ORDEN DE FILAS DATOS DE LA CARGA DATOS DEL CONDUCTOR RESULTADO

CORR. CABLE
DISEÑO FINAL DE
CORREGID TEMP. DE TIERRA
CORR. A CALIBRE DAÑO EN VERIFICAD CABLE FINAL
TENSIO FAC. POR POR CALIBRE POR CAIDA CALIBRE POR CALIBRE POR LOS O POR SELECCIONADO POR EL CABLE FINAL SELECCIONADO
CODIGO TENSIO N DEL POTENCI COR CORR. CONDUCT TEMP POR DE % ΔV EN CORTOCIRCUI STATUS POR TEMPERATUR TERMINALE CORTOCIR PROGRAMA POR EL USUARIO
CODIGO DE EQUIPO CODIGO EQUIPO N DE EQUIPO A R. FP LONG TIPO DE COND./ NOMINAL OR AMB AMPACIDA TENSIÓN ARRANQU TO NCC ICC INT. A EN S CUITO (FASE+TIERRA) (FASE+TIERRA)
LINEA REV CABLE DESDE HASTA TIPO DE EQUIPO RED (V) (V) NOMINAL FP EF FS ARR. ARR. FASES (M) INSTAL. FASE (A) (A) (A) D (AWG) (AWG) % ΔV E (AWG) (KA) LIMITADORES TERMINALES (°C) (AWG) (AWG) (AWG) OBSERVACIONES
BANDEJA -
1 0 0 GEN1-CHB1-001 CCM-CHB1-01 MCC/SWG 480 480 750 KW 0.80 0.91 N/A 0.00 0.00 3 50 3 1239.16 413.05 688.42 500 2 4.53 - 4/0 65.00 OK 500 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]

BANDEJA -
2 0 0 GEN2-CHB1-001 CCM-CHB1-01 MCC/SWG 480 480 750 KW 0.80 0.91 N/A 0.00 0.00 3 50 3 1239.16 413.05 688.42 500 2 4.53 - 4/0 65.00 OK 500 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]

BANDEJA -
3 0 0 GEN3-CHB1-001 CCM-CHB1-01 MCC/SWG 480 480 750 KW 0.80 0.91 N/A 0.00 0.00 3 50 3 1239.16 413.05 688.42 500 2 4.53 - 4/0 65.00 OK 500 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]

BANDEJA -
4 0 0 GEN3-CHB1-001 CCM-CHB1-01 MCC/SWG 480 480 750 KW 0.80 0.91 N/A 0.00 0.00 3 50 3 1239.16 413.05 688.42 500 2 4.53 - 4/0 65.00 OK 500 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]

TUBO -
5 0 0 CCM-CHB1-01 TX1-CHB1-001 TRANSFORMADOR 480 480 45 KVA 0.90 0.91 N/A 0.00 0.00 3 20 1 59.48 59.48 74.35 4 12 2.71 - 4 10.83 OK 4 60.00 4 1 x3C 4+1 x4 0,6 kV 1 x [3C #4 0.6 kV +1C #4 0.6 kV]

