Problemas Capitulo 6 Unidad 4 Completos
Problemas Capitulo 6 Unidad 4 Completos
Grupo: 7A.
Z = R + jX
(18 km)
R = 0.3792 Ω*milla = 4.242137 Ω
(1.609 millas)
X = Xa + Xd = (0.465 + 0.2012) Ω*milla = 0.6662 Ω*milla
(18 km)
X = (0.6662 Ω*milla) = 7.452827 Ω
(1.609 millas)
Z = 4.242137 Ω + j 7.452827 Ω
Z = 8.575567 Ω ⦟67.05°
b) i) f.p = 0.8 en retraso
2500kW
IR = = 164.019962 A
√3 (11kV)(0.8)
11kW
VS = VR + IR Z = ( ) + (164.019962 A ⦟ − 36.87°)( 8.575567 Ω
⦟67.05°)
√3
VS = 7,602.300304 + j 642.107717 = 7,629.369059 ⦟5.36°
VS = √3 (7,629.369059) = 13,214.45484 V
ii) f.p = 1 (unidad)
2500kW
IR = = 131.215970 A
√3 (11kV)(1)
11kW
VS = VR + IR Z = ( ) + 131.215970 A (4.242137 Ω + j 7.452827 Ω)
√3
VS = √3 (6,976.371002) = 12,083.42903 V
iii) f.p = 0.9 en adelanto
2500𝑘𝑊
𝐼𝑅 = = 145.795522𝐴
√3 (11𝑘𝑉)(0.9)
11𝑘𝑊
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 𝑍 = ( ) + (145.795522 𝐴 ⦟25.84°)( 8.575567 Ω
⦟67.05°)
√3
𝑉𝑆 = √3 (6,608.060118) = 11,445.49586 𝑉
c) f.p = 0.8 en retraso
% de regulacion = 20.13%
f.p = 1 (unidad)
% de regulación = 9.84%
% de regulación = 4.04%
d) f.p = 0.8 en retraso
f.p = 1 (unidad)
Solución.
A B
C
Datos:
f.p.= 0.8 en retraso
l = 100 millas
11.9 ft 11.9
ft
P = 55 MVA
V = 132Kv (línea a línea)
Conductor Drake: RMG= 0.0373
Espaciamiento plano horizontal: 11.9ft
Temperatura del conductor: 50°C - 0.1284 Ω/milla
Reactancia por conductor: 0.399
Deq = 14.9930 ft
Impedancia en serie
Tablas A.3 y A.5 para un conductor tipo Drake
z = (0.1284 + j0.399 + j0.3286)(100 millas)
z = 12.84 + j72.76
z = √(12.84)2 + (72.76)2
z = √5,458.8832
z = 73.8842
72.76
tan 𝜃 −1 = 88.8800°
12.84
z = 73.8842 ∠88.8800°Ω
La admitancia en paralelo
1
Y = 50j ( ) x 10−6
0.912 + 0.0803
Y = 50j(1.0077) (10−6 )
Y = 5.03879x10−4 ∠90°S
b) Las constantes ABCD de la línea.
Como sabemos
ZY
A=D= +1
2
𝐵=𝑍
ZY
C = Y (1 + )
2
Entonces
(73.8842∠88.8800)(5.03879x10−4 ∠90°)
A=1+
2
A = 1 + 0.01861∠178.88°
A = √(1)2 + (0.01861)2
A = 1.0017∠ 1.1846°
A=D
B = 73.8842∠88.8800°
(73.8842)(5.03879x10−4 )
C = 5.03879x10−4 (1 + ∠178.88°)
4
P
IR = (0.8 − j0.6)
√3VR
55MVA
IR = (0.8 − j0.6)
√3(132kV)
IR = 240.5626(0.8 − j0.6)
IR = 192.4500 − j144.3375 A
VR
Iserie = IR + (Y)
√3
132kV
Iserie = 192.4500 − j144.3375 + (j5.03879x10−4 )
√3
Iserie = 192.4500 − j144.3375 + j38.4007
Iserie = 192.4500 − j105.9367
Is = √(200.6284)2 + (−67.536)2
Is = 211.6904∠ − 20.67° A
Is = |Is |
|Is | = 211.6904 A
θ = vs − I𝐬
θ = 13.35° − (−20.67) = 34.0215°
f. p = cos θ
f. p = cos 34.0215
f. p = 0.86 en retraso
|v |
( s − |vR,FL |)
|A|
%Reg = x 100%
|vR,FL |
134.9604 x 103
( − 132kV)
1.0017
%Reg = x 100%
132kV
(2.7313 x 103 )
%Reg = x 100%
132kV
%Reg = 2.0691%
6.3 Encuentre las constantes ABCD de un circuito 𝜋 que tiene una resistencia de
600 Ω para
la rama paralelo en el extremo generador, una resistencia de 1kΩ en la rama
paralelo del
extremo receptor y una resistencia de 80 Ω para la rama serie.
