Está en la página 1de 198

ESTUDIO DE CARGABILIDAD EN TRANSFORMADORES DE

PODER ZONA METROPOLITANA


ÍNDICE
ZONA METROPOLITANA ................................................................................................................. 4
1.1. SE ALCONES T-45700 T1 ID22092 ............................................................................................................. 4
1.2. SE ALHUE T-45800 T1 ID40180 ................................................................................................................. 9
1.3. SE BOLLENAR T-46000 T1 ID39720.......................................................................................................... 14
1.4. SE CHOCALÁN T-46500 T1 ID 23124 ........................................................................................................ 19
1.5. SE EL MAITÉN T-47600 T1 ID18969 ........................................................................................................ 24
1.6. SE EL MONTE T-47700 T1 ID 19680 ........................................................................................................ 29
1.7. SE EL PAICO T-47800 T1 ID XA19344001 ................................................................................................ 34
1.8. SE LA ESPERANZA T-48500 T1 ID 40745 ................................................................................................... 39
1.9. SE LA MANGA T-48600 T1 ID 23018 ........................................................................................................ 44
1.10. SE LAS ARAÑAS T-48900 T3 ID40163 ....................................................................................................... 49
1.11. SE LAS ARAÑAS T-49000 ATR1 ID ET91373 .............................................................................................. 54
1.12. SE LAS ARAÑAS T-49100 ATR2 IDET91371 .............................................................................................. 59
1.13. SE LEYDA T-49200 T1 ID18954 ............................................................................................................... 64
1.14. SE MARCHIGÜE T-15400 T2 ID 7320054.0 ............................................................................................... 69
1.15. SE MELIPILLA T-50200 T1 ID20590 .......................................................................................................... 74
1.16. SE MELIPILLA T-50300 T2 IDXA1689A001 ............................................................................................... 79
1.17. SE PORTEZUELO T-51800 T1 IDET91372 .................................................................................................. 84
1.18. SE PORTEZUELO T-52900 T3 ID20591 ...................................................................................................... 89
1.19. SE QUELENTARO T-18400 T5 ID7320065 ................................................................................................. 94
1.20. SE RAPEL T-50100 T3 ID18968............................................................................................................... 99
1.21. SE RAPEL T-52600 T1 ID 21796............................................................................................................. 104
1.22. SE RAPEL T-52700 T2 ID22830 ............................................................................................................. 109
1.23. SE SANTA ROSA T-53500 T1 ID87070 .................................................................................................... 114
1.24. SE EL PEUMO T-47900 RESERVA FRÍA PARA PROYECTO ID 73200300 .......................................................... 119
1.25. SE EL PEUMO T-54137 T1 ID7320154 ................................................................................................... 124
1.26. SE ISLA DE MAIPO T-20000 T1 ID 18340 ................................................................................................ 129
1.27. SE MELIPILLA T-45500 T3 ID44630 ........................................................................................................ 134
1.28. SE MELIPILLA T-50400 RESERVA FRÍA ID17353......................................................................................... 139
1.29. SE MELIPILLA T-MÓVIL RESERVA FRÍA ID XA1957A001 .............................................................................. 144
1.30. SE PADRE HURTADO T-24500 RESERVA FRÍA PARA PROYECTO ID37463 ........................................................ 149
1.31. SE PAPELERA TALAGANTE T-54103 T1 ID 47700 ...................................................................................... 154

Estudio de sobrecargas Página 2 de 198


Marzo 2017
1.32. SE QUELENTARO T-51900, T-52000, T-52100 ATR123 IDET91361-2-3 .................................................. 159
1.33. SE QUELENTARO T-52200 RESERVA FRÍA ID ET 91364 ............................................................................... 164
1.34. SE ISLA DE MAIPO T3 T-24400 ID 11111 ................................................................................................. 169
1.35. SE ISLA DE MAIPO T-19800 T2 ID 79745 ................................................................................................ 174
1.36. SE LAS ARAÑAS T-18880 T4 ID 72221 .................................................................................................... 179
1.37. SE MANDINGA T-49900 T1 ID 15662 ..................................................................................................... 184
1.38. SE MARCHIGÜE T-50000 T1 ID570207 ................................................................................................... 189
1.39. SE PORTEZUELO T-17700 T2 ID30414 .................................................................................................... 194