BANCAD -
6 0 0 CCM-CHB1-01 TAB-RETROLA TABLERO 480 480 80 HP 0.90 0.91 N/A 0.00 0.00 3 200 A NO 1 87.65 87.65 136.95 1/0 2 4.10 - 1/0 30.00 OK 1/0 60.00 1/0 1 x3 x1C 1/0+1 x1/0 0,6 kV
1 x [3x1C #2/0 0.6 kV +1C #8 0.6 kV]
MAG
BANCAD -
7 0 0 CCM-CHB1-01 VFD-HPS-CHB1-01 TABLERO 480 480 800 HP 0.90 1.00 N/A 0.00 0.00 3 120 A NO 3 797.60 265.87 415.42 500 1/0 4.95 - 4/0 65.00 OK 250 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
MAG
BANCAD -
8 0 0 CCM-CHB1-01 VFD-HPS-CHB1-02 TABLERO 480 480 800 HP 0.90 1.00 N/A 0.00 0.00 3 120 A NO 3 797.60 265.87 415.42 500 1/0 4.95 - 4/0 65.00 OK 250 75.00 4/0 3 x3 x1C 500+3 x4/0 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
MAG
BANCAD -
9 0 0 VFD-HPS-CHB1-01 HPS-CHB1-01 MOTOR 480 460 800 HP 0.91 1.00 1.00 2.00 0.50 3 40 A NO 3 823.13 274.38 428.71 500 4 4.11 5.54 250 65.00 OK 350 75.00 250 3 x3 x1C 500+3 x250 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
MAG
BANCAD -
10 0 0 VFD-HPS-CHB1-02 HPS-CHB1-02 MOTOR 480 460 800 HP 0.91 1.00 1.00 2.00 0.20 3 40 A NO 3 823.13 274.38 428.71 500 4 4.11 3.04 250 65.00 OK 350 75.00 250 3 x3 x1C 500+3 x250 0,63kV
x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
MAG
BANCAD -
11 0 0 CCM-CHB1-01 CCM-CHB1-02 MCC/SWG 480 480 750 KVA 0.85 0.91 N/A 0.00 0.00 3 280 A NO 3 991.33 330.44 413.05 500 500 4.89 - 250 65.00 OK 350 75.00 250 3 x3 x1C 500+3 x250 0,63 kV
x [3x1C #500 0.6 kV +1C #250 0.6 kV]
MAG
BANDEJA -
12 0 0 CCM-CHB1-01 CCM-CHB1-03 MCC/SWG 480 480 750 KVA 0.70 0.80 N/A 0.00 0.00 3 20 3 1127.64 375.88 626.47 500 6 3.52 - 250 65.00 OK 500 75.00 250 3 x3 x1C 500+3 x250 0,63 kV
x [3x1C #500 0.6 kV +1C #250 0.6 kV]