Paso 1
Solución Un circuito 𝜋 contiene resistencias serie, paralelo como se mostrará a
continuación.
Se determinarán las constantes ABCD del circuito con base a las resistencias
conocidas.
Paso 2
La figura siguiente muestra el circuito que conceptualiza de una manera más
grafica el
problema.
𝐼𝑆 80 Ω
𝐼𝑅
1kΩ
𝑉𝑆 600 Ω 𝑉𝑅
Se parte del voltaje del extremo generador y como habrá pérdidas se debe restar a
este voltaje
VR
VS − 80IR − (80)
1000
𝑉𝑆 = 𝑉𝑅 + 80𝐼𝑅 + 0.08𝑉𝑅
VS = 1.08VR + 80IR
Para 𝐼𝑆
VS VR
IS − IR − −
600 1000
Se sustituye 𝑉𝑆 en la ecuación anterior y se despeja.
1.08𝑉𝑅 + 80𝐼𝑅 𝑉𝑅
𝐼𝑆 = 𝐼𝑅 + +
600 1000
𝐼𝑆 = 𝐼𝑅 + 0.0018𝑉𝑅 + 0.13333𝐼𝑅 + 0.001𝑉𝑅
𝐼𝑆 = 0.0028𝑉𝑅 + 1.13333𝐼𝑅
El valor de las constantes ABCD estará dado por
𝑉𝑠 = 𝐴𝑉𝑅 + 𝐵𝐼𝑅
𝐼𝑆 = 𝐶𝑉𝑅 + 𝐷𝐼𝑅
Donde A =1.08, el valor de A es adimensional; B=80 Ω, este valor es en función de
la
resistencia porque debe ser el producto I x R para representar la caída de voltaje
que hay en la
resistencia de 80 Ω; C=0.0028 S, esta está representada en Siemens porque este
valor pertenece
a la admitancia ya que 𝑉𝑅 estará multiplicado por 𝑌; D= 1.1333 𝐼𝑅 .
Y= j (1/0.1074 + 0.0874)𝑥10−6
Y= 8.137470𝑥10−6 ∠90° 𝑠⁄𝑚𝑖𝑙𝑙𝑎
230
b) VR = = 132790.56 ∠36.86 V al neutro
√3
60 𝑀𝑊
𝐼𝑅 = = 150.6131 ∠36.86° 𝐴
√3(230000)
1002
Impedancia base = = 966.66 Ω
60
100000
Corriente base = = 251.021 𝐴
√3(230)
0.8822 67.33−90
Zc= √5.133x10̅6 ( )
2
=414.57 ∠-11.24°Ω
414.57 (−11.24
Zc= = 2.4875 ∠ − 11.24 por unidad
166.66
tan̅168= 38.65
230
VR= 211.78 = 1.086 ∠38.65 por unidad
230
VRFL= 230 = 1.0 por unidad
NL
|VR, |− |VR,FL|
A
c) % DE REGULACIÓN = X100%
|VR,FL|
Zy
A= 1 - =
2
1
1 - 2 (0.1166 (67.5304’ X 0.192 (90°)
= 0.9888
1.0866
−1
% DE REGULACIÓN= 0.9888
x 100%
1
= 9.8900%
6.6 Una línea de transmisión trifásica de un solo circuito está compuesta de
conductores
Parakeet con espaciamiento horizontal plano de 19.85 pies entre conductores
adyacentes.
Determine la impedancia característica y la constante de propagación de la línea a
60Hz y
50⁰C de temperatura.
Datos:
Tipo de conductor: Parakeet
Espaciamiento horizontal: 19.85ft entre conductores adyacentes.
Solución.
z
Zc = √
y
Así como también la constante de propagación y esta se representa de la siguiente
manera:
𝛾√𝑧. 𝑦
Donde:
𝑧 = 𝑟 + 𝑗(𝑋𝒶 + 𝑋𝒹)
𝑗
𝒴=
𝑋´𝒶 + 𝑋𝒹
Para esto en las tablas A-3, A-4 y A-5 encontraremos:
Xa= 0.423 Ω/milla
Xd= 0.3906 Ω/milla
X´a= 0.0969 MΩ. milla
Xd= 0.0955 MΩ. milla
r= 0.1832 Ω/milla
𝑧 = 0.1832 + 𝑗(0.423 + 0.3906)
𝑧 = 0.1832 + 𝑗0.8136
= √(0.1832)2 + (0.8136)
𝑧 = 0.834Ω/𝑚𝑖𝑙𝑙𝑎
0.8136
𝜃 = tan−1
0.1832
𝜃 = 77.31°
𝑧 = 0.834, 77.31° Ω/𝑚𝑖𝑙𝑙𝑎
1,000,00 (90°)
𝑦=
0.0969 + 0.0955
𝑦 = 5.1975𝐸𝑋𝑃 − 6 (90°) 𝑆/𝑚𝑖𝑙𝑙𝑎
Ahora la impedancia capacitiva es la siguiente:
0.834(77.31°)
𝑍𝑐 = √
5.1975𝐸𝑋𝑃 − 6(90°)
𝑍𝑐 = 400.5767 ≅ 400.6(−6.345°)
La constante de propagación es:
Υ = √(0.834)(5.1975𝐸𝑋𝑃 − 6)
= √4.334715𝐸𝑋𝑃 − 6
Υ = 2.081997𝐸𝑋𝑃 − 3(83.655°)
6.7 Mediante las ecuaciones (6.23) y (6.24) demuestre que, si el extremo receptor
de una línea
termina en su impedancia característica, Zc, entonces la impedancia vista en el
extremo
generador de la línea también es Zc, independientemente de la longitud de la línea.