Estudio de sobrecargas Página 3 de 198


Marzo 2017
ZONA METROPOLITANA
1.1. SE ALCONES T-45700 T1 ID22092
Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00 0:35
125, 24:00:00 24:00:00 24:00:00 2:15 1:05 0:40 0:25
130, 24:00:00 24:00:00 2:20 1:10 0:45 0:30 0:20
135, 24:00:00 2:25 1:15 0:45 0:30 0:25 0:20
140, 2:25 1:20 0:50 0:35 0:25 0:20 0:15

Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:55 0:35
125, 24:00:00 24:00:00 24:00:00 2:10 1:00 0:35 0:25
130, 24:00:00 24:00:00 2:15 1:10 0:40 0:30 0:20
135, 24:00:00 2:20 1:15 0:45 0:30 0:25 0:15
140, 2:20 1:15 0:50 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 4 de 198


Marzo 2017
Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:55 0:30
125, 24:00:00 24:00:00 24:00:00 2:10 1:00 0:35 0:25
130, 24:00:00 24:00:00 2:15 1:05 0:40 0:25 0:20
135, 24:00:00 2:20 1:10 0:45 0:30 0:20 0:15
140, 2:20 1:15 0:45 0:30 0:25 0:20 0:15

Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:50 0:30
125, 24:00:00 24:00:00 24:00:00 2:05 0:55 0:35 0:20
130, 24:00:00 24:00:00 2:10 1:00 0:35 0:25 0:20
135, 24:00:00 2:15 1:10 0:40 0:30 0:20 0:15
140, 2:15 1:10 0:45 0:30 0:25 0:15 0:15

Estudio de sobrecargas Página 5 de 198


Marzo 2017
Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:45 0:25
125, 24:00:00 24:00:00 24:00:00 2:00 0:55 0:30 0:20
130, 24:00:00 24:00:00 2:05 1:00 0:35 0:25 0:15
135, 24:00:00 2:10 1:05 0:40 0:25 0:20 0:15
140, 2:15 1:10 0:40 0:30 0:20 0:15 0:10

Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:40 0:25
125, 24:00:00 24:00:00 24:00:00 1:55 0:50 0:30 0:20
130, 24:00:00 24:00:00 2:00 0:55 0:30 0:20 0:15
135, 24:00:00 2:05 1:00 0:35 0:25 0:15 0:10
140, 2:10 1:05 0:40 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 6 de 198


Marzo 2017
Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40 0:20
125, 24:00:00 24:00:00 24:00:00 1:50 0:45 0:25 0:15
130, 24:00:00 24:00:00 1:55 0:50 0:30 0:20 0:10
135, 24:00:00 2:00 0:55 0:35 0:20 0:15 0:10
140, 2:05 1:00 0:35 0:25 0:15 0:10 0:10

Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:35 0:15
125, 24:00:00 24:00:00 24:00:00 1:40 0:40 0:20 0:15
130, 24:00:00 24:00:00 1:50 0:45 0:25 0:15 0:10
135, 24:00:00 1:55 0:55 0:30 0:20 0:15 0:10
140, 2:00 1:00 0:35 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 7 de 198


Marzo 2017
Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:30 0:15
125, 24:00:00 24:00:00 24:00:00 1:35 0:35 0:20 0:10
130, 24:00:00 24:00:00 1:45 0:40 0:25 0:15 0:10
135, 24:00:00 1:50 0:50 0:25 0:15 0:10 0:05
140, 1:55 0:55 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID22092 Rhona 10 MVA 66 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE Alcones T1 T-45700 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50 0:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:25 0:10
125, 24:00:00 24:00:00 24:00:00 1:25 0:30 0:15 0:05
130, 24:00:00 24:00:00 1:35 0:35 0:20 0:10 0:05
135, 24:00:00 1:45 0:45 0:25 0:15 0:10 0:05
140, 1:50 0:50 0:30 0:20 0:10 0:05 0:05