BANCAD -
13 0 0 CCM-CHB1-02 MP-6100 MOTOR 480 460 40 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 47.34 47.34 73.96 6 12 4.12 6.65 6 65.00 OK 2 60.00 6 1 x3C 2+1 x6 0,6 kV 1 x [3C #2 0.6 kV +1C #2 0.6 kV]
MAG
BANCAD -
14 0 0 CCM-CHB1-02 MP-6110 MOTOR 480 460 40 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 47.34 47.34 73.96 6 12 4.12 6.65 6 65.00 OK 2 60.00 6 1 x3C 2+1 x6 0,6 kV 1 x [3C #2 0.6 kV +1C #2 0.6 kV]
MAG
BANCAD -
15 0 0 CCM-CHB1-02 MP-6120 MOTOR 480 460 100 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 118.34 118.34 184.91 2/0 8 4.09 7.52 6 65.00 OK 1/0 75.00 6 1 x3 x1C 2/0+1 x6 0,6 kV
1 x [3x1C #2/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
16 0 0 CCM-CHB1-02 MP-6130 MOTOR 480 460 100 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 118.34 118.34 184.91 2/0 8 4.09 7.52 6 65.00 OK 1/0 75.00 6 1 x3 x1C 2/0+1 x6 0,6 kV
1 x [3x1C #2/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
17 0 0 CCM-CHB1-02 MP-4140 MOTOR 480 460 100 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 118.34 118.34 184.91 2/0 8 4.09 7.52 6 65.00 OK 1/0 75.00 6 1 x3 x1C 2/0+1 x6 0,6 kV
1 x [3x1C #2/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
18 0 0 CCM-CHB1-02 MP-4145 MOTOR 480 460 100 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 118.34 118.34 184.91 2/0 8 4.09 7.52 6 65.00 OK 1/0 75.00 6 1 x3 x1C 2/0+1 x6 0,6 kV
1 x [3x1C #2/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
19 0 0 CCM-CHB1-02 MP-4150 MOTOR 480 460 125 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 147.93 147.93 231.13 4/0 6 3.28 6.69 6 65.00 OK 3/0 75.00 6 1 x3 x1C 4/0+1 x6 0,6 kV
1 x [3x1C #4/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
20 0 0 CCM-CHB1-02 MP-4155 MOTOR 480 460 125 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 147.93 147.93 231.13 4/0 6 3.28 6.69 6 65.00 OK 3/0 75.00 6 1 x3 x1C 4/0+1 x6 0,6 kV
1 x [3x1C #4/0 0.6 kV +1C #6 0.6 kV]
MAG
BANCAD -
21 0 0 CCM-CHB1-02 MP-4100 MOTOR 480 460 40 HP 0.86 0.92 1.15 2.00 0.20 3 250 A NO 1 47.34 47.34 73.96 6 4 4.26 3.27 6 65.00 OK 6 75.00 6 1 x3C 4+1 x6 0,6 kV 1 x [3C #4 0.6 kV +1C #4 0.6 kV]
MAG
BANCAD -
22 0 0 CCM-CHB1-02 MP-4110 MOTOR 480 460 40 HP 0.86 0.92 1.15 2.00 0.20 3 250 A NO 1 47.34 47.34 73.96 6 4 4.26 3.27 6 65.00 OK 6 75.00 6 1 x3C 4+1 x6 0,6 kV 1 x [3C #4 0.6 kV +1C #4 0.6 kV]
MAG
BANCAD -
23 0 0 CCM-CHB1-02 MP-4120 MOTOR 480 460 20 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 23.67 23.67 36.98 10 12 2.06 3.33 6 65.00 OK 10 75.00 6 1 x3C 6+1 x6 0,6 kV 1 x [3C #10 0.6 kV +1C #10 0.6 kV]
MAG
BANCAD -
24 0 0 CCM-CHB1-02 MP-4130 MOTOR 480 460 20 HP 0.86 0.92 1.15 6.00 0.20 3 40 A NO 1 23.67 23.67 36.98 10 12 2.06 3.33 6 65.00 OK 10 75.00 6 1 x3C 6+1 x6 0,6 kV 1 x [3C #10 0.6 kV +1C #10 0.6 kV]
MAG
BANCAD -
25 0 0 CCM-CHB1-02 CCM-PK-500 MCC/SWG 480 480 100 KW 0.85 0.91 N/A 0.00 0.00 3 70 A NO 1 155.50 155.50 194.38 2/0 4 3.89 - 2 1.00 OK 2/0 75.00 2 1 x3 x1C 2/0+1 x2 0,6 kV
3 x [3x1C #2/0 0.6 kV +1C #2 0.6 kV]
MAG
PROYECTO: COHEMBÍ EXPANSION
COHEMBÍ 3
ORDEN DE FILAS DATOS DE LA CARGA

CODIGO CODIGO TENSIO


CODIGO DE EQUIPO EQUIPO N DE
LINEA REV CABLE DESDE HASTA TIPO DE EQUIPO RED (V)
1 A 0 GEN1-CHB3-001CCM-CHB3-01 MCC/SWG 480
2 A 0 GEN2-CHB3-001CCM-CHB3-01 MCC/SWG 480
3 A 0 GEN3-CHB3-001CCM-CHB3-01 MCC/SWG 480
4 A 0 GEN3-CHB3-001CCM-CHB3-01 MCC/SWG 480
7 A 0 CCM-CHB3-01 FI-CHB3-03 TABLERO 480
8 A 0 CCM-CHB3-01 FI-CHB3-07 TABLERO 480
9 A 0 CCM-CHB3-01 FI-CHB3-05 TABLERO 480
10 A 0 CCM-CHB3-01 FI-CHB3-20 TABLERO 480
11 A 0 CCM-CHB3-01 FI-CHB3-21 TABLERO 480
12 A 0 CCM-CHB3-01 TX-TCH3-01 TRANSFORMADOR 480
13 A 0 CCM-CHB3-01 HPS-CHB-07 TABLERO 480

