factor element.
element 2.  Configuration variable for 3PW power element.
 Configuration variable for 50P3P instantaneous overcurrent of  Configuration variable for 87D1TP frequency element 1.
element 3.
 Configuration variable for 87D2TP frequency element 2.
 Configuration variable for 50P3D define time overcurrent of
 Configuration variable for 87D3TP frequency element 3.
element 3.
 Configuration variable for 87D4TP frequency element 4.
 Configuration variable for 50P4P instantaneous overcurrent of
element 4.  Configuration variable for 87D5TP frequency element 5.

 Configuration variable for 50P4D define time overcurrent of  Configuration variable for 87D6TP frequency element 6.
element 4.  Configuration variable for 27P1P sub-voltage element 1.
 Configuration variable for 50N1P instantaneous to neutral  Configuration variable for 27P2P sub-voltage element 2.
overcurrent of element 1.
 Configuration variable for 59P1P over-voltage element 1
 Configuration variable for 50N1D define time neutral
 Configuration variable for 59P2P over-voltage element 2.
overcurrent of element 1.
Page 11 www.edibon.com
1. GENERATION SYSTEMS

Page 5

The generation systems area has been designed to transfer to the student all the knowledge required for the operation of today's electrical generation
possibilities.
Main features of the Generation Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Generation Systems options:
- AEL-GCA- Automatic Control Generation Systems options.
- AEL-GCM- Manual Control Generation Systems options.
- AEL-GAD- Additional Generation Systems options.

AEL-GCA- Automatic Control Generation Systems options:


We offer modular applications focused on the advanced study of electrical generators. The objective is to familiarize the student with the control
devices employed in generation systems nowadays. These generation applications are more complex due to the control included in every module. It is
possible to perform either a direct local control on each module or to control the entire application with SCADA.
It is possible to visualize from the software the electrical diagrams of a generation electrical substation, the transmission lines and the loads and to
perform a direct control of the isolating switches and circuit breakers with each application. Besides, it is possible to inject different types of faults
remotely and to analyze the behaviour of the protection relays located at strategic points of the system. Other possible operation is to perform
alternately a manual control or an automatic control of the turbine-generator group.
There are different topics included, depending on the application:
- Study of generation substations with manual and automatic control of synchronous generator, synchronization and protections.
- Study of generation substations with manual and automatic control of synchronous generator and synchronization.
- Study of generation substations and synchronization with servomotor as prime mover.
- Study of generation substations with manual and automatic control of synchronous generator in isolated grids with protections.
- Study of generation substations with manual and automatic control of synchronous generator in isolated grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GCA-
Automatic Control Generation Systems options

Applications
Synchronization Studies
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection R e l a y s ,
with SCADA.
AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization, with SCADA.
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with Servomotor and Protection Relays, with SCADA.
AEL-GCA-03S. Automatic Synchronization System of Synchronous Generator with Servomotor, with SCADA.
Isolated Grid Studies
AEL-GCA-P-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid and Protection Relays,
with SCADA .
AEL-GCA-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid, with SCADA.

Page 12 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and
Protection Relays, with SCADA
The AEL-GCA-P-02S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of With local control mode:
synchronous generator, protection relays and the necessary
1.- Studying of generation power systems with double busbar
operations for synchronization with the mains.
configuration.
This application includes a SCADA System for remote control 2.- Studying of opening and closing maneuvers of isolator
operations. switches and circuit breaker in double busbar systems.
This application represents an actual generation substation with 3.- Analysis of the measurements of the power flows of the
double bus bar configuration, one synchronous generator and the synchronous generator.
electrical network in order to make the synchronization operations, 4.- Analysis of the active and reactive power of the generator.
opening and closing maneuvers with disconnectors and circuit
breakers of the generation substation, etc. 5.- Manual synchronization maneuvers of synchronous generator
with the mains.
This application includes a series of protection relays to study different 6.- Automatic synchronization maneuvers of synchronous
electrical faults. generator with the mains.
This application includes: 7.- Studying of the synchronous generator in island operation
Modules: mode.
8.- Studying of the Micro-Grids.
 N-ALI01. Industrial Main Power Supply.
9.- Studying of the synchronous generator in grid parallel
 N-BUS01. Generation Busbar. operation mode.
 N-BUS02. Coupling Busbar. 10.- Studying of excitation/voltage regulation of synchronous
 N-BUS03. Grid Busbar. generator in island mode.
11.- Studying of turbine regulation (frequency control) in island
 N-EALD. Network Analyzer Unit with Computer Data mode.
Acquisition. (2 units)
12.- Studying of excitation/voltage regulation of synchronous
 N-EALDC/G. DC Generator Analyzer. generator in parallel grid operation mode.
 N-AVR/P. Automatic Voltage Regulator. 13.- Studying of turbine regulation (frequency control) in parallel
grid operation mode.
 N-VVCA5K. 5KW Motor Speed Controller.
14.- Studying of the power factor regulation of synchronous
 N-ASY3PH. Three-Phase Automatic Synchronoscope. generator in parallel grid operation mode.
 N-PLC01. PLC01 Control Module. 15.- Studying of short circuits in different points of generation
 N-ERP-SFT01. Overcurrent Protection Relay Module. power system:
a. Symmetric short circuits: three-phase short circuits with
 N-ERP-PDF01. Differential Protection Relay Module.
and without contact impedance.
 N-ERP-PGC01. Generator Protection and Control Relay b. Asymmetric faults:
Module.
i. Two-phase short circuit with and without contact
 N-ERP-MF01. Digital Fault Simulator Module. impedance.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. ii. Two-phase to ground shortcircuit with and without
contact impedance.
Transformers:
iii.Single-phase short circuit with and without contact
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer. impedance.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer. 16.- Studying of synchronous generator protection and control
relay.
Generators:
17.- Studying of differential protection relay.
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
18.- Studying of overcurrent protection relay.
SCADA (Supervision, Control and Data Acquisition). Remote control mode (with SCADA):
This application can be combined with other applications of 19.- Remotely control of generation power systems with double
transmission/distribution systems and loads systems areas. Some busbar.
examples of recommended configurations are shown at the end of 20.- Remotely control of opening and closing maneuvers of
this catalogue. isolator switches and circuit breaker in doble busbar systems.
21.- Analysis with the SCADA software of synchronous generator
power flows.
22.- Analysis with SCADA software of active and reactive power of
synchronous generator.
23.- Remotely control of manual synchronization of synchronous
generator with the mains.
24.- Remotely control of automatic synchronization of synchronous
generator with the mains.
25.- Remotely control of synchronous generator in island grid
operation mode.
26.- Studying of Micro-Grids.
27.- Remotely control of synchronous generator in parallel grid
operation mode.
28.- Remotely control of excitation/voltage regulation of
synchronous generator in island mode.
Continue...
Page 13 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays,
with SCADA (continuation)

Some practical possibilities (continuation):


29.- Remotely control of the turbine regulation (frequency control)
in island operation mode.
30.- Remotely control of excitation/ voltage regulation of the
synchronous generator in parallel grid operation mode.
32.- Remotely control of turbine regulation (frequency control) in
parallel grid operation mode.
33.- Remotely control of power factor regulation of synchronous
generator in parallel grid operation mode.
34.- Remotely control of short circuits in different points of the
generation power system:
a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
b. Asymmetric faults:
i. Two-phase short circuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without
contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
35.- Supervision of TRIPS from the SCADA software (protection
relays shooting) in the power system.
36.- Remotely control of the synchronous generator protection and
control relay.
37.- Remotely control of the differential protection relay.
38.- Remotely control of the overcurrent protection relay.
39.- Supervision of the electrical parameters of the generation
system with the SCADA software.

AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization,
with SCADA
The AEL-GCA-02S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator and the necessary operations for synchronization with generator.
the mains. 2.- Manual/automatic current excitation control of the
This application includes a SCADA System for remote control synchronous generator.
operations. 3.- Manual/automatic generation output control of the
This application represents an actual generation substation with synchronous generator.
double bus bar configuration, one synchronous generator and the 4.- Manual/automatic power factor control of the synchronous
electrical network in order to make the synchronization operations, generator.
opening and closing maneuvers with disconnectors and circuit 5.- Manual/automatic power flows control of the synchronous
breakers of the generation substation, etc. generator.
This application includes: 6.- Logic operations of disconnectors and circuit breakers of a
Modules: generation substation.
 N-ALI01. Industrial Main Power Supply. 7.- Manual/automatic operation for synchronization of the
 N-BUS01. Generation Busbar. synchronous generator with the mains.
 N-BUS02. Coupling Busbar. 8.- Synchronoscope use for measuring mismatch voltages,
 N-BUS03. Grid Busbar. frequencies and voltage modules.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-EALDC/G. DC Generator Analyzer.
 N-ASY3PH. Three-Phase Automatic Synchronoscope.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-ERP-PGC01. Generation Protection and Control Relay
Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.
Page 14 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with Servomotor and Protection
Relays, with SCADA
The AEL-GCA-P-03S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of 1.- Manual/automatic frequency control of the synchronous
synchronous generator and the necessary operations for generator.
synchronization with the mains.
2.- Manual/automatic current excitation control of the
Besides, this application includes a series of protection relays in synchronous generator.
order to make different short circuit tests.
3.- Manual/automatic generation output control of the
The speed of generator-motor group is controlled through synchronous generator.
servomotor.
4.- Manual/automatic power factor control of the synchronous
This application includes a SCADA System for remote control generator.
operations.
5.- Manual/automatic power flows control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator moved
by means of servomotor and the electrical network in order to make 6.- Logic operations of disconnectors and circuit breakers of a
the synchronization operations. generation substation.
This application can be combined with other applications of 7.- Manual/automatic operation for synchronization of the
transmission/distribution systems and loads systems areas. Some synchronous generator with the mains.
examples of recommended configurations are shown at the end of 8.- Synchronoscope use for measuring mismatch voltages,
this catalogue. frequencies and voltage modules.
9.- Studying of the following protection relays: differential
protection relay of the step-up transformer and the generator
protection relay.
10.- Studying of the following short circuits types:
Three-Phase short circuit.
Two-Phase short circuit.
Two-Phase to ground short circuit.
Single-Phase short circuit.
11.- Adjusting of protection relay depending of the situation.
12.- Analyzing of the electrical faults transients with a special
software.

AEL-GCA-03S. Automatic Synchronization System of Synchronous Generator with Servomotor, with SCADA
The AEL-GCA-03S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator and the necessary operations for synchronization with generator.
the mains.
2.- Manual/automatic current excitation control of the
The speed of generator-motor group is controlled through synchronous generator.
servomotor.
3.- Manual/automatic generation output control of the
This application includes a SCADA System for remote control synchronous generator.
operations.
4.- Manual/automatic power factor control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator moved
by means of servomotor and the electrical network in order to make 5.- Manual/automatic power flows control of the synchronous
the synchronization operations. generator.
This application can be combined with other applications of 6.- Logic operations of disconnectors and circuit breakers of a
transmission/distribution systems and loads systems areas. Some generation substation.
examples of recommended configurations are shown at the end of 7.- Manual/automatic operation for synchronization of the
this catalogue. synchronous generator with the mains.
8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.

Page 15 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid
and Protection Relays, with SCADA
The AEL-GCA-P-01S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of 1.- Manual/automatic frequency control of the synchronous
synchronous generator in an isolated grid and protection relays, generator.
with SCADA.
2.- Manual/automatic current excitation control of the
This application represents an actual generation substation with synchronous generator.
double bus bar configuration, one synchronous generator and
3.- Manual/automatic generation output control of the
different protection relays to study electrical faults.
synchronous generator.
This application includes:
4.- Manual/automatic power factor control of the synchronous
Modules: generator.
 N-ALI01. Industrial Main Power Supply. 5.- Manual/automatic power flows control of the synchronous
 N-BUS01. Generation Busbar. generator.
 N-BUS02. Coupling Busbar. 6.- Logic operations of disconnectors and circuit breakers of a
 N-AVR/P. Automatic Voltage Regulator. generation substation.
 N-EALD. Network Analyzer Unit with Computer Data 7.- Studying of the following protection relay, differential
Acquisition. protection relay of the step-up transformer and the generator
protection relay.
 N-EALDC/G. DC Generator Analyzer.
8.- Studying of the following short circuits types:
 N-VVCA5K. 5KW Motor Speed Controller.
Three-Phase short circuit.
 N-PLC01. PLC01 Control Module.
Two-Phase short circuit.
 N-ERP-MF01. Digital Fault Simulator Module.
Two-Phase to ground short circuit.
 N-ERP-PGC01. Generation Protection and Control Relay
Module. Single-Phase short circuit.
 N-ERP-PDF01. Differential Protection Relay Module. 9.- Adjusting of protection relay depending of the situation.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. 10.- Analyzing of the electrical faults transients with a special
software.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

AEL-GCA-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid,
with SCADA
The AEL-GCA-01S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator in an isolated grid with SCADA. generator.
This application represents an actual generation substation with 2.- Manual/automatic current excitation control of the
double bus bar configuration and one synchronous generator. synchronous generator.
This application includes: 3.- Manual/automatic generation output control of the
Modules: synchronous generator.
 N-ALI01. Industrial Main Power Supply. 4.- Manual/automatic power factor control of the synchronous
 N-BUS01. Generation Busbar. generator.
 N-BUS02. Coupling Busbar. 5.- Manual/automatic power flows control of the synchronous
 N-AVR/P. Automatic Voltage Regulator. generator.
 N-EALD. Network Analyzer Unit with Computer Data 6.- Logic operations of disconnectors and circuit breakers of a
Acquisition. generation substation.
 N-EALDC/G. DC Generator Analyzer.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-ERP-PGC01. Generation Protection and Control Relay
Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 16 www.edibon.com
1. GENERATION SYSTEMS

AEL-GCM- Manual Control Generation Systems options:


We offer modular applications focused on the basic study of electrical generators. The objective is to familiarize the student with the main operations
performed in the electrical generators, controlling all the parameters of the turbine-generator group manually.
There are different topics included, depending on the application:
- Study of generation substations with manual control of synchronous generator, synchronization and protections.
- Study of generation substations with manual control of synchronous generator and synchronization.
- Study of generation substations and synchronization with servomotor as prime mover.
- Study of generation substations with manual control of synchronous generator in isolated grids and protections.
- Study of generation substations with manual control of synchronous generator in isolated grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GCM-
Manual Control Generation Systems options

Applications
Synchronization Studies
AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization, with SCADA.
AEL-GCM-P-03S. Manual Synchronization System of Synchronous Generator with Servomotor and Protection Relays, with SCADA.
AEL-GCM-03S. Manual Synchronization System of Synchronous Generator with Servomotor, with SCADA.
Isolated Grid Studies
AEL-GCM-P-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid and Protection Relays,
with SCADA.
AEL-GCM-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid, with SCADA.

Applications
AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and
Protection Relays, with SCADA
The AEL-GCM-P-02S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator, protection relays and the necessary operations for 2.- Manual current excitation control of the synchronous
synchronization with the mains. generator.
This application includes a SCADA System for remote control 3.- Manual generation output control of the synchronous
operations. generator.
This application represents an actual generation substation with 4.- Manual power factor control of the synchronous generator.
double bus bar configuration, one synchronous generator and the
electrical network in order to make the synchronization operations. 5.- Manual power flows control of the synchronous generator.
Besides, this application includes a series of protection relays to 6.- Logic operations of disconnectors and circuit breakers of a
study different electrical faults. generation substation.
This application includes: 7.- Manual operation for synchronization of the synchronous
Modules: generator with the mains.
 N-ALI01. Industrial Main Power Supply. 8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.
 N-BUS01. Generation Busbar.
9.- Studying of the following protection relays: the overcurrent
 N-BUS02. Coupling Busbar. and earth fault protection relay and the differential protection
 N-BUS03. Grid Busbar. relay.
 N-AVR/P. Automatic Voltage Regulator. 10.- Studying of the following short circuits types:
 N-EALD. Network Analyzer Unit with Computer Data Three-Phase short circuit.
Acquisition. (2 units) Two-Phase short circuit.
 N-EALDC/G. DC Generator Analyzer. Two-Phase to ground short circuit.
 N-ASY3PH. Three-Phase Automatic Synchronoscope. Single-Phase short circuit.
 N-VVCA5K. 5KW Motor Speed Controller. 11.- Adjusting of protection relays depending of the situation.
 N-PLC01. PLC01 Control Module. 12.- Analyzing of the electrical faults transients with a special
 N-ERP-SFT01. Overcurrent Protection Relay Module. software.
 N-ERP-PDF01. Differential Protection Relay Module.
 N-ERP-MF01. Digital Fault Simulator Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.
Page 17 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization,
with SCADA
The AEL-GCM-02S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
and the necessary operations for synchronization with the mains.
2.- Manual current excitation control of the synchronous
This application includes a SCADA System for remote control generator.
operations.
3.- Manual generation output control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator and the
electrical network in order to make the synchronization operations. 4.- Manual power factor control of the synchronous generator.
This application includes: 5.- Manual power flows control of the synchronous generator.
Modules: 6.- Logic operations of disconnectors and circuit breakers of a
generation substation.
 N-ALI01. Industrial Main Power Supply.
7.- Manual operation for synchronization of the synchronous
 N-BUS01. Generation Busbar. generator with the mains.
 N-BUS02. Coupling Busbar. 8.- Synchronoscope use for measuring mismatch voltages,
 N-BUS03. Grid Busbar. frequencies and voltage modules.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-EALDC/G. DC Generator Analyzer.
 N-ASY3PH. Three-Phase Automatic Synchronoscope.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

AEL-GCM-P-03S. Manual Synchronization System of Synchronous Generator with Servomotor and Protection
Relays, with SCADA
The AEL-GCM-P-03S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator and the necessary operations for synchronization with
2.- Manual current excitation control of the synchronous
the mains.
generator.
The speed of generator-motor group is controlled by means of
3.- Manual generation output control of the synchronous
servomotor.
generator.
Besides, this application includes a series of protection relays in
4.- Manual power factor control of the synchronous generator.
order to make different short circuit tests.
5.- Manual power flows control of the synchronous generator.
This application includes a SCADA System for remote control
operations. 6.- Logic operations of disconnectors and circuit breakers of a
generation substation.
This application represents an actual generation substation with
double bus bar configuration, one synchronous generator moved 7.- Manual operation for synchronization of the synchronous
by mean of servomotor and the electrical network in order to make generator with the mains.
the synchronization operations. 8.- Synchronoscope use for measuring mismatch voltages,
This application can be combined with other applications of frequencies and voltage modules.
transmission/distribution systems and loads systems areas. Some 9.- Studying of the following protection relays: differential
examples of recommended configurations are shown at the end of protection relay of the step-up transformer and the generator
this catalogue. protection relay.
10.- Studying of the following short circuits types:
Three-Phase short circuit.
Two-Phase short circuit.
Two-Phase to ground short circuit.
Single-Phase short circuit.
11.- Adjusting of protection relay depending of the situation.
12.- Analyzing of the electrical faults transients with a special
software.

Page 18 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-03S. Manual Synchronization System of Synchronous Generator with Servomotor, with SCADA
The AEL-GCM-03S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
and the necessary operations for synchronization with the mains.
The speed of generator-motor group is controlled by means of 2.- Manual current excitation control of the synchronous
servomotor. generator.
This application includes a SCADA System for remote control 3.- Manual generation output control of the synchronous
operations. generator.
This application represents an actual generation substation with 4.- Manual power factor control of the synchronous generator.
double bus bar configuration, one synchronous generator moved 5.- Manual power flows control of the synchronous generator.
by mean of servomotor and the electrical network in order to make
6.- Logic operations of disconnectors and circuit breakers of a
the synchronization operations.
generation substation.
This application can be combined with other applications of
7.- Manual operation for synchronization of the synchronous
transmission/distribution systems and loads systems areas. Some
generator with the mains.
examples of recommended configurations are shown at the end of
this catalogue. 8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.

AEL-GCM-P-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid and
Protection Relays, with SCADA
The AEL-GCM-P-01S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator in an isolated grid and protection relays, with SCADA.
2.- Manual current excitation control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator and
different protection relays to study electrical faults. 3.- Manual generation output control of the synchronous
generator.
This application includes:
4.- Manual power factor control of the synchronous generator.
Modules:
5.- Manual power flows control of the synchronous generator.
 N-ALI01. Industrial Main Power Supply.
6.- Logic operations of disconnectors and circuit breakers of a
 N-BUS01. Generation Busbar. generation substation.
 N-BUS02. Coupling Busbar. 7.- Studying of the following protection relay: differential
 N-AVR/P. Automatic Voltage Regulator. protection relay.
 N-EALD. Network Analyzer Unit with Computer Data 8.- Studying of the following short circuits types:
Acquisition. Three-Phase short circuit.
 N-EALDC/G. DC Generator Analyzer. Two-Phase short circuit.
 N-VVCA5K. 5KW Motor Speed Controller. Two-Phase to ground short circuit.
 N-PLC01. PLC01 Control Module. Single-Phase short circuit.
 N-ERP-PDF01. Differential Protection Relay Module.
9.- Adjusting of protection relay depending of the situation.
 N-ERP-MF01. Digital Fault Simulator Module. 10.- Analyzing of the electrical faults transients with a special
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. software.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 19 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid,
with SCADA
The AEL-GCM-01S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
in an isolated grid, with SCADA.
2.- Manual current excitation control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration and one synchronous generator.
3.- Manual generation output control of the synchronous
This application includes: generator.
Modules: 4.- Manual power factor control of the synchronous generator.
 N-ALI01. Industrial Main Power Supply. 5.- Manual power flows control of the synchronous generator.
 N-BUS01. Generation Busbar. 6.- Logic operations of disconnectors and circuit breakers of a
 N-BUS02. Coupling Busbar. generation substation.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-EALDC/G. DC Generator Analyzer.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 20 www.edibon.com
1. GENERATION SYSTEMS

AEL-GAD- Additional Generation Systems options:


They are additional modular applications focused on the study of different generation power plants, such as pumping power systems, energy recovery
systems in the event of black-outs, power generation systems with two generators in parallel and hydroelectric generation systems.
The objective is to familiarize the student with the control devices employed in this type of systems nowadays.
These applications can work individually or be complemented with other applications of generation, power transmission and loads.
These applications allow to perform either a direct local control on each module or to control the entire application with the SCADA.
There are different topics included, depending on the application:
- Pumping Power Plant.
- Diesel generator with auto-start for the recovery of the energy in the event of black-outs.
- Automatic generation system with two generators in parallel.
- Hydroelectric Power Plant.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GAD-
Additional Generation Systems options

Applications
AEL-GAD-01S. Pumping Power Plant, with SCADA.
AEL-GAD-02S. Auto-Start Diesel Generator Trainer for Recovery of the Energy System due to Black-Outs, with SCADA .
AEL-GAD-03S. Automatic Generation System with Two Parallel Generators, with SCADA.
AEL-GAD-04S. Hydroelectric Power Plant, with SCADA.

Applications
AEL-GAD-01S. Pumping Power Plant, with SCADA
The AEL-GAD-01S is a modular application designed to study the Some practical possibilities:
pumped storage power stations. 1.- How pumped storage power plants operate.
This application has a SCADA Control Software to simulate how 2.- Start and synchronisation of synchronous machines.
the electrical energy is stored and how the potential energy of water
is converted into electrical power which is then fed back into the 3.- Manual power regulation: both in generator and motor
grid. modes.
4.- Semi-automatic active and reactive power control.
5.- Smart grid integration of pumped storage power plants.
6.- Fully-automatic compensation for externally measured active
and reactive power.
7.- SCADA open and closed-loop system control.

AEL-GAD-02S. Auto-Start Diesel Generator Trainer for Recovery of the Energy System due to Black-Outs,
with SCADA
The AEL-GAD-02S is a modular system designed to study the Some practical possibilities:
recovery of the energy of the electrical grid due to black-outs. 1.- Simulation of black-out.
It includes a diesel generator used to supply the energy needed 2.- Recovery of the power when a black-out appear.
when the electrical grid is disconnected.
3.- Controlling of a diesel-generator.
Besides, this system includes SCADA System with which the student
will control different maneuvers. 4.- Automatic starting of diesel-generator and coupling to the grid.

AEL-GAD-03S. Automatic Generation System with Two Parallel Generators, with SCADA
The AEL-GAD-03S is a modular application designed to study how Some practical possibilities:
two parallel generators work. 1.- Manual/automatic frequency control of the synchronous
It includes two voltage and frequency controllers to study the most generators in parallel operation.
important operations carried out to control the synchronous 2.- Manual/automatic current excitation control of the
generator. synchronous generator.
This application has a SCADA Control System to monitor all 3.- Manual/automatic generation output control of the
control process of the electrical machines. synchronous generators in parallel operation.
4.- Manual/automatic power factor control of the synchronous
generators in parallel and isolated operation.
5.- Manual/automatic power flows control of the synchronous
generators in parallel and isolated operation.
6.- Manual/automatic operation for synchronization of the
synchronous generator with the mains.
7.- Load sharing of two parallel generators.
8.- Active power load sharing with two parallel generators.
9.- Reactive power load sharing with two parallel generators.