Estudio de sobrecargas Página 8 de 198


Marzo 2017
1.2. SE ALHUE T-45800 T1 ID40180
Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:25 0:55
115, 24:00:00 24:00:00 24:00:00 2:35 1:30 1:00 0:40
120, 24:00:00 24:00:00 2:30 1:30 1:00 0:45 0:30
125, 24:00:00 2:25 1:35 1:05 0:45 0:35 0:25
130, 2:20 1:35 1:05 0:50 0:35 0:25 0:20
135, 1:35 1:10 0:50 0:40 0:30 0:25 0:20
140, 1:10 0:55 0:40 0:30 0:25 0:20 0:15

Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:20 0:50
115, 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55 0:35
120, 24:00:00 24:00:00 2:25 1:30 1:00 0:40 0:30
125, 24:00:00 2:25 1:30 1:00 0:45 0:30 0:25
130, 2:20 1:30 1:05 0:45 0:35 0:25 0:20
135, 1:30 1:05 0:50 0:35 0:30 0:20 0:15
140, 1:10 0:50 0:40 0:30 0:25 0:20 0:15

Estudio de sobrecargas Página 9 de 198


Marzo 2017
Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:15 0:45
115, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:30
120, 24:00:00 24:00:00 2:20 1:25 0:55 0:35 0:25
125, 24:00:00 2:20 1:25 1:00 0:40 0:30 0:20
130, 2:15 1:30 1:00 0:45 0:30 0:25 0:15
135, 1:30 1:05 0:45 0:35 0:25 0:20 0:15
140, 1:05 0:50 0:35 0:30 0:20 0:15 0:15

Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:10 0:40
115, 24:00:00 24:00:00 24:00:00 2:20 1:15 0:45 0:30
120, 24:00:00 24:00:00 2:15 1:20 0:50 0:35 0:20
125, 24:00:00 2:15 1:25 0:55 0:35 0:25 0:20
130, 2:10 1:25 1:00 0:40 0:30 0:20 0:15
135, 1:25 1:00 0:45 0:30 0:25 0:20 0:15
140, 1:00 0:45 0:35 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 10 de 198


Marzo 2017
Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05 0:35
115, 24:00:00 24:00:00 24:00:00 2:15 1:10 0:40 0:25
120, 24:00:00 24:00:00 2:10 1:15 0:45 0:30 0:20
125, 24:00:00 2:10 1:20 0:50 0:35 0:25 0:15
130, 2:05 1:20 0:55 0:35 0:25 0:20 0:15
135, 1:20 0:55 0:40 0:30 0:20 0:15 0:10
140, 1:00 0:45 0:30 0:25 0:20 0:15 0:10

Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:55 0:30
115, 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35 0:20
120, 24:00:00 24:00:00 2:05 1:10 0:40 0:25 0:15
125, 24:00:00 2:05 1:15 0:45 0:30 0:20 0:15
130, 2:00 1:15 0:50 0:35 0:25 0:15 0:10
135, 1:15 0:55 0:35 0:25 0:20 0:15 0:10
140, 0:55 0:40 0:30 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 11 de 198


Marzo 2017
Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:50 0:25
115, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30 0:15
120, 24:00:00 24:00:00 2:00 1:00 0:35 0:20 0:10
125, 24:00:00 2:00 1:05 0:40 0:25 0:15 0:10
130, 1:55 1:10 0:45 0:30 0:20 0:15 0:10
135, 1:15 0:50 0:35 0:25 0:15 0:10 0:05
140, 0:50 0:35 0:25 0:20 0:15 0:10 0:05

Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:40 0:15
115, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:25 0:10
120, 24:00:00 24:00:00 1:50 0:55 0:30 0:15 0:10
125, 24:00:00 1:50 1:00 0:35 0:20 0:15 0:05
130, 1:50 1:05 0:40 0:25 0:15 0:10 0:05
135, 1:05 0:45 0:30 0:20 0:15 0:10 0:05
140, 0:45 0:30 0:25 0:15 0:10 0:05 0:05