14 A 0 CCM-CHB3-01 HPS-CHB-19-1 TABLERO 480

15 A 0 CCM-CHB3-01 HPS-CHB-19-2 TABLERO 480


CALCULO D

DE LA CARGA DATOS DEL CONDUCTOR

TENSIO
N DEL POTENCI FAC.
EQUIPO A CORR. FP LONG TIPO DE COND./
(V) NOMINAL FP EF FS ARR. ARR. FASES (M) INSTAL. FASE
480 1000 KW 0.80 0.94 N/A 0.00 0.00 3 50 BANDEJA 4
480 1000 KW 0.80 0.94 N/A 0.00 0.00 3 50 BANDEJA 4
480 1000 KW 0.80 0.94 N/A 0.00 0.00 3 50 BANDEJA 4
480 1000 KW 0.80 0.94 N/A 0.00 0.00 3 50 BANDEJA 4
480 530 KVA 0.80 0.91 N/A 0.00 0.00 3 150 BANDEJA 3
480 530 KVA 0.80 0.91 N/A 0.00 0.00 3 120 BANDEJA 3
480 530 KVA 0.80 0.91 N/A 0.00 0.00 3 130 BANDEJA 3
480 530 KVA 0.80 0.91 N/A 0.00 0.00 3 150 BANDEJA 3
480 530 KVA 0.80 0.91 N/A 0.00 0.00 3 160 BANDEJA 3
480 45 KVA 0.85 0.91 N/A 0.00 0.00 3 60 BANDEJA 1
BANCAD
480 800 HP 0.96 0.91 N/A 0.00 0.00 3 150 3
A NO
MAG
BANCAD
480 900 HP 0.85 0.94 N/A 0.00 0.00 3 150 3
A NO
MAG
BANCAD
480 800 HP 0.96 0.91 N/A 0.00 0.00 3 150 3
A NO
MAG
CALCULO DE ALIMENTADORES ELÉCTRICOS

CORR.
DISEÑO
CORREGID
CORR. A CALIBRE
POR POR CALIBRE POR CAIDA CALIBRE POR
CORR. CONDUCT TEMP POR DE % ΔV EN CORTOCIRCUI
NOMINAL OR AMB AMPACIDA TENSIÓN ARRANQU TO NCC
(A) (A) (A) D (AWG) (AWG) % ΔV E (AWG) (KA)
1599.49 399.87 666.45 500 2 4.39 - 4/0 65.00
1599.49 399.87 666.45 500 2 4.39 - 4/0 65.00
1599.49 399.87 666.45 500 2 4.39 - 4/0 65.00
1599.49 399.87 666.45 500 2 4.39 - 4/0 65.00
700.54 233.51 486.49 350 2/0 4.56 - 4/0 30.00
700.54 233.51 486.49 350 1/0 4.18 - 4/0 10.83
700.54 233.51 486.49 350 1/0 4.52 - 4/0 65.00
700.54 233.51 486.49 350 2/0 4.56 - 4/0 65.00
700.54 233.51 486.49 350 2/0 4.87 - 4/0 65.00
59.48 59.48 78.26 4 10 4.58 - 10 65.00
821.70 273.90 427.97 500 3/0 4.34 - 4/0 65.00

1010.72 336.91 526.42 750 4/0 4.59 - 4/0 65.00

821.70 273.90 427.97 500 3/0 4.34 - 4/0 65.00


RICOS

RESULTADO
CABLE
FINAL DE
TEMP. DE TIERRA
DAÑO EN VERIFICAD
CALIBRE POR LOS O POR
STATUS POR TEMPERATUR TERMINALE CORTOCIR
ICC INT. A EN S CUITO
LIMITADORES TERMINALES (°C) (AWG)
OK 500 75.00 4/0
OK 500 75.00 4/0
OK 500 75.00 4/0
OK 500 75.00 4/0
OK 4/0 75.00 4/0
OK 250 75.00 4/0
OK 250 75.00 4/0
OK 350 75.00 4/0
OK 350 75.00 4/0
OK 4 60.00 8
OK 350 75.00 4/0

