Está en la página 1de 26

CORRIENTE PRIMARIO

I=S/√3*34500V CALIBRE 4/0 41 CONDUCTORES


16.7 A 3300.5 A
20.9 A

CORRIENTE SECUNDARIO
I=S/√3*220V
2624.3 A
3280.4 A
PRIMERA PLANTA
CUADRO DE CARGAS LOCAL 101
CTO ÁREA VA/M^2 CANT. VA
1 LUCES 72 32
2 TOMACORRIENTES 4 180
3 AIRE ACONDICIONADO
TOTAL

22.08 A interruptor de 1*25A 24 A Se designa = 1*#10 Cu TW F+1*#8 Cu TW


6.9 A interruptor de 1* 15 A 7.5 A Se designa = 1*#10 Cu TW F+1*#8 Cu TW
22.9794362 A interruptor de 2* 30 A 24.98 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 102


CTO ÁREA VA/M^2 CANT. VA
1 LUCES 72 32
2 TOMACORRIENTES 4 180
3 AIRE ACONDICIONADO
TOTAL

22.1 A interruptor de 1*25A 24 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW


6.9 A interruptor de 1* 15 A 7.5 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
23.0 A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 103


CTO ÁREA VA/M^2 CANT. VA
1 LUCES 75 32
2 TOMACORRIENTES 5 180
3 AIRE ACONDICIONADO
TOTAL

23 A interruptor de 1*25A 25 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW


8.6 A interruptor de 1* 15 A 9.4 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
23.0 A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 104


CTO ÁREA VA/M^2 CANT. VA
1 LUCES 72 32
2 TOMACORRIENTES 5 180
3 AIRE ACONDICIONADO
TOTAL
22.08 A interruptor de 1*25A 24 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
8.6 A interruptor de 1* 15 A 9.4 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
23.0 A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 105


CTO ÁREA VA/M^2 CANT. VA
1 LUCES 72 32
2 TOMACORRIENTES 5 180
3 AIRE ACONDICIONADO
TOTAL

22.08 A interruptor de 1*25A 24 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW


8.6 A interruptor de 1* 15 A 9.4 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
23.0 A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 106


CTO ÁREA VA/M^2 CANT. VA
1 LUCES 78 32
2 TOMACORRIENTES 5 180
3 AIRE ACONDICIONADO
TOTAL

23.92 A interruptor de 1*25A 26 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW


8.6 A interruptor de 1* 15 A 9.4 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW
23.0 A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

TOMAS ESPECIALES PRIMER PISO


CTO ÁREA VA/M^2 CANT. VA
2 TOMACORRIENTES 3 180
TOTAL
5.175 A interruptor de 1*10A 5.625 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW

ASCENSOR
8 PERSONAS 4000 W 5hp
5000 kVA
I=(SACC)/220 A
Para calcular protección se multiplica por el 1.15% 26.1363636
22.7272727272727 y se llega a laA conclusión
de poner una protección de 2*30 A

Para calcular el calibre del conductor debe estar 25 % por encima de la


corriente según tabla 3.15 norma tecnica ESSA.
28.4090909 A
Se designa= 2*#10 Cu tw F
BOMBA CENTRIFUGA
4 4HP
11936 13,262 Kva

I=(SACC)/220 A
60.2828282828283
Para calcular protección se multiplica por el 1.15% 69.3252525
y se llega a laA conclusión
de poner una protección de 1*20 A

Para calcular el calibre del conductor debe estar 25 % por encima de la


corriente según tabla 3.15 norma tecnica ESSA.