Estudio de sobrecargas Página 12 de 198


Marzo 2017
Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30 0:10
115, 24:00:00 24:00:00 24:00:00 1:35 0:40 0:15 0:05
120, 24:00:00 24:00:00 1:40 0:45 0:25 0:10 0:05
125, 24:00:00 1:40 0:55 0:30 0:15 0:10 0:05
130, 1:40 0:55 0:35 0:20 0:15 0:05 0:00
135, 1:00 0:40 0:25 0:15 0:10 0:05 0:00
140, 0:40 0:30 0:20 0:15 0:10 0:05 0:00

Cuadro de carga
ID40180 Rhona 20 MVA 66 25-15 KV ONAN 16 ONAF1 20
Transformador SE Alhue T1 T-45800 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45 0:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:15 0:00
115, 24:00:00 24:00:00 24:00:00 1:20 0:25 0:10 0:00
120, 24:00:00 24:00:00 1:30 0:35 0:15 0:05 0:00
125, 24:00:00 1:30 0:45 0:25 0:10 0:05 0:00
130, 1:35 0:50 0:30 0:15 0:10 0:05 0:00
135, 0:55 0:35 0:20 0:10 0:05 0:00 0:00
140, 0:35 0:25 0:15 0:10 0:05 0:00 0:00

Estudio de sobrecargas Página 13 de 198


Marzo 2017
1.3. SE BOLLENAR T-46000 T1 ID39720
Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55
130, 24:00:00 24:00:00 24:00:00 2:35 1:35 1:05 0:45
135, 24:00:00 24:00:00 2:45 1:40 1:10 0:50 0:35
140, 24:00:00 2:50 1:45 1:15 0:55 0:40 0:30

Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55
130, 24:00:00 24:00:00 24:00:00 2:35 1:30 1:00 0:40
135, 24:00:00 24:00:00 2:40 1:40 1:05 0:45 0:35
140, 24:00:00 2:45 1:45 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 14 de 198


Marzo 2017
Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
130, 24:00:00 24:00:00 24:00:00 2:30 1:30 0:55 0:40
135, 24:00:00 24:00:00 2:40 1:35 1:05 0:45 0:30
140, 24:00:00 2:45 1:40 1:10 0:50 0:35 0:25

Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45
130, 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55 0:35
135, 24:00:00 24:00:00 2:35 1:35 1:00 0:40 0:30
140, 24:00:00 2:40 1:40 1:05 0:45 0:30 0:25

Estudio de sobrecargas Página 15 de 198


Marzo 2017
Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:45
130, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:30
135, 24:00:00 24:00:00 2:30 1:30 0:55 0:40 0:25
140, 24:00:00 2:40 1:35 1:05 0:45 0:30 0:20

Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05 0:40
130, 24:00:00 24:00:00 24:00:00 2:20 1:15 0:45 0:30
135, 24:00:00 24:00:00 2:25 1:25 0:55 0:35 0:25
140, 24:00:00 2:35 1:30 1:00 0:40 0:25 0:20

Estudio de sobrecargas Página 16 de 198


Marzo 2017
Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35
130, 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40 0:25
135, 24:00:00 24:00:00 2:20 1:20 0:50 0:30 0:20
140, 24:00:00 2:30 1:25 0:55 0:35 0:25 0:15

Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:45
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:55 0:30
130, 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35 0:20
135, 24:00:00 24:00:00 2:15 1:15 0:45 0:25 0:15
140, 24:00:00 2:25 1:20 0:50 0:30 0:20 0:15

Estudio de sobrecargas Página 17 de 198


Marzo 2017
Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45 0:25
130, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:30 0:15
135, 24:00:00 24:00:00 2:10 1:10 0:40 0:25 0:15
140, 24:00:00 2:20 1:15 0:45 0:30 0:20 0:10

Cuadro de carga
ID39720 Rhona 20 MVA 110 13,8 KV ONAN 16 ONAF1 20
Transformador SE Bollenar T1 T-46000 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40 0:15
130, 24:00:00 24:00:00 24:00:00 1:50 0:50 0:25 0:15
135, 24:00:00 24:00:00 2:00 1:00 0:35 0:20 0:10
140, 24:00:00 2:10 1:10 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 18 de 198