OK 350 75.00 4/0

OK 350 75.00 4/0


O

CABLE FINAL SELECCIONADO POR EL PROGRAMA


(FASE+TIERRA)
(AWG)
4 x3 x1C 500+4 x4/0 0,6 kV
4 x3 x1C 500+4 x4/0 0,6 kV
4 x3 x1C 500+4 x4/0 0,6 kV
4 x3 x1C 500+4 x4/0 0,6 kV
3 x3 x1C 350+3 x4/0 0,6 kV
3 x3 x1C 350+3 x4/0 0,6 kV
3 x3 x1C 350+3 x4/0 0,6 kV
3 x3 x1C 350+3 x4/0 0,6 kV
3 x3 x1C 350+3 x4/0 0,6 kV
1 x3C 4+1 x8 0,6 kV
3 x3 x1C 500+3 x4/0 0,6 kV

3 x3 x1C 750+3 x4/0 0,6 kV

3 x3 x1C 500+3 x4/0 0,6 kV


REV: A

CABLE FINAL SELECCIONADO POR EL USUARIO


(FASE+TIERRA)
(AWG) OBSERVACIONES
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
1 x [3C #4 0.6 kV +1C #4 0.6 kV] -
-
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
-
4 x [3x1C #750 0.6 kV +1C #4/0 0.6 kV]
-
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
PROYECTO:COHEMBÍ EXPANSION
COHEMBÍ 4
ORDEN DE FILAS DATOS DE LA CARGA

CODIGO
DE CODIGO TIPO DE
LINEA REV CABLE EQUIPO DESDE CODIGO EQUIPO HASTA EQUIPO

1 0 0 CCM-CHB4-01 VFD-HPS-CHB4-01 (P-6520) TABLERO

2 0 0 CCM-CHB4-01 VFD-HPS-CHB1-02 (P-6525) TABLERO


CALCULO DE ALIMEN

DATOS DE LA CARGA DATOS DEL CONDUC

TENSIO POTENC
TENSIO N DEL IA FAC.
N DE EQUIPO NOMINA CORR. LONG
RED (V) (V) L FP EF FS ARR. FP ARR. FASES (M)

480 480 500 HP 0.85 1.00 N/A 0.00 0.00 3 220

480 480 500 HP 0.85 1.00 N/A 0.00 0.00 3 220


DE ALIMENTADORES ELÉCTRICOS

DATOS DEL CONDUCTOR

CORR.
DISEÑO CALIBRE
CORREG POR
CORR. IDA CALIBRE CAIDA CALIBRE
POR POR POR DE POR
CORR. CONDUC TEMP AMPACI TENSIÓ % ΔV EN CORTOC
TIPO DE COND./ NOMINA TOR AMB DAD N ARRANQ IRCUITO
INSTAL. FASE L (A) (A) (A) (AWG) (AWG) % ΔV UE (AWG)
BANCAD
A NO 2 527.82 263.91 412.36 500 250 4.68 - 4/0
MAG
BANCAD
A NO 2 527.82 263.91 412.36 500 250 4.68 - 4/0
MAG
RESULTADO CABLE
FINAL
DE
CALIBRE TEMP. TIERRA
POR DE VERIFIC
STATUS TEMPER DAÑO ADO CABLE FINAL
POR ICC ATURA EN LOS POR SELECCIONADO POR EL
INT. EN TERMIN CORTOC PROGRAMA
NCC LIMITAD TERMIN ALES IRCUITO (FASE+TIERRA)
(KA) ORES ALES (°C) (AWG) (AWG)

65.00 OK 250 75.00 4/0 2 x3 x1C 500+2 x4/0 0,6 kV

65.00 OK 250 75.00 4/0 2 x3 x1C 500+2 x4/0 0,6 kV


REV: A

CABLE FINAL SELECCIONADO POR EL


USUARIO OBSERV
(FASE+TIERRA) ACIONE
(AWG) S
-
2 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]