75.3535354 A

Se designa= 2*#12 Cu tw F

MOTOR ELECTRICO DE LA ESCALERA

10 HP 7460 Kw
3 MOTORES 24866.67 VA 24,867 KVA
I=(SACC)/220
124.333333333333 A

SC: CARGA DEMANDA SECTOR COMERCIAL= 216774.30 VA 216,774


SACC: CARGA DE ÁREAS COMUNES SECTOR COMERCIAL= 41802.7 VA 41802.7
SEGUNDA
CUADRO DE CARG
BTU W VA TOTAL I(A) CTO
2304 19.2 1
720 6 2
15000 0.29307107 4396.07 19.98 3
7420.07 45.2 TOTAL

CTO
= 1*#10 Cu TW F+1*#8 Cu TW N 1 21.7
= 1*#10 Cu TW F+1*#8 Cu TW N 2 10.4
designa = 2*10 Cu TW F 3 23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


2304 19.2 CTO
720 6 1
15000 0.29307107 4396.07 19.98 2
7420.07 45.2 3
TOTAL
CTO
= 1*#10 Cu TW F+1*#10 Cu TW N 1
= 1*#10 Cu TW F+1*#10 Cu TW N 2 22.4
designa = 2*10 Cu TW F 3 12.1
23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


2400 20 CTO
900 7.5 1
15000 0.29307107 4396.07 19.98 2
7696.07 47.5 3
TOTAL
CTO
= 1*#10 Cu TW F+1*#10 Cu TW N 1
= 1*#10 Cu TW F+1*#10 Cu TW N 2 22.4
designa = 2*10 Cu TW F 3 10.4
23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


2304 19.2 CTO
900 7.5 1
15000 0.29307107 4396.07 19.98 2
7600.07 46.7 3
TOTAL
CTO
= 1*#10 Cu TW F+1*#10 Cu TW N 1
= 1*#10 Cu TW F+1*#10 Cu TW N 2 22.4
designa = 2*10 Cu TW F 3 10.4
23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


2304 19.2 CTO
900 7.5 1
15000 0.29307107 4396.07 19.98 2
7600.07 46.7 3
TOTAL
CTO
= 1*#10 Cu TW F+1*#10 Cu TW N 1
= 1*#10 Cu TW F+1*#10 Cu TW N 2 22.4
designa = 2*10 Cu TW F 3 10.4
23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


2496 20.8 CTO
900 7.5 1
15000 0.29307107 4396.07 19.98 2
7792.07 48.3 3
TOTAL
CTO
= 1*#10 Cu TW F+1*#10 Cu TW N 1
= 1*#10 Cu TW F+1*#10 Cu TW N 2 22.4
designa = 2*10 Cu TW F 3 12.1
23.0

BTU W VA TOTAL I(A) CUADRO DE CARG


540 4.5 CTO
540.00 4.5 1
= 1*#10 Cu TW F+1*#10 Cu TW N 1 2
3
TOTAL

15.3
12.1
20.7

TOMAS ESPECIALES
CTO
1
TOTAL

8.625

CUARTA P
CUADRO DE CAR
CTO

1
2
3
TOTAL

85.3
10.4
34.5

TOMAS ESPECIA
CTO
1
TOTAL
8.625

KVA 985.34 A
KVA 190.0 A
CUADRO DE CARGAS PARQUEADERO
CTO
1
2
TOTAL
SEGUNDA PLANTA
CUADRO DE CARGAS LOCAL 201
ÁREA VA/M^2 CANT.
LUCES 70.9 32
TOMACORRIENTES 6
AIRE ACONDICIONADO

A interruptor de 1*25A 23.6 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 202


ÁREA VA/M^2 CANT.
LUCES 72.9 32
TOMACORRIENTES 7
AIRE ACONDICIONADO

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 203


ÁREA VA/M^2 CANT.
LUCES 72.9 32
TOMACORRIENTES 6
AIRE ACONDICIONADO

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 204


ÁREA VA/M^2 CANT.
LUCES 72.9 32
TOMACORRIENTES 6
AIRE ACONDICIONADO
A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 205