Page 21 www.edibon.com
1. GENERATION SYSTEMS

AEL-GAD-04S. Hydroelectric Power Plant, with SCADA


The AEL-GAD-04S is a modular application designed to study the Some practical possibilities:
Hydroelectric Power Plants. 1.- How hydroelectric power plants operate.
On this application the students will learn how hydroelectric power 2.- Start and synchronisation of synchronous machines.
plants work. In order to simulate the main operations of these
alternative power systems, with a motor driving a slip ring three- 3.- Manual power regulation.
phase asynchronous motor will be simulate the main operations of 4.- Manual active and reactive power control.
these power systems.
5.- Automatic active and reactive power control.
This application includes a SCADA Control System in order to carry
6.- Smart grid integration of hydroelectric power plants.
out remote control operations as open and close circuit breakers,
monitoring all electrical parameters as active and reactive power, 7.- Fully-automatic compensation for externally measured active
currents, voltages, etc. and reactive power.
This application includes: 8.- SCADA open and closed-loop system control.
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS03. Grid Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC06. PLC06 Control Module.
Generators:
 GMG1.5K3PH. 1.5KW Slip Ring Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).

Page 22 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS

The transmission/distribution systems area has been designed to provide the student the required knowledge for operating energy transmission systems.
Main features of the Transmission/Distribution Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Transmission/Distribution Systems options:
- AEL-T. Transmission and Distribution Power Systems options.

AEL-T- Transmission and Distribution Power Systems options:


We offer modular applications focused on the study of the power distribution and transmission systems.
Starting from simple transmission systems we can upgrade with complex devices, such as protection relays, aerial lines in parallel, transformers with
voltage regulation, meshed network systems, etc.
There are different topics included, depending on the application:
- Study of transmission and distribution power systems with regulation transformer.
- Study of transmission and distribution power systems with regulation transformer and protection relays.
- Transmission and distribution power systems with two aerial lines in parallel.
- Transmission and distribution power systems with two aerial lines in parallel and protections.
- Power flow control in meshed networks.
- Electrical distribution grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA .
AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA.
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

Page 23 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays,
with SCADA
The AEL-T-P-01S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with voltage regulation
Local control:
transformer and protection relays.
1.- Opening and closing basic maneuvers of isolator switches
The AEL-T-P-01S includes a series of modules such as busbars,
and circuit breaker.
transmission line module, distribution transformer with voltage
regulator (TAP), distance protection relay and network analyzers to 2.- Measurements of energy losses in the transmission line.
study different principles of the transmission and distribution systems. 3.- Droop voltage compensation with the voltage regulator TAP.
This application includes SCADA System to control different 4.- Real time measurements of the electrical parameters (voltage,
elements. current, frequency, power factor, active power, reactive power,
This application includes: aparent power, active energy, reactive energy, aparent energy,
etc.).
Modules:
5.- Studying of the energy losses of the transmission line.
 N-ALI01. Industrial Main Power Supply.
6.- Studying of the droop voltages in the transmission line in
 N-BUS04. Emitter Transport Busbar.
function on the load system.
 N-BUS05. Receptor Transport Busbar.
7.- Automatic configuration of the line parameters.
 N-EALD. Network Analyzer Unit with Computer Data
8.- Automatic selection of the line to line capacitive effect.
Acquisition. (2 units)
9.- Automatic selection of line resistor.
 N-PLC02. PLC02 Control Module.
10.- Automatic selection of line inductance.
 N-REG15. Tap Module Regulator.
11.- Simulation of one phase loss.
 N-AE1CD. Transmission Lines Simulator Digital Unit.
12.- Simulation of two phases loss.
 N-ERP-PD01. Distance Protection Relay Module.
13.- Studying of short circuits in different points of transmission
 N-ERP-MF01. Digital Fault Simulator Module.
power system:
Transformers:
a. Symmetric short circuits: three-phase short circuits with
 TRANS3/5KR. 5KW Step-Down Transformer with voltage and without contact impedance.
regulator.
b. Asymmetric faults:
SCADA (Supervision, Control and Data Acquisition).
i. Two-phase short circuit with and without contact
This application can be combined with other applications of impedance.
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this ii. Two-phase to ground shortcircuit with and without
catalogue. contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
14.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
15.- Calculation of the electrical parameters of the line to
configure the distance protection relay (mho characteristic).
16.- Studying in depth of the distance protection relay.
Remote control (with SCADA):
17.- Supervision, Control and Data Acquisition of all electrical
parameters of the transmission line.
18.- Monitoring of energy losses of transmission lines from the PC.
19.- Remotely control of distribution transformer voltage regulator
(TAP). Compensation of droop voltages of the transmission
line.
20.- Studying of energy losses of the transmission line.
21.- Remote measurement of droop voltages in the transmission
line in function on the system load.
22.- Remote automatic configuration of the transmission line
impedance.
23.- Remote automatic selection of the line to line capacitive effect
of the transmission line.
24.- Remote automatic selection of the line resistor of the
transmission line.
25.- Remote automatic selection of the line inductance of the
transmission line.
26.- Remote automatic selection of one line phase loss.
27.- Remote automatic selection of two line phases loss.

Continue...

Page 24 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA (continuation)

Some practical possibilities (continuation):


28.- Remotely control of short circuits in different points of the
transmission power system:
a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
b. Asymmetric faults:
i. Two-phase short circuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without
contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
29.- Short circuits temporal evolution recording of voltage and
currents phasors for further analysis.
30.- Calculation of the electrical parameters of the transmission
line for subsequent configuration of the distance relay (mho
characteristic).
31.- Studying in depth of the distance protection relay.

AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA
The AEL-T-01S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with voltage regulation 1.- Open and close basic maneuvers with disconnectors and
transformer. circuit breakers.
The AEL-T-01S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module, distribution transformer with voltage
regulator (TAP) and network analyzers to study different principles 3.- Drop voltage compensation with the voltage regulator of the
of the transmission and distribution systems. distribution transformer (TAP).
This application includes SCADA System to control different 4.- Real time measurement of the electrical parameters of the
elements. system.
This application includes: 5.- Studying of the energy losses in the transmission line.
Modules: 6.- Studying of the drop voltage in function on the line currents.
 N-ALI01. Industrial Main Power Supply.
 N-BUS04. Emitter Transport Busbar.
 N-BUS05. Receptor Transport Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-PLC02. PLC02 Control Module.
 N-REG15. Tap Regulator Module.
 N-AE1CD. Commutable Transmission Line Simulation
Unit.
Transformers:
 TRANS3/5KR. 5kW Step-Down Transformer with voltage
regulator.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

Page 25 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays,
with SCADA
The AEL-T-P-02S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with two aerial parallel 1.- Open and close basic maneuvers with disconnectors and
lines and protection relays. circuit breakers.
The AEL-T-P-02S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module, distance protection relay and network 3.- Real time measurement of the electrical parameters of the
analyzers to study different principles of the transmission lines system.
working in series and parallel.
4.- Studying of the energy losses in the transmission lines.
This application includes SCADA System to control different
elements. 5.- Studying of the drop voltage in function on the line currents.
This application can be combined with other applications of 6.- Distribution of power and current among parallel-connected
generation systems and loads systems areas. Some examples of lines of equal length.
recommended configurations are shown at the end of this 7.- Distribution of power and current among parallel-connected
catalogue. lines of unequal length.
8.- Distribution of power and current among series-connected
lines of equal length.
9.- Distribution of power and current among series-connected
lines of unequal length.
10.- Load distribution, power flow.
11.- Voltage distribution.
12.- Studying of short circuits:
Three-Phase short circuit.
Single-Phase short circuit.
Two-Phase short circuit.
14.- Recording of voltage and current phasors evolution during the
short circuits for further analysis.
15.- Real time measurement of the electrical parameters of the
system.
16.- Studying of the energy losses in the transmission line.
17.- Studying of the drop voltage in function on the line currents.

AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA
The AEL-T-02S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with two aerial parallel 1.- Open and close basic maneuvers with disconnectors and
lines. circuit breakers.
The AEL-T-02S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module and network analyzers to study different 3.- Real time measurement of the electrical parameters of the
principles of the transmission lines working in series and parallel. system.
This application includes SCADA System to control different 4.- Studying of the energy losses in the transmission lines.
elements. 5.- Studying of the drop voltage in function on the line currents.
This application can be combined with other applications of 6.- Distribution of power and current among parallel-connected
generation systems and loads systems areas. Some examples of lines of equal length.
recommended configurations are shown at the end of this 7.- Distribution of power and current among parallel-connected
catalogue. lines of unequal length.
8.- Distribution of power and current among series-connected
lines of equal length.
9.- Distribution of power and current among series-connected
lines of unequal length.
10.- Load distribution, power flow.
11.- Voltage distribution.

AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA
The AEL-T-P-04S is a modular application designed to study Some practical possibilities:
switching operations and protection relays in the double busbar 1.- Basic circuits of a three-pole, double busbar system with
used in the electrical substations. incoming/ outgoing feeder.
With this application the student will learn the most important 2.- Three-phase, double busbar system with load.
maneuvers carried out in the substations busbars.
3.- Busbar changeover without interruption of the branch.
The AEL-T-P-04S includes a series of modules such as busbar with
incoming/outgoing feeder, loads, protection relays and network 4.- Preparation of algorithms for various switching operations.
analyzers to study different principles of the distribution networks. 5.- Busbar coupling.
The double busbar model incorporates all functions of practical 6.- Studying of different short circuits in the busbars.
relevance. On this application are integrated instruments for
measuring currents and voltages which permit direct analyses of
switching operations.
This application includes SCADA System to control different
substation elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.
Page 26 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA
The AEL-T-04S is a modular application designed to study the Some practical possibilities:
double busbar configuration used in the electrical substations. 1.- Basic circuits of a three-pole, double busbar system with
With this application the student will learn the most important incoming/ outgoing feeder.
maneuvers carried out in the substations busbars. 2.- Three-phase, double busbar system with load.
The AEL-T-04S includes a series of modules such as busbar with 3.- Busbar changeover without interruption of the branch.
incoming/outgoing feeder, loads and network analyzers to study
different principles of the distribution networks. 4.- Preparation of algorithms for various switching operations.
The double busbar model incorporates all functions of practical 5.- Busbar coupling.
relevance. On this application are integrated instruments for
measuring currents and voltages which permit direct analyses of
switching operations.
This application includes SCADA System to control different
substation elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA


The AEL-T-03S is a modular application designed to study the
power flow control in meshed networks.
The AEL-T-03S includes a series of modules such as transmission
line modules, loads and network analyzers to study different
principles of the power flows in meshed networks.
This application includes SCADA System to control different
elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

Page 27 www.edibon.com
3. LOADS SYSTEMS

The loads systems area has been designed to provide all the knowledge related with operation of loads systems required: control of the reactive power,
protection systems used in the “feeders”, request against bad changes, etc.
Main features of the Load Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Load Systems options:
- AEL-C- Conventional Loads options.
- AEL-CS- Special Loads options.

AEL-C- Conventional Loads options:


We offer modular applications focused on the study of the final loads energy management in a power system.
Starting from basic applications, in which the regulation of the reactive power is studied manually, we can upgrade to applications in which advanced
control devices for the reactive power, protection systems, etc, are included.
There are different topics included, depending on the application:
- Study of the power correction devices employed nowadays. Startup and check of an automatic power factor controller.
- Study of the “feeder” overcurrent protection relay by injecting faults in final loads systems.
- Study of the different power factors depending on the type of load connected to the grid and manual compensation of the reactive power based
on previous theoretical calculations.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-C-
Conventional Loads options

Applications

AEL-C-P-02S. Load Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

AEL-C-02S. Load Systems with Automatic Power Factor Compensation, with SCADA.

AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA.

AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

Page 28 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-P-02S. Load Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA
The AEL-C-P-02S is a modular application designed to study Some practical possibilities:
automatic reactive power compensation controllers and protection
Local control:
relays in a feeder. With this application the student will learn to
calculate the required capacitor banks in function on the 1.- Opening and closing basic maneuvers of isolator switches
demanded reactive energy. and circuit breaker of distribution substation.
Besides, the theorey will be compared with an actual power factor 2.- Real time measurements of all electrical parameters of the
controller. distribution systems.
The AEL-C-P-02S inlcudes a series of modules such as automatic 3.- Studying of short circuits in different points of load power
reactive power controller, capacitor banks, resistor loads, inductor system:
loads, feeder manager protection relay and network analyzers to
study different principles of the energy quality, power factor a. Symmetric short circuits: three-phase short circuits with
compensation, short circuits, etc. and without contact impedance.

The feeder protection relay includes on this application lets the b. Asymmetric faults:
student to study different faults in the distribution and loads i. Two-phase short circuit with and without contact
systems. impedance.
This application includes a SCADA System to control different ii. Two-phase to ground shortcircuit with and without
elements and analyze the energy quality. contact impedance.
This application includes: iii. Single-phase short circuit with and without contact
Modules: impedance.

 N-ALI01. Industrial Main Power Supply. 4.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
 N-BUS06. Distribution Busbar.
5.- Studying in depth of feeder protection relay.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. Remote control (with SCADA System):

 N-CFP. Advanced Power Factor Controller Module. 6.- Supervision, Control and Data Acquisition of all electrical
parameters of the load distribution system.
 N-PLC03. PLC03 Control Module.
7.- Remote control of the demanded active power.
 N-CAR19T4D. Three-Phase Digital Capacitor Banks
Module. 8.- Remote control of the demanded inductive reactive power.

 N-CAR36T3D. Three-Phase Digital Bank of Commutable


9.- Remote control of the demanded capacitive reactive power.
Inductances Module. 10.- Remote measurement of all electrical parameters of load
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
distribution system.

 N-CAR19T3D. Three-Phase Digital Bank of Commutable


11.- Remotely control of short circuits in different points of the load
Capacitors Module. power system:

 N-ERP-MA01. Feeder Management Relay Module.


a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
 N-ERP-MF01. Digital Fault Simulator Module.
b. Asymmetric faults:
SCADA (Supervision, Control and Data Acquisition).
i. Two-phase short circuit with and without contact
This application can be combined with other applications of impedance.
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the ii. Two-phase to ground shortcircuit with and without
end of this catalogue. contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
12.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
13.- Studying in depth of feeder protection relay.
14.- Automatic power factor compensation in function on the
demanded reactive energy.

Continue...

Page 29 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-02S. Load Systems with Automatic Power Factor Compensation, with SCADA
The AEL-C-02S is a modular application designed to study Some practical possibilities:
automatic reactive power compensation controllers. 1.- Calculating parameters for compensation capacitors.
With this application the student will learn to calculate the required 2.- Compensation using various capacitors.
capacitor banks in function on the demanded reactive energy.
3.- Determining stage power.
Besides, the theory will be compared with an actual power factor
controller. 4.- Manual compensation of reactive power.
The AEL-C-02S includes a series of modules such as automatic 5.- Studying of the power factor controller:
reactive power controller, capacitor banks, resistor loads, inductor Commissioning.
loads and network analyzers to study different principles of the
energy quality, power factor compensation, etc. Programming.
This application includes a SCADA System to control different Capacitor banks connections.
elements and analyze the energy quality. 6.- Automatic compensation of reactive power.
This application includes: 7.- Manual compensation of reactive power.
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS06. Distribution Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CFP. Advanced Power Factor Controller Module.
 N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA
The AEL-C-P-01S is a modular application designed to study Some practical possibilities:
manual reactive power compensation with feeder protection relay. 1.- Calculating parameters for compensation capacitors.
With this application the student will learn to calculate the required
2.- Compensation using various capacitors.
capacitor banks in function on the demanded reactive energy.
3.- Determining stage power.
The AEL-C-P-01S includes a series of modules such as capacitor
banks, resistor loads, inductor loads, feeder protection relay and 4.- Manual compensation of reactive power.
network analyzers to study different principles of the energy quality, 5.- Studying of short circuits:
power factor compensation, short circuits, etc. Three-Phase short circuit.
This application includes SCADA System to control different Single-Phase short circuit.
elements and analyze the energy quality.
Two-Phase short circuit.
This application includes:
6.- Recording of voltage and current phasors evolution during the
Modules: short circuits for further analysis.
 N-ALI01. Industrial Main Power Supply. 7.- Real time measurement of the electrical parameters of the
 N-BUS06. Distribution Busbar. system.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
 N-ERP-MA01. Feeder Management Relay Module.
 N-ERP-MF01. Digital Fault Simulator Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 30 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA
The AEL-C-01S is a modular application designed to study manual Some practical possibilities:
reactive power compensation. With this application the student will
1.- Calculating parameters for compensation capacitors.
learn to calculate the required capacitor banks in function on the
demanded reactive energy. 2.- Compensation using various capacitors.
The AEL-C-01S includes a series of modules such as capacitor 3.- Determining stage power.
banks, resistor loads, inductor loads and network analyzers to 4.- Manual compensation of reactive power.
study different principles of the energy quality, power factor
compensation, etc.
This application includes SCADA System to control different
elements and analyze the energy quality.
This application includes:
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS06. Distribution Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 31 www.edibon.com
3. LOADS SYSTEMS

AEL-CS- Special Loads options:


We offer modular applications focused on the study of the dynamic loads, complex loads, consumption measurement, control of peak loads, etc.
There are different topics included, depending on the application:
- Analysis, measurement of complex loads and control of peak loads.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-CS-
Special Loads options

Applications
AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load Monitoring, with SCADA.

Applications

AEL-CS-03S. Complex Loads, Power Consumption Measurement and Peak Load Monitoring, with SCADA
The AEL-C-03S is a modular application designed to study the
complex load, power consumption measurement and peak load
monitoring.
With this application the student will learn the difference between
star-delta loads connection, measurement of reactive and active
energy for symmetric and asymmetric RL loads, over-compensation
RC load, etc.
The AEL-C-03S includes a series of modules such as capacitor
banks, resistor loads, inductor loads and network analyzers to study
different principles of the complex loads.
This application includes SCADA System.
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 32 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

SCADA

In order to understand in depth how work actual power systems, EDIBON offers a series of "Modular Smart Grid Power Systems Simulators".

The "Modular Smart Grid Power Systems Simulators" are configured applications of generation, transmission and loads areas that has been described
individually at the beginning of this catalogue.

The objective of these Power Systems Simulators is give the students different technical solutions to understand how nowadays work together the actual
generation, transmission, distribution and load power systems.

Due to EDIBON provides a wide variety of applications, different applications configurations of generation, transmission/distribution and loads are
recommended in order to form a “Modular Smart Grid Power Systems Simulator”.

Examples of Recommended Systems Simulators Configurations:

AEL-MPSS-01. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission Line, Loads and Protection
Relays, with SCADA.

AEL-MPSS-02. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission Line and Loads, with SCADA.

AEL-MPSS-03. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission Line, Loads and Protection
Relays, with SCADA.

AEL-MPSS-04. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission Line and Loads, with SCADA.

Page 33 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-01. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission
Line, Loads and Protection Relays, with SCADA
The AEL-MPSS-01S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It is one of the most comprehensive and advanced modular smart grid power systems simulator because it shows the most important operations of an
entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
 AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
 AEL-GCA-P-02S. Generation System with Automatic
Control of Synchronous Generator,
AEL-GCM-P-02S. Generation System with Manual
Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S.
SCADA.
Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
AEL-GCM-02S. Generation System with Manual System due to Black-Outs, with
AEL-GCA-02S. Generation System with Automatic SCADA.
Control of Synchronous Generator and Control of Synchronous Generator
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with Servomotor Synchronous Generator with with SCADA.
and Protection Relays, with SCADA. Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
 AEL-T-P-01S.
AEL-T-01S.
Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

 AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and


Protection Relays, with SCADA .
AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-01S offers the following possibilities and others:


Studying of high voltage protection systems:
It is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in real electrical
substations that give to AEL-MPSS-01S a great authenticity and variety of fault tests.
It incorporates protection relays as the overcurrent protection relay, the differential protection relay for generators and transformers, the distance
protection relay and the feeder protection relay.
Studying of generation substations:
It incorporates a sophisticated system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the energy carried along line like energy losses, drop voltages, etc. It
includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the load. It includes
different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations. It incorporates
different loads modules to simulate energy consumptions.
The AEL-MPSS-01S has a SCADA System for remotely control operations.
Page 34 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-02. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission
Line and Loads, with SCADA
The AEL-MPSS-02S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows different operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
 AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic AEL-GCM-P-02S. Generation System with Manual SCADA.
Control of Synchronous Generator, Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S. Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
System due to Black-Outs, with
 AEL-GCA-02S. Generation System with Automatic
Control of Synchronous Generator and
AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator
and Synchronization, with SCADA. AEL-GAD-03S.
SCADA.
Automatic Generation System
Synchronization, with SCADA.
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with
Synchronous Generator with Servomotor with SCADA.
Servomotor and Protection Relays,
and Protection Relays, with SCADA. AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.

 AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with


SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-02S offers the following possibilities and others:


Studying of generation substations:
It incorporates a sophisticated system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc. It
includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the load.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations.
It incorporates different loads modules to simulate energy consumptions.
The AEL-MPSS-02S has a SCADA System for remotely control operations.
Page 35 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-03. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission
Line, Loads and Protection Relays, with SCADA
The AEL-MPSS-03S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows the most important operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
 AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic
Control of Synchronous Generator,
 AEL-GCM-P-02S. Generation System with Manual
Control of Synchronous Generator,
AEL-GAD-02S.
SCADA.
Auto-Start Diesel Generator
Synchronization and Protection Relays, Synchronization and Protection
Relays, with SCADA. Trainer for Recovery of the Energy
with SCADA. System due to Black-Outs, with
AEL-GCA-02S. Generation System with Automatic AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator SCADA.
Control of Synchronous Generator and
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with Servomotor Synchronous Generator with with SCADA.
and Protection Relays, with SCADA. Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
 AEL-T-P-01S.
AEL-T-01S.
Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
 AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-03S offers the following possibilities and others:


Studying of high voltage protection systems:
It is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in real electrical
substations that give to AEL-MPSS-03S a great authenticity. It incorporates protection relays as the overcurrent protection relay, the differential
protection relay for generators and transformers, distance protection relay and feeder protection relay.
Studying of generation substations:
It incorporates a manual control system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc. It includes
a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations. It
incorporates different loads modules to simulate energy consumptions and to study the manual compensation of reactive power.
The AEL-MPSS-03S has a SCADA System for remotely control operations.

Page 36 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-04. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission
Line and Loads, with SCADA
The AEL-MPSS-04S is a Modular Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows different operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
 AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic AEL-GCM-P-02S. Generation System with Manual SCADA.
Control of Synchronous Generator, Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S. Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
AEL-GCA-02S. Generation System with Automatic
Control of Synchronous Generator and
 AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator
System due to Black-Outs, with
SCADA.
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with with SCADA.
Synchronous Generator with Servomotor
Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
and Protection Relays, with SCADA.
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in an Control of Synchronous Generator in
Isolated Grid and Protection Relays, with an Isolated Grid and Protection
SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in an Control of Synchronous Generator in
Isolated Grid, with SCADA. an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .

 AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-04S offers the following possibilities and others:


Studying of generation substations:
It incorporates a manual control system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc.
It includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations.
It incorporates different loads modules to simulate energy consumptions and to study the manual compensation of reactive power.
The AEL-MPSS-04S has a SCADA System for remotely control operations.

Page 37 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

Modular Smart Grid Power Systems Simulator,


with Automatic Control Generation,Transmission Line,
Loads and Protection Relays, with SCADA
Technical Teaching Equipment
AEL-MPSS-01

AEL-GCA-P-02S AEL-T-P-01S AEL-C-P-02S


Generation System with Automatic Control Transmission and Distribution Power Systems Loads Systems with Automatic Power Factor
of Synchronous Generator, Synchronization with Regulation Transformer and Protection Relays, Compensation and Protection Relays, with SCADA
and Protection Relays, with SCADA with SCADA

+ +

EDIBON SCADA System

OPEN CONTROL
+ Control
MULTICONTROL Interface
+
REAL TIME CONTROL
SCADA Software

This simulator consists of:

AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection
Relays, with SCADA.

AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with
SCADA.

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

SCADA (Supervision, Control and Data Acquisition).

Workbenches and PC.

Page 38 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
INTRODUCTION
Due to electricity can not be stored in large quantities and economically not profitable, so that at each instant must be generated that is consumed. The
demanded electric power varies from day to day, so that the generation should follow the same temporal variation, keeping the nominal value of the
system frequency, 50 Hz, and other conditions that define the normal operating state of the power system, all with the economic objective of lower cost of
production.
For this purpose, the basic objective of the systems of regulation and control of generators installed in power plants generation is to ensure that the
demanded power meets continuously, maintaining continuity of supply and the operating parameters of the system within limits. This function is performed
automatically from the generators and control centers through automatic voltage regulation (AVR") and, above all, through automatic generation control
(AGC").
The AEL-MPSS-01 simulator has been developed to demonstrate how Smart Grids operate within the large power systems:
How electricity is generated?
How electricity is transported?
What happens when there is a change in the energy demand?
What protection systems are used in generation, transmission, distribution and consumption systems?
What happens when there is a fault anywhere in the power system? What is the proper configuration of the protection relays so that there is selectivity in
the power system?
How is carried out the regulation of the turbine and synchronous generator?
These and many other questions answers the Modular Smart Grid Power Systems Simulator, with automatic control generation, transmission line, loads
and protection relays, with SCADA.