-
2 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
PROYECTO: COHEMBÍ EXPANSION
COHEMBÍ 6
ORDEN DE FILAS

CODIGO
CODIGO DE EQUIPO CODIGO EQUIPO
LINEA REV CABLE DESDE HASTA
1 0 0 TX-CHB6-01 TX-CHB6-02
2 A 0 GEN1-CHB6-001 CCM-CHB1-01
3 A 0 GEN2-CHB6-001 CCM-CHB6-01
4 A 0 GEN3-CHB6-001 CCM-CHB6-01
5 A 0 GEN4-CHB6-001 CCM-CHB6-01
8 A 0 CCM-CHB6-01 TX1-CHB1-001
9 A 0 CCM-CHB6-01 CHB-16
10 A 0 CCM-CHB6-01 CHB-09
11 A 0 CCM-CHB6-01 CHB-10
12 A 0 CCM-CHB6-01 CHB-14
13 A 0 CCM-CHB6-01 CHB-15
14 A 0 CCM-CHB6-01 TX-CHB6-01
15 A 0 TX-CHB6-02 CCM-CHB6-02
16 A 0 CCM-CHB6-01 MP-6630

17 A 0 CCM-CHB6-01 MP-6640

18 A 0 CCM-CHB6-01 MP-6650

19 A 0 CCM-CHB6-01 CCM-PK-501

20 A 0 CCM-CHB6-02 HPS-CHB6-01 (PM-201A)

21 A 0 CCM-CHB6-02 HPS-CHB6-01 (PM-201B)

22 A 0 CCM-CHB6-02 HPS-CHB9-01 (CHB-9)

23 A 0 CCM-CHB6-02 HPS-CHB15-01 (CHB-15)


EXPANSION

DATOS DE LA CARGA

TENSION DE TENSION DEL POTENCIA


TIPO DE EQUIPO RED (V) EQUIPO (V) NOMINAL FP EF
TRANSFORMADOR 4160 4160 2500 KVA 0.85 0.91
MCC/SWG 480 480 1000 KW 0.80 0.94
MCC/SWG 480 480 1000 KW 0.80 0.94
MCC/SWG 480 480 1000 KW 0.80 0.94
MCC/SWG 480 480 1000 KW 0.80 0.94
TRANSFORMADOR 480 480 15 KVA 0.90 0.91
TABLERO 480 480 530 KVA 0.85 0.91
TABLERO 480 480 350 KVA 0.85 0.91
TABLERO 480 480 530 KVA 0.85 0.91
TABLERO 480 480 530 KVA 0.85 0.91
TABLERO 480 480 530 KVA 0.85 0.91
TRANSFORMADOR 480 480 2500 KVA 0.85 0.91
TRANSFORMADOR 480 480 2500 KVA 0.85 0.91
MOTOR 480 460 15 HP 0.86 0.92

MOTOR 480 460 15 HP 0.86 0.92

MOTOR 480 460 15 HP 0.86 0.92

MCC/SWG 480 480 150 KW 0.85 0.91

TABLERO 480 480 800 HP 0.90 0.97

TABLERO 480 480 800 HP 0.90 0.97

TABLERO 480 480 900 HP 0.90 0.92

TABLERO 480 480 800 HP 0.90 0.97


CALCULO DE ALIMENTAD

DATOS DEL CONDUCTOR

FAC. LONG TIPO DE


FS CORR. ARR. FP ARR. FASES (M) INSTAL.
N/A 0.00 0.00 3 350 BANDEJA
N/A 0.00 0.00 3 70 BANDEJA
N/A 0.00 0.00 3 70 BANDEJA
N/A 0.00 0.00 3 60 BANDEJA
N/A 0.00 0.00 3 60 BANDEJA
N/A 0.00 0.00 3 50 TUBO
N/A 0.00 0.00 3 80 BANDEJA
N/A 0.00 0.00 3 100 BANDEJA
N/A 0.00 0.00 3 120 BANDEJA
N/A 0.00 0.00 3 90 BANDEJA
N/A 0.00 0.00 3 85 BANDEJA
N/A 0.00 0.00 3 25 BANDEJA
N/A 0.00 0.00 3 25 BANDEJA
BANCADA NO
1.15 6.00 0.20 3 80
MAG
BANCADA NO
1.15 6.00 0.20 3 80
MAG
BANCADA NO
1.15 6.00 0.20 3 80
MAG
BANCADA NO
N/A 0.00 0.00 3 100
MAG
BANCADA NO
N/A 0.00 0.00 3 100
MAG
BANCADA NO
N/A 0.00 0.00 3 100
MAG
BANCADA NO
N/A 0.00 0.00 3 100
MAG
BANCADA NO
N/A 0.00 0.00 3 100
MAG
E ALIMENTADORES ELÉCTRICOS