Valores de rms de I y V
Ecuación 6.23: V = (VR + IR Zc/2) (𝑒 𝑦𝐿 ) + (VR - IR Zc/2) (𝑒 −𝑦𝐿 )
Ecuación 6.24: I = (VR/Zc + IR/2) (𝑒 𝑦𝐿 ) - (VR/Zc - IR/2) (𝑒 −𝑦𝐿 )
Si X punto de la línea a una distancia, entonces X=L
6.8 Una línea de transmisión de 200 millas tiene los siguientes parámetros a 60 Hz.
Resistencia R = 0.21 Ω/millas por fase
Reactancia serie x = 0.78 Ω/millas por fase
Suceptancia paralelo b = (5.42) ∗ 10−6 S/millas por fase
a) Determine la constante de atenuación α, la longitud de onda λ, y la
velocidad de
propagación de la línea a 60 Hz.
b) Aplique las ecuaciones 6.26 y 6.27 para determinar las componentes,
incidentes y
reflejada del voltaje y la corriente.
c) Una vez hecho lo anterior determine el voltaje en el extremo generador y la
corriente
de la línea.
Datos:
R = 0.21 Ω/millas por fase x= 0.78 Ω/millas por fase
Z = (0.21 Ω/millas por fase + 0.78 Ω/millas por fase) = 0.808, 77.31° Ω/millas por
fase
Y == (5.42) ∗ 10−6 77.31° S/millas por fase
2
ϓ = √𝑧𝑦 = (2.092) ∗ 10−3
Atenuación constante α = (2.744) ∗ 10−4 milla
2𝜋
Λ== = (2𝜋) ∗ 103 /2.74 = 3030 millas
𝛽
2𝜋𝑓 (5.42)∗10−6
Velocidad de propagación = = millas/S = 181771 millas/
S
𝛽 2.074
2
Zc = √𝑧/𝑦 = 386.05, -7.53°
Ahora calculamos, después de obtener la impedancia los voltajes Vi, Vr, así como Ii
e Ir.
100
Vi = x 1,0567, 23,76° KV = 52.821, 23.77° KV
2
100
Vr = x 0.9466, -23.77KV = 47.33, -23.77°KV
2
100 1.0564,23.76°
Ir=2𝑥3865,−7.53 x = 78.97, 1.33°A
1.7373,30°
Donde debemos obtener el cosh y el senh donde las fórmulas son las siguientes:
𝜀 𝛼 𝜀 𝑗𝛽 + 𝜖 −𝛼 𝜀 −𝑗𝛽 1
cosh(𝛼 + 𝑗𝛽) = = (𝜀 𝛼 ⦟𝛽 + 𝜀 −𝛼 ⦟ − 𝛽)
2 2
𝜀 𝛼 𝜀 𝑗𝛽 − 𝜖 −𝛼 𝜀 −𝑗𝛽 1
senh(𝛼 + 𝑗𝛽) = = (𝜀 𝛼 ⦟𝛽 − 𝜀 −𝛼 ⦟ − 𝛽)
2 2
1
6) cosh(𝜃) = (𝜀 𝛼 ⦟𝛽 + 𝜀 −𝛼 ⦟ − 𝛽) =
2
1 0.06958655
7) = (𝜀 ⦟26.10944151° + 𝜀 −0.06958655 ⦟ − 26.10944151°)
2
1
8) = 2 (1.072064844⦟26.10944151° + 0.932779397 ⦟ − 26.10944151°)
9) (1.072064844𝑐𝑜𝑠⦟26.10944151° 𝑦 1.072064844𝑠en⦟26.10944151°)
= (0.962666 + j0.471801957)
10) (0.932779397𝑐𝑜𝑠⦟ − 26.10944151° 𝑦 0.932779397𝑠en ⦟ − 26.10944151°)
= (0.83759398 -j0.41050422)
1
Cosh =2(0.962666 + j0.471801957 + 0.83759398 - j0.41050422) =
1
(1.8002599 − j0.06129773) = 0.90012995 – j0.030648865.