Marzo 2017
1.4. SE CHOCALÁN T-46500 T1 ID 23124

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 50, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:45
110, 24:00:00 24:00:00 24:00:00 6:25 1:35 0:50 0:30
115, 24:00:00 24:00:00 4:30 1:35 0:55 0:35 0:25
120, 24:00:00 3:45 1:35 0:55 0:35 0:25 0:20
125, 3:15 1:35 1:00 0:40 0:30 0:20 0:15
130, 1:35 1:00 0:40 0:30 0:25 0:20 0:15
135, 1:00 0:45 0:30 0:25 0:20 0:15 0:10
140, 0:45 0:35 0:25 0:20 0:15 0:15 0:10

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 55, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:40
110, 24:00:00 24:00:00 24:00:00 6:20 1:30 0:45 0:30
115, 24:00:00 24:00:00 4:25 1:30 0:50 0:30 0:20
120, 24:00:00 3:40 1:35 0:55 0:35 0:25 0:20
125, 3:15 1:35 0:55 0:35 0:25 0:20 0:15
130, 1:30 0:55 0:40 0:30 0:20 0:15 0:15
135, 1:00 0:40 0:30 0:25 0:20 0:15 0:10
140, 0:40 0:30 0:25 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 19 de 198


Marzo 2017
Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 60, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:40
110, 24:00:00 24:00:00 24:00:00 6:15 1:25 0:45 0:25
115, 24:00:00 24:00:00 4:20 1:30 0:45 0:30 0:20
120, 24:00:00 3:40 1:30 0:50 0:30 0:20 0:15
125, 3:10 1:30 0:55 0:35 0:25 0:20 0:15
130, 1:30 0:55 0:35 0:25 0:20 0:15 0:10
135, 0:55 0:40 0:30 0:20 0:15 0:15 0:10
140, 0:40 0:30 0:25 0:20 0:15 0:10 0:10

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 65, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:35
110, 24:00:00 24:00:00 24:00:00 6:10 1:20 0:40 0:25
115, 24:00:00 24:00:00 4:15 1:25 0:45 0:25 0:20
120, 24:00:00 3:35 1:25 0:45 0:30 0:20 0:15
125, 3:05 1:25 0:50 0:30 0:25 0:15 0:10
130, 1:25 0:50 0:35 0:25 0:20 0:15 0:10
135, 0:55 0:35 0:25 0:20 0:15 0:10 0:10
140, 0:40 0:30 0:20 0:15 0:15 0:10 0:05

Estudio de sobrecargas Página 20 de 198


Marzo 2017
Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 70, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:30
110, 24:00:00 24:00:00 24:00:00 6:00 1:15 0:35 0:20
115, 24:00:00 24:00:00 4:10 1:20 0:40 0:25 0:15
120, 24:00:00 3:30 1:20 0:45 0:25 0:20 0:10
125, 3:00 1:20 0:45 0:30 0:20 0:15 0:10
130, 1:20 0:50 0:30 0:25 0:15 0:10 0:10
135, 0:50 0:35 0:25 0:20 0:15 0:10 0:05
140, 0:35 0:25 0:20 0:15 0:10 0:10 0:05

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 75, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:25
110, 24:00:00 24:00:00 24:00:00 5:55 1:05 0:30 0:15
115, 24:00:00 24:00:00 4:05 1:10 0:35 0:20 0:15
120, 24:00:00 3:20 1:15 0:40 0:25 0:15 0:10
125, 2:55 1:15 0:45 0:25 0:20 0:10 0:10
130, 1:15 0:45 0:30 0:20 0:15 0:10 0:05
135, 0:45 0:30 0:25 0:15 0:10 0:10 0:05
140, 0:35 0:25 0:20 0:15 0:10 0:05 0:05

Estudio de sobrecargas Página 21 de 198


Marzo 2017
Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 80, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:40
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50 0:20
110, 24:00:00 24:00:00 24:00:00 5:45 1:00 0:25 0:15
115, 24:00:00 24:00:00 3:55 1:05 0:30 0:15 0:10
120, 24:00:00 3:15 1:10 0:35 0:20 0:15 0:05
125, 2:50 1:10 0:40 0:25 0:15 0:10 0:05
130, 1:10 0:40 0:25 0:20 0:10 0:10 0:05
135, 0:45 0:30 0:20 0:15 0:10 0:05 0:05
140, 0:30 0:25 0:15 0:10 0:10 0:05 0:05