L CONDUCTOR

CORR.
DISEÑO
CORREGIDA
CORR. POR CALIBRE POR
POR TEMP CALIBRE POR CAIDA DE
COND./ CORR. CONDUCTOR AMB AMPACIDAD TENSIÓN
FASE NOMINAL (A) (A) (A) (AWG) (AWG)
1 381.28 381.28 497.23 350 3/0
4 1599.49 399.87 666.45 500 1/0
4 1599.49 399.87 666.45 500 1/0
4 1599.49 399.87 666.45 500 1/0
4 1599.49 399.87 666.45 500 1/0
1 19.83 19.83 24.78 12 12
3 700.54 233.51 486.49 350 2
2 462.62 231.31 481.90 350 1/0
3 700.54 233.51 486.49 350 1/0
3 700.54 233.51 486.49 350 2
3 700.54 233.51 486.49 350 2
10 3304.43 330.44 688.42 500 6
10 3304.43 330.44 688.42 500 6
1 17.75 17.75 27.74 12 12

1 17.75 17.75 27.74 12 12

1 17.75 17.75 27.74 12 12

2 233.25 116.63 145.78 1/0 4

3 822.27 274.09 428.26 500 1/0

3 822.27 274.09 428.26 500 1/0

4 975.32 243.83 380.99 500 1/0

3 822.27 274.09 428.26 500 1/0


RESULTADO

CALIBRE POR CALIBRE POR


CORTOCIRCU STATUS POR TEMPERATUR
% ΔV EN ITO NCC ICC INT. A EN
% ΔV ARRANQUE (AWG) (KA) LIMITADORES TERMINALES
1.79 - 2/0 24.98 OK 350
4.17 - 4/0 65.00 OK 500
4.17 - 4/0 65.00 OK 500
3.58 - 4/0 65.00 OK 500
3.58 - 4/0 65.00 OK 500
2.26 - 12 10.83 OK 8
4.25 - 4/0 30.00 OK 4/0
3.53 - 4/0 10.83 OK 4/0
4.28 - 4/0 65.00 OK 4/0
4.78 - 4/0 65.00 OK 4/0
4.51 - 4/0 65.00 OK 4/0
4.53 - 250 65.00 OK 500
4.53 - 250 65.00 OK 500
3.09 4.99 12 65.00 OK 10

3.09 4.99 12 65.00 OK 10

3.09 4.99 12 65.00 OK 10

4.17 - 2 42.00 OK 1/0

4.26 - 1/0 65.00 OK 350

4.26 - 1/0 65.00 OK 350

3.79 - 1/0 65.00 OK 350

4.26 - 1/0 65.00 OK 350


CABLE FINAL
DE TIERRA
TEMP. DE VERIFICADO CABLE FINAL SELECCIONADO
DAÑO EN LOS POR POR EL PROGRAMA
TERMINALES CORTOCIRCU (FASE+TIERRA)
(°C) ITO (AWG) (AWG)
90.00 2/0 1 x3 x1C 350 5 kV + 1 x2/0
75.00 4/0 4 x3 x1C 500+4 x4/0 0,6 kV
75.00 4/0 4 x3 x1C 500+4 x4/0 0,6 kV
75.00 4/0 4 x3 x1C 500+4 x4/0 0,6 kV
75.00 4/0 4 x3 x1C 500+4 x4/0 0,6 kV
60.00 10 1 x3C 8+1 x10 0,6 kV
75.00 4/0 3 x3 x1C 350+3 x4/0 0,6 kV
75.00 4/0 2 x3 x1C 350+2 x4/0 0,6 kV
75.00 4/0 3 x3 x1C 350+3 x4/0 0,6 kV
75.00 4/0 3 x3 x1C 350+3 x4/0 0,6 kV
75.00 4/0 3 x3 x1C 350+3 x4/0 0,6 kV
75.00 500 10 x3 x1C 500+10 x500 0,6 kV
75.00 500 10 x3 x1C 500+10 x500 0,6 kV
60.00 10 1 x3C 10+1 x10 0,6 kV