2
1
Senh= 2(0.962666 -+j0.471801957 - 0.83759398 + j0.41050422) =
1
= (0.12507202 + j0.882306177) = 0.06253601 + j0.441153088.
2
6.10 Por medio de las ecuaciones (6.1), (6.2), (6.10) y (6.37), demuestre que las
constantes
generalizadas de circuito de los tres modelos de líneas de transmisión satisfacen
la condición:
𝐴𝐷 − 𝐵𝐶 = 1
Ecuación 6.1: 𝐼𝑠 = 𝐼𝑅
Ecuación 6.2: 𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅𝑍
𝑍𝑌 𝑍𝑌
Ecuación 6.10: 𝐴 = 𝐷 = + 1 𝐵 = 𝑍 𝐶 = 𝑌 (1 + )
2 4
𝑠𝑒𝑛ℎ 𝛾𝑙
Ecuación 6.37: 𝐴 = cosh 𝛾𝑙 𝐵 = 𝑍𝑐 𝑠𝑒𝑛ℎ 𝛾𝑙 𝐶= 𝐷 = cosh 𝛾𝑙
𝑍𝑐
𝑍𝑌 𝑍𝑌 𝑍𝑌
𝐴𝐷 − 𝐵𝐶 = (1 + ) (1 + ) − 𝑍𝑌 (1 + )
2 2 4
𝑍𝑌 2 𝑍𝑌
𝐴𝐷 − 𝐵𝐶 = (1 + ) − 𝑍𝑌 (1 + )
2 4
𝑍𝑌 𝑍 2 𝑌 2 𝑍2𝑌2
𝐴𝐷 − 𝐵𝐶 = 1 + 2 + − 𝑍𝑌 −
2 4 4
𝑍2𝑌2 𝑍2 𝑌2
𝐴𝐷 − 𝐵𝐶 = 1 + 𝑍𝑌 + − 𝑍𝑌 − =1
4 4
Funciones hiperbólicas:
A = D = cosh 𝑦𝑙
𝐵 = 𝑧𝑐 ∗ sinhyl
sinh 𝑦𝑙
𝐶=
𝑧𝑐
Solución.
Paso 1: Debemos encontrar los valores de las incógnitas A, B, C Y D
• Calculando A Y D
El valor de es coshyl = 0.8903 ∟ 1.3450° que es un valor donde están inmersos los
valores
de admitancia del extremo generador.
• Calculando B
B = (406.3564 ∟ − 5.48105 )(0.4594 ∟84.9433°)
Para desarrollar dicha expresión nos apoyamos de la identidad de Euler
𝑒 𝑖𝜔𝑡 = cos 𝑖𝑤𝑡 + sin 𝑖𝑤𝑡 Para descomponer en parte real e imaginaria nuestros
fasores.
𝐵 = [(406.3564) cos(−5.48105) + 406.3564 sin(−5.48105)]
= (404.4984 − 38.8137 𝑗)
𝐵 = 186.6801 ∟74.46225°
6.12 Una línea de transmisión trifásica de 60 Hz. Tiene una longitud de 175 milla.
La línea
tiene una impedancia serie total de 35 + 𝑗140 Ω y una admitancia en paralelo de
930 𝑥 10−6 ∠90°𝑆. Entrega 40 MW a 220 kV con 90% de factor de potencia en atraso.
Encuentre el voltaje en el extremo generador mediante:
a) La aproximación de las líneas cortas.
b) La aproximación del circuito nominal π.
c) La ecuación de las líneas largas.
Datos
𝑙 = 175 𝑚𝑖𝑙𝑙𝑎𝑠
𝑍 = 35 + 𝑗40
𝑍 53.150729
𝑍𝐶 = √ = √ = 239.06 ∠ − 69.40°
𝑌 930 𝑥 10−6
𝑌 = 930 𝑥 10−6 𝑆
Solución.