ÁREA VA/M^2 CANT.
LUCES 72.9 32
TOMACORRIENTES 6
AIRE ACONDICIONADO

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 206


ÁREA VA/M^2 CANT.
LUCES 72.9 32
TOMACORRIENTES 7
AIRE ACONDICIONADO

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu

CUADRO DE CARGAS LOCAL 207


ÁREA VA/M^2 CANT.
LUCES 50 32
TOMACORRIENTES 7
AIRE ACONDICIONADO

A interruptor de 1*25A 16.7 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 30 A 22.5 A Se designa = 2*10 Cu

TOMAS ESPECIALES SEGUNDO PISO


ÁREA VA/M^2 CANT.
TOMACORRIENTES ESPECIALES 5
A interruptor de 1*10A 9.375 A Se designa = 1*#10 Cu TW F+1

CUARTA PLANTA
CUADRO DE CARGAS AZOTEA
ÁREA VA/M^2 CANT.

LUCES 278 32
TOMACORRIENTES 6
AIRE ACONDICIONADO

A interruptor de 1*25A 92.7 A Se designa = 1*#10 Cu TW F+1


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1
A interruptor de 2* 40A 37.5 A Se designa = 2*#8 Cu TW F

TOMAS ESPECIALES AZOTEA


ÁREA VA/M^2 CANT.
TOMACORRIENTES ESPECIALES 5

A interruptor de 1*10A 9.375 A Se designa = 1*#10 Cu TW F+1


UADRO DE CARGAS PARQUEADERO
ÁREA VA/m^2 VA

0
TERCERA P
CUADRO DE CARG
VA BTU W VA TOTAL I(A) CTO
2268.8 18.9 1
180 1080 9 2
15000 0.29307107 4396.07 20.0 3
7744.87 47.9 TOTAL

CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1 21.7426667
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 10.4
Se designa = 2*10 Cu TW F 3 23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


2332.8 19.4 CTO
180 1260 10.5 1
15000 0.29307107 4396.07 20.0 2
7988.87 49.9 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 22.356
Se designa = 2*10 Cu TW F 3 12.1
23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


2332.8 19.4 CTO
180 1080 9 1
15000 0.29307107 4396.07 20.0 2
7808.87 48.4 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 22.356
Se designa = 2*10 Cu TW F 3 10.4
23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


2332.8 19.4 CTO
180 1080 9 1
15000 0.29307107 4396.07 20.0 2
7808.87 48.4 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#8 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#8 Cu TW N 2 21.7426667
Se designa = 2*10 Cu TW F 3 10.4
23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


2332.8 19.4 CTO
180 1080 9 1
15000 0.29307107 4396.07 20.0 2
7808.87 48.4 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 22.356
Se designa = 2*10 Cu TW F 3 10.4
23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


2332.8 19.4 CTO
180 1260 10.5 1
15000 0.29307107 4396.07 20.0 2
7988.87 49.9 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 22.356
Se designa = 2*10 Cu TW F 3 12.1
23.0

VA BTU W VA TOTAL I(A) CUADRO DE CARG


1600 13.3 CTO
180 1260 10.5 1
13500 0.29307107 3956.46 18.0 2
6816.46 41.8 3
TOTAL
CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2 15.3333333
Se designa = 2*10 Cu TW F 3 12.1
23.0

TOMAS ESPECIALE
VA BTU W VA TOTAL I(A) CTO
180 900 7.5 1
900.00 7.5 TOTAL

Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1 8.625

VA BTU W VA TOTAL I(A)

8896 74.1
180 1080 9
22500 0.29307107 6594.10 30.0
16570.10 113.1

CTO
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 2
na = 2*#8 Cu TW F 3

VA BTU W VA TOTAL I(A)


180 900 7.5
900.00 7.5
Se designa = 1*#10 Cu TW F+1*#10 Cu TW N 1
TERCERA PLANTA
CUADRO DE CARGAS LOCAL 301
ÁREA VA/M^2 CANT. VA BTU W
LUCES 70.9 32
TOMACORRIENTES 6 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 23.6333333 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 302