GENERAL DESCRIPTION
The AEL-MPSS-01 has been developed to study in depth the Smart Grid in Generation, Transmission/Distribution and Loads areas.
To facilitate the study of all characteristics issues, and many more, the AEL-MPSS-01 simulator is divided in three applications. Each application has been
developed to study in depth a different area of Smart Grids Power Systems:
- AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
- AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
- AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.
The AEL-MPSS-01 is one of the most comprehensive and advanced modular smart grid power systems simulator for the following reasons:
- The AEL-MPSS-01 integrates the most important Smart Grid technology in all elements that form the power system.
- In a single system we can study the operation of an entire power system, from energy is generated until it reaches the final consumer.
- The AEL-MPSS-01 is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in
real electrical substations that give to AEL-MPSS-01 a great authenticity.
- The AEL-MPSS-01 incorporates protection relays as the overcurrent protection relay, the differential protection relay for generators and transformers,
long distance protection relay and the protection relay for feeders, which make the system AEL-MPSS-01 a forefront unit in the field of Smart Grids.
- The AEL-MPSS-01 incorporates a sophisticated system of control and regulation of the turbine and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation:
- Manual/automatic control and regulation of the generator voltage (Automatic Voltage Regulator).
- Manual/automatic control and regulation of the generator frequency (turbine control).
- Manual/automatic control and regulation of the power factor of the generator.
- The AEL-MPSS-01 incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the
load.
- The SCADA System (Supervision, Control and Data Acquisition) whose description can be read below.
Note: AEL-MPSS-01 includes the workbenches and PC.
SCADA System description
The most innovative of the Modular Smart Grid Power Systems Simulator is that it includes SCADA (Supervision, Control and Data Acquisition System) that
shows the same behaviour of actual SCADA systems used in the actual power systems. The SCADA Software allows students to take full remote control of
the power system and perform all sorts of maneuvers from a synoptic that represents the national power grid. This software allows, among other options,
the following:
- Opening and closing actual logic of disconnect switches and circuit breakers.
- Manual and automatic control of the synchronous generator excitation.
- Manual and automatic control of the synchronous generator frequency.
- Manual and automatic power factor control of the synchronous generator.
- Manual and Automatic synchronization control of the synchronous generator with the mains.
- Faults injection in different parts of the system.
- Change in the energy demand of the system with automatic response of the turbine-generator group.
- Real time monitoring the status of disconnectors and circuit breakers.
- Real time monitoring system alarms when the electrical faults are injected.
- Measurement of active, reactive and apparent power at different points of the system.
- Measurement of voltage, current and power factor at different points of the system.
Continue...

Page 39 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
The SCADA System (Supervision, Control and Data Acquisition ) allows the user to understand, in a clear and simple way, how is the management and
control of generation, transmission/distribution and loads power systems.
Here are some screenshots of the SCADA Software shown:

General scheme of the power grid that allows us to control the "generation", "transmission/distribution" and "loads".

By "clicking" on generation, the most important functions are deployed to control the power flows of our substation power generation:
opening and closing logic control of disconnect switches and circuit breakers, measuremetns of the electrical parameters of the generator
and the network, possibilities of faults injections in many points of the generation system, supervision of electrical faults, emergency stop of
the generator, etc.
Continue...

Page 40 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

Screen for preselecting electrical faults: fault preselecting of three-phase, two-phase and single-phase with or without fault resistor.

Display control of the turbine and the synchronous generator. This menu offers multiple possibilities for control and regulation of the group.
-Precise and manual control of turbine frequency.
-Automatic control of the turbine frequency.
-Precise manual control of the excitation of the synchronous generator.
-Automatic control of synchronous generator excitation.
-Manual synchronization of synchronous generator with the mains.
-Automatic synchronization of synchronous generator with electrical network.
-Island operation mode.
-Alarm monitoring of frequency and reverse power.
-Emergency stop.
-Supervision of the electrical parameters of the generator and the power grid.
-Monitoring the speed of the turbine.
Continue...

Page 41 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

By "clicking" on transmission/distribution, the most important functions are deployed to control the elements of our receiving and emitter
substation:
-Setting of resistance, inductance and capacitance parameters of the transmission line.
-Opening and closing logic control of disconnect switches and circuit breakers.
-Measurements of the electrical parameters upstream and downstream of the transmission line for the study of energy losses in
transporting.
-Faults injection in many points of the transmission system.
-Supervision of electrical faults.
-Voltage adjusting with the distribution transformer with the voltage regulator TAP.

Setup menu of the electrical parameters of the transmission line.


Continue...

Page 42 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

Load voltage regulation menu.

By "clicking" on loads, the most important functions are deployed to control the elements of our distribution substation:
-Setting the resistance, inductance and capacitance parameters loads.
-Opening and closing control logic of disconnect switches and circuit breakers.
-Measuring of the demanded electrical parameters.
-Faults injection in many points of the loads system.
-Supervision of electrical faults.

Page 43 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
SPECIFICATIONS
The AEL-MPSS-01 simulator includes three applications. Each application has been developed to study in depth a different area of Smart Grids Power
Systems:
- AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
- AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
- AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection
Relays, with SCADA.

Continue...

Page 44 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)
The AEL-GCA-P-02S is a modular application developed to study the actual generation power systems with Smart Grid Technology.
The Generation System with Automatic Control of the Synchronous Generator, Synchronization and Protection Relays, with SCADA (AEL-GCA-P-02S),
consists of a series of modules that allows us to simulate the most important operations of control, regulation and supervision performed in a Generation
Power System, that is to say, from the electrical energy is generated and raised it with the step-up transformer, until the injection of this energy to the grid.
To perform these operations, in the AEL-GCA-P-02S application are included certain devices that make our application a true Smart Grid:
- Modules to control and regulate the turbine-generator group:
Manual/Automatic control and regulation of the generator voltage (Automatic Voltage Regulator).
Manual/Automatic control and regulation of the generator frequency (turbine control).
Manual/Automatic control and regulation of the generator power factor.
- The overcurrent protection relay, the differential protection relay for generators and transformers, and management relay of generators.
- It includes a sophisticated fault injection system in order to analyze the transients evolution and to observe the request of the protection relays used on
this application.
- Network Analyzers that show us in real time the electrical parameters of the nodes of the system.
- Synchronizing devices for the synchronization maneuvers of synchronous generator and the grid that show us the phases sequence, the difference of
voltage and frequency between the generator and the grid.

The AEL-GCA-P-02S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS01. Generation Busbar.
N-BUS02. Coupling Busbar.
N-BUS03. Grid Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)
N-EALDC/G. DC Generator Analyzer.
N-AVR/P. Automatic Voltage Regulator.
N-VVCA5K. 5KW Motor Speed Controller.
N-ASY3PH. Three-Phase Automatic Synchronoscope.
N-PLC01. PLC01 Control Module.
N-ERP-SFT01. Overcurrent Protection Relay Module.
N-ERP-PDF01. Differential Protection Relay Module.
N-ERP-PGC01. Generator Protection and Control Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
Transformers:
TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
 N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button.
Safety key.
Three-phase terminal connections.
Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS01. Generation Busbar.


Double generation busbar Module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.
Continue...

Page 45 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-BUS02. Coupling Busbar.


Double coupling busbar Module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.

N-BUS03. Grid Busbar.


Grid busbar module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Fuses: Line fuses 3x10A.
Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-EALDC/G. DC Generatoy Analyzer.


DC Analyzer Module.
Rated voltage range: 0-100 Vdc.
Rated current range: 0-10 A.
Communication port RS-485.
2 Power connectors with 7 pin.
ON-OFF Switch.
Terminal connections.
Fuse 10 A.

N-AVR/P. Automatic Voltage Regulator.


Generator voltage regulator module.
Local/Remote control switch.
Manual/Automatic control switch of generator excitation in local mode.
Potentiometer for manual control of the current excitation.
ON-OFF Switch.
Terminal connections.
Signal connector SUB-D 62 pins.

N-VVCA5K. 5KW Motor Speed Controller.


5KW Motor Speed Controller Module.
Three-Phase Power Supply: 400VAC + N.
Nominal Power: 5KW.
Potentiometer speed control motor.
Start/Stop control switch.
Local/Remote control switch.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
Connection terminals.
Continue...

Page 46 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ASY3PH. Three-Phase Automatic Synchronoscope.


Three-Phase digital and programmable synchronoscope.
Display:
Mains voltage display.
Generator voltage display.
Phases difference of mains and generator display.
Synchronization manual push-button.
Disable push-button sync.
Local/remote control switch.
Indicator lamp of synchronizing contactor.
ON-OFF switch.
Terminal connections.
Safety fuses.
Signal connector SUB-D 62 pins.

N-PLC01. PLC01 Control Module.


PLC Siemens S7-300.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
2 x Fuses 2A.

N-ERP-SFT01. Overcurrent Protection Relay.


Overcurrent protection relay module.
Power supply: 230 VAC.
TRIP indicator lamps.
Overcurrent and Earth fault protection.
Communications connector DB9 RS-232.
Signals connector SUB-D 62 pin.
ON-OFF Switch.
Terminal connections.
Characteristics:
- Phase, ground and negative sequence overcurrent protection.
- Time-Overcurrent curves of US and IEC.
- Reclosing relays of multiple trips with sequence coordination.
- SELOGIC® enhanced control equations to develop traditional or advanced schemes.
- Logic of local / remote control to change the schemes, operating circuit breakers, etc.
- Recorder of the sequence of events (SER) and reports of events stored in nonvolatile memory.
- Supports ASCII, SEL LMD, and Modbus RTU protocols.

N-ERP-PDF01. Differential Protection Relay Module.


Differential protection relay module.
Power supply: 230 VAC.
TRIP lamp indicator.
Differential protection.
Communications connector DB9 RS-232.
Signals connector SUB-D 62 pins.
ON-OFF switch.
Terminal connectors.
Characteristics:
This module protects transformers with two terminals, generators, reactances and other power devices using a combination of differential,
instantaneous and overcurrent elements. Differential security scheme is achieved through the following actions:
- Dual-slope restricting percentage.
- Lock second and fourth harmonic.
- Lock the fifth harmonic for transformer overexcitation.
- Compensation of the CT connection and the transformers.

Continue...

Page 47 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ERP-PGC01. Generator Relay Protection Module.


Generator protection relay and control module.
Power supply: 230 VAC.
"island grid/parallel grid" control switch.
"local/remote" control switch.
Manual control switches of the generator relay module:
1. SW1 Emergency Stop.
2. SW2 Automatic start of generator-motor group.
3. SW3 reset alarms push-button.
4. SW4 enable frequency control of the generator.
5. SW5 manual permission to close the 52G1 synchronization circuit breaker.
Status indicator lamps. Status indicator alarms lamps. Safety key for synchronization. Emergency stop push-button.
Signal connector SUB-D 62 pins.
ON-OFF switch.
Terminal connections.
Some characteristic of the generator protection relay module N-ERP-PGC01:
- The N-ERP-PGC01 allows to operate with until 16 synchronous generators in island grid mode with reactive and active load share,
automatic start/stop of the generators in function of the demanded energy.
- The N-ERP-PGC01 allows parallel operations of one generator with the mains.
- The N-ERP-PGC01 allows different control modes of circuit breakers as opening, closing and synchronization.
- The N-ERP-PGC01 has analog outputs to control the voltage and frequency regulators of the market.
- Three-phase measurement of the mains and generator voltage.
- Three-phase measurement of the current and power of the generator.
- Single-phase measurement of the mains.
Protections:
- Generator: max/mín-voltage (59/27), max/min-frequency (81O/U), voltage asymmetry, dead bus detection, overload (32), unbalance
load (46), reverse power/reduce (32R/F), overcurrent time define curve (50/51), inverse time overcurrent (IEC255), fault ground
(50N/51N), phases, breakers fault.
- Motor: over/sub speed (12).
- Mains: max/min-voltage (59/27), max/min-frequency (81O/U), vector surge.

N-ERP-MF01. Digital Faults Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
5KVA Three-Phase Grid transformer.
Rated Power: 5KVA.
Rated Primary Voltage: 400VAC Star.
Rated Secondary Voltage: 400VAC Delta.

TRANS3/5KSU. 5KW Three-Phase Step-up Transformer.


5KVA Step-Up transformer.
Rated Power: 5KVA.
Rated Primary Voltage: 400VAC Star.
Rated Secondary Voltage: 400VAC Delta.

Generators:
GMG4.5K3PH. 4.5KW Generator-Motor Group.
Generator-Motor Group mounted in aluminum structure with wheels.
Rated generator power: 4,5 KVA.
I rated stator: 6.5A.
I rated excitation: 4A.
RPM: 3000 rpm.
Rated motor power: 5 KVA.
I rated: 7.2A.
RPM: 3000 rpm.

SCADA (Supervision, Control and Data Acquisition).


Continue...

Page 48 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-GCA-P-02S

With local control mode:

1.- Studying of generation power systems with double busbar 22.- Analysis with SCADA software of active and reactive power of
configuration. synchronous generator.

2.- Studying of opening and closing maneuvers of isolator switches and 23.- Remotely control of manual synchronization of synchronous
circuit breaker in double busbar systems. generator with the mains.

3.- Analysis of the measurements of the power flows of the synchronous 24.- Remotely control of automatic synchronization of synchronous
generator. generator with the mains.

4.- Analysis of the active and reactive power of the generator. 25.- Remotely control of synchronous generator in island grid operation
mode.
5.- Manual synchronization maneuvers of synchronous generator with
the mains. 26.- Studying of Micro-Grids.

6.- Automatic synchronization maneuvers of synchronous generator 27.- Remotely control of synchronous generator in parallel grid operation
with the mains. mode.

7.- Studying of the synchronous generator in island operation mode. 28.- Remotely control of excitation/voltage regulation of synchronous
generator in island mode.
8.- Studying of the Micro-Grids.
29.- Remotely control of the turbine regulation (frequency control) in
9.- Studying of the synchronous generator in grid parallel operation island operation mode.
mode.
30.- Remotely control of excitation/voltage regulation of the synchronous
10.- Studying of excitation/voltage regulation of synchronous generator generator in parallel grid operation mode.
in island mode.
32.- Remotely control of turbine regulation (frequency control) in paralel
11.- Studying of turbine regulation (frequency control) in island mode. grid operation mode.
12.- Studying of excitation/voltage regulation of synchronous generator 33.- Remotely control of power factor regulation of synchronous generator
in parallel grid operation mode. in parallel grid operation mode.
13.- Studying of turbine regulation (frequency control) in parallel grid 34.- Remotely control of short circuits in different points of the generation
operation mode. power system:
14.- Studying of the power factor regulation of synchronous generator in a. Symmetric short circuits: three-phase short circuits with and
parallel grid operation mode. without contact impedance.
15.- Studying of short circuits in different points of generation power b. Asymetric faults:
system:
i. Two-phase short circuit with and without contact impedance.
a. Symmetric short circuits: three-phase short circuits with and
without contact impedance. ii. Two-phase to ground shortcircuit with and without contact
impedance.
b. Asymmetric faults:
iii.Single-phase short circuit with and without contact impedance.
i. Two-phase short circuit with and without contact impedance.
35.- Supervision of TRIPS from the SCADA software (protection relays
ii. Two-phase to ground shortcircuit with and without contact shooting) in the power system.
impedance.
36.- Remotely control of the synchronous generator protection and control
iii.Single-phase short circuit with and without contact relay.
impedance.
37.- Remotely control of the differential protection relay.
16.- Studying of synchronous generator protection and control relay.
38.- Remotely control of the overcurrent protection relay.
17.- Studying of differential protection relay.
39.- Supervision of the electrical parameters of the generation system with
18.- Studying of overcurrent protection relay. the SCADA software.
Remote control mode (with SCADA System):

19.- Remotely control of generation power systems with double busbar.

20.- Remotely control of opening and closing maneuvers of isolator


switches and circuit breaker in doble busbar systems.

21.- Analysis with the SCADA software of synchronous generator power


flows.

Page 49 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.

Continue...
Page 50 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

The Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA (AEL-T-P-01S) is a modular application
with Smart Grid technology developed to study the Transport and Distribution power systems.
This application allows the student to acquire the most important knowledge about how the electrical energy is transported, why it is rised until certain
voltage levels, what is the function of the transformers with voltage regulator, etc. Besides, the student will know how are performed the basic maneuvers in
double busbar systems, what is the correct sequence of actuation between isolator switches and circuit breaker and many other questions.
The AEL-T-P-01S application consists of a series of modules that allow us simulate the most important operations of control, regulation and supervision
performed in emitter and receiver substations joined with an aerial transmission line.
In order to put in practice all these knowledge, in the AEL-T-P-01S application are included certain devices that make our application a true Smart Grid:
- It includes a distance protection relay. This relay monitors, in real time, the impedance parameters of the transmission line.
- It includes a sophisticated faults injection module to analyze the evolution of transients and observe the request of the protection relays used in the
application.
- It includes network analyzers that show us in real time the electrical parameters in the transmission line to study the energy losses, droop voltages, line
currents, etc.
- It includes a voltage regulator TAP in the distribution transformer to compensate the droop voltage of the transmission line.

The AEL-T-P-01S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS04. Emitter Transport Busbar.
N-BUS05. Receptor Transport Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)
N-PLC02. PLC02 Control Module.
N-REG15. Tap Module Regulator.
N-AE1CD. Transmission Lines Simulator Digital Unit.
N-ERP-PD01. Distance Protection Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
Transformers:
TRANS3/5KR. 5KW Step-Down Transformer with Voltage Regulator.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button.
Safety key.
Three-phase terminal connections.
Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS04. Emitter Transport Busbar.


Emitter transport busbar module.
Local/remote switch.
Slide commutators of disconnectors and circuit breaker.
Status indicator lamps. ON-OFF switch.
Communication connector.
Power supply: 230 VAC.

N-BUS05. Receptor Transport Busbar.


Double distribution busbar module.
Local/Remote control switch.
Slide commutators of of disconnectors and circuit breaker.
Status indicator lamps. ON-OFF switch.
Communications connector SUB-D 62 pin.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Continue...
Page 51 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

Fuses: Line fuses 3x10A.


Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-PLC02. PLC02 Control Module.


PLC Siemens S7-300.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
2 x Fuses 2A.

N-REG15. Tap Module Regulator.


TAP voltage regulator module.
Single-Phase power supply: 230VAC.
Voltage TAP selector:
+7,5%; +5%; +2,5%; 0%; -7,5%; -5%; -2,5%.
Indicator lamps regulation percentage.
Local/remote control switch.
OFF-ON Commutator.
ON-OFF switch.
Signal connector SUB-D 62 pins.

N-AE1CD. Transmission Lines Simulator Digital Unit.


Transmission lines simulation digital unit.
Local/remote switch.
Switches to preselect a line resistance.
Switches to preselect a line inductance.
Switches to simulate R phase lost.
Switches to simulate S and T phase lost.
Status indicator lamp. ON-OFF switch.
Voltage Lines ( 400 VAC).

N-ERP-PD01. Distance Protection Relay Module.


It is used to enable investigations into protection and monitoring of overhead transmission lines and underground cables. It enables a
wide range of test and investigations and it demonstrates the latest relay technology.
Modern industrial application distance protection relay presented in an educational and teaching format.
The connections are via safety sockets.
The main functions:
Two zones of Phase Mho Distance Protection Element (21P).
Two zones of Ground Mho Distance Protection Element (21G).
Directional Phase Overcurrent Protection Element (67P).
Directional Ground Overcurrent Protection Element (67G).
Phase Overcurrent Protection Element (50P).
Ground Overcurrent Protection Element (50G).
Phase Time-Overcurrent Protection Element (51P).
Ground Time-Overcurrent Protection Element (51G).
Event Reports.
Breaker Wear Monitor.
Fault Locator.
Local Display.
Synchronophasors.
Load Encroachment.
Metering and Monitoring Functions.
Creating fault and disturbance records.
Blocking of any one protection element.
The connection to the experimental circuit is via current transformers with ratio to suit the inputs of the relay.
It allows an effective demonstration of the effect of current and voltage transformer ratio, connection and rating on protective relays.
Accuracy: +- 10%. Current: 5 A (A. C.). Frequency: 50 or 60 Hz.
Operating time: typically 10 ms to 25 ms.
Continue...

Page 52 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

 N-ERP-MF01. Digital Fault Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

Transformers:
 TRANS3/5KR. 5KW Step-Down Transformer with Voltage Regulator.
Isolating three-phase power transformer.
Pn: 5KVA. Vp with regulation: 400VAC delta. +7,5%, +5%, +2,5%, 0%, -2,5%, -5%, 7,5%. Vs: 400VAC Star.

SCADA (Supervision, Control and Data Acquisition).

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-T-P-01S


Local control:
1.- Opening and closing basic maneuvers of isolator switches and 20.- Studying of energy losses of the transmission line.
circuit breaker. 21.- Remote measurement of droop voltages in the transmission line in
2.- Measurements of energy losses in the transmission line. function on the system load.
3.- Droop voltage compensation with the voltage regulator TAP. 22.- Remote automatic configuration of the transmission line impedance.
4.- Real time measurements of the electrical parameters (voltage, 23.- Remote automatic selection of the line to line capacitive effect of the
current, frequency, power factor, active power, reactive power, transmission line.
aparent power, active energy, reactive energy, aparent energy, etc.). 24.- Remote automatic selection of the line resistor of the transmission line.
5.- Studying of the energy losses of the transmission line. 25.- Remote automatic selection of the line inductance of the transmission
6.- Studying of the droop voltages in the transmission line in function on line.
the load system. 26.- Remote automatic selection of one line phase loss.
7.- Automatic configuration of the line parameters. 27.- Remote automatic selection of two line phases loss.
8.- Automatic selection of the line to line capacitive effect. 28.- Remotely control of short circuits in different points of the transmission
9.- Automatic selection of line resistor. power system:
10.- Automatic selection of line inductance. a. Symmetric short circuits: three-phase short circuits with and
11.- Simulation of one phase loss. without contact impedance.
12.- Simulation of two phase loss. b. Asymmetric faults:
13.- Studying of short circuits in different points of transmission power i. Two-phase short circuit with and without contact impedance.
system: ii. Two-phase to ground shortcircuit with and without contact
a. Symmetric short circuits: three-phase short circuits with and impedance.
without contact impedance. iii.Single-phase short circuit with and without contact impedance.
b. Asymmetric faults: 29.- Short circuits temporal evolution recording of voltage and currents
i. Two-phase short circuit with and without contact impedance. phasors for further analysis.
ii. Two-phase to ground shortcircuit with and without contact 30.- Calculation of the electrical parameters of the transmission line for
impedance. subsequent configuration of the distance relay (mho characteristic).
iii.Single-phase short circuit with and without contact 31.- Studying in depth of the distance protection relay.
impedance.
14.- Recording the evolution of voltage and current phasors during short
circuit for further analysis.
15.- Calculation of the electrical parameters of the line to configure the
distance protection relay (mho characteristic).
16.- Studying in depth of the distance protection relay.
Remote control (with SCADA System):
17.- Supervision, Control and Data Acquisition of all electrical
parameters of the transmission line.
18.- Monitoring of energy losses of transmission lines from the PC.
19.- Remotely control of distribution transformer voltage regulator (TAP).
Compensation of droop voltages of the transmission line.
Continue...

Page 53 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA

Continue...

Page 54 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

The AEL-C-P-02S is a modular application developed to study the operation and control of the final loads of the power systems. This application is
equipped with the most advanced protection systems used nowadays in substations and distribution lines. Besides, the AEL-C-P-02S has an automatic
power factor compensation (SVC type). The AEL-C-P-02S has an overcurrent protection relay used in distribution systems (feeders) with which the student
will simulate different short circuits along the load distribution system and subsequently, the student will analyze how the protection relay acts over
corresponding circuit breaker. Besides, the AEL-C-P-02S application has an automatic power factor controller with six stages. For the analysis of the
automatic response of the power factor controller, we have a group of resistive, inductive and capacitive loads in order to simulate actual process of the
energy demand and the power factor compensation.

The AEL-C-P-02S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS06. Distribution Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition.
N-CFP. Advanced Power Factor Controller Module.
N-PLC03. PLC03 Control Module.
N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.
N-CAR36T3D. Three-Phase Digital Bank of Commutable Inductances module.
N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
N-CAR19T3D. Three-Phase Digital Bank of Commutable Capacitors Module.
N-ERP-MA01. Feeder Management Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button. Safety key.
Three-phase terminal connections. Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS06. Distribution Busbar.