𝑃 40000000
𝐼𝑅 = = = 116.636 𝐴
√3 𝑥 𝑉 𝑥 𝐹. 𝑃. √3 𝑥 220000 𝑥 .9
𝑐𝑜𝑠 −1 0.9 = 25.84°
𝐼𝑅 = 116.638 ∠ − 25.84° 𝐴
220 𝑘𝑉
𝑉𝑅 = = 127017.0592 𝑉
√3
𝛾 = √(𝑍)(𝑌) = √(53.150729)(930 𝑥 10−6 ) = .2223289
a)
𝑉𝑆 = 𝑉𝑅 𝑐𝑜𝑠ℎ𝛾𝑙 + 𝐼𝑅 𝑍𝑅 𝑠𝑒𝑛ℎ𝛾𝑙
𝑉𝑆 = (127017.0592 𝑉) + (116.636∠ − 25.84°)(53.150729 ∠48.81° )
𝑉𝑠 = (127017.0592 𝑉) + (6199.288 ∠22.97°)
𝑉𝑠 = (127017.0592 𝑉) + (6199.288 cos 22.97° + 6199.288 sen 22.97°)
𝑉𝑠 = (127017.0592 𝑉) + 5707.742 + 𝑗2419.266)
𝑉𝑠 = 132724.8012 + 𝑗2419.266
𝑉𝑠 = 132746.848 ∠ 1.044° 𝑉
|𝑉𝑠 | = (√3 )(132746.848) = 𝟐𝟐𝟗. 𝟗𝟐𝟒 𝒌𝑽
b)
(𝑍)(𝑌)
𝑉𝑠 = (𝑉𝑅 ) ( + 1) + (𝑍)(𝐼𝑅 )
2
(150.145)(930 𝑥 10−6 )
𝑉𝑠 = (127017.0592) ( + 1) + (53.150729 ∠48.81°)(116.636 ∠
− 25.84°)
2
(. 1396)
𝑉𝑠 = (127017.0592) ( ∠165.96° + 1) + (53.150729 ∠48.81°)(116.636 ∠ −
25.84°)
2
𝑉𝑠 = 130412 ∠ 6.6°
𝑉𝑠 = (√3)(130412) = 𝟐𝟐𝟓. 𝟖𝟖 𝒌𝑽
c)
𝛾𝑙 = √(𝑍)(𝑌) = √(53.150729)(930 𝑥 10−6 ∠165.96°) = .3663 ∠83°
= .0448 + 𝑗. 364
Que estos números encontrados (números reales e imaginarios) son el resultado de:
𝑒 0.0448 𝑒 𝑗0.364
= 0.9773 + 𝑗0.3724
𝑒 −0.0448 𝑒 −𝑗0.364
= 0.8935 − 𝑗0.3405
Ya solo nos queda calcular la regulación de voltaje:
|VR, NL| − |VR, FL|
% 𝑑𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑐𝑖𝑜𝑛 = × 100
|VR, FL|
Sustituyendo en la formula nos queda:
139.12 − 127.02
% 𝑑𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑐𝑖𝑜𝑛 = × 100
127.02
12.1
= 127.02 × 100 = 0.09526 × 100
6.14 Una línea de trasmisión trifásica de 60 Hz tiene una longitud de 250 millas.
El voltaje en
el extremo generador es de 220 kV. Los parámetros de la línea son R= 0.2 Ω/milla, X
= 0.8
Ω/milla y Y= 5.3 µS/milla. Encuentre la corriente en el extremo generador cuando no
hay
carga en la línea.
Datos:
f= 60 Hz
𝑙 = 250 millas
V= 220kV
Ω
R= 0.2 milla
Ω
X= 0. 8 milla
µS
ɣ = 5.3 𝑚𝑖𝑙𝑙𝑎
Solución.
• Admitancia 𝑌 = ɣ𝑙
• Constante de propagación por longitud ɣ𝑙 = √𝑍𝑌
• Impedancia característica 𝑍𝑐 = √𝑌
𝑍
• Simplificación
0.8
Cos −1 = 75.96375653°
0.2
• 𝑌 = 5.3
µS
(250 milla) = 𝟏. 𝟑𝟐𝟓𝐦𝐒 < 𝟗𝟎°
𝑚𝑖𝑙𝑙𝑎
1.325x10−3
Cos −1 = 89.99963°
206.15528
𝟎. 𝟓𝟐𝟐𝟔𝟒𝟑𝟎𝟒𝟎𝟒 < 𝟖𝟗. 𝟗𝟗𝟗𝟔𝟑°
• 𝑍𝑐 = √
𝟐𝟎𝟔.𝟏𝟓𝟓𝟐𝟖𝟏𝟑 Ω<𝟕𝟓.𝟗𝟔𝟑𝟕𝟓𝟔𝟓°
𝟏.𝟑𝟐𝟓𝐦𝐒<𝟗𝟎°
𝒁𝒄 = 𝟑𝟗𝟓. 𝟏𝟗𝟑𝟗𝟑𝟎𝟏 Ω < −𝟕. 𝟎𝟑𝟑𝟑𝟑𝟑°
220𝐾𝑉
𝑉𝑅 = = 127𝐾𝑉.
√3
80,000𝐾𝐴
𝐼𝑅 = = 209.95𝐴.
√3 × 220𝐾𝑉
Para saber los valores de voltaje y corriente tenemos que usar las siguientes
ecuaciones.
𝑉𝑅
𝐼𝑆 = 𝐼𝑅 cosh 𝛾𝑙 + 𝑠𝑒𝑛ℎ𝛾𝑙.
𝑍𝑐
127,000
𝐼𝑆 = 209.95(0.8703 + 𝑗0.0317) + × 0.4999 < 83.61°.