ÁREA VA/M^2 CANT. VA BTU W
LUCES 72.9 32
TOMACORRIENTES 7 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 303


ÁREA VA/M^2 CANT. VA BTU W
LUCES 72.9 32
TOMACORRIENTES 6 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 304


ÁREA VA/M^2 CANT. VA BTU W
LUCES 70.9 32
TOMACORRIENTES 6 180
AIRE ACONDICIONADO 15000 0.29307107
A interruptor de 1*25A 23.6333333 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 305


ÁREA VA/M^2 CANT. VA BTU W
LUCES 72.9 32
TOMACORRIENTES 6 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 11.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 306


ÁREA VA/M^2 CANT. VA BTU W
LUCES 72.9 32
TOMACORRIENTES 7 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 24.3 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

CUADRO DE CARGAS LOCAL 307


ÁREA VA/M^2 CANT. VA BTU W
LUCES 50 32
TOMACORRIENTES 7 180
AIRE ACONDICIONADO 15000 0.29307107

A interruptor de 1*25A 16.6666667 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N


A interruptor de 1* 15 A 13.1 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
A interruptor de 2* 30 A 25.0 A Se designa = 2*10 Cu TW F

TOMAS ESPECIALES TERCER PISO


ÁREA VA/M^2 CANT. VA BTU W
TOMACORRIENTES ESPECIALES 5 180
A interruptor de 1*10A 9.375 A Se designa = 1*#10 Cu TW F+1*#10 Cu TW N
VA TOTAL I(A)
2268.8 18.9
1080 9
4396.1 20.0
7744.9 47.9

CTO
1
2
3

VA TOTAL I(A)
2332.8 19.4
1260 10.5
4396.1 20.0
7988.9 49.9

CTO
1
2
3

VA TOTAL I(A)
2332.8 19.4
1080 9
4396.1 20.0
7808.9 48.4

CTO
1
2
3

VA TOTAL I(A)
2268.8 18.9
1080 9
4396.1 20.0
7744.9 47.9
CTO
1
2
3

VA TOTAL I(A)
2332.8 19.4
1080 9
4396.1 20.0
7808.9 48.4

CTO
1
2
3

VA TOTAL I(A)
2332.8 19.4
1260 10.5
4396.1 20.0
7988.9 49.9

CTO
1
2
3

VA TOTAL I(A)
1600 13.3
1260 10.5
4396.1 20.0
7256.1 43.8

CTO
1
2
3

VA TOTAL I(A)
900 7.5
900.00 7.5

1
FACTOR DE DIVERIDAD RESIDENCIAL 1,2,3
0.873295075624905

FACTOR DE DIVERSIDAD RESIDENCIAL 5,6,7


0.887349011804277

FACTOR DE DIVERSIDAD COMERCIAL USUARIOS MONOFASICOS BIFILARES

4.77566543785134

FACTOR DE DIVERSIDAD COMERCIAL USUARIOS TRIFILARES Y TETRAFILARES

0.851647873009695

Demanda maxima= 87194.10


87,194

I=Dmax/√3*208
242.0 A
278.3 A

Para calcular protección se multiplica por el 1.15% y se llega a la conclusión de poner u

302.533277996603 A

Para calcular el calibre del conductor debe estar 25 % por encima de la corriente según tabla 3.15 norma tecnica ESSA.
Se designa= 3*#350 kcmil Cu THW F+1*#350 kcmil Cu THW N
Numero de usuarios residencial 1,2,3= 0 Numero de usuarios r

Fdiv_com= 4.77566544
Fdiv_res= 0
Sr= 0
Sacr= 0

Sc= 216774.30 VA
Sacc= 41802.67 VA

FILARES

VA
KVA

y se llega a la conclusión de poner una protección ajustable de 3*300 A

gún tabla 3.15 norma tecnica ESSA.


Numero de usuarios residencial 5,6,7= Numero de usuarios monofasicos bifilares=
0
Numero de usuarios monofasicos bifilares= Numero de usuarios trifilares y tetrafilares=
21
0

También podría gustarte