Distribution bus-bar module.
Local/remote switch.
Slide commutators of disconnectors and circuit breaker.
Status indicator lamps. ON/OFF switch.
Communications connector SUD-D 62 pin.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Fuses: Line fuses 3x10A.
Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-CFP. Advanced Power Factor Controller Module.


Automatic power factor controller module.
Four quadrants regulation.
FCP System (fast computerized program).
Compensation stages: 6 relay outputs.
LCD display with three digits and more than 20 icons to indicate different operation conditions.
ON-OFF switch.
Continue...

Page 55 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

 N-PLC03. PLC03 Control Module.


PLC Siemens.
Communications connector SUB-D 62 pin.
ON-OFF switch
2 x Fuses 2A.

N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.


Three-phase digital banks of commutable capacitors module.
Three-phase commutable capacitor banks:6x(3x7uF).
Signals connector.

N-CAR36T3D. Three-Phase Digital Bank of Commutable Inductances Module.


Three-phase digital banks of commutable inductances module.
Three load slide commutators.
3 x three-phase commutable inductance banks:3x(3x1,4 H).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

N-CAR35T3D. Three-Phase Digital Bank Resistors Module.


Three-phase digital bank of commutable resistors module.
Three load slide commutators.
Three-phase commutable resistor banks:3x150 ohms (1000W, 2000W, 3000W).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

N-CAR19T3D. Three-Phase Digital Bank of Commutable Capacitors Module.


Three-phase digital banks of commutable capacitors module.
Three load slide commutators.
3 x three-phase commutable capacitor banks:3x(3x7uF).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

 N-ERP-MA01. Feeder Management Relay Module.


The main functions:
Four levels of Phase Instantaneous Overcurrent Element (50P).
Four levels of Negative-Sequence Overcurrent Element (50Q).
Four levels of Residual Overcurrent Element (50G).
Four levels of Neutral Overcurrent Element (50G).
Two levels of Phase Time-Overcurrent Element (51P).
Two levels of Residual Time-Overcurrent Element (51G).
Two levels of Ground Time-Overcurrent Element (51G).
One level of Negative-Sequence Time-Overcurrent Element (51Q).
Phase to Ground Overvoltage (59G).
Phase to Phase Overvoltage (59P).
Negative-Sequence Overvoltage (59Q).
Residual Overvoltage (59G).
Phase to Ground Undervoltage (27G).
Phase to Phase Undervoltage (27P).
Six levels of Secure Overfrequency (81O).
Six levels of Secure Underfrequency (81U).
Two levels of Negative Power Flow with Definite Time Delay (32).
Two levels of Positive Power Flow with Definite Time Delay (32).
Station Battery Monitor.
Breaker Wear Monitoring.
Synchrophasor Protocol.
Peak Demand and Demand Metering.
Auto-Reclosing.
Creating fault and disturbance records.
Accuracy: +- 10%. Current: 5 A (A. C.) Frequency: 50 or 60 Hz
Operating time: typically 10 ms to 25 ms.
Continue...

Page 56 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ERP-MF01. Digital Fault Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

SCADA (Supervision, Control and Data Acquisition).

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-C-P-02S


Local control:

1.- Opening and closing basic maneuvers of isolator switches and 10.- Remote measurement of all electrical parameters of load distribution
circuit breaker of distribution substation. system.

2.- Real time measurements of all electrical parameters of the 11.- Remotely control of short circuits in different points of the load power
distribution systems. system:

3.- Studying of short circuits in different points of load power system: a. Symmetric short circuits: three-phase short circuits with and
without contact impedance.
a. Symmetric short circuits: three-phase short circuits with and
without contact impedance. b. Asymmetric faults:

b. Asymmetric faults: i. Two-phase short circuit with and without contact impedance.

i. Two-phase short circuit with and without contact impedance. ii. Two-phase to ground shortcircuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without contact
impedance. iii.Single-phase short circuit with and without contact impedance.

iii.Single-phase short circuit with and without contact


impedance.
12.- Recording the evolution of voltage and current phasors during short
4.- Recording the evolution of voltage and current phasors during short circuit for further analysis.
circuit for further analysis.
13.- Studying in depth of feeder protection relay.
5.- Studying in depth of feeder protection relay.
14.- Automatic power factor compensation in function on the demanded
Remote control (with SCADA System): reactive energy.

6.- Supervision, Control and Data Acquisition of all electrical


parameters of the load distribution system.

7.- Remote control of the demanded active power.

8.- Remote control of the demanded inductive reactive power.

9.- Remote control of the demanded capacitive reactive power.

*Specifications subject to change without previous notice, due to the convenience of improvements of the product.
REPRESENTATIVE:

C/ Del Agua, 14. Polígono Industrial San José de Valderas.


28918 LEGANÉS. (Madrid). SPAIN.
Phone: 34-91-6199363 FAX: 34-91-6198647
E-mail: edibon@edibon.com WEB site: www.edibon.com

Issue: ED01/16
Date: April/2016

Page 57 www.edibon.com
Modular Smart Grid Power Systems Simulators
(Utilities)
AEL-MPSS
Technical Teaching Equipment

SCADA

Key features:
Several Utilities and Final User options.

Modular and scalable applications (from simple to advance complexity).

Scalable and expandable applications.

Possibility to work either with individual applications or combined applications to


form simulators (Generation + Transmission/Distribution + Loads).

Use of real devices as substations protection relays, generators management


devices, frequency controllers, etc. www.edibon.com
Products
Products range
EDIBON SCADA System (Supervision, Control and Data Acquisition) always included. Units
5.-Energy
Smart Grid devices.

Micro-Grids.

ISO 9000: Quality Management European Union Certificate Certificates ISO 14000 and Worlddidac Quality Charter
(for Design, Manufacturing, (total safety) ECO-Management and Audit Scheme Certificate and
Commercialization and After-sales service) (environmental management) Worlddidac Member
Page 1
AEL-MPSS

2. TRANSMISSION/DISTRIBUTION
1. GENERATION SYSTEMS 3. LOADS SYSTEMS
SYSTEMS

+ +

AEL-GCA- Automatic Control Generation AEL-T- Transmission and Distribution Power AEL-C- Conventional Loads options.
Systems options. Systems options. AEL-CS- Special Loads options.
AEL-GCM- Manual Control Generation
Systems options.
AEL-GAD- Additional Generation Systems
options.

EDIBON SCADA System

OPEN CONTROL
+ Control
MULTICONTROL Interface
+
REAL TIME CONTROL
SCADA Software

Page 2 www.edibon.com
ALL AVAILABLE OPTIONS
1. GENERATION SYSTEMS
AEL-GCA- AEL-GCM- AEL-GAD-
Automatic Control Generation Systems Manual Control Generation Systems Additional Generation Systems
options options options
Applications Applications Applications
Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCM-P-02S. Generation System with SCADA.
AEL-GCA-P-02S. Generation System with
Manual Control of AEL-GAD-02S. Auto-Start Diesel Generator
Automatic Control of
Synchronous Generator, Trainer for Recovery of the
Synchronous Generator,
Synchronization and Energy System due to Black-
Synchronization and
Protection Relays, with Outs, with SCADA.
Protection Relays, with
SCADA.
SCADA. AEL-GAD-03S. A u t o m a t i c G e n e r a t i o n
AEL-GCM-02S. Generation System with System with Two Parallel
AEL-GCA-02S. Generation System with Manual Control of Generators, with SCADA.
Automatic Control of Synchronous Generator and
Synchronous Generator and Synchronization, with AEL-GAD-04S. Hydroelectric Power Plant,
Synchronization, with SCADA. with SCADA.
SCADA.
AEL-GCM-P-03S. Manual Synchronization
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous These applications can be complemented with AEL-
System of Synchronous Generator with Servomotor GCA and AEL-GCM applications.
Generator with Servomotor and Protection Relays, with
and Protection Relays, with SCADA.
SCADA. AEL-GCM-03S. Manual Synchronization
AEL-GCA-03S. Automatic Synchronization System of Synchronous
System of Synchronous Generator with Servomotor,
Generator with Servomotor, with SCADA.
with SCADA. Isolated Grid Studies
Isolated Grid Studies AEL-GCM-P-01S. Generation System with
Manual Control of
AEL-GCA-P-01S. Generation System with Synchronous Generator in
Automatic Control of an Isolated Grid and
Synchronous Generator in an Protection Relays, with
Isolated Grid and Protection SCADA.
Relays, with SCADA.
AEL-GCM-01S. Generation System with
AEL-GCA-01S. Generation System with Manual Control of
Automatic Control of Synchronous Generator in
Synchronous Generator in an an Isolated Grid, with
Isolated Grid, with SCADA. SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS
AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA.
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)


AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. L o a d s S y s t e m s w i t h A u t o m a t i c Po w e r F a c t o r AEL-C-03S. Complex Loads, Power Consumption Measurement and


Compensation and Protection Relays, with SCADA. Peak Load Monitoring, with SCADA.
AEL-C-02S. L o a d s S y s t e m s w i t h A u t o m a t i c Po w e r F a c t o r
Compensation, with SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation
and Protection Relays, with SCADA.
AEL-C-01S. L o a d s S y s t e m s w i t h M a n u a l Po w e r F a c t o r
Compensation, with SCADA.

* Each application can work individually or combined with other applications to form systems simulators (Generation + Transmission/Distribution + Loads).
Page 3 www.edibon.com
INTRODUCTION
Due to the growth and development of electric power systems it has been required to design increasingly sophisticated devices to manage electric
power in a safer and more efficient way.

Nowadays, protection and monitoring devices, which allow to know the electrical parameters in real time, such as voltage level in the nodes of the
grid, current level in the lines, active and reactive power level, frequency values, etc., are essential in the electrical grids. Protection systems play an
important role in power systems, since they can control in a practically independent way the safety and continuity of the power supply, as well as the
quality of the energy the final consumer gets.

The Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS”, with more than 285 control variables, have been designed to make
and use the same technology employed in power systems available in the industrial world, easy to use by experts and inexperienced people. We
included the safety conditions required to perform different short-circuit tests and experiments.

The AEL-MPSS systems simulators are specially designed and aimed at technical professional training, vocational training, for higher education
and even applied research, as well as the improvement in all fields through advanced systems.

The Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS” can be configured from three great areas formed by several options and
applications as:

1. Generation systems applications.

2. Transmission/Distribution systems applications.

3. Loads systems applications.

The objective of each area is to study a field of the electric power systems. All the options available in these three great areas have been designed
to be able to work either independently or combining with several options and applications in order to configure systems simulators (generation +
trasmission/ distribution + loads).

Due to the flexibility of our modular applications, it is possible to begin with easy applications for students with basic knowledge of power systems
and/or to combine several applications for intermediate or advanced levels. Thus, a system simulator consisting of applications of generation,
transmission/ distribution and loads will be created. Optionally, all of them including cutting edge protection relays to test their efficiency and
reliability against any electrical fault.

All applications on this catalogue include the SCADA (Supervision, Control and Data Acquisition), which allows to study the operation of today's
power systems in depth. This software enables the student to control the devices that make up the power systems remotely, observe in real time how
the typical operations of an electrical substation work, which are the voltage and current values at different points of the transport networks, how
much energy is generated and what occurs when the excitation current of our generator is increased or decreased.

Main features of Modular Smart Grid Power Systems Simulators (Utilities) “AEL-MPSS”:

-Several Utilities and Final User options.

-Modular and scalable applications (from simple to advance complexity).

-Scalable and expandable applications.

-Possibility to work either with individual applications or combined applications to form simulators (Generation + Transmission/Distribution +
Loads).

-Use of real devices as substations protection relays, generators management devices, frequency controllers, etc.

-EDIBON SCADA System (Supervision, Control and Data Acquisition) always included.

-Smart Grid devices.

-Micro-Grids.

Page 4 www.edibon.com
SOME CONTROL VARIABLES USED WITH AEL-MPSS MODULAR SMART GRID POWER SYSTEMS
The AEL-MPSS Modular Power Systems is one of the most advanced and complete modular power systems of the market. In the following pages
the most important variables which allow the control of the system both in local and remote through the included SCADA are indicated.

The following are the most important 285 control variables that make the AEL-MPSS a forefront system able to interact with the user thanks to the
cutting-edge included devices.

The AEL-MPSS has been designed to show any electric phenomenon that are present in real power systems, such as short circuits, over currents,
over voltages, over frequencies, reverse power, generator runaway, etc.

A variable is any element or symbol of our system susceptible to be modified directly or indirectly by the user and the control system.

All power systems are formed by three fundamental parts:

1. Generation System.

2. Transmission/Distribution System.

3. Load System.

1. Generation System:

Power generation is the point where all power systems born, where transmission lines emerge up to distribution lines and finally, to give
electrical service to the final consumer. It is necessary a great quantity of control variables for a power system reliable, safe and optimal
because of these variables depend the electrical energy quality. This is the reason why the generation systems of the AEL-MPSS includes the
145 control variables most important that will allow user to interact with a sophisticated, real and intelligent generation system, which is
able to respond automatically against energy demand, it is able to protect automatically against short circuits, with light indicators and
alarms that will allow us to understand at all time the generation system state.

See the 145 control variables in next page.

2. Transmission/Distribution System:

After power generation, transmission and distribution systems are required to give power to the final consumer. These systems are highways of
aluminum and steel which transport great quantities of power up to strategic points of the country and even other countries. In the
transmission systems is very important to know variables such as transported energy, length transmission lines, capacitive effect, energy losses
produced along kilometers and kilometers, etc. Besides, in a transmission line system is not enough a conventional protection system. For
these systems are required distance protection relays able to detect changes in the line impedances and to sense undetectable anomalies for
other conventional protection relays.

Distribution substations adapt the transmission lines voltage levels up to lower voltage levels for energy distribution. On this point take
importance the distribution transformer with voltage regulator, which are able to compensate the transmission liens drop voltages.

The transmission/distribution power system of AEL-MPSS allows to study all these control variables and much more. In the following page the
most important 76 control variables that allow the user to interact with the transmission/distribution system are listed.

See the 76 control variables in next page.

3. Load System:

Once the energy is transported, this has to be carried to the consumption points through distribution lines. Final consumer provokes changes
in the power balance of the system from generation up to distribution. On this way, all machinery of the system (generation, transmission and
distribution) works in real time in order to the electrical parameters remain constants in the consumption points.

In the consumption points is very important to ensure the electrical energy quality through reactive energy compensation devices. Besides, on
this point are essential the feeders management protection relays, which are installed in strategic points of the distribution lines giving to the
grid the required reliability, safety and efficiency. These protection relays monitor electrical variables such as frequency, voltage, current,
power factor, etc. in order to protect the grid.

In the following page the most important 64 control variables which allow user to interact with the load system are listed.

See the 64 control variables in next page.


Continue...
Page 5 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

The most important 285 control variables which allow user to interact with the load system are listed below:

1. Generation System: the most important and used 145 physical variables in the industrial power systems.

1.1. Some general control variables of the Turbine-Generator group.  Manual Control Variable for 52G breaker open/close.
 Manual Control Variable for emergency stop of the Turbine- - Load Sharing/Parallel Grid Mode:
Generator group.  Manual Control Variable for synchronization the generator and
 Control Variable for starting order of the Turbine-Generator in the grid.
automatic mode.  Manual Control Variable for Active Power given to the grid.
 Permission Variable for synchronization in automatic mode.  Manual Control Variable for Reactive Power given to the grid.
 Manual Control Variable for 52G breaker open/close.
1.2. Local Control Mode of Turbine-Generator group.
1.2.1. Local Control of the group in manual mode. 1.3.2. Automatic Remote Control (SCADA) of Turbine-Generator
- Island mode: group.
 Manual Control Variable for turbine frequency/speed - Island Mode:
control with analog potentiometer.  Automatic Control Variable for turbine frequency/speed control
 Manual Control Variable for synchronous generator through AVR (Automatic Voltage Regulator).
excitation with analog potentiometer.  Automatic Control Variable for synchronous generator
 Manual Control Variable for 52G breaker open/close. excitation/voltage control through AVR (Automatic Voltage
- “ Load sharing/parallel grid” mode: Regulator).
 Automatic Control Variable for line and phase voltages.
 Manual Control Variable for synchronization the generator and
the grid.  Automatic Control Variable for Reactive Power given to the grid.

 Manual Control Variable for Active Power given to the grid.  Automatic Control Variable for maximum line current.

 Manual Control Variable for Reactive Power given to the grid.  Automatic Control Variable for 52G breaker open/close.

 Manual Control Variable for 52G breaker open/close. - Load Sharing/Parallel Grid Mode:
 Automatic Control Variable for synchronization the synchronous
generator with the grid.
1.2.2. Local Control of the group in automatic mode.
 Automatic Control Variable for Active Power given to the grid.
- Island mode:
 Automatic Control Variable for Active Power maximum limit.
 Automatic Control Variable for turbine frequency/speed
control through AVR (Automatic Voltage Regulator).  Automatic Control Variable for Reactive Power given to the grid.

 Automatic Control Variable for synchronous generator  Automatic Control Variable for Reactive Power maximum limit.
excitation/voltage control through AVR (Automatic Voltage  Automatic Control Variable for adjusting the synchronous
Regulator). generator optimum power factor.
 Automatic Control Variable for line and phase voltages.  Automatic Control Variable for 52G breaker open/close.
 Automatic Control Variable for Reactive Power given to the grid.  Automatic Control Variable for line and phase voltages.
 Automatic Control Variable for maximum line current.  Automatic Control Variable for maximum line current.
 Automatic Control Variable for 52G breaker open/close.
- “ Load sharing/parallel grid” mode: 1.4. Control Variables for protection system.
 Automatic Control Variable for synchronization the synchronous 1.4.1.Over Current and Earth fault protection relay.
generator with the grid.  Configuration variable for the current transformer relationship.
 Automatic Control Variable for Active Power given to the grid.  Configuration variable for the voltage transformer relationship.
 Automatic Control Variable for Active Power maximum limit.  Configuration variable for the removing fault time (TRIP duration).
 Automatic Control Variable for Reactive Power given to the grid.  Configuration variable for Level 1 instantaneous overcurrent
 Automatic Control Variable for Reactive Power maximum limit. 50P1P.
 Automatic Control Variable for adjusting the synchronous  Configuration variable for Level 2 instantaneous overcurrent
generator optimum power factor. 50P2P.
 Automatic Control Variable for 52G breaker open/close.  Configuration variable for Level 3 instantaneous overcurrent
 Automatic Control Variable for line and phase voltages. 50P3P.
 Automatic Control Variable for maximum line current.  Configuration variable for Level 4 instantaneous overcurrent
50P4P.
 Configuration variable for Level 5 instantaneous overcurrent
1.3. Remote Control (SCADA) of Turbine-Generator group 50P5P.
1.3.1. Manual Remote Control (SCADA) of Turbine-Generator group.  Configuration variable for Level 6 instantaneous overcurrent
- Island Mode: 50P6P.
 Manual Control Variable for turbine frequency/speed control  Configuration variable for the inverse time overcurrent
with analog potentiometer. parameter threshold.
 Manual Control Variable for synchronous generator excitation  Configuration variable for inverse time curve type 51P1T: U1,
with analog potentiometer. U2, U3, U4, U5, C1, C2, C3, C4, C5.
Continue...
Page 6 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

1.4.1. Over Current and Earth fault protection relay. (continuation)  Configuration variable for 2º harmonic restriction percentage.
 Configuration variable for the 51P1T Time-Dial of the inverse  Configuration variable for 4º harmonic restriction percentage.
time overcurrent protection curve parameter.
 Configuration variable for 5º harmonic restriction percentage.
 Configuration variable for the 51P2T inverse time curve
 Configuration variable for 50P1P instantaneous overcurrent
threshold.
level of the primary winding power transformer.
 Configuration variable for inverse time curve type 51P2T: U1,
 Configuration variable for 51P1D define time instantaneous
U2, U3, U4, U5, C1, C2, C3, C4, C5.
overcurrent level of the primary winding power transformer.
 Configuration variable for the 51P2P Time-Dial of the inverse
 Configuration variable for 51P1P inverse time overcurrent
time overcurrent protection curve parameter.
threshold of the power transformer primary winding.
 Configuration variable for 50N1 neutral instantaneous
 Configuration variable for inverse time curve type 51P1P: U1,
overcurrent threshold.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 50N2 neutral instantaneous
 Configuration variable for the 51P1P Time-Dial of the inverse
overcurrent threshold.
time overcurrent protection curve parameter.
 Configuration variable for 51N1T inverse time neutral
 Configuration variable for 50Q1P negative sequence
overcurrent parameter threshold.
instantaneous overcurrent threshold of the power transformer
 Configuration variable for inverse time curve type 51N1T: U1, primary winding.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q1P negative sequence inverse
 Configuration variable for the 51N1T Time-Dial of the inverse time overcurrent threshold of the power transformer primary
time overcurrent protection curve parameter. winding.
 Configuration variable for 50G1 instantaneous residual  Configuration variable for inverse time curve type 51Q1P: U1,
overcurrent parameter threshold. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 50G2 instantaneous residual  Configuration variable for 51Q1P Time-Dial of the inverse time
overcurrent parameter threshold. overcurrent protection curve parameter.
 Configuration variable for 50G1T inverse time residual  Configuration variable for 50N1P instantaneous residual
overcurrent parameter threshold. overcurrent threshold of the power transformer primary winding.
 Configuration variable for inverse time curve type 51G1T: U1,  Configuration variable for 50N1P inverse time residual
U2, U3, U4, U5, C1, C2, C3, C4, C5. overcurrent threshold of the power transformer primary winding.
 Configuration variable for the 51G1T Time-Dial of the inverse  Configuration variable for inverse time curve type 51N1P: U1,
time overcurrent protection curve parameter. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q1P negative sequence  Configuration variable for 51N1P Time-Dial of the inverse time
instantaneous overcurrent parameter threshold. overcurrent protection curve parameter.
 Configuration variable for 51Q2P negative sequence  Configuration variable for 50P2P instantaneous overcurrent
instantaneous overcurrent parameter threshold. level of the power transformer secondary winding.
 Configuration variable for 51Q1T inverse time overcurrent  Configuration variable for 50P2D define time instantaneous
parameter threshold. overcurrent level of the power transformer secondary winding.
 Configuration variable for inverse time curve type 51Q1T: U1,  Configuration variable 51P2P inverse time overcurrent threshold
U2, U3, U4, U5, C1, C2, C3, C4, C5. of the power transformer secondary winding.
 Configuration variable for the 51Q1T Time-Dial of the inverse  Configuration variable for inverse time curve type 51P2P: U1,
time overcurrent protection curve parameter. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for 51Q2T inverse time overcurrent  Configuration variable for 51P2P Time-Dial of the inverse time
parameter threshold. overcurrent protection curve parameter.
 Configuration variable for inverse time curve type 51Q2T: U1,  Configuration variable for 50Q2P negative sequence
U2, U3, U4, U5, C1, C2, C3, C4, C5. instantaneous overcurrent threshold of the power transformer
 Configuration variable for the 51Q2T Time-Dial of the inverse secondary winding.
time overcurrent protection curve parameter.  Configuration variable for 51Q2P negative sequence inverse
time overcurrent threshold of the power transformer secondary
winding.
1.4.2. Differential Protection Relay of Step-Up power transformer
 Configuration variable for inverse time curve type 51Q2P: U1,
 Configuration variable for the current transformer relationship.
U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for the voltage transformer relationship.
 Configuration variable for 51Q2P Time-Dial of the inverse time
 Configuration variable for the removing fault time (TRIP overcurrent protection curve parameter.
duration).
 Configuration variable for 50N2P instantaneous residual
 Configuration variable for power transformer connection type. overcurrent threshold of the power transformer secondary
 Configuration variable for measurement transformer connection winding.
type.  Configuration variable for 50N2P inverse time residual
 Configuration variable for 87P differential protection element. overcurrent threshold of the power transformer primary winding.
 Configuration variable for SLP1 restriction percentage of 87P  Configuration variable for inverse time curve type 51N2P: U1,
differential element. U2, U3, U4, U5, C1, C2, C3, C4, C5.
 Configuration variable for SLP2 restriction percentage of 87P  Configuration variable for 51N2P Time-Dial of the inverse time
differential element. overcurrent protection curve parameter.
Continue...
Page 7 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

1.4.3. Protection Relay of Turbine-Generator Group.


 Configuration variable of synchronous generator nominal
power.
 Configuration variable of synchronous generator poles number.
 Configuration variable of instantaneous overcurrent protection
threshold.
 Configuration variable of inverse time overcurrent protection
threshold.
 Configuration variable of overvoltage protection threshold.
 Configuration variable of undervoltage protection threshold.
 Configuration variable of overfrequency protection threshold.
 Configuration variable of subfrequency protection threshold.
 Configuration variable of reverse power level.
 Configuration variable of Proportional, Integral and Derivative
(PID) for Turbine-Generator group control and regulation.