394 < −7.02°
= 182.72 + 6.66 − 1.77 + 𝑗161.13 = 246.8 < 42.84 𝐴.
También tenemos que sacar el voltaje al neutro por lo que haremos lo siguiente.
127,000𝑉
|𝑉𝑅| = = 145,826 𝑉 𝑎𝑙 𝑛𝑒𝑢𝑡𝑟𝑜.
0.8709
6.16 Una línea de transmisión trifásica tiene una longitud de 300 millas y alimenta
una carga
de 400 MVA con factor de potencia de .8 en atraso a 345 kV. Las constantes ABCD en
la línea
son
A = D = .8180 𝜃1.3°
B = 172.2 𝜃84.2° Ω
C= 001933 𝜃90.4° Ѕ
Datos:
Sistema trifásico.
345 kV trifásicos.
A = D = .8180 𝜃1.3°
B = 172.2 𝜃84.2° Ω
C= .001933 𝜃90.4° Ѕ
Solución.
𝑉 3Ø ∁
VLR= E IR=√3∗𝑉𝐿𝑅
√3
Los cálculos fueron para el extremo receptor es lo que se tenía, ahora el análisis
es del extremo
receptor hacia el extremo suministrador para ello se tendrá que calcular la caída
de voltaje y
tenemos la siguiente formula.
Vs= AVR +BIR formula general (6.8) del libro de sistemas de potencia
Continuando con los incisos nos pide calcular lo mismo, pero ahora sin carga para
lo cual se
tienen las siguientes formulas:
𝑉𝑆 256.7358 𝜃20.1525°
VR= = = 313.8579 𝜃18.8525° V
𝐴 .8180 𝜃1.3°
6.17 Justifique la ecuación 6.50 sustituyendo las funciones hiperbólicas por las
expresiones
exponenciales equivalentes.
La ecuación 6.50 es:
𝛾2 𝑐𝑜𝑠ℎ𝛾𝑙−1
tanh =
2 𝑠𝑒𝑛ℎ𝛾𝑙
𝜀 𝜃 − 𝜀 −𝜃
1. 𝑠𝑒𝑛ℎ𝜃 = 2
𝜀 𝜃 + 𝜀 −𝜃
2. 𝑐𝑜𝑠ℎ𝜃 = 2
Sabemos que
𝜃 = 𝛾𝑙 y esto es igual a; (𝛼𝑙 + 𝑗𝛽𝑙)
Analizaremos por ambos extremos, el receptor y el generador:
En el lado izquierdo tenemos que;
𝜀 𝛾𝑙⁄2 + 𝜀 −𝛾𝑙⁄2
=
𝜀 𝛾𝑙⁄2 + 𝜀 𝛾𝑙⁄2
Esto nos quiere dar a entender que tanto el lado derecho y el izquierdo son iguales
y que las
expresiones exponenciales con las hiperbólicas son equivalentes.
6.18 Determine el circuito equivalente π para la línea del problema 6.12.
En circuito equivalentes como el circuito π, pero se sustituye Z por Z´ en la rama
en serie, y
se sustituye Y/2 por Y´/2 en la rama paralelo.
𝒀´ 𝟏 𝒄𝒐𝒔𝒉 𝜸𝒍−𝟏
= 𝒁𝒄
𝟐 𝒔𝒆𝒏𝒉 𝜸𝒍
𝛾𝑙 = 0.3663 ∠82.98°
𝒛 0.8246 75.9637−90
𝒁𝒄 = √𝒚 = √5.3142 × 10−6 ∠ 2
𝑍𝑐 = 393.915 ∠ − 7.018
Ahora para utilizar las funciones hiperbólicas en las ecuaciones 6.42 y 6.43
Pasamos a rectangular 𝛾𝑙
𝛾𝑙 = 0.04476 + 𝑗0.3635
El primer término es α y el segundo término son radianes y los pasamos a grados y
obtenemos
β
α= 0.04476 β=20.827°
𝟏 𝜶 𝟏
𝒄𝒐𝒔𝜸𝒍 = 𝜺 ∠𝜷 + 𝜺−𝜶 ∠ − 𝜷
𝟐 𝟐
1 0.04476 1
𝑐𝑜𝑠𝛾𝑙 = 𝜀 ∠20.82 + 𝜀 −0.04476 ∠ − 20.82
2 2
= 0.4886 + 𝑗0.1858 + 0.4468 − 𝑗0.1588
= 0.5228∠20.82 + 0.4781∠ − 20.82
= 0.9354 + 𝑗 0.027 = 0.9357∠1.653°
𝟏 𝜶 𝟏
𝒔𝒆𝒏𝜸𝒍 = 𝜺 ∠𝜷 − 𝜺−𝜶 ∠ − 𝜷
𝟐 𝟐
Como los valores ya están en la ecuación del coseno y solo se cambia el signo + por
el de – en
la ecuación que sigue de la sustitución