60.00 10 1 x3C 10+1 x10 0,6 kV

60.00 10 1 x3C 10+1 x10 0,6 kV

75.00 2 2 x3 x1C 1/0+2 x2 0,6 kV

75.00 2/0 3 x3 x1C 500+3 x2/0 0,6 kV

75.00 2/0 3 x3 x1C 500+3 x2/0 0,6 kV

75.00 2/0 4 x3 x1C 500+4 x2/0 0,6 kV

75.00 2/0 3 x3 x1C 500+3 x2/0 0,6 kV


REV: A

CABLE FINAL SELECCIONADO POR EL


USUARIO
(FASE+TIERRA) OBSERVACIO
(AWG) NES
1 x [3x1C #350 35 KV + 1C #2/0 0.6 KV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
1 x [3C #8 0.6 kV +1C #8 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #2/0 0.6 kV] -
2 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] -
10 x [3x1C #500 0.6 kV +1C #500 0.6 kV] -
10 x [3x1C #500 0.6 kV +1C #500 0.6 kV] -
-
1 x [3C #10 0.6 kV +1C #10 0.6 kV]
-
1 x [3C #10 0.6 kV +1C #10 0.6 kV]
-
1 x [3C #10 0.6 kV +1C #10 0.6 kV]
-
2 x [3x1C #1/0 0.6 kV +1C #2 0.6 kV]
-
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
-
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
-
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
-
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV]
Total Cable
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] 50 m 4Un
Generadores 1800 500 kcmil
Generadores 600 4/0
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] 120 m 2Un, 40 m 2Un
2880 500 kcmil
960 4/0
3 x [3x1C #500 0.6 kV +1C #250 0.6 kV] 280 m 1Un, 20 m 1 Un
2700 500 kcmil
900 250 kcmil
1 x [3x1C #4/0 0.6 kV +1C #6 0.6 kV] 40 m 2UN
720 4/0
240 6 AWG
3 x [3x1C #2/0 0.6 kV +1C #2 0.6 kV] 70 m 1 Un
630 2/0
210 2 AWG
1 x [3x1C #2/0 0.6 kV +1C #6 0.6 kV] 40 m 4Un
480 2/0
160 6 AWG
1 x [3C #2 0.6 kV +1C #2 0.6 kV] 40 m 2Un
240 2 AWG
80 2 AWG
1 x [3C #4 0.6 kV +1C #4 0.6 kV] 250 m 2Un
1500 4 AWG
500 4 AWG
1 x [3C #10 0.6 kV +1C #10 0.6 kV] 40 m 2Un
240 10 AWG
80 10 AWG

Calibre Cohembí 1 Cohembí 3 Cohembí 4 Cohembí 6 Total


750 kcmil 1,800 1,800
500 kcmil 7,380 11,490 18,870
250 kcmil 900 900
4/0 2,280 4,430 6,710
2/0 1,110 1,110
2 AWG 210 210
4x2 AWG 80 80
4x4 AWG 500 500
6 AWG 400 400
4x10 AWG 80 80
4 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] 50 m 4Un
2400 500 kcmil
800 4/0
3 x [3x1C #500 0.6 kV +1C #4/0 0.6 kV] 150 m 4Un, 130 m 1 Un, 120 m 1 Un, 160 m 1 Un
9090 500 kcmil
3030 4/0
4 x [3x1C #750 0.6 kV +1C #4/0 0.6 kV] 150 m 1Un
1800 750 kcmil
600 4/0