1.5. Control variables of double bus bar generation substation


switchgear. Local and remote control possibility (SCADA).
 Control variable of open/close 89GC1-1 coupling
disconnector.
 Control variable of open/close 89GC1-2 coupling
disconnector.
 Control variable of open/close 52GC1-1 coupling breaker.
 Control variable of open/close 89GT1-1 transformer
disconnector.
 Control variable of open/close 89GT1-2 transformer
disconnector.
 Control variable of open/close 89GT1-3 transformer
disconnector.
 Control variable of open/close 52GT1-1 transformer breaker.
 Control variable of open/close 52NET grid breaker.
 Control variable of open/close 52G1 generation breaker.

1.6. Control variables for faults selection.


1.6.1. Local/Remote control (SCADA):
 Control variable for direct single phase short preselection.
 Control variable for single phase short circuit with fault
impedance.
 Control variable for direct two phases to ground short circuit
preselection.
 Control variable for two phases to ground short circuit
preselection with fault impedance.
 Control variable for direct two phase short circuit preselection.
 Control variable for two phase short circuit preselection with
fault impedance.
 Control variable for direct three-phase phase short circuit
preselection.
 Control variable for three-phase phase short circuit preselection
with fault impedance.
 Control variable for fault injection.

Continue...
Page 8 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

2. Transmission/Distribution System: the most important and used 76 physical variables in the industrial power systems.
2.1. Control variables of double bus bar emitter substation - Configuration variable for Z2MG ground impedance element
switchgear. Possibility to control both local and remote modes of zone 2.
(SCADA). - Configuration variable for Z3MG ground impedance element
 Control variable of open/close 89T1-1 disconnector. of zone 3.
 Control variable of open/close 89T1-2 disconnector. - Configuration variable for Z4MG ground impedance element
 Control variable of open/close 89T1-3 disconnector. of zone 4.
 Control variable of open/close 52T1-1 breaker. - Configuration variable for Z1D time distance element of zone
1.
2.2. Control variables of double bus bar receptor substation - Configuration variable for Z2D time distance element of zone
switchgear. Possibility to control both local and remote modes 2.
(SCADA). - Configuration variable for Z3D time distance element of zone
 Control variable of open/close 89L1-1 disconnector. 3.
 Control variable of open/close 89L1-2 disconnector. - Configuration variable for Z4D time distance element of zone
4.
 Control variable of open/close 89L1-3 disconnector.
 Configuration variable for 50P1P instantaneous overcurrent
 Control variable of open/close 52T2-1 breaker.
element of level 1.
 Configuration variable for 50P2P instantaneous overcurrent
2.3. Control variables of distribution transformer voltage regulator. element of level 2.
Possibility to control both local and remote modes (SCADA).
 Configuration variable for 50P3P instantaneous overcurrent
 Control variable for voltage regulation at 0 %.
element of level 3.
 Control variable for voltage regulation at 2, 5 %.
 Configuration variable for 50P4P instantaneous overcurrent
 Control variable for voltage regulation at 5 %. element of level 4.
 Control variable for voltage regulation at 7, 5 %.  Configuration variable for 67P1D define time overcurrent
 Control variable for voltage regulation at -2, 5 %. element of level 1.
 Control variable for voltage regulation at -5 %.  Configuration variable for 67P2D define time overcurrent
 Control variable for voltage regulation at -7,5 %. element of level 2.
 Configuration variable for 67P3D define time overcurrent
2.4. Control variables of transmission line parameters. Local and element of level 3.
remote control possibility (SCADA).  Configuration variable for 67P4D define time overcurrent
 Variable control for line resistor. element of level 4.
 Variable control for line inductance.  Configuration variable for 50G1P residual instantaneous
 Variable control for line capacitance.
overcurrent element of level 1.
 Configuration variable for 50G2P residual instantaneous
 Variable control for breaking line 1.
overcurrent element of level 2.
 Variable control for breaking line 1 and line 2.
 Configuration variable for 50G3P residual instantaneous
 Variable control for breaking line 1, line 2 and line 3.
overcurrent element of level 3.
 Configuration variable for 50G4P residual instantaneous
2.5. Control variables of distance protection relay. overcurrent element of level 4.
 Configuration variable for current transformer relationship.  Configuration variable for 67G1P residual define time
 Configuration variable for voltage transformer relationship. overcurrent element of level 1.
 Configuration variable for remove fault duration.  Configuration variable for 67G2P residual define time
 Configuration variable for line impedance. overcurrent element of level 2.
 Configuration variable for length line.  Configuration variable for 67G3P residual define time
 Configuration variables for Mho distance elements. overcurrent element of level 3.
- Configuration variable for Z1P instantaneous distance  Configuration variable for 67G4P residual define time
element of zone 1. overcurrent element of level 4.
- Configuration variable for Z2P instantaneous distance  Configuration variable for 50Q1P negative sequence
element of zone 2. instantaneous overcurrent element of level 1.
- Configuration variable for Z3P instantaneous distance  Configuration variable for 50Q2P negative sequence
element of zone 3. instantaneous overcurrent element of level 2.
- Configuration variable for Z4P instantaneous distance  Configuration variable for 50Q3P negative sequence
element of zone 4. instantaneous overcurrent element of level 3.
- Configuration variable for 50PP1 instantaneous overcurrent  Configuration variable for 50Q4P negative sequence
element of zone 1. instantaneous overcurrent element of level 4.
- Configuration variable for 50PP2 instantaneous overcurrent  Configuration variable for 67Q1D negative sequence define
element of zone 2. time overcurrent element of level 1.
- Configuration variable for 50PP3 instantaneous overcurrent  Configuration variable for 67Q2D negative sequence define
element of zone 3. time overcurrent element of level 2.
- Configuration variable for 50PP4 instantaneous overcurrent  Configuration variable for 67Q3D negative sequence define
element of zone 4. time overcurrent element of level 3.
- Configuration variable for Z1MG ground impedance element  Configuration variable for 67Q4D negative sequence define
of zone 1. time overcurrent element of level 4.
Continue...
Page 9 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems
2.5. Control variables of distance protection relay. (continuation)
 Configuration variable for 51PP inverse time overcurrent
element of level 1.
 Configuration variable for 51PP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51PP “Time Dial”.
 Configuration variable for 51GP inverse time residual
overcurrent element.
 Configuration variable for 51GP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51GP “Time Dial”.
 Configuration variable for 51QP inverse time negative
sequence overcurrent element.
 Configuration variable for 51QP inverse time overcurrent
element type: U1-U5, C1-C5.
 Configuration variable for 51QP “Time Dial”.
 Configuration variable for directional element.

Continue...
Page 10 www.edibon.com
Some control variables used with AEL-MPSS Modular Smart Grid Power Systems

3. Load System: the most important and used 64 physical variables in the industrial power systems.
3.1. Control variables of double bus bar emitter distribution  Configuration variable for 50N2P instantaneous to neutral
substation switchgear. Local and remote control possibility overcurrent of element 2.
(SCADA).  Configuration variable for 50N2D define time neutral
 Control variable of open/close 89T2-1 disconnector. overcurrent of element 2.
 Control variable of open/close 89T2-2 disconnector.  Configuration variable for 50N3P instantaneous to neutral
 Control variable of open/close 89T2-3 disconnector.
overcurrent of element 3.
Configuration variable for 50N3D define time neutral
 Control variable of open/close 52T2-1 breaker.
overcurrent of element 3.
 Control variable of open/close 89T1-1 disconnector.
 Configuration variable for 50N4P instantaneous to neutral
 Control variable of open/close 89T1-2 disconnector. overcurrent of element 4.
 Control variable of open/close 89T1-3 disconnector.  Configuration variable for 50N4D define time neutral
 Control variable of open/close 52T1-1 breaker. overcurrent of element 4.
 Configuration variable for 50G1P instantaneous residual
overcurrent of level 1.
3.2. Control variables for the connected type load. Possibility to
control both local and remote modes (SCADA).  Configuration variable for 50G1D define time residual
overcurrent of element 1.
 Control variable for minimum resistive load.
 Configuration variable for 50G2P instantaneous residual
 Control variable for medium resistive load.
overcurrent of level 2.
 Control variable for maximum resistive load.
 Configuration variable for 50G2D define time residual
 Control variable for minimum inductive load. overcurrent of element 2.
 Control variable for medium inductive load.  Configuration variable for 50G3P instantaneous residual
 Control variable for maximum inductive load. overcurrent of level 3.
 Control variable for minimum capacitive load. Configuration variable for 50G3D define time residual
overcurrent of element 3.
 Control variable for medium capacitive load.
 Configuration variable for 50G4P instantaneous residual
 Control variable for maximum capacitive load.
overcurrent of level 4.
Configuration variable for 50G4D define time residual
3.3. Control variables for load power factor compensation. overcurrent of element 4.
Possibility to control both local and remote modes (SCADA).
 Configuration variable for 50Q1P instantaneous negative
The load system has an automatic power factor controller able to sequence of element 1.
remain constant the load power factor according to the set point
 Configuration variable for 50Q1D define time negative
previously adjusted by the user. Six capacitor steps give more or
sequence overcurrent of element 1.
less reactive power in function of the connected load.
 Configuration variable for 50Q2P instantaneous negative
sequence of element 2.
3.4. Control variables of feeder management protection relay
 Configuration variable for 50Q2D define time negative
 Configuration variable for current transformer relationship. sequence overcurrent of element 2.
 Configuration variable for voltage transformer relationship.  Configuration variable for 50Q3P instantaneous negative
 Configuration variable for remove fault duration. sequence of element 3.
 Configuration variable for 50P1P instantaneous overcurrent of  Configuration variable for 50Q3D define time negative
element 1. sequence overcurrent of element 3.
 Configuration variable for 50P1D define time overcurrent of  Configuration variable for 50Q4P instantaneous negative
element 1. sequence of element 4.
 Configuration variable for 50P2P instantaneous overcurrent of  Configuration variable for 50Q4D define time negative
element 2. sequence overcurrent of element 4.
 Configuration variable for 50P2D define time overcurrent of  Configuration variable for 55 power factor element.
element 2.  Configuration variable for 3PW power element.
 Configuration variable for 50P3P instantaneous overcurrent of  Configuration variable for 87D1TP frequency element 1.
element 3.
 Configuration variable for 87D2TP frequency element 2.
 Configuration variable for 50P3D define time overcurrent of
 Configuration variable for 87D3TP frequency element 3.
element 3.
 Configuration variable for 87D4TP frequency element 4.
 Configuration variable for 50P4P instantaneous overcurrent of
element 4.  Configuration variable for 87D5TP frequency element 5.

 Configuration variable for 50P4D define time overcurrent of  Configuration variable for 87D6TP frequency element 6.
element 4.  Configuration variable for 27P1P sub-voltage element 1.
 Configuration variable for 50N1P instantaneous to neutral  Configuration variable for 27P2P sub-voltage element 2.
overcurrent of element 1.
 Configuration variable for 59P1P over-voltage element 1
 Configuration variable for 50N1D define time neutral
 Configuration variable for 59P2P over-voltage element 2.
overcurrent of element 1.
Page 11 www.edibon.com
1. GENERATION SYSTEMS

Page 5

The generation systems area has been designed to transfer to the student all the knowledge required for the operation of today's electrical generation
possibilities.
Main features of the Generation Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Generation Systems options:
- AEL-GCA- Automatic Control Generation Systems options.
- AEL-GCM- Manual Control Generation Systems options.
- AEL-GAD- Additional Generation Systems options.

AEL-GCA- Automatic Control Generation Systems options:


We offer modular applications focused on the advanced study of electrical generators. The objective is to familiarize the student with the control
devices employed in generation systems nowadays. These generation applications are more complex due to the control included in every module. It is
possible to perform either a direct local control on each module or to control the entire application with SCADA.
It is possible to visualize from the software the electrical diagrams of a generation electrical substation, the transmission lines and the loads and to
perform a direct control of the isolating switches and circuit breakers with each application. Besides, it is possible to inject different types of faults
remotely and to analyze the behaviour of the protection relays located at strategic points of the system. Other possible operation is to perform
alternately a manual control or an automatic control of the turbine-generator group.
There are different topics included, depending on the application:
- Study of generation substations with manual and automatic control of synchronous generator, synchronization and protections.
- Study of generation substations with manual and automatic control of synchronous generator and synchronization.
- Study of generation substations and synchronization with servomotor as prime mover.
- Study of generation substations with manual and automatic control of synchronous generator in isolated grids with protections.
- Study of generation substations with manual and automatic control of synchronous generator in isolated grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GCA-
Automatic Control Generation Systems options

Applications
Synchronization Studies
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection R e l a y s ,
with SCADA.
AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization, with SCADA.
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with Servomotor and Protection Relays, with SCADA.
AEL-GCA-03S. Automatic Synchronization System of Synchronous Generator with Servomotor, with SCADA.
Isolated Grid Studies
AEL-GCA-P-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid and Protection Relays,
with SCADA .
AEL-GCA-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid, with SCADA.

Page 12 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and
Protection Relays, with SCADA
The AEL-GCA-P-02S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of With local control mode:
synchronous generator, protection relays and the necessary
1.- Studying of generation power systems with double busbar
operations for synchronization with the mains.
configuration.
This application includes a SCADA System for remote control 2.- Studying of opening and closing maneuvers of isolator
operations. switches and circuit breaker in double busbar systems.
This application represents an actual generation substation with 3.- Analysis of the measurements of the power flows of the
double bus bar configuration, one synchronous generator and the synchronous generator.
electrical network in order to make the synchronization operations, 4.- Analysis of the active and reactive power of the generator.
opening and closing maneuvers with disconnectors and circuit
breakers of the generation substation, etc. 5.- Manual synchronization maneuvers of synchronous generator
with the mains.
This application includes a series of protection relays to study different 6.- Automatic synchronization maneuvers of synchronous
electrical faults. generator with the mains.
This application includes: 7.- Studying of the synchronous generator in island operation
Modules: mode.
8.- Studying of the Micro-Grids.
 N-ALI01. Industrial Main Power Supply.
9.- Studying of the synchronous generator in grid parallel
 N-BUS01. Generation Busbar. operation mode.
 N-BUS02. Coupling Busbar. 10.- Studying of excitation/voltage regulation of synchronous
 N-BUS03. Grid Busbar. generator in island mode.
11.- Studying of turbine regulation (frequency control) in island
 N-EALD. Network Analyzer Unit with Computer Data mode.
Acquisition. (2 units)
12.- Studying of excitation/voltage regulation of synchronous
 N-EALDC/G. DC Generator Analyzer. generator in parallel grid operation mode.
 N-AVR/P. Automatic Voltage Regulator. 13.- Studying of turbine regulation (frequency control) in parallel
grid operation mode.
 N-VVCA5K. 5KW Motor Speed Controller.
14.- Studying of the power factor regulation of synchronous
 N-ASY3PH. Three-Phase Automatic Synchronoscope. generator in parallel grid operation mode.
 N-PLC01. PLC01 Control Module. 15.- Studying of short circuits in different points of generation
 N-ERP-SFT01. Overcurrent Protection Relay Module. power system:
a. Symmetric short circuits: three-phase short circuits with
 N-ERP-PDF01. Differential Protection Relay Module.
and without contact impedance.
 N-ERP-PGC01. Generator Protection and Control Relay b. Asymmetric faults:
Module.
i. Two-phase short circuit with and without contact
 N-ERP-MF01. Digital Fault Simulator Module. impedance.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. ii. Two-phase to ground shortcircuit with and without
contact impedance.
Transformers:
iii.Single-phase short circuit with and without contact
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer. impedance.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer. 16.- Studying of synchronous generator protection and control
relay.
Generators:
17.- Studying of differential protection relay.
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
18.- Studying of overcurrent protection relay.
SCADA (Supervision, Control and Data Acquisition). Remote control mode (with SCADA):
This application can be combined with other applications of 19.- Remotely control of generation power systems with double
transmission/distribution systems and loads systems areas. Some busbar.
examples of recommended configurations are shown at the end of 20.- Remotely control of opening and closing maneuvers of
this catalogue. isolator switches and circuit breaker in doble busbar systems.
21.- Analysis with the SCADA software of synchronous generator
power flows.
22.- Analysis with SCADA software of active and reactive power of
synchronous generator.
23.- Remotely control of manual synchronization of synchronous
generator with the mains.
24.- Remotely control of automatic synchronization of synchronous
generator with the mains.
25.- Remotely control of synchronous generator in island grid
operation mode.
26.- Studying of Micro-Grids.
27.- Remotely control of synchronous generator in parallel grid
operation mode.
28.- Remotely control of excitation/voltage regulation of
synchronous generator in island mode.
Continue...
Page 13 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays,
with SCADA (continuation)

Some practical possibilities (continuation):


29.- Remotely control of the turbine regulation (frequency control)
in island operation mode.
30.- Remotely control of excitation/ voltage regulation of the
synchronous generator in parallel grid operation mode.
32.- Remotely control of turbine regulation (frequency control) in
parallel grid operation mode.
33.- Remotely control of power factor regulation of synchronous
generator in parallel grid operation mode.
34.- Remotely control of short circuits in different points of the
generation power system:
a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
b. Asymmetric faults:
i. Two-phase short circuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without
contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
35.- Supervision of TRIPS from the SCADA software (protection
relays shooting) in the power system.
36.- Remotely control of the synchronous generator protection and
control relay.
37.- Remotely control of the differential protection relay.
38.- Remotely control of the overcurrent protection relay.
39.- Supervision of the electrical parameters of the generation
system with the SCADA software.

AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization,
with SCADA
The AEL-GCA-02S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator and the necessary operations for synchronization with generator.
the mains. 2.- Manual/automatic current excitation control of the
This application includes a SCADA System for remote control synchronous generator.
operations. 3.- Manual/automatic generation output control of the
This application represents an actual generation substation with synchronous generator.
double bus bar configuration, one synchronous generator and the 4.- Manual/automatic power factor control of the synchronous
electrical network in order to make the synchronization operations, generator.
opening and closing maneuvers with disconnectors and circuit 5.- Manual/automatic power flows control of the synchronous
breakers of the generation substation, etc. generator.
This application includes: 6.- Logic operations of disconnectors and circuit breakers of a
Modules: generation substation.
 N-ALI01. Industrial Main Power Supply. 7.- Manual/automatic operation for synchronization of the
 N-BUS01. Generation Busbar. synchronous generator with the mains.
 N-BUS02. Coupling Busbar. 8.- Synchronoscope use for measuring mismatch voltages,
 N-BUS03. Grid Busbar. frequencies and voltage modules.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-EALDC/G. DC Generator Analyzer.
 N-ASY3PH. Three-Phase Automatic Synchronoscope.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-ERP-PGC01. Generation Protection and Control Relay
Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.
Page 14 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with Servomotor and Protection
Relays, with SCADA
The AEL-GCA-P-03S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of 1.- Manual/automatic frequency control of the synchronous
synchronous generator and the necessary operations for generator.
synchronization with the mains.
2.- Manual/automatic current excitation control of the
Besides, this application includes a series of protection relays in synchronous generator.
order to make different short circuit tests.
3.- Manual/automatic generation output control of the
The speed of generator-motor group is controlled through synchronous generator.
servomotor.
4.- Manual/automatic power factor control of the synchronous
This application includes a SCADA System for remote control generator.
operations.
5.- Manual/automatic power flows control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator moved
by means of servomotor and the electrical network in order to make 6.- Logic operations of disconnectors and circuit breakers of a
the synchronization operations. generation substation.
This application can be combined with other applications of 7.- Manual/automatic operation for synchronization of the
transmission/distribution systems and loads systems areas. Some synchronous generator with the mains.
examples of recommended configurations are shown at the end of 8.- Synchronoscope use for measuring mismatch voltages,
this catalogue. frequencies and voltage modules.
9.- Studying of the following protection relays: differential
protection relay of the step-up transformer and the generator
protection relay.
10.- Studying of the following short circuits types:
Three-Phase short circuit.
Two-Phase short circuit.
Two-Phase to ground short circuit.
Single-Phase short circuit.
11.- Adjusting of protection relay depending of the situation.
12.- Analyzing of the electrical faults transients with a special
software.

AEL-GCA-03S. Automatic Synchronization System of Synchronous Generator with Servomotor, with SCADA
The AEL-GCA-03S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator and the necessary operations for synchronization with generator.
the mains.
2.- Manual/automatic current excitation control of the
The speed of generator-motor group is controlled through synchronous generator.
servomotor.
3.- Manual/automatic generation output control of the
This application includes a SCADA System for remote control synchronous generator.
operations.
4.- Manual/automatic power factor control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator moved
by means of servomotor and the electrical network in order to make 5.- Manual/automatic power flows control of the synchronous
the synchronization operations. generator.
This application can be combined with other applications of 6.- Logic operations of disconnectors and circuit breakers of a
transmission/distribution systems and loads systems areas. Some generation substation.
examples of recommended configurations are shown at the end of 7.- Manual/automatic operation for synchronization of the
this catalogue. synchronous generator with the mains.
8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.

Page 15 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCA-P-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid
and Protection Relays, with SCADA
The AEL-GCA-P-01S is a modular application designed to study Some practical possibilities:
the generation systems with manual/automatic control of 1.- Manual/automatic frequency control of the synchronous
synchronous generator in an isolated grid and protection relays, generator.
with SCADA.
2.- Manual/automatic current excitation control of the
This application represents an actual generation substation with synchronous generator.
double bus bar configuration, one synchronous generator and
3.- Manual/automatic generation output control of the
different protection relays to study electrical faults.
synchronous generator.
This application includes:
4.- Manual/automatic power factor control of the synchronous
Modules: generator.
 N-ALI01. Industrial Main Power Supply. 5.- Manual/automatic power flows control of the synchronous
 N-BUS01. Generation Busbar. generator.
 N-BUS02. Coupling Busbar. 6.- Logic operations of disconnectors and circuit breakers of a
 N-AVR/P. Automatic Voltage Regulator. generation substation.
 N-EALD. Network Analyzer Unit with Computer Data 7.- Studying of the following protection relay, differential
Acquisition. protection relay of the step-up transformer and the generator
protection relay.
 N-EALDC/G. DC Generator Analyzer.
8.- Studying of the following short circuits types:
 N-VVCA5K. 5KW Motor Speed Controller.
Three-Phase short circuit.
 N-PLC01. PLC01 Control Module.
Two-Phase short circuit.
 N-ERP-MF01. Digital Fault Simulator Module.
Two-Phase to ground short circuit.
 N-ERP-PGC01. Generation Protection and Control Relay
Module. Single-Phase short circuit.
 N-ERP-PDF01. Differential Protection Relay Module. 9.- Adjusting of protection relay depending of the situation.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. 10.- Analyzing of the electrical faults transients with a special
software.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

AEL-GCA-01S. Generation System with Automatic Control of Synchronous Generator in an Isolated Grid,
with SCADA
The AEL-GCA-01S is a modular application designed to study the Some practical possibilities:
generation systems with manual/automatic control of synchronous 1.- Manual/automatic frequency control of the synchronous
generator in an isolated grid with SCADA. generator.
This application represents an actual generation substation with 2.- Manual/automatic current excitation control of the
double bus bar configuration and one synchronous generator. synchronous generator.
This application includes: 3.- Manual/automatic generation output control of the
Modules: synchronous generator.
 N-ALI01. Industrial Main Power Supply. 4.- Manual/automatic power factor control of the synchronous
 N-BUS01. Generation Busbar. generator.
 N-BUS02. Coupling Busbar. 5.- Manual/automatic power flows control of the synchronous
 N-AVR/P. Automatic Voltage Regulator. generator.
 N-EALD. Network Analyzer Unit with Computer Data 6.- Logic operations of disconnectors and circuit breakers of a
Acquisition. generation substation.
 N-EALDC/G. DC Generator Analyzer.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-ERP-PGC01. Generation Protection and Control Relay
Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 16 www.edibon.com
1. GENERATION SYSTEMS

AEL-GCM- Manual Control Generation Systems options:


We offer modular applications focused on the basic study of electrical generators. The objective is to familiarize the student with the main operations
performed in the electrical generators, controlling all the parameters of the turbine-generator group manually.
There are different topics included, depending on the application:
- Study of generation substations with manual control of synchronous generator, synchronization and protections.
- Study of generation substations with manual control of synchronous generator and synchronization.
- Study of generation substations and synchronization with servomotor as prime mover.
- Study of generation substations with manual control of synchronous generator in isolated grids and protections.
- Study of generation substations with manual control of synchronous generator in isolated grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GCM-
Manual Control Generation Systems options

Applications
Synchronization Studies
AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization, with SCADA.
AEL-GCM-P-03S. Manual Synchronization System of Synchronous Generator with Servomotor and Protection Relays, with SCADA.
AEL-GCM-03S. Manual Synchronization System of Synchronous Generator with Servomotor, with SCADA.
Isolated Grid Studies
AEL-GCM-P-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid and Protection Relays,
with SCADA.
AEL-GCM-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid, with SCADA.