= 0.4886 + 𝑗0.1858 − 0.4468 + 𝑗0.1588
= 0.0418 + 𝑗 0.3446 = 0.3471 ∠83.08
𝑌´
Ahora si ya podemos sacar Z´ y 2
𝒁´ = 𝒁𝒄 𝒔𝒆𝒏𝒉 𝜸𝒍
𝑍´ = (393.915 ∠ − 7.018)(0.3471 ∠83.08)
𝒁´ = 𝟏𝟑𝟔. 𝟕𝟐∠𝟕𝟔. 𝟎𝟔𝟐° 𝛀
𝒀´ 𝟏 𝒄𝒐𝒔𝒉 𝜸𝒍−𝟏
= 𝒁𝒄
𝟐 𝒔𝒆𝒏𝒉 𝜸𝒍
𝑌´ 1 (0.9354+𝑗 0.027)−1
= (393.915 ∠−7.018) ×
2 0.3471 ∠83.08
𝑌´ −0.0646+𝑗0.027
= (393.915 ∠−7.018°)
2
𝑌´ 0.07∠−22.68°
= 136.727∠76.06°
2
𝒀´
= 𝟓𝟏𝟐 × 𝟏𝟎−𝟔 ∠ − 𝟗𝟖. 𝟕𝟒° S
𝟐
6.19 Aplique las ecuaciones (6.1) y (6.2) para simplificar las ecuaciones (6.57) y
(6.58) para
la línea de transmisión corta con a) una reactancia serie X y una resistencia R y
b) una
reactancia serie X y una resistencia despreciable.
Solución.
Se debe simplificar las ecuaciones (6.57) y (6.58) tomando en cuenta la reactancia
serie 𝑋, 𝑅
y reactancia serie con resistencia despreciable.
El problema ya propone utilizar las ecuaciones (6.1) y (6.2)
𝐼𝑆 = 𝐼𝑅
𝑉𝑆 = 𝑉𝑅 + 𝐼𝑅 𝑍
|𝑉𝑆 ||𝑉𝑅 | |𝐴||𝑉𝑅 |2
𝑃𝑅 = 𝐶𝑜𝑠(𝛽 − 𝛿) − cos(𝛽 − 𝛼)
|𝐵| |𝐵|
|𝑉𝑆 ||𝑉𝑅 | |𝐴||𝑉𝑅 |2
𝑄𝑅 = 𝑠𝑒𝑛(𝛽 − 𝛿) − 𝑠𝑒𝑛(𝛽 − 𝛼)
|𝐵| |𝐵|
Al aplicar las ecuaciones (6.1) y (6.2) a (6.57) y (6.58) para el inciso a
𝐼𝑆 = 𝐼𝑅 = 𝐴 = 𝐷 = 1
Se aumenta R como se estipula en el inciso
𝐵 = 𝑍 = 𝑅 + 𝐽𝑋
𝐶=0
𝛼=0
Ahora se sustituye en las ecuaciones 6.57) y (6.58)
|𝑉𝑆 ||𝑉𝑅 | |𝑉𝑅 |2
𝑃𝑅 = 𝐶𝑜𝑠(𝛽 − 𝛿) − cos(𝛽)
|𝑍| |𝑍|
|𝑉𝑆 ||𝑉𝑅 | |𝑉𝑅 |2
𝑄𝑅 = 𝑠𝑒𝑛(𝛽 − 𝛿) − 𝑠𝑒𝑛(𝛽)
|𝑍| |𝑍|
b)
La potencia real quedara en función se seno porque en coseno seria 0
𝑋∡ 90°
|𝑉𝑆 ||𝑉𝑅 |
𝑃𝑅 = 𝑠𝑒𝑛(𝛿)
|𝑋|
Para la potencia reactiva
|𝑉𝑆 ||𝑉𝑅 | |𝑉𝑅 |2
𝑄𝑅 = 𝑐𝑜𝑠(𝛽) − 𝑠𝑒𝑛(90°)
|𝑋| |𝑋|
6.20 Los derechos de vía para circuitos de transmisión son difíciles de obtener en
áreas urbanas
y las líneas ya existentes son frecuentemente llevadas a un mayor nivel recableando
la línea
con conductores más grandes o volviendo a aislarla para la operación de un voltaje
más alto.
Los aspectos térmicos y la máxima potencia que la línea puede transmitir son las
consideraciones importantes. Una línea de 13 kV tiene una longitud de 50 km y se
compone
de conductores Partridge con espaciamiento horizontal plano de 5 m entre
conductores
adyacentes. Desprecie la resistencia y encuentre el por ciento en incremento de
potencia que
se puede transmitir para |VS | y |𝑉𝑅 | constantes mientras que δ se limita a 45°,
si
a) el conductor Partridge se reemplaza por el Ospery que tiene más de dos veces el
área de
aluminio en milímetros cuadrados,
b) un segundo conductor Partridge se coloca en un arreglo de dos conductores
separados 40
cm dl conductor original y a una distancia entre centros de los agrupamientos de 5
m y,
c) el voltaje de la línea original se eleva a 230kv con un espaciamiento entre
conductores de
8m.
