Está en la página 1de 7

LONGITUD KM 0.

006
CORRIENTE CIRCUITO 205
FP 0.95
VOLTAJE 208

CALCULO DE REGULACION

CALIBRE RESISTENCIA REACTANCIA IMPEDANCIA MONOFASICO TRIFASICO


R X Z=R COS + X SEN DV fn = Z 2L I DV fn = Z L I
14 10.17 0.19 9.720 23.9 12.0
12 6.56 0.177 6.287 15.5 7.7
10 3.94 0.164 3.794 9.3 4.7
8 2.56 0.171 2.485 6.1 3.1
6 1.61 0.167 1.581 3.9 1.9
4 1.02 0.157 1.018 2.5 1.3
2 0.623 0.148 0.638 1.6 0.8
1/0 0.394 0.144 0.419 1.0 0.5
2/0 0.328 0.141 0.355 0.9 0.4
3/0 0.253 0.138 0.283 0.7 0.3
4/0 0.203 0.135 0.235 0.6 0.3
250 0.171 0.135 0.204 0.5 0.3
350 0.125 0.131 0.159 0.4 0.2
500 0.089 0.128 0.124 0.3 0.2

SEN 0.31
COS 0.95
EGULACION

TRIFASICO REGULACION MONO REGULACION TRIF


DV ff = 1,732*DV fn %R=DV/Dr * 100 %R=DV/Dr * 100
20.7 11.5 10.0
13.4 7.4 6.4
8.1 4.5 3.9
5.3 2.9 2.5
3.4 1.9 1.6
2.2 1.2 1.0
1.4 0.8 0.7
0.9 0.5 0.4
0.8 0.4 0.4
0.6 0.3 0.3
0.5 0.3 0.2
0.4 0.2 0.2
0.3 0.2 0.2
0.3 0.1 0.1
CALCULO DE RED PRIMARIA 13,200 VOLTIOS
UDENAR TUMACO
MUNICIPIO DE TUMACO

LONGITU CARGA MOMENTO REGULACION REGULACION PERDIDAS


NODO D (Km) (KVA) (KVA*L) KREGULACION PARCIAL (%) TOTAL (%) PARCIALES KW
NODO CONEX 2 2
0-A 0.41163 112.5 46.308375 0.000388 0.0179676495 2.0179676495 0.0156763178
CIRCUITO:
S/TUMACO
13,200 VOLTIO

constantes ACSR
1/0 0.000388

PERDIDAS PERDIDAS PERDIDAS CALIBRE


I(A)
TOTALES KW PARCIALES % TOTALES % CONDUCTOR

0.0156763178025 0.0146678997 0.0146678997 1/0 4.9205988851


CONSTANTES DE REGULACION UTILIZADAS EN LOS CALCULOS
ACOMETIDAS SUBTERRANEAS
factor multiplicafactormultiplicativo calibre kte reg kte reg kte reg kte reg
1 fase 2 fases conductor 3 fases 1 fase 2 fases TRIFILAR FFN
6 1.732 12 0.01361 0.08166 0.02357252 0.0306225
6 1.732 10 0.00858 0.05148 0.01486056 0.019305
6 1.732 8 0.00547 0.03282 0.00947404 0.0123075
6 1.732 6 0.00353 0.02118 0.00611396 0.0079425
6 1.732 4 0.00228 0.01368 0.00394896 0.00513
6 1.732 2 0.00149 0.00894 0.00258068 0.0033525
6 1.732 1/0 0.001008 0.006048 0.001745856 0.002268
6 1.732 2/0 0.0008112 0.0048672 0.0014049984 0.0018252
6 1.732 3/0 0.000655 0.00393 0.00113446 0.00147375
6 1.732 4/0 0.000539 0.003234 0.000933548 0.00121275
6 1.732 250mcm 0.000474 0.002844 0.000820968 0.0010665
6 1.732 500mcm 0.0002729 0.0016374 0.0004726628 0.000614025

DEPARTAMENTO DE NARIÑO
MUNICIPIO DE TUMACO
UNIVERSIDAD DE NARIÑO

1.0501428
CALCULOS DE REGULACION DE VOLTAJE Y PERDIDAS DE ENERGIA

TRANSFORMADOR No1, 112,5 Kva, UNIVERSIDAD DE NARIÑO, MUNI


CALCULO DE REGULACION Y PERDIDAS A 208 V, FACTOR DE POTENCIA 0,95 ACOMETIDAS SUBT

TABLERO DESCRIPCION LONGITUD CARGA CORRIENTE KVA X M REG PARCIAL


O SALIDA (m) KVA (A) %
T-GRAL TG 97 112.50 312 10,913 2.941
TDT-1 14.93 11.70 32 175 0.617
TGT-2 9.89 71.65 199 709 0.382
TGDSB 31.47 14.19 39 447 1.576
TGDB 29.18 17.70 49 516 1.823
CALCULOS

factor mult
Ohn/m FFN
5.35 2.25 12
3.35 2.25 10
2.101 2.25 8
1.325 2.25 6
0.832 2.25 4 0.00376457
0.523 2.25 2 0.00240607
0.329 2.25 1/0 0.00155128
0.261 2.25 2/0
0.207 2.25 3/0
0.164 2.25 4/0 0.00125017
0.139 2.25 250mcm
0.069 2.25 500mcm

MENTO DE NARIÑO
IO DE TUMACO
DAD DE NARIÑO

JE Y PERDIDAS DE ENERGIA, DE ACOMETIDAS

VERSIDAD DE NARIÑO, MUNICIPIO DE TUMACO


IA 0,95 ACOMETIDAS SUBTERRANEAS EN CABLE DE COBRE AISLADO THHN

REG TOTAL VOLTAJE PERDIDAS PRO- PERDIDAS CALIBRE CANA-


% FINAL (v) (kW) TECCION % ACOMETIDA LIZACION
2.941 201.883 1.235 3X350 A 4.574 2x3x4/0 + 1x4/0 + 4 T 2 3" 2.08
3.558 200.600 0.067 3x40A 0.249 3X6 + 6N + 10 T 1 1" 2.08
3.323 201.088 0.206 3X200A 0.763 3x4/0 + 1x4/0 + 4 T 1 3" 2.08
4.517 198.604 0.213 3X40A 0.788 3X6 + 6N + 10 T 1 1" 2.08
4.764 198.091 0.309 3X50A 1.143 3X6 + 6N + 10 T 1 1" 2.08
6.117111 208 0.015908 278.626883 278.626883 77632.9397 1.2349848
7.39968877 208 0.01978225 58.3249344 58.3249344 3401.79798 0.06729522
6.91155737 208 0.00162196 356.31088 356.31088 126957.443 0.20591989
9.395928 208 0.04169775 71.4486861 71.4486861 5104.91475 0.21286346
9.90935781 208 0.0386635 89.3530346 89.3530346 7983.96479 0.30868802