Applications
AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and
Protection Relays, with SCADA
The AEL-GCM-P-02S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator, protection relays and the necessary operations for 2.- Manual current excitation control of the synchronous
synchronization with the mains. generator.
This application includes a SCADA System for remote control 3.- Manual generation output control of the synchronous
operations. generator.
This application represents an actual generation substation with 4.- Manual power factor control of the synchronous generator.
double bus bar configuration, one synchronous generator and the
electrical network in order to make the synchronization operations. 5.- Manual power flows control of the synchronous generator.
Besides, this application includes a series of protection relays to 6.- Logic operations of disconnectors and circuit breakers of a
study different electrical faults. generation substation.
This application includes: 7.- Manual operation for synchronization of the synchronous
Modules: generator with the mains.
 N-ALI01. Industrial Main Power Supply. 8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.
 N-BUS01. Generation Busbar.
9.- Studying of the following protection relays: the overcurrent
 N-BUS02. Coupling Busbar. and earth fault protection relay and the differential protection
 N-BUS03. Grid Busbar. relay.
 N-AVR/P. Automatic Voltage Regulator. 10.- Studying of the following short circuits types:
 N-EALD. Network Analyzer Unit with Computer Data Three-Phase short circuit.
Acquisition. (2 units) Two-Phase short circuit.
 N-EALDC/G. DC Generator Analyzer. Two-Phase to ground short circuit.
 N-ASY3PH. Three-Phase Automatic Synchronoscope. Single-Phase short circuit.
 N-VVCA5K. 5KW Motor Speed Controller. 11.- Adjusting of protection relays depending of the situation.
 N-PLC01. PLC01 Control Module. 12.- Analyzing of the electrical faults transients with a special
 N-ERP-SFT01. Overcurrent Protection Relay Module. software.
 N-ERP-PDF01. Differential Protection Relay Module.
 N-ERP-MF01. Digital Fault Simulator Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.
Page 17 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization,
with SCADA
The AEL-GCM-02S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
and the necessary operations for synchronization with the mains.
2.- Manual current excitation control of the synchronous
This application includes a SCADA System for remote control generator.
operations.
3.- Manual generation output control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator and the
electrical network in order to make the synchronization operations. 4.- Manual power factor control of the synchronous generator.
This application includes: 5.- Manual power flows control of the synchronous generator.
Modules: 6.- Logic operations of disconnectors and circuit breakers of a
generation substation.
 N-ALI01. Industrial Main Power Supply.
7.- Manual operation for synchronization of the synchronous
 N-BUS01. Generation Busbar. generator with the mains.
 N-BUS02. Coupling Busbar. 8.- Synchronoscope use for measuring mismatch voltages,
 N-BUS03. Grid Busbar. frequencies and voltage modules.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-EALDC/G. DC Generator Analyzer.
 N-ASY3PH. Three-Phase Automatic Synchronoscope.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

AEL-GCM-P-03S. Manual Synchronization System of Synchronous Generator with Servomotor and Protection
Relays, with SCADA
The AEL-GCM-P-03S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator and the necessary operations for synchronization with
2.- Manual current excitation control of the synchronous
the mains.
generator.
The speed of generator-motor group is controlled by means of
3.- Manual generation output control of the synchronous
servomotor.
generator.
Besides, this application includes a series of protection relays in
4.- Manual power factor control of the synchronous generator.
order to make different short circuit tests.
5.- Manual power flows control of the synchronous generator.
This application includes a SCADA System for remote control
operations. 6.- Logic operations of disconnectors and circuit breakers of a
generation substation.
This application represents an actual generation substation with
double bus bar configuration, one synchronous generator moved 7.- Manual operation for synchronization of the synchronous
by mean of servomotor and the electrical network in order to make generator with the mains.
the synchronization operations. 8.- Synchronoscope use for measuring mismatch voltages,
This application can be combined with other applications of frequencies and voltage modules.
transmission/distribution systems and loads systems areas. Some 9.- Studying of the following protection relays: differential
examples of recommended configurations are shown at the end of protection relay of the step-up transformer and the generator
this catalogue. protection relay.
10.- Studying of the following short circuits types:
Three-Phase short circuit.
Two-Phase short circuit.
Two-Phase to ground short circuit.
Single-Phase short circuit.
11.- Adjusting of protection relay depending of the situation.
12.- Analyzing of the electrical faults transients with a special
software.

Page 18 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-03S. Manual Synchronization System of Synchronous Generator with Servomotor, with SCADA
The AEL-GCM-03S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
and the necessary operations for synchronization with the mains.
The speed of generator-motor group is controlled by means of 2.- Manual current excitation control of the synchronous
servomotor. generator.
This application includes a SCADA System for remote control 3.- Manual generation output control of the synchronous
operations. generator.
This application represents an actual generation substation with 4.- Manual power factor control of the synchronous generator.
double bus bar configuration, one synchronous generator moved 5.- Manual power flows control of the synchronous generator.
by mean of servomotor and the electrical network in order to make
6.- Logic operations of disconnectors and circuit breakers of a
the synchronization operations.
generation substation.
This application can be combined with other applications of
7.- Manual operation for synchronization of the synchronous
transmission/distribution systems and loads systems areas. Some
generator with the mains.
examples of recommended configurations are shown at the end of
this catalogue. 8.- Synchronoscope use for measuring mismatch voltages,
frequencies and voltage modules.

AEL-GCM-P-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid and
Protection Relays, with SCADA
The AEL-GCM-P-01S is a modular application designed to study Some practical possibilities:
the generation systems with manual control of synchronous 1.- Manual frequency control of the synchronous generator.
generator in an isolated grid and protection relays, with SCADA.
2.- Manual current excitation control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration, one synchronous generator and
different protection relays to study electrical faults. 3.- Manual generation output control of the synchronous
generator.
This application includes:
4.- Manual power factor control of the synchronous generator.
Modules:
5.- Manual power flows control of the synchronous generator.
 N-ALI01. Industrial Main Power Supply.
6.- Logic operations of disconnectors and circuit breakers of a
 N-BUS01. Generation Busbar. generation substation.
 N-BUS02. Coupling Busbar. 7.- Studying of the following protection relay: differential
 N-AVR/P. Automatic Voltage Regulator. protection relay.
 N-EALD. Network Analyzer Unit with Computer Data 8.- Studying of the following short circuits types:
Acquisition. Three-Phase short circuit.
 N-EALDC/G. DC Generator Analyzer. Two-Phase short circuit.
 N-VVCA5K. 5KW Motor Speed Controller. Two-Phase to ground short circuit.
 N-PLC01. PLC01 Control Module. Single-Phase short circuit.
 N-ERP-PDF01. Differential Protection Relay Module.
9.- Adjusting of protection relay depending of the situation.
 N-ERP-MF01. Digital Fault Simulator Module. 10.- Analyzing of the electrical faults transients with a special
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module. software.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 19 www.edibon.com
1. GENERATION SYSTEMS
Applications
AEL-GCM-01S. Generation System with Manual Control of Synchronous Generator in an Isolated Grid,
with SCADA
The AEL-GCM-01S is a modular application designed to study the Some practical possibilities:
generation systems with manual control of synchronous generator 1.- Manual frequency control of the synchronous generator.
in an isolated grid, with SCADA.
2.- Manual current excitation control of the synchronous
This application represents an actual generation substation with generator.
double bus bar configuration and one synchronous generator.
3.- Manual generation output control of the synchronous
This application includes: generator.
Modules: 4.- Manual power factor control of the synchronous generator.
 N-ALI01. Industrial Main Power Supply. 5.- Manual power flows control of the synchronous generator.
 N-BUS01. Generation Busbar. 6.- Logic operations of disconnectors and circuit breakers of a
 N-BUS02. Coupling Busbar. generation substation.
 N-AVR/P. Automatic Voltage Regulator.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-EALDC/G. DC Generator Analyzer.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC01. PLC01 Control Module.
 N-TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer Module.
Transformers:
 TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
 GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
transmission/distribution systems and loads systems areas. Some
examples of recommended configurations are shown at the end of
this catalogue.

Page 20 www.edibon.com
1. GENERATION SYSTEMS

AEL-GAD- Additional Generation Systems options:


They are additional modular applications focused on the study of different generation power plants, such as pumping power systems, energy recovery
systems in the event of black-outs, power generation systems with two generators in parallel and hydroelectric generation systems.
The objective is to familiarize the student with the control devices employed in this type of systems nowadays.
These applications can work individually or be complemented with other applications of generation, power transmission and loads.
These applications allow to perform either a direct local control on each module or to control the entire application with the SCADA.
There are different topics included, depending on the application:
- Pumping Power Plant.
- Diesel generator with auto-start for the recovery of the energy in the event of black-outs.
- Automatic generation system with two generators in parallel.
- Hydroelectric Power Plant.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-GAD-
Additional Generation Systems options

Applications
AEL-GAD-01S. Pumping Power Plant, with SCADA.
AEL-GAD-02S. Auto-Start Diesel Generator Trainer for Recovery of the Energy System due to Black-Outs, with SCADA .
AEL-GAD-03S. Automatic Generation System with Two Parallel Generators, with SCADA.
AEL-GAD-04S. Hydroelectric Power Plant, with SCADA.

Applications
AEL-GAD-01S. Pumping Power Plant, with SCADA
The AEL-GAD-01S is a modular application designed to study the Some practical possibilities:
pumped storage power stations. 1.- How pumped storage power plants operate.
This application has a SCADA Control Software to simulate how 2.- Start and synchronisation of synchronous machines.
the electrical energy is stored and how the potential energy of water
is converted into electrical power which is then fed back into the 3.- Manual power regulation: both in generator and motor
grid. modes.
4.- Semi-automatic active and reactive power control.
5.- Smart grid integration of pumped storage power plants.
6.- Fully-automatic compensation for externally measured active
and reactive power.
7.- SCADA open and closed-loop system control.

AEL-GAD-02S. Auto-Start Diesel Generator Trainer for Recovery of the Energy System due to Black-Outs,
with SCADA
The AEL-GAD-02S is a modular system designed to study the Some practical possibilities:
recovery of the energy of the electrical grid due to black-outs. 1.- Simulation of black-out.
It includes a diesel generator used to supply the energy needed 2.- Recovery of the power when a black-out appear.
when the electrical grid is disconnected.
3.- Controlling of a diesel-generator.
Besides, this system includes SCADA System with which the student
will control different maneuvers. 4.- Automatic starting of diesel-generator and coupling to the grid.

AEL-GAD-03S. Automatic Generation System with Two Parallel Generators, with SCADA
The AEL-GAD-03S is a modular application designed to study how Some practical possibilities:
two parallel generators work. 1.- Manual/automatic frequency control of the synchronous
It includes two voltage and frequency controllers to study the most generators in parallel operation.
important operations carried out to control the synchronous 2.- Manual/automatic current excitation control of the
generator. synchronous generator.
This application has a SCADA Control System to monitor all 3.- Manual/automatic generation output control of the
control process of the electrical machines. synchronous generators in parallel operation.
4.- Manual/automatic power factor control of the synchronous
generators in parallel and isolated operation.
5.- Manual/automatic power flows control of the synchronous
generators in parallel and isolated operation.
6.- Manual/automatic operation for synchronization of the
synchronous generator with the mains.
7.- Load sharing of two parallel generators.
8.- Active power load sharing with two parallel generators.
9.- Reactive power load sharing with two parallel generators.

Page 21 www.edibon.com
1. GENERATION SYSTEMS

AEL-GAD-04S. Hydroelectric Power Plant, with SCADA


The AEL-GAD-04S is a modular application designed to study the Some practical possibilities:
Hydroelectric Power Plants. 1.- How hydroelectric power plants operate.
On this application the students will learn how hydroelectric power 2.- Start and synchronisation of synchronous machines.
plants work. In order to simulate the main operations of these
alternative power systems, with a motor driving a slip ring three- 3.- Manual power regulation.
phase asynchronous motor will be simulate the main operations of 4.- Manual active and reactive power control.
these power systems.
5.- Automatic active and reactive power control.
This application includes a SCADA Control System in order to carry
6.- Smart grid integration of hydroelectric power plants.
out remote control operations as open and close circuit breakers,
monitoring all electrical parameters as active and reactive power, 7.- Fully-automatic compensation for externally measured active
currents, voltages, etc. and reactive power.
This application includes: 8.- SCADA open and closed-loop system control.
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS03. Grid Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-VVCA5K. 5KW Motor Speed Controller.
 N-PLC06. PLC06 Control Module.
Generators:
 GMG1.5K3PH. 1.5KW Slip Ring Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).

Page 22 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS

The transmission/distribution systems area has been designed to provide the student the required knowledge for operating energy transmission systems.
Main features of the Transmission/Distribution Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Transmission/Distribution Systems options:
- AEL-T. Transmission and Distribution Power Systems options.

AEL-T- Transmission and Distribution Power Systems options:


We offer modular applications focused on the study of the power distribution and transmission systems.
Starting from simple transmission systems we can upgrade with complex devices, such as protection relays, aerial lines in parallel, transformers with
voltage regulation, meshed network systems, etc.
There are different topics included, depending on the application:
- Study of transmission and distribution power systems with regulation transformer.
- Study of transmission and distribution power systems with regulation transformer and protection relays.
- Transmission and distribution power systems with two aerial lines in parallel.
- Transmission and distribution power systems with two aerial lines in parallel and protections.
- Power flow control in meshed networks.
- Electrical distribution grids.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA .
AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA.
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

Page 23 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays,
with SCADA
The AEL-T-P-01S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with voltage regulation
Local control:
transformer and protection relays.
1.- Opening and closing basic maneuvers of isolator switches
The AEL-T-P-01S includes a series of modules such as busbars,
and circuit breaker.
transmission line module, distribution transformer with voltage
regulator (TAP), distance protection relay and network analyzers to 2.- Measurements of energy losses in the transmission line.
study different principles of the transmission and distribution systems. 3.- Droop voltage compensation with the voltage regulator TAP.
This application includes SCADA System to control different 4.- Real time measurements of the electrical parameters (voltage,
elements. current, frequency, power factor, active power, reactive power,
This application includes: aparent power, active energy, reactive energy, aparent energy,
etc.).
Modules:
5.- Studying of the energy losses of the transmission line.
 N-ALI01. Industrial Main Power Supply.
6.- Studying of the droop voltages in the transmission line in
 N-BUS04. Emitter Transport Busbar.
function on the load system.
 N-BUS05. Receptor Transport Busbar.
7.- Automatic configuration of the line parameters.
 N-EALD. Network Analyzer Unit with Computer Data
8.- Automatic selection of the line to line capacitive effect.
Acquisition. (2 units)
9.- Automatic selection of line resistor.
 N-PLC02. PLC02 Control Module.
10.- Automatic selection of line inductance.
 N-REG15. Tap Module Regulator.
11.- Simulation of one phase loss.
 N-AE1CD. Transmission Lines Simulator Digital Unit.
12.- Simulation of two phases loss.
 N-ERP-PD01. Distance Protection Relay Module.
13.- Studying of short circuits in different points of transmission
 N-ERP-MF01. Digital Fault Simulator Module.
power system:
Transformers:
a. Symmetric short circuits: three-phase short circuits with
 TRANS3/5KR. 5KW Step-Down Transformer with voltage and without contact impedance.
regulator.
b. Asymmetric faults:
SCADA (Supervision, Control and Data Acquisition).
i. Two-phase short circuit with and without contact
This application can be combined with other applications of impedance.
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this ii. Two-phase to ground shortcircuit with and without
catalogue. contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
14.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
15.- Calculation of the electrical parameters of the line to
configure the distance protection relay (mho characteristic).
16.- Studying in depth of the distance protection relay.
Remote control (with SCADA):
17.- Supervision, Control and Data Acquisition of all electrical
parameters of the transmission line.
18.- Monitoring of energy losses of transmission lines from the PC.
19.- Remotely control of distribution transformer voltage regulator
(TAP). Compensation of droop voltages of the transmission
line.
20.- Studying of energy losses of the transmission line.
21.- Remote measurement of droop voltages in the transmission
line in function on the system load.
22.- Remote automatic configuration of the transmission line
impedance.
23.- Remote automatic selection of the line to line capacitive effect
of the transmission line.
24.- Remote automatic selection of the line resistor of the
transmission line.
25.- Remote automatic selection of the line inductance of the
transmission line.
26.- Remote automatic selection of one line phase loss.
27.- Remote automatic selection of two line phases loss.

Continue...

Page 24 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA (continuation)

Some practical possibilities (continuation):


28.- Remotely control of short circuits in different points of the
transmission power system:
a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
b. Asymmetric faults:
i. Two-phase short circuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without
contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
29.- Short circuits temporal evolution recording of voltage and
currents phasors for further analysis.
30.- Calculation of the electrical parameters of the transmission
line for subsequent configuration of the distance relay (mho
characteristic).
31.- Studying in depth of the distance protection relay.

AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA
The AEL-T-01S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with voltage regulation 1.- Open and close basic maneuvers with disconnectors and
transformer. circuit breakers.
The AEL-T-01S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module, distribution transformer with voltage
regulator (TAP) and network analyzers to study different principles 3.- Drop voltage compensation with the voltage regulator of the
of the transmission and distribution systems. distribution transformer (TAP).
This application includes SCADA System to control different 4.- Real time measurement of the electrical parameters of the
elements. system.
This application includes: 5.- Studying of the energy losses in the transmission line.
Modules: 6.- Studying of the drop voltage in function on the line currents.
 N-ALI01. Industrial Main Power Supply.
 N-BUS04. Emitter Transport Busbar.
 N-BUS05. Receptor Transport Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. (2 units)
 N-PLC02. PLC02 Control Module.
 N-REG15. Tap Regulator Module.
 N-AE1CD. Commutable Transmission Line Simulation
Unit.
Transformers:
 TRANS3/5KR. 5kW Step-Down Transformer with voltage
regulator.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

Page 25 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays,
with SCADA
The AEL-T-P-02S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with two aerial parallel 1.- Open and close basic maneuvers with disconnectors and
lines and protection relays. circuit breakers.
The AEL-T-P-02S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module, distance protection relay and network 3.- Real time measurement of the electrical parameters of the
analyzers to study different principles of the transmission lines system.
working in series and parallel.
4.- Studying of the energy losses in the transmission lines.
This application includes SCADA System to control different
elements. 5.- Studying of the drop voltage in function on the line currents.
This application can be combined with other applications of 6.- Distribution of power and current among parallel-connected
generation systems and loads systems areas. Some examples of lines of equal length.
recommended configurations are shown at the end of this 7.- Distribution of power and current among parallel-connected
catalogue. lines of unequal length.
8.- Distribution of power and current among series-connected
lines of equal length.
9.- Distribution of power and current among series-connected
lines of unequal length.
10.- Load distribution, power flow.
11.- Voltage distribution.
12.- Studying of short circuits:
Three-Phase short circuit.
Single-Phase short circuit.
Two-Phase short circuit.
14.- Recording of voltage and current phasors evolution during the
short circuits for further analysis.
15.- Real time measurement of the electrical parameters of the
system.
16.- Studying of the energy losses in the transmission line.
17.- Studying of the drop voltage in function on the line currents.

AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA
The AEL-T-02S is a modular application designed to study the Some practical possibilities:
transmission/distribution energy systems with two aerial parallel 1.- Open and close basic maneuvers with disconnectors and
lines. circuit breakers.
The AEL-T-02S includes a series of modules such as busbars, 2.- Measurement of energy losses in the transmission line.
transmission line module and network analyzers to study different 3.- Real time measurement of the electrical parameters of the
principles of the transmission lines working in series and parallel. system.
This application includes SCADA System to control different 4.- Studying of the energy losses in the transmission lines.
elements. 5.- Studying of the drop voltage in function on the line currents.
This application can be combined with other applications of 6.- Distribution of power and current among parallel-connected
generation systems and loads systems areas. Some examples of lines of equal length.
recommended configurations are shown at the end of this 7.- Distribution of power and current among parallel-connected
catalogue. lines of unequal length.
8.- Distribution of power and current among series-connected
lines of equal length.
9.- Distribution of power and current among series-connected
lines of unequal length.
10.- Load distribution, power flow.
11.- Voltage distribution.

AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA
The AEL-T-P-04S is a modular application designed to study Some practical possibilities:
switching operations and protection relays in the double busbar 1.- Basic circuits of a three-pole, double busbar system with
used in the electrical substations. incoming/ outgoing feeder.
With this application the student will learn the most important 2.- Three-phase, double busbar system with load.
maneuvers carried out in the substations busbars.
3.- Busbar changeover without interruption of the branch.
The AEL-T-P-04S includes a series of modules such as busbar with
incoming/outgoing feeder, loads, protection relays and network 4.- Preparation of algorithms for various switching operations.
analyzers to study different principles of the distribution networks. 5.- Busbar coupling.
The double busbar model incorporates all functions of practical 6.- Studying of different short circuits in the busbars.
relevance. On this application are integrated instruments for
measuring currents and voltages which permit direct analyses of
switching operations.
This application includes SCADA System to control different
substation elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.
Page 26 www.edibon.com
2. TRANSMISSION/DISTRIBUTION SYSTEMS
Applications
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA
The AEL-T-04S is a modular application designed to study the Some practical possibilities:
double busbar configuration used in the electrical substations. 1.- Basic circuits of a three-pole, double busbar system with
With this application the student will learn the most important incoming/ outgoing feeder.
maneuvers carried out in the substations busbars. 2.- Three-phase, double busbar system with load.
The AEL-T-04S includes a series of modules such as busbar with 3.- Busbar changeover without interruption of the branch.
incoming/outgoing feeder, loads and network analyzers to study
different principles of the distribution networks. 4.- Preparation of algorithms for various switching operations.
The double busbar model incorporates all functions of practical 5.- Busbar coupling.
relevance. On this application are integrated instruments for
measuring currents and voltages which permit direct analyses of
switching operations.
This application includes SCADA System to control different
substation elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA


The AEL-T-03S is a modular application designed to study the
power flow control in meshed networks.
The AEL-T-03S includes a series of modules such as transmission
line modules, loads and network analyzers to study different
principles of the power flows in meshed networks.
This application includes SCADA System to control different
elements.
This application can be combined with other applications of
generation systems and loads systems areas. Some examples of
recommended configurations are shown at the end of this
catalogue.

Page 27 www.edibon.com
3. LOADS SYSTEMS

The loads systems area has been designed to provide all the knowledge related with operation of loads systems required: control of the reactive power,
protection systems used in the “feeders”, request against bad changes, etc.
Main features of the Load Systems:
- Modular and configurable applications.
- Possibility to work either with individual applications or combined applications to form systems simulators (Generation + Transmission/Distribution +
Loads).
- All applications include SCADA (Supervision, Control and Data Acquisition), Electrical Workbench and PC.
Main Load Systems options:
- AEL-C- Conventional Loads options.
- AEL-CS- Special Loads options.

AEL-C- Conventional Loads options:


We offer modular applications focused on the study of the final loads energy management in a power system.
Starting from basic applications, in which the regulation of the reactive power is studied manually, we can upgrade to applications in which advanced
control devices for the reactive power, protection systems, etc, are included.
There are different topics included, depending on the application:
- Study of the power correction devices employed nowadays. Startup and check of an automatic power factor controller.
- Study of the “feeder” overcurrent protection relay by injecting faults in final loads systems.
- Study of the different power factors depending on the type of load connected to the grid and manual compensation of the reactive power based
on previous theoretical calculations.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-C-
Conventional Loads options

Applications

AEL-C-P-02S. Load Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

AEL-C-02S. Load Systems with Automatic Power Factor Compensation, with SCADA.

AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA.

AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

Page 28 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-P-02S. Load Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA
The AEL-C-P-02S is a modular application designed to study Some practical possibilities:
automatic reactive power compensation controllers and protection
Local control:
relays in a feeder. With this application the student will learn to
calculate the required capacitor banks in function on the 1.- Opening and closing basic maneuvers of isolator switches
demanded reactive energy. and circuit breaker of distribution substation.
Besides, the theorey will be compared with an actual power factor 2.- Real time measurements of all electrical parameters of the
controller. distribution systems.
The AEL-C-P-02S inlcudes a series of modules such as automatic 3.- Studying of short circuits in different points of load power
reactive power controller, capacitor banks, resistor loads, inductor system:
loads, feeder manager protection relay and network analyzers to
study different principles of the energy quality, power factor a. Symmetric short circuits: three-phase short circuits with
compensation, short circuits, etc. and without contact impedance.

The feeder protection relay includes on this application lets the b. Asymmetric faults:
student to study different faults in the distribution and loads i. Two-phase short circuit with and without contact
systems. impedance.
This application includes a SCADA System to control different ii. Two-phase to ground shortcircuit with and without
elements and analyze the energy quality. contact impedance.
This application includes: iii. Single-phase short circuit with and without contact
Modules: impedance.

 N-ALI01. Industrial Main Power Supply. 4.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
 N-BUS06. Distribution Busbar.
5.- Studying in depth of feeder protection relay.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition. Remote control (with SCADA System):

 N-CFP. Advanced Power Factor Controller Module. 6.- Supervision, Control and Data Acquisition of all electrical
parameters of the load distribution system.
 N-PLC03. PLC03 Control Module.
7.- Remote control of the demanded active power.
 N-CAR19T4D. Three-Phase Digital Capacitor Banks
Module. 8.- Remote control of the demanded inductive reactive power.