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 85, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:30
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:40 0:15
110, 24:00:00 24:00:00 24:00:00 5:30 0:50 0:20 0:10
115, 24:00:00 24:00:00 3:45 0:55 0:25 0:15 0:05
120, 24:00:00 3:05 1:00 0:30 0:15 0:10 0:05
125, 2:40 1:05 0:35 0:20 0:15 0:10 0:05
130, 1:05 0:35 0:25 0:15 0:10 0:05 0:05
135, 0:40 0:25 0:20 0:10 0:10 0:05 0:00
140, 0:30 0:20 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 22 de 198


Marzo 2017
Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 90, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:30 0:05
110, 24:00:00 24:00:00 24:00:00 5:15 0:40 0:15 0:05
115, 24:00:00 24:00:00 3:35 0:45 0:20 0:10 0:00
120, 24:00:00 2:55 0:55 0:25 0:15 0:05 0:00
125, 2:35 0:55 0:30 0:15 0:10 0:05 0:00
130, 1:00 0:35 0:20 0:15 0:05 0:05 0:00
135, 0:35 0:25 0:15 0:10 0:05 0:05 0:00
140, 0:25 0:20 0:10 0:10 0:05 0:00 0:00

Cuadro de carga

Transformador SE Chocalán T1 T-46500 Grado de carga inicial de 95, %


Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15 0:00
110, 24:00:00 24:00:00 24:00:00 5:00 0:25 0:05 0:00
115, 24:00:00 24:00:00 3:20 0:35 0:15 0:05 0:00
120, 24:00:00 2:45 0:45 0:20 0:10 0:00 0:00
125, 2:25 0:50 0:25 0:15 0:05 0:00 0:00
130, 0:55 0:30 0:15 0:10 0:05 0:00 0:00
135, 0:30 0:20 0:10 0:05 0:05 0:00 0:00
140, 0:20 0:15 0:10 0:05 0:05 0:00 0:00

Estudio de sobrecargas Página 23 de 198


Marzo 2017
1.5. SE EL MAITÉN T-47600 T1 ID18969
Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:45
125, 24:00:00 24:00:00 24:00:00 2:20 1:15 0:50 0:30
130, 24:00:00 24:00:00 2:25 1:25 0:55 0:35 0:25
135, 24:00:00 2:30 1:30 0:55 0:40 0:30 0:20
140, 2:30 1:30 1:00 0:45 0:30 0:25 0:20

Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05 0:40
125, 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45 0:30
130, 24:00:00 24:00:00 2:20 1:20 0:50 0:35 0:25
135, 24:00:00 2:25 1:25 0:55 0:40 0:25 0:20
140, 2:25 1:30 1:00 0:40 0:30 0:25 0:15

Estudio de sobrecargas Página 24 de 198


Marzo 2017
Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35
125, 24:00:00 24:00:00 24:00:00 2:15 1:10 0:45 0:30
130, 24:00:00 24:00:00 2:20 1:15 0:50 0:30 0:25
135, 24:00:00 2:25 1:20 0:55 0:35 0:25 0:20
140, 2:25 1:25 0:55 0:40 0:30 0:20 0:15

Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35
125, 24:00:00 24:00:00 24:00:00 2:10 1:05 0:40 0:25
130, 24:00:00 24:00:00 2:15 1:15 0:45 0:30 0:20
135, 24:00:00 2:20 1:20 0:50 0:35 0:25 0:15
140, 2:20 1:25 0:55 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 25 de 198


Marzo 2017
Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30
125, 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35 0:25
130, 24:00:00 24:00:00 2:10 1:10 0:40 0:25 0:20
135, 24:00:00 2:15 1:15 0:45 0:30 0:20 0:15
140, 2:15 1:20 0:50 0:35 0:25 0:20 0:15

Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:30
125, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35 0:20
130, 24:00:00 24:00:00 2:05 1:05 0:40 0:25 0:15
135, 24:00:00 2:10 1:10 0:45 0:30 0:20 0:15
140, 2:15 1:15 0:50 0:30 0:25 0:15 0:10