La ecuación principal para el problema es la de la potencia real:
|𝑉𝑆 ||𝑉𝑅 | |𝐴||𝑉𝑅 |2
𝑃𝑅 = cos(𝛽 − 𝛿) − cos(𝛽 − 𝛿)
|𝐵| |𝐵|
Y 𝐷𝑠 = RGM = Radio medio geométrico listado en la tabla A.3 para cada tipo de
conductor.
𝑋𝑁𝑢𝑒𝑣𝑎
El porcentaje del incremento de potencia es igual a 𝑋𝐴𝑛𝑡𝑒𝑟𝑖𝑜𝑟
Paso 3.-
3
𝐷𝑒𝑞 = √5 × 5 × 10
1 𝑓𝑡
𝐷𝑒𝑞 = 6.2996 𝑚 ( ) = 20.66 𝑓𝑡
0.3048 𝑚
a)
Partridge:
𝐷𝑠 = 0.0217 𝑓𝑡
20.66 Ω
𝑋 = 0.0754 log = 0.5174
0.0217 𝑘𝑚
Ospery:
𝐷𝑠 = 0.0284 𝑓𝑡
20.66 Ω
𝑋 = 0.0754 log = 0.4971
0.0284 𝑘𝑚
Porcentaje de potencia:
0.4971
= 1.040
0.5174
Lo cual nos dice que la potencia incrementa un 4%
b)
0.4
𝐷𝑆 = √0.0217 × ( ) = 0.1687 𝑓𝑡
0.3048
20.66 Ω
𝑋 = 0.0754 log = 0.3625
0.1687 𝑘𝑚
Porcentaje de potencia
0.5174
= 1.4272
0.3625
Lo cual nos dice que la potencia incrementa en un 42.7%
c)
𝑃𝑅 incrementa debido a que el voltaje aumenta de 138 kV a 230 kV
230 2
( ) = 2.77
138
El espaciamiento entre conductores es diferente así que
3
𝐷𝑒𝑞 = √8 × 8 × 16
1 𝑓𝑡
𝐷𝑒𝑞 = 10.07 𝑚 ( ) = 33.06 𝑓𝑡
0.3048 𝑚
33.06 Ω
𝑋 = 0.0754 log = 0.5526
0.0217 𝑘𝑚
Porcentaje de potencia
0.5174
2.77 = 2.5935
0.5526
Lo cual nos dice que la potencia incrementa 159.3%.
7.05 𝑋 50 = 352.5
׀ 𝑉𝑅׀ ׀ 𝑉𝑠׀
= 352.5
׀𝐵׀
352.5 𝑋 141.4
226.5 = = ׀ 𝑉𝑠׀KV
220
6.22 Un condensador sincrónico se conecta en paralelo con la carga descrita en el
problema
6.21 para mejorar el factor de potencia en el extremo receptor. El voltaje en el
generador se
ajusta para mantener el voltaje fijo en el extremo receptor a 220 kV. Mediante el
diagrama
circular de potencia construido para el problema 6.21, determine el voltaje en el
extremo
generador y la potencia reactiva suministrada por el condensador sincrónico cuando
el factor
de potencia total en el extremo receptor se a) la unidad, b)0.9 en adelanto.
a)
𝐴 𝐵
𝐴̅ =
𝐶 𝐷
SUSTITUCION:
0.9534∟0.3° 90.33∟84.1° Ω
𝐴̅ =
0.001014∟90.1° 𝑆 0.9534∟0.3°
0.9597∟1.18° 42.3∟64.5°
=
0.002084∟90.4° 0.9534∟1.18°
𝐴 𝐵
=
𝐶 𝐷𝑛𝑢𝑒𝑣𝑎
216.87∟4.5° − 199,186∟0°
Caída de voltaje = 8.5%
216.87∟4.5°
Comparación de la caída de voltaje con la de los resultados del ejercicio 6.16:
216.87∟4.5°
𝑉𝑅,𝑁𝐿 = = 225,977∟3.32 𝑉
0.9597∟1.18°
𝐼𝑅,𝑁𝐿 = 0.002084∟90.4° × 225,977∟3.32 = 470.9∟93.7 𝐴
225,977 − 199,186
%𝑅 = × 100 = 13.45%
199,186
Ceq C1 CA
Ceq 0.001933 90.4 (0.0021 90 * 0.8180 1.3)
(0.000013494 j 0.0019329 ) (0.0017178 88.7)
(0.000013494 j 0.0019329 ) (0.000038972 j 0.001773 )
0.000025032 j 0.0002156
0.00021704 83.37
Deq 0.8180 1.3