 N-CAR36T3D. Three-Phase Digital Bank of Commutable


9.- Remote control of the demanded capacitive reactive power.
Inductances Module. 10.- Remote measurement of all electrical parameters of load
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
distribution system.

 N-CAR19T3D. Three-Phase Digital Bank of Commutable


11.- Remotely control of short circuits in different points of the load
Capacitors Module. power system:

 N-ERP-MA01. Feeder Management Relay Module.


a. Symmetric short circuits: three-phase short circuits with
and without contact impedance.
 N-ERP-MF01. Digital Fault Simulator Module.
b. Asymmetric faults:
SCADA (Supervision, Control and Data Acquisition).
i. Two-phase short circuit with and without contact
This application can be combined with other applications of impedance.
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the ii. Two-phase to ground shortcircuit with and without
end of this catalogue. contact impedance.
iii.Single-phase short circuit with and without contact
impedance.
12.- Recording the evolution of voltage and current phasors during
short circuit for further analysis.
13.- Studying in depth of feeder protection relay.
14.- Automatic power factor compensation in function on the
demanded reactive energy.

Continue...

Page 29 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-02S. Load Systems with Automatic Power Factor Compensation, with SCADA
The AEL-C-02S is a modular application designed to study Some practical possibilities:
automatic reactive power compensation controllers. 1.- Calculating parameters for compensation capacitors.
With this application the student will learn to calculate the required 2.- Compensation using various capacitors.
capacitor banks in function on the demanded reactive energy.
3.- Determining stage power.
Besides, the theory will be compared with an actual power factor
controller. 4.- Manual compensation of reactive power.
The AEL-C-02S includes a series of modules such as automatic 5.- Studying of the power factor controller:
reactive power controller, capacitor banks, resistor loads, inductor Commissioning.
loads and network analyzers to study different principles of the
energy quality, power factor compensation, etc. Programming.
This application includes a SCADA System to control different Capacitor banks connections.
elements and analyze the energy quality. 6.- Automatic compensation of reactive power.
This application includes: 7.- Manual compensation of reactive power.
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS06. Distribution Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CFP. Advanced Power Factor Controller Module.
 N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA
The AEL-C-P-01S is a modular application designed to study Some practical possibilities:
manual reactive power compensation with feeder protection relay. 1.- Calculating parameters for compensation capacitors.
With this application the student will learn to calculate the required
2.- Compensation using various capacitors.
capacitor banks in function on the demanded reactive energy.
3.- Determining stage power.
The AEL-C-P-01S includes a series of modules such as capacitor
banks, resistor loads, inductor loads, feeder protection relay and 4.- Manual compensation of reactive power.
network analyzers to study different principles of the energy quality, 5.- Studying of short circuits:
power factor compensation, short circuits, etc. Three-Phase short circuit.
This application includes SCADA System to control different Single-Phase short circuit.
elements and analyze the energy quality.
Two-Phase short circuit.
This application includes:
6.- Recording of voltage and current phasors evolution during the
Modules: short circuits for further analysis.
 N-ALI01. Industrial Main Power Supply. 7.- Real time measurement of the electrical parameters of the
 N-BUS06. Distribution Busbar. system.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
 N-ERP-MA01. Feeder Management Relay Module.
 N-ERP-MF01. Digital Fault Simulator Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 30 www.edibon.com
3. LOADS SYSTEMS

Applications
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA
The AEL-C-01S is a modular application designed to study manual Some practical possibilities:
reactive power compensation. With this application the student will
1.- Calculating parameters for compensation capacitors.
learn to calculate the required capacitor banks in function on the
demanded reactive energy. 2.- Compensation using various capacitors.
The AEL-C-01S includes a series of modules such as capacitor 3.- Determining stage power.
banks, resistor loads, inductor loads and network analyzers to 4.- Manual compensation of reactive power.
study different principles of the energy quality, power factor
compensation, etc.
This application includes SCADA System to control different
elements and analyze the energy quality.
This application includes:
Modules:
 N-ALI01. Industrial Main Power Supply.
 N-BUS06. Distribution Busbar.
 N-EALD. Network Analyzer Unit with Computer Data
Acquisition.
 N-PLC03. PLC03 Control Module.
 N-CAR19T3D. Three-Phase Digital Bank of Commutable
Capacitors Module.
 N-CAR36T3D. Three-Phase Digital Bank of Commutable
Inductances Module.
 N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
SCADA (Supervision, Control and Data Acquisition).
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 31 www.edibon.com
3. LOADS SYSTEMS

AEL-CS- Special Loads options:


We offer modular applications focused on the study of the dynamic loads, complex loads, consumption measurement, control of peak loads, etc.
There are different topics included, depending on the application:
- Analysis, measurement of complex loads and control of peak loads.
All applications include SCADA (Supervision, Control and Data Acquisition).

AEL-CS-
Special Loads options

Applications
AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load Monitoring, with SCADA.

Applications

AEL-CS-03S. Complex Loads, Power Consumption Measurement and Peak Load Monitoring, with SCADA
The AEL-C-03S is a modular application designed to study the
complex load, power consumption measurement and peak load
monitoring.
With this application the student will learn the difference between
star-delta loads connection, measurement of reactive and active
energy for symmetric and asymmetric RL loads, over-compensation
RC load, etc.
The AEL-C-03S includes a series of modules such as capacitor
banks, resistor loads, inductor loads and network analyzers to study
different principles of the complex loads.
This application includes SCADA System.
This application can be combined with other applications of
generation systems and transmission/distribution systems areas.
Some examples of recommended configurations are shown at the
end of this catalogue.

Page 32 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

SCADA

In order to understand in depth how work actual power systems, EDIBON offers a series of "Modular Smart Grid Power Systems Simulators".

The "Modular Smart Grid Power Systems Simulators" are configured applications of generation, transmission and loads areas that has been described
individually at the beginning of this catalogue.

The objective of these Power Systems Simulators is give the students different technical solutions to understand how nowadays work together the actual
generation, transmission, distribution and load power systems.

Due to EDIBON provides a wide variety of applications, different applications configurations of generation, transmission/distribution and loads are
recommended in order to form a “Modular Smart Grid Power Systems Simulator”.

Examples of Recommended Systems Simulators Configurations:

AEL-MPSS-01. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission Line, Loads and Protection
Relays, with SCADA.

AEL-MPSS-02. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission Line and Loads, with SCADA.

AEL-MPSS-03. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission Line, Loads and Protection
Relays, with SCADA.

AEL-MPSS-04. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission Line and Loads, with SCADA.

Page 33 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-01. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission
Line, Loads and Protection Relays, with SCADA
The AEL-MPSS-01S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It is one of the most comprehensive and advanced modular smart grid power systems simulator because it shows the most important operations of an
entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
 AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
 AEL-GCA-P-02S. Generation System with Automatic
Control of Synchronous Generator,
AEL-GCM-P-02S. Generation System with Manual
Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S.
SCADA.
Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
AEL-GCM-02S. Generation System with Manual System due to Black-Outs, with
AEL-GCA-02S. Generation System with Automatic SCADA.
Control of Synchronous Generator and Control of Synchronous Generator
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with Servomotor Synchronous Generator with with SCADA.
and Protection Relays, with SCADA. Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
 AEL-T-P-01S.
AEL-T-01S.
Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

 AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and


Protection Relays, with SCADA .
AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-01S offers the following possibilities and others:


Studying of high voltage protection systems:
It is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in real electrical
substations that give to AEL-MPSS-01S a great authenticity and variety of fault tests.
It incorporates protection relays as the overcurrent protection relay, the differential protection relay for generators and transformers, the distance
protection relay and the feeder protection relay.
Studying of generation substations:
It incorporates a sophisticated system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the energy carried along line like energy losses, drop voltages, etc. It
includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the load. It includes
different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations. It incorporates
different loads modules to simulate energy consumptions.
The AEL-MPSS-01S has a SCADA System for remotely control operations.
Page 34 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-02. Modular Smart Grid Power Systems Simulator, with Automatic Control Generation, Transmission
Line and Loads, with SCADA
The AEL-MPSS-02S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows different operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCA-02S. Generation System with Automatic Control of Synchronous Generator and Synchronization, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
 AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic AEL-GCM-P-02S. Generation System with Manual SCADA.
Control of Synchronous Generator, Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S. Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
System due to Black-Outs, with
 AEL-GCA-02S. Generation System with Automatic
Control of Synchronous Generator and
AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator
and Synchronization, with SCADA. AEL-GAD-03S.
SCADA.
Automatic Generation System
Synchronization, with SCADA.
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of Synchronous Generator with
Synchronous Generator with Servomotor with SCADA.
Servomotor and Protection Relays,
and Protection Relays, with SCADA. AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.

 AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with


SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-02S offers the following possibilities and others:


Studying of generation substations:
It incorporates a sophisticated system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc. It
includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the load.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations.
It incorporates different loads modules to simulate energy consumptions.
The AEL-MPSS-02S has a SCADA System for remotely control operations.
Page 35 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-03. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission
Line, Loads and Protection Relays, with SCADA
The AEL-MPSS-03S is a Modular Smart Grid Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows the most important operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCM-P-02S. Generation System with Manual Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
 AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection Relays, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic
Control of Synchronous Generator,
 AEL-GCM-P-02S. Generation System with Manual
Control of Synchronous Generator,
AEL-GAD-02S.
SCADA.
Auto-Start Diesel Generator
Synchronization and Protection Relays, Synchronization and Protection
Relays, with SCADA. Trainer for Recovery of the Energy
with SCADA. System due to Black-Outs, with
AEL-GCA-02S. Generation System with Automatic AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator SCADA.
Control of Synchronous Generator and
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with Servomotor Synchronous Generator with with SCADA.
and Protection Relays, with SCADA. Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator in
an Isolated Grid and Protection Relays, an Isolated Grid and Protection
with SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in Control of Synchronous Generator
an Isolated Grid, with SCADA. in an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
 AEL-T-P-01S.
AEL-T-01S.
Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
 AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .
AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-03S offers the following possibilities and others:


Studying of high voltage protection systems:
It is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in real electrical
substations that give to AEL-MPSS-03S a great authenticity. It incorporates protection relays as the overcurrent protection relay, the differential
protection relay for generators and transformers, distance protection relay and feeder protection relay.
Studying of generation substations:
It incorporates a manual control system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc. It includes
a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations. It
incorporates different loads modules to simulate energy consumptions and to study the manual compensation of reactive power.
The AEL-MPSS-03S has a SCADA System for remotely control operations.

Page 36 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -

AEL-MPSS-04. Modular Smart Grid Power Systems Simulator, with Manual Control Generation, Transmission
Line and Loads, with SCADA
The AEL-MPSS-04S is a Modular Power Systems Simulator designed to study how Smart Grids operate within the large actual power systems.
It shows different operations of an entire power system, from the energy is generated until it reaches the final consumer.
This simulator consists of:
 AEL-GCM-02S. Generation System with Manual Control of Synchronous Generator and Synchronization, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
 AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.
 SCADA (Supervision, Control and Data Acquisition), Workbenches and PC.

1. GENERATION SYSTEMS

AEL-GCA- AEL-GCM- AEL-GAD-


Automatic Control Generation Systems options Manual Control Generation Systems options Additional Generation Systems options

Applications Applications Applications


Synchronization Studies Synchronization Studies AEL-GAD-01S. Pumping Power Plant, with
AEL-GCA-P-02S. Generation System with Automatic AEL-GCM-P-02S. Generation System with Manual SCADA.
Control of Synchronous Generator, Control of Synchronous Generator,
Synchronization and Protection AEL-GAD-02S. Auto-Start Diesel Generator
Synchronization and Protection Relays, Trainer for Recovery of the Energy
with SCADA. Relays, with SCADA.
AEL-GCA-02S. Generation System with Automatic
Control of Synchronous Generator and
 AEL-GCM-02S. Generation System with Manual
Control of Synchronous Generator
System due to Black-Outs, with
SCADA.
Synchronization, with SCADA. and Synchronization, with SCADA. AEL-GAD-03S. Automatic Generation System
AEL-GCM-P-03S. Manual Synchronization System of with Two Parallel Generators,
AEL-GCA-P-03S. Automatic Synchronization System of
Synchronous Generator with with SCADA.
Synchronous Generator with Servomotor
Servomotor and Protection Relays, AEL-GAD-04S. Hydroelectric Power Plant, with
and Protection Relays, with SCADA.
with SCADA.
AEL-GCA-03S. Automatic Synchronization System of SCADA.
AEL-GCM-03S. Manual Synchronization System of
Synchronous Generator with Servomotor, Synchronous Generator with
with SCADA. Servomotor, with SCADA. These applications are additional for AEL-GCA and AEL-
Isolated Grid Studies Isolated Grid Studies GCM applications.
AEL-GCA-P-01S. Generation System with Automatic AEL-GCM-P-01S. Generation System with Manual
Control of Synchronous Generator in an Control of Synchronous Generator in
Isolated Grid and Protection Relays, with an Isolated Grid and Protection
SCADA . Relays, with SCADA.
AEL-GCA-01S. Generation System with Automatic AEL-GCM-01S. Generation System with Manual
Control of Synchronous Generator in an Control of Synchronous Generator in
Isolated Grid, with SCADA. an Isolated Grid, with SCADA.

2. TRANSMISSION/DISTRIBUTION SYSTEMS

AEL-T-
Transmission and Distribution Power Systems options

Applications
One Line and Regulation Transformer Studies
AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
 AEL-T-01S. Transmission and Distribution Power Systems with Regulation Transformer, with SCADA.
Two Aerial Lines Studies
AEL-T-P-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines and Protection Relays, with SCADA.
AEL-T-02S. Transmission and Distribution Power Systems with Two Aerial Parallel Lines, with SCADA.
Additional Studies Possibilities
AEL-T-P-04S. Electrical Distribution Grids Trainer with Protections Relays, with SCADA .
AEL-T-04S. Electrical Distribution Grids Trainer, with SCADA.
AEL-T-03S. Power Flow Control in Meshed Networks, with SCADA.

3. LOADS SYSTEMS (Energy Utilization)

AEL-C- AEL-CS-
Conventional Loads options Special Loads options

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and AEL-C-03S. Complex Loads, Power Consumption Measurement and Peak Load
Protection Relays, with SCADA . Monitoring, with SCADA.
AEL-C-02S. Loads Systems with Automatic Power Factor Compensation, with
SCADA.
AEL-C-P-01S. Loads Systems with Manual Power Factor Compensation and Protection
Relays, with SCADA .

 AEL-C-01S. Loads Systems with Manual Power Factor Compensation, with SCADA.

The AEL-MPSS-04S offers the following possibilities and others:


Studying of generation substations:
It incorporates a manual control system for control and regulation of the turbine (prime mover) and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the generation substations.
Studying of the transmission/distribution systems:
It incorporates a transmission line module to study different events in function on the transmitted energy like energy losses, drop voltages, etc.
It includes a regulation transformer and network analyzers to study the drop voltage compensation in the transmission lines.
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the emitter and receiver
substations.
Studying of energy consumption systems:
It includes different bus-bars to demonstrate the main maneuvers carried out with disconnectors and circuit breakers in the distribution substations.
It incorporates different loads modules to simulate energy consumptions and to study the manual compensation of reactive power.
The AEL-MPSS-04S has a SCADA System for remotely control operations.

Page 37 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

Modular Smart Grid Power Systems Simulator,


with Automatic Control Generation,Transmission Line,
Loads and Protection Relays, with SCADA
Technical Teaching Equipment
AEL-MPSS-01

AEL-GCA-P-02S AEL-T-P-01S AEL-C-P-02S


Generation System with Automatic Control Transmission and Distribution Power Systems Loads Systems with Automatic Power Factor
of Synchronous Generator, Synchronization with Regulation Transformer and Protection Relays, Compensation and Protection Relays, with SCADA
and Protection Relays, with SCADA with SCADA

+ +

EDIBON SCADA System

OPEN CONTROL
+ Control
MULTICONTROL Interface
+
REAL TIME CONTROL
SCADA Software

This simulator consists of:

AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection
Relays, with SCADA.

AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with
SCADA.

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

SCADA (Supervision, Control and Data Acquisition).

Workbenches and PC.

Page 38 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
INTRODUCTION
Due to electricity can not be stored in large quantities and economically not profitable, so that at each instant must be generated that is consumed. The
demanded electric power varies from day to day, so that the generation should follow the same temporal variation, keeping the nominal value of the
system frequency, 50 Hz, and other conditions that define the normal operating state of the power system, all with the economic objective of lower cost of
production.
For this purpose, the basic objective of the systems of regulation and control of generators installed in power plants generation is to ensure that the
demanded power meets continuously, maintaining continuity of supply and the operating parameters of the system within limits. This function is performed
automatically from the generators and control centers through automatic voltage regulation (AVR") and, above all, through automatic generation control
(AGC").
The AEL-MPSS-01 simulator has been developed to demonstrate how Smart Grids operate within the large power systems:
How electricity is generated?
How electricity is transported?
What happens when there is a change in the energy demand?
What protection systems are used in generation, transmission, distribution and consumption systems?
What happens when there is a fault anywhere in the power system? What is the proper configuration of the protection relays so that there is selectivity in
the power system?
How is carried out the regulation of the turbine and synchronous generator?
These and many other questions answers the Modular Smart Grid Power Systems Simulator, with automatic control generation, transmission line, loads
and protection relays, with SCADA.

GENERAL DESCRIPTION
The AEL-MPSS-01 has been developed to study in depth the Smart Grid in Generation, Transmission/Distribution and Loads areas.
To facilitate the study of all characteristics issues, and many more, the AEL-MPSS-01 simulator is divided in three applications. Each application has been
developed to study in depth a different area of Smart Grids Power Systems:
- AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
- AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
- AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.
The AEL-MPSS-01 is one of the most comprehensive and advanced modular smart grid power systems simulator for the following reasons:
- The AEL-MPSS-01 integrates the most important Smart Grid technology in all elements that form the power system.
- In a single system we can study the operation of an entire power system, from energy is generated until it reaches the final consumer.
- The AEL-MPSS-01 is provided with 5 latest generation protection relays (renowned manufacturer Schweitzer Engineering Laboratories SEL) used in
real electrical substations that give to AEL-MPSS-01 a great authenticity.
- The AEL-MPSS-01 incorporates protection relays as the overcurrent protection relay, the differential protection relay for generators and transformers,
long distance protection relay and the protection relay for feeders, which make the system AEL-MPSS-01 a forefront unit in the field of Smart Grids.
- The AEL-MPSS-01 incorporates a sophisticated system of control and regulation of the turbine and synchronous generator that will allow the student to
know how carried out the control and regulation in large groups of power generation:
- Manual/automatic control and regulation of the generator voltage (Automatic Voltage Regulator).
- Manual/automatic control and regulation of the generator frequency (turbine control).
- Manual/automatic control and regulation of the power factor of the generator.
- The AEL-MPSS-01 incorporates an automatic reactive power compensation controller that acts autonomously according to the power factor of the
load.
- The SCADA System (Supervision, Control and Data Acquisition) whose description can be read below.
Note: AEL-MPSS-01 includes the workbenches and PC.
SCADA System description
The most innovative of the Modular Smart Grid Power Systems Simulator is that it includes SCADA (Supervision, Control and Data Acquisition System) that
shows the same behaviour of actual SCADA systems used in the actual power systems. The SCADA Software allows students to take full remote control of
the power system and perform all sorts of maneuvers from a synoptic that represents the national power grid. This software allows, among other options,
the following:
- Opening and closing actual logic of disconnect switches and circuit breakers.
- Manual and automatic control of the synchronous generator excitation.
- Manual and automatic control of the synchronous generator frequency.
- Manual and automatic power factor control of the synchronous generator.
- Manual and Automatic synchronization control of the synchronous generator with the mains.
- Faults injection in different parts of the system.
- Change in the energy demand of the system with automatic response of the turbine-generator group.
- Real time monitoring the status of disconnectors and circuit breakers.
- Real time monitoring system alarms when the electrical faults are injected.
- Measurement of active, reactive and apparent power at different points of the system.
- Measurement of voltage, current and power factor at different points of the system.
Continue...

Page 39 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
The SCADA System (Supervision, Control and Data Acquisition ) allows the user to understand, in a clear and simple way, how is the management and
control of generation, transmission/distribution and loads power systems.
Here are some screenshots of the SCADA Software shown:

General scheme of the power grid that allows us to control the "generation", "transmission/distribution" and "loads".

By "clicking" on generation, the most important functions are deployed to control the power flows of our substation power generation:
opening and closing logic control of disconnect switches and circuit breakers, measuremetns of the electrical parameters of the generator
and the network, possibilities of faults injections in many points of the generation system, supervision of electrical faults, emergency stop of
the generator, etc.
Continue...

Page 40 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

Screen for preselecting electrical faults: fault preselecting of three-phase, two-phase and single-phase with or without fault resistor.

Display control of the turbine and the synchronous generator. This menu offers multiple possibilities for control and regulation of the group.
-Precise and manual control of turbine frequency.
-Automatic control of the turbine frequency.
-Precise manual control of the excitation of the synchronous generator.
-Automatic control of synchronous generator excitation.
-Manual synchronization of synchronous generator with the mains.
-Automatic synchronization of synchronous generator with electrical network.
-Island operation mode.
-Alarm monitoring of frequency and reverse power.
-Emergency stop.
-Supervision of the electrical parameters of the generator and the power grid.
-Monitoring the speed of the turbine.
Continue...

Page 41 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

By "clicking" on transmission/distribution, the most important functions are deployed to control the elements of our receiving and emitter
substation:
-Setting of resistance, inductance and capacitance parameters of the transmission line.
-Opening and closing logic control of disconnect switches and circuit breakers.
-Measurements of the electrical parameters upstream and downstream of the transmission line for the study of energy losses in
transporting.
-Faults injection in many points of the transmission system.
-Supervision of electrical faults.
-Voltage adjusting with the distribution transformer with the voltage regulator TAP.

Setup menu of the electrical parameters of the transmission line.


Continue...

Page 42 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01

Load voltage regulation menu.

By "clicking" on loads, the most important functions are deployed to control the elements of our distribution substation:
-Setting the resistance, inductance and capacitance parameters loads.
-Opening and closing control logic of disconnect switches and circuit breakers.
-Measuring of the demanded electrical parameters.
-Faults injection in many points of the loads system.
-Supervision of electrical faults.

Page 43 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
SPECIFICATIONS
The AEL-MPSS-01 simulator includes three applications. Each application has been developed to study in depth a different area of Smart Grids Power
Systems:
- AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection Relays, with
SCADA.
- AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.
- AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA.

AEL-GCA-P-02S. Generation System with Automatic Control of Synchronous Generator, Synchronization and Protection
Relays, with SCADA.

Continue...

Page 44 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)
The AEL-GCA-P-02S is a modular application developed to study the actual generation power systems with Smart Grid Technology.
The Generation System with Automatic Control of the Synchronous Generator, Synchronization and Protection Relays, with SCADA (AEL-GCA-P-02S),
consists of a series of modules that allows us to simulate the most important operations of control, regulation and supervision performed in a Generation
Power System, that is to say, from the electrical energy is generated and raised it with the step-up transformer, until the injection of this energy to the grid.
To perform these operations, in the AEL-GCA-P-02S application are included certain devices that make our application a true Smart Grid:
- Modules to control and regulate the turbine-generator group:
Manual/Automatic control and regulation of the generator voltage (Automatic Voltage Regulator).
Manual/Automatic control and regulation of the generator frequency (turbine control).
Manual/Automatic control and regulation of the generator power factor.
- The overcurrent protection relay, the differential protection relay for generators and transformers, and management relay of generators.
- It includes a sophisticated fault injection system in order to analyze the transients evolution and to observe the request of the protection relays used on
this application.
- Network Analyzers that show us in real time the electrical parameters of the nodes of the system.
- Synchronizing devices for the synchronization maneuvers of synchronous generator and the grid that show us the phases sequence, the difference of
voltage and frequency between the generator and the grid.

The AEL-GCA-P-02S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS01. Generation Busbar.
N-BUS02. Coupling Busbar.
N-BUS03. Grid Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)
N-EALDC/G. DC Generator Analyzer.
N-AVR/P. Automatic Voltage Regulator.
N-VVCA5K. 5KW Motor Speed Controller.
N-ASY3PH. Three-Phase Automatic Synchronoscope.
N-PLC01. PLC01 Control Module.
N-ERP-SFT01. Overcurrent Protection Relay Module.
N-ERP-PDF01. Differential Protection Relay Module.
N-ERP-PGC01. Generator Protection and Control Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
Transformers:
TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
TRANS3/5KSU. 5KW Three-Phase Step-Up Transformer.
Generators:
GMG4.5K3PH. 4.5KW Generator-Motor Group.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
 N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button.
Safety key.
Three-phase terminal connections.
Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS01. Generation Busbar.


Double generation busbar Module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.
Continue...

Page 45 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-BUS02. Coupling Busbar.


Double coupling busbar Module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.

N-BUS03. Grid Busbar.


Grid busbar module.
Local/Remote control switch.
Slide commutators of disconnectors and circuit breaker.
Indicator status lamps. ON-OFF switch.
Signal connector SUB-D 62 pins.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Fuses: Line fuses 3x10A.
Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-EALDC/G. DC Generatoy Analyzer.


DC Analyzer Module.
Rated voltage range: 0-100 Vdc.
Rated current range: 0-10 A.
Communication port RS-485.
2 Power connectors with 7 pin.
ON-OFF Switch.
Terminal connections.
Fuse 10 A.

N-AVR/P. Automatic Voltage Regulator.


Generator voltage regulator module.
Local/Remote control switch.
Manual/Automatic control switch of generator excitation in local mode.
Potentiometer for manual control of the current excitation.
ON-OFF Switch.
Terminal connections.
Signal connector SUB-D 62 pins.

N-VVCA5K. 5KW Motor Speed Controller.


5KW Motor Speed Controller Module.
Three-Phase Power Supply: 400VAC + N.
Nominal Power: 5KW.
Potentiometer speed control motor.
Start/Stop control switch.
Local/Remote control switch.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
Connection terminals.
Continue...

Page 46 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ASY3PH. Three-Phase Automatic Synchronoscope.


Three-Phase digital and programmable synchronoscope.
Display:
Mains voltage display.
Generator voltage display.
Phases difference of mains and generator display.
Synchronization manual push-button.
Disable push-button sync.
Local/remote control switch.
Indicator lamp of synchronizing contactor.
ON-OFF switch.
Terminal connections.
Safety fuses.
Signal connector SUB-D 62 pins.

N-PLC01. PLC01 Control Module.


PLC Siemens S7-300.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
2 x Fuses 2A.

N-ERP-SFT01. Overcurrent Protection Relay.


Overcurrent protection relay module.
Power supply: 230 VAC.
TRIP indicator lamps.
Overcurrent and Earth fault protection.
Communications connector DB9 RS-232.
Signals connector SUB-D 62 pin.
ON-OFF Switch.
Terminal connections.
Characteristics:
- Phase, ground and negative sequence overcurrent protection.
- Time-Overcurrent curves of US and IEC.
- Reclosing relays of multiple trips with sequence coordination.
- SELOGIC® enhanced control equations to develop traditional or advanced schemes.
- Logic of local / remote control to change the schemes, operating circuit breakers, etc.
- Recorder of the sequence of events (SER) and reports of events stored in nonvolatile memory.
- Supports ASCII, SEL LMD, and Modbus RTU protocols.

N-ERP-PDF01. Differential Protection Relay Module.


Differential protection relay module.
Power supply: 230 VAC.
TRIP lamp indicator.
Differential protection.
Communications connector DB9 RS-232.
Signals connector SUB-D 62 pins.
ON-OFF switch.
Terminal connectors.
Characteristics:
This module protects transformers with two terminals, generators, reactances and other power devices using a combination of differential,
instantaneous and overcurrent elements. Differential security scheme is achieved through the following actions:
- Dual-slope restricting percentage.
- Lock second and fourth harmonic.
- Lock the fifth harmonic for transformer overexcitation.
- Compensation of the CT connection and the transformers.

Continue...

Page 47 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ERP-PGC01. Generator Relay Protection Module.


Generator protection relay and control module.
Power supply: 230 VAC.
"island grid/parallel grid" control switch.
"local/remote" control switch.
Manual control switches of the generator relay module:
1. SW1 Emergency Stop.
2. SW2 Automatic start of generator-motor group.
3. SW3 reset alarms push-button.
4. SW4 enable frequency control of the generator.
5. SW5 manual permission to close the 52G1 synchronization circuit breaker.
Status indicator lamps. Status indicator alarms lamps. Safety key for synchronization. Emergency stop push-button.
Signal connector SUB-D 62 pins.
ON-OFF switch.
Terminal connections.
Some characteristic of the generator protection relay module N-ERP-PGC01:
- The N-ERP-PGC01 allows to operate with until 16 synchronous generators in island grid mode with reactive and active load share,
automatic start/stop of the generators in function of the demanded energy.
- The N-ERP-PGC01 allows parallel operations of one generator with the mains.
- The N-ERP-PGC01 allows different control modes of circuit breakers as opening, closing and synchronization.
- The N-ERP-PGC01 has analog outputs to control the voltage and frequency regulators of the market.
- Three-phase measurement of the mains and generator voltage.
- Three-phase measurement of the current and power of the generator.
- Single-phase measurement of the mains.
Protections:
- Generator: max/mín-voltage (59/27), max/min-frequency (81O/U), voltage asymmetry, dead bus detection, overload (32), unbalance
load (46), reverse power/reduce (32R/F), overcurrent time define curve (50/51), inverse time overcurrent (IEC255), fault ground
(50N/51N), phases, breakers fault.
- Motor: over/sub speed (12).
- Mains: max/min-voltage (59/27), max/min-frequency (81O/U), vector surge.

N-ERP-MF01. Digital Faults Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

Transformers:
 TRANS3/5KGR. 5KW Three-Phase Grid Transformer.
5KVA Three-Phase Grid transformer.
Rated Power: 5KVA.
Rated Primary Voltage: 400VAC Star.
Rated Secondary Voltage: 400VAC Delta.

TRANS3/5KSU. 5KW Three-Phase Step-up Transformer.


5KVA Step-Up transformer.
Rated Power: 5KVA.
Rated Primary Voltage: 400VAC Star.
Rated Secondary Voltage: 400VAC Delta.

Generators:
GMG4.5K3PH. 4.5KW Generator-Motor Group.
Generator-Motor Group mounted in aluminum structure with wheels.
Rated generator power: 4,5 KVA.
I rated stator: 6.5A.
I rated excitation: 4A.
RPM: 3000 rpm.
Rated motor power: 5 KVA.
I rated: 7.2A.
RPM: 3000 rpm.

SCADA (Supervision, Control and Data Acquisition).


Continue...

Page 48 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-GCA-P-02S

With local control mode:

1.- Studying of generation power systems with double busbar 22.- Analysis with SCADA software of active and reactive power of
configuration. synchronous generator.

2.- Studying of opening and closing maneuvers of isolator switches and 23.- Remotely control of manual synchronization of synchronous
circuit breaker in double busbar systems. generator with the mains.

3.- Analysis of the measurements of the power flows of the synchronous 24.- Remotely control of automatic synchronization of synchronous
generator. generator with the mains.

4.- Analysis of the active and reactive power of the generator. 25.- Remotely control of synchronous generator in island grid operation
mode.
5.- Manual synchronization maneuvers of synchronous generator with
the mains. 26.- Studying of Micro-Grids.

6.- Automatic synchronization maneuvers of synchronous generator 27.- Remotely control of synchronous generator in parallel grid operation
with the mains. mode.

7.- Studying of the synchronous generator in island operation mode. 28.- Remotely control of excitation/voltage regulation of synchronous
generator in island mode.
8.- Studying of the Micro-Grids.
29.- Remotely control of the turbine regulation (frequency control) in
9.- Studying of the synchronous generator in grid parallel operation island operation mode.
mode.
30.- Remotely control of excitation/voltage regulation of the synchronous
10.- Studying of excitation/voltage regulation of synchronous generator generator in parallel grid operation mode.
in island mode.
32.- Remotely control of turbine regulation (frequency control) in paralel
11.- Studying of turbine regulation (frequency control) in island mode. grid operation mode.
12.- Studying of excitation/voltage regulation of synchronous generator 33.- Remotely control of power factor regulation of synchronous generator
in parallel grid operation mode. in parallel grid operation mode.
13.- Studying of turbine regulation (frequency control) in parallel grid 34.- Remotely control of short circuits in different points of the generation
operation mode. power system:
14.- Studying of the power factor regulation of synchronous generator in a. Symmetric short circuits: three-phase short circuits with and
parallel grid operation mode. without contact impedance.
15.- Studying of short circuits in different points of generation power b. Asymetric faults:
system:
i. Two-phase short circuit with and without contact impedance.
a. Symmetric short circuits: three-phase short circuits with and
without contact impedance. ii. Two-phase to ground shortcircuit with and without contact
impedance.
b. Asymmetric faults:
iii.Single-phase short circuit with and without contact impedance.
i. Two-phase short circuit with and without contact impedance.
35.- Supervision of TRIPS from the SCADA software (protection relays
ii. Two-phase to ground shortcircuit with and without contact shooting) in the power system.
impedance.
36.- Remotely control of the synchronous generator protection and control
iii.Single-phase short circuit with and without contact relay.
impedance.
37.- Remotely control of the differential protection relay.
16.- Studying of synchronous generator protection and control relay.
38.- Remotely control of the overcurrent protection relay.
17.- Studying of differential protection relay.
39.- Supervision of the electrical parameters of the generation system with
18.- Studying of overcurrent protection relay. the SCADA software.
Remote control mode (with SCADA System):

19.- Remotely control of generation power systems with double busbar.

20.- Remotely control of opening and closing maneuvers of isolator


switches and circuit breaker in doble busbar systems.

21.- Analysis with the SCADA software of synchronous generator power


flows.

Page 49 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

AEL-T-P-01S. Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA.

Continue...
Page 50 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

The Transmission and Distribution Power Systems with Regulation Transformer and Protection Relays, with SCADA (AEL-T-P-01S) is a modular application
with Smart Grid technology developed to study the Transport and Distribution power systems.
This application allows the student to acquire the most important knowledge about how the electrical energy is transported, why it is rised until certain
voltage levels, what is the function of the transformers with voltage regulator, etc. Besides, the student will know how are performed the basic maneuvers in
double busbar systems, what is the correct sequence of actuation between isolator switches and circuit breaker and many other questions.
The AEL-T-P-01S application consists of a series of modules that allow us simulate the most important operations of control, regulation and supervision
performed in emitter and receiver substations joined with an aerial transmission line.
In order to put in practice all these knowledge, in the AEL-T-P-01S application are included certain devices that make our application a true Smart Grid:
- It includes a distance protection relay. This relay monitors, in real time, the impedance parameters of the transmission line.
- It includes a sophisticated faults injection module to analyze the evolution of transients and observe the request of the protection relays used in the
application.
- It includes network analyzers that show us in real time the electrical parameters in the transmission line to study the energy losses, droop voltages, line
currents, etc.
- It includes a voltage regulator TAP in the distribution transformer to compensate the droop voltage of the transmission line.

The AEL-T-P-01S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS04. Emitter Transport Busbar.
N-BUS05. Receptor Transport Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)
N-PLC02. PLC02 Control Module.
N-REG15. Tap Module Regulator.
N-AE1CD. Transmission Lines Simulator Digital Unit.
N-ERP-PD01. Distance Protection Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
Transformers:
TRANS3/5KR. 5KW Step-Down Transformer with Voltage Regulator.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button.
Safety key.
Three-phase terminal connections.
Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS04. Emitter Transport Busbar.


Emitter transport busbar module.
Local/remote switch.
Slide commutators of disconnectors and circuit breaker.
Status indicator lamps. ON-OFF switch.
Communication connector.
Power supply: 230 VAC.

N-BUS05. Receptor Transport Busbar.


Double distribution busbar module.
Local/Remote control switch.
Slide commutators of of disconnectors and circuit breaker.
Status indicator lamps. ON-OFF switch.
Communications connector SUB-D 62 pin.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Continue...
Page 51 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

Fuses: Line fuses 3x10A.


Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-PLC02. PLC02 Control Module.


PLC Siemens S7-300.
Signal connector SUB-D 62 pins.
ON-OFF Switch.
2 x Fuses 2A.

N-REG15. Tap Module Regulator.


TAP voltage regulator module.
Single-Phase power supply: 230VAC.
Voltage TAP selector:
+7,5%; +5%; +2,5%; 0%; -7,5%; -5%; -2,5%.
Indicator lamps regulation percentage.
Local/remote control switch.
OFF-ON Commutator.
ON-OFF switch.
Signal connector SUB-D 62 pins.

N-AE1CD. Transmission Lines Simulator Digital Unit.


Transmission lines simulation digital unit.
Local/remote switch.
Switches to preselect a line resistance.
Switches to preselect a line inductance.
Switches to simulate R phase lost.
Switches to simulate S and T phase lost.
Status indicator lamp. ON-OFF switch.
Voltage Lines ( 400 VAC).

N-ERP-PD01. Distance Protection Relay Module.


It is used to enable investigations into protection and monitoring of overhead transmission lines and underground cables. It enables a
wide range of test and investigations and it demonstrates the latest relay technology.
Modern industrial application distance protection relay presented in an educational and teaching format.
The connections are via safety sockets.
The main functions:
Two zones of Phase Mho Distance Protection Element (21P).
Two zones of Ground Mho Distance Protection Element (21G).
Directional Phase Overcurrent Protection Element (67P).
Directional Ground Overcurrent Protection Element (67G).
Phase Overcurrent Protection Element (50P).
Ground Overcurrent Protection Element (50G).
Phase Time-Overcurrent Protection Element (51P).
Ground Time-Overcurrent Protection Element (51G).
Event Reports.
Breaker Wear Monitor.
Fault Locator.
Local Display.
Synchronophasors.
Load Encroachment.
Metering and Monitoring Functions.
Creating fault and disturbance records.
Blocking of any one protection element.
The connection to the experimental circuit is via current transformers with ratio to suit the inputs of the relay.
It allows an effective demonstration of the effect of current and voltage transformer ratio, connection and rating on protective relays.
Accuracy: +- 10%. Current: 5 A (A. C.). Frequency: 50 or 60 Hz.
Operating time: typically 10 ms to 25 ms.
Continue...

Page 52 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

 N-ERP-MF01. Digital Fault Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

Transformers:
 TRANS3/5KR. 5KW Step-Down Transformer with Voltage Regulator.
Isolating three-phase power transformer.
Pn: 5KVA. Vp with regulation: 400VAC delta. +7,5%, +5%, +2,5%, 0%, -2,5%, -5%, 7,5%. Vs: 400VAC Star.

SCADA (Supervision, Control and Data Acquisition).

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-T-P-01S


Local control:
1.- Opening and closing basic maneuvers of isolator switches and 20.- Studying of energy losses of the transmission line.
circuit breaker. 21.- Remote measurement of droop voltages in the transmission line in
2.- Measurements of energy losses in the transmission line. function on the system load.
3.- Droop voltage compensation with the voltage regulator TAP. 22.- Remote automatic configuration of the transmission line impedance.
4.- Real time measurements of the electrical parameters (voltage, 23.- Remote automatic selection of the line to line capacitive effect of the
current, frequency, power factor, active power, reactive power, transmission line.
aparent power, active energy, reactive energy, aparent energy, etc.). 24.- Remote automatic selection of the line resistor of the transmission line.
5.- Studying of the energy losses of the transmission line. 25.- Remote automatic selection of the line inductance of the transmission
6.- Studying of the droop voltages in the transmission line in function on line.
the load system. 26.- Remote automatic selection of one line phase loss.
7.- Automatic configuration of the line parameters. 27.- Remote automatic selection of two line phases loss.
8.- Automatic selection of the line to line capacitive effect. 28.- Remotely control of short circuits in different points of the transmission
9.- Automatic selection of line resistor. power system:
10.- Automatic selection of line inductance. a. Symmetric short circuits: three-phase short circuits with and
11.- Simulation of one phase loss. without contact impedance.
12.- Simulation of two phase loss. b. Asymmetric faults:
13.- Studying of short circuits in different points of transmission power i. Two-phase short circuit with and without contact impedance.
system: ii. Two-phase to ground shortcircuit with and without contact
a. Symmetric short circuits: three-phase short circuits with and impedance.
without contact impedance. iii.Single-phase short circuit with and without contact impedance.
b. Asymmetric faults: 29.- Short circuits temporal evolution recording of voltage and currents
i. Two-phase short circuit with and without contact impedance. phasors for further analysis.
ii. Two-phase to ground shortcircuit with and without contact 30.- Calculation of the electrical parameters of the transmission line for
impedance. subsequent configuration of the distance relay (mho characteristic).
iii.Single-phase short circuit with and without contact 31.- Studying in depth of the distance protection relay.
impedance.
14.- Recording the evolution of voltage and current phasors during short
circuit for further analysis.
15.- Calculation of the electrical parameters of the line to configure the
distance protection relay (mho characteristic).
16.- Studying in depth of the distance protection relay.
Remote control (with SCADA System):
17.- Supervision, Control and Data Acquisition of all electrical
parameters of the transmission line.
18.- Monitoring of energy losses of transmission lines from the PC.
19.- Remotely control of distribution transformer voltage regulator (TAP).
Compensation of droop voltages of the transmission line.
Continue...

Page 53 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

AEL-C-P-02S. Loads Systems with Automatic Power Factor Compensation and Protection Relays, with SCADA

Continue...

Page 54 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

The AEL-C-P-02S is a modular application developed to study the operation and control of the final loads of the power systems. This application is
equipped with the most advanced protection systems used nowadays in substations and distribution lines. Besides, the AEL-C-P-02S has an automatic
power factor compensation (SVC type). The AEL-C-P-02S has an overcurrent protection relay used in distribution systems (feeders) with which the student
will simulate different short circuits along the load distribution system and subsequently, the student will analyze how the protection relay acts over
corresponding circuit breaker. Besides, the AEL-C-P-02S application has an automatic power factor controller with six stages. For the analysis of the
automatic response of the power factor controller, we have a group of resistive, inductive and capacitive loads in order to simulate actual process of the
energy demand and the power factor compensation.

The AEL-C-P-02S includes:


Modules:
N-ALI01. Industrial Main Power Supply.
N-BUS06. Distribution Busbar.
N-EALD. Network Analyzer Unit with Computer Data Acquisition.
N-CFP. Advanced Power Factor Controller Module.
N-PLC03. PLC03 Control Module.
N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.
N-CAR36T3D. Three-Phase Digital Bank of Commutable Inductances module.
N-CAR35T3D. Three-Phase Digital Bank Resistors Module.
N-CAR19T3D. Three-Phase Digital Bank of Commutable Capacitors Module.
N-ERP-MA01. Feeder Management Relay Module.
N-ERP-MF01. Digital Fault Simulator Module.
SCADA (Supervision, Control and Data Acquisition).

Technical Data:
Modules:
N-ALI01. Industrial Main Power Supply.
Industrial three-phase power supply.
Three-Phase power supply: 400 VAC.
Emergency stop push-button. Safety key.
Three-phase terminal connections. Single-phase terminal connections.
7 pin connector to supply the module.
30mA Three-phase differential protection.

N-BUS06. Distribution Busbar.


Distribution bus-bar module.
Local/remote switch.
Slide commutators of disconnectors and circuit breaker.
Status indicator lamps. ON/OFF switch.
Communications connector SUD-D 62 pin.

N-EALD. Network Analyzer Unit with Computer Data Acquisition. (2 units)


Power Switch.
Input terminals: Three-Phase measurement input terminals with neutral, 400VAC.
Output terminals: Three-Phase measurement output terminals with neutral, 400VAC.
Communication port Rs485.
Supply terminals: Nominal Voltage: 230VAC.
Fuses: Line fuses 3x10A.
Digital Outputs: Three digital outputs for pulses or alarms, or for combining either.
Network Analyzer:
It allows to measure the voltage, currents, active power, reactive power, frequencies, energies per phases, armonics, etc.
Navigation Joystick: It allows us to navigate with different analyzer parameters.
Preselector:
This element allows us to preselect different standard measurements:
Position 1: Measurement of phase voltage.
Position 2: Measurement of line currents.
Position 3: Measurement of line powers.

N-CFP. Advanced Power Factor Controller Module.


Automatic power factor controller module.
Four quadrants regulation.
FCP System (fast computerized program).
Compensation stages: 6 relay outputs.
LCD display with three digits and more than 20 icons to indicate different operation conditions.
ON-OFF switch.
Continue...

Page 55 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

 N-PLC03. PLC03 Control Module.


PLC Siemens.
Communications connector SUB-D 62 pin.
ON-OFF switch
2 x Fuses 2A.

N-CAR19T4D. Three-Phase Digital Capacitor Banks Module.


Three-phase digital banks of commutable capacitors module.
Three-phase commutable capacitor banks:6x(3x7uF).
Signals connector.

N-CAR36T3D. Three-Phase Digital Bank of Commutable Inductances Module.


Three-phase digital banks of commutable inductances module.
Three load slide commutators.
3 x three-phase commutable inductance banks:3x(3x1,4 H).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

N-CAR35T3D. Three-Phase Digital Bank Resistors Module.


Three-phase digital bank of commutable resistors module.
Three load slide commutators.
Three-phase commutable resistor banks:3x150 ohms (1000W, 2000W, 3000W).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

N-CAR19T3D. Three-Phase Digital Bank of Commutable Capacitors Module.


Three-phase digital banks of commutable capacitors module.
Three load slide commutators.
3 x three-phase commutable capacitor banks:3x(3x7uF).
Local/Remote control switch.
ON-OFF switch.
Communications connector SUB-D 62 pin.

 N-ERP-MA01. Feeder Management Relay Module.


The main functions:
Four levels of Phase Instantaneous Overcurrent Element (50P).
Four levels of Negative-Sequence Overcurrent Element (50Q).
Four levels of Residual Overcurrent Element (50G).
Four levels of Neutral Overcurrent Element (50G).
Two levels of Phase Time-Overcurrent Element (51P).
Two levels of Residual Time-Overcurrent Element (51G).
Two levels of Ground Time-Overcurrent Element (51G).
One level of Negative-Sequence Time-Overcurrent Element (51Q).
Phase to Ground Overvoltage (59G).
Phase to Phase Overvoltage (59P).
Negative-Sequence Overvoltage (59Q).
Residual Overvoltage (59G).
Phase to Ground Undervoltage (27G).
Phase to Phase Undervoltage (27P).
Six levels of Secure Overfrequency (81O).
Six levels of Secure Underfrequency (81U).
Two levels of Negative Power Flow with Definite Time Delay (32).
Two levels of Positive Power Flow with Definite Time Delay (32).
Station Battery Monitor.
Breaker Wear Monitoring.
Synchrophasor Protocol.
Peak Demand and Demand Metering.
Auto-Reclosing.
Creating fault and disturbance records.
Accuracy: +- 10%. Current: 5 A (A. C.) Frequency: 50 or 60 Hz
Operating time: typically 10 ms to 25 ms.
Continue...

Page 56 www.edibon.com
MODULAR SMART GRID POWER SYSTEMS SIMULATORS
- RECOMMENDED SYSTEMS SIMULATORS CONFIGURATIONS -
EXAMPLE

AEL-MPSS-01
Specifications (continuation)

N-ERP-MF01. Digital Fault Simulator Module.


Faults injection module.
Preselector of kind of fault:
Three-Phase short circuit.
Two-phase short circuit.
Two-phase to ground short circuit.
Single-phase short circuit.
Local/Remote control switch.
ON-OFF switch.
Terminal connections.
Signals connector SUB-D 62 pins.

SCADA (Supervision, Control and Data Acquisition).

EXERCISES AND PRACTICAL POSSIBILITIES WITH AEL-C-P-02S


Local control:

1.- Opening and closing basic maneuvers of isolator switches and 10.- Remote measurement of all electrical parameters of load distribution
circuit breaker of distribution substation. system.

2.- Real time measurements of all electrical parameters of the 11.- Remotely control of short circuits in different points of the load power
distribution systems. system:

3.- Studying of short circuits in different points of load power system: a. Symmetric short circuits: three-phase short circuits with and
without contact impedance.
a. Symmetric short circuits: three-phase short circuits with and
without contact impedance. b. Asymmetric faults:

b. Asymmetric faults: i. Two-phase short circuit with and without contact impedance.

i. Two-phase short circuit with and without contact impedance. ii. Two-phase to ground shortcircuit with and without contact
impedance.
ii. Two-phase to ground shortcircuit with and without contact
impedance. iii.Single-phase short circuit with and without contact impedance.

iii.Single-phase short circuit with and without contact


impedance.
12.- Recording the evolution of voltage and current phasors during short
4.- Recording the evolution of voltage and current phasors during short circuit for further analysis.
circuit for further analysis.
13.- Studying in depth of feeder protection relay.
5.- Studying in depth of feeder protection relay.
14.- Automatic power factor compensation in function on the demanded
Remote control (with SCADA System): reactive energy.

6.- Supervision, Control and Data Acquisition of all electrical


parameters of the load distribution system.

7.- Remote control of the demanded active power.

8.- Remote control of the demanded inductive reactive power.

9.- Remote control of the demanded capacitive reactive power.

*Specifications subject to change without previous notice, due to the convenience of improvements of the product.
REPRESENTATIVE:

C/ Del Agua, 14. Polígono Industrial San José de Valderas.


28918 LEGANÉS. (Madrid). SPAIN.
Phone: 34-91-6199363 FAX: 34-91-6198647
E-mail: edibon@edibon.com WEB site: www.edibon.com

Issue: ED01/16
Date: April/2016

Page 57 www.edibon.com