Estudio de sobrecargas Página 26 de 198


Marzo 2017
Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25
125, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30 0:20
130, 24:00:00 24:00:00 2:00 1:00 0:35 0:20 0:15
135, 24:00:00 2:05 1:05 0:40 0:25 0:15 0:10
140, 2:10 1:10 0:45 0:30 0:20 0:15 0:10

Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40 0:20
125, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:25 0:15
130, 24:00:00 24:00:00 1:55 0:55 0:30 0:20 0:10
135, 24:00:00 2:00 1:00 0:35 0:25 0:15 0:10
140, 2:05 1:10 0:40 0:25 0:20 0:10 0:10

Estudio de sobrecargas Página 27 de 198


Marzo 2017
Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30 0:15
125, 24:00:00 24:00:00 24:00:00 1:35 0:40 0:20 0:10
130, 24:00:00 24:00:00 1:45 0:50 0:25 0:15 0:10
135, 24:00:00 1:55 0:55 0:30 0:20 0:10 0:05
140, 2:00 1:00 0:35 0:25 0:15 0:10 0:05

Cuadro de carga
ID18969 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE EL Maitén T1 T-47600 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55 0:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:25 0:10
125, 24:00:00 24:00:00 24:00:00 1:30 0:35 0:15 0:05
130, 24:00:00 24:00:00 1:40 0:45 0:20 0:10 0:05
135, 24:00:00 1:45 0:50 0:30 0:15 0:10 0:05
140, 1:50 0:55 0:35 0:20 0:15 0:05 0:05

Estudio de sobrecargas Página 28 de 198


Marzo 2017
1.6. SE EL MONTE T-47700 T1 ID 19680
Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30 2:05
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:50 2:20 1:30
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:40 1:10

Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:25 2:00
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:50 2:15 1:25
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:35 1:05

Estudio de sobrecargas Página 29 de 198


Marzo 2017
Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 2:00
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:45 2:15 1:25
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:35 1:05

Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:55
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:45 2:10 1:20
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:30 1:00

Estudio de sobrecargas Página 30 de 198


Marzo 2017
Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:50
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:40 2:05 1:15
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55

Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:40
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:30 1:55 1:05
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:20 0:50

Estudio de sobrecargas Página 31 de 198


Marzo 2017
Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 0, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:30
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:25 1:50 1:00
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:15 0:45

Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:25
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:15 1:45 0:55
140, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:10 0:40

Estudio de sobrecargas Página 32 de 198


Marzo 2017
Cuadro de carga
ID 19680 Rhona 10 MVA 69 24-13,8 KV ONAN 8 ONAF1 10
Transformador SE El Monte T1 T-47700 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:15
135, 24:00:00 24:00:00 24:00:00 24:00:00 6:10 1:35 0:50
140, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 1:00 0:35

Estudio de sobrecargas Página 33 de 198


Marzo 2017
1.7. SE EL PAICO T-47800 T1 ID XA19344001
Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:50 1:10
125, 24:00:00 24:00:00 24:00:00 3:35 2:00 1:15 0:55
130, 24:00:00 24:00:00 3:40 2:05 1:25 1:00 0:40
135, 24:00:00 3:40 2:10 1:30 1:05 0:45 0:35
140, 3:35 2:10 1:30 1:05 0:50 0:40 0:30

Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:45 1:05
125, 24:00:00 24:00:00 24:00:00 3:35 1:55 1:15 0:50
130, 24:00:00 24:00:00 3:40 2:00 1:20 0:55 0:40
135, 24:00:00 3:40 2:05 1:25 1:00 0:45 0:30
140, 3:35 2:10 1:30 1:05 0:50 0:35 0:25

Estudio de sobrecargas Página 34 de 198


Marzo 2017
Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:45 1:05
125, 24:00:00 24:00:00 24:00:00 3:30 1:50 1:10 0:45
130, 24:00:00 24:00:00 3:35 1:55 1:15 0:50 0:35
135, 24:00:00 3:35 2:00 1:20 1:00 0:40 0:30
140, 3:30 2:05 1:25 1:00 0:45 0:35 0:25

Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 3:25 1:45 1:05 0:45
130, 24:00:00 24:00:00 3:30 1:55 1:15 0:50 0:35
135, 24:00:00 3:30 2:00 1:20 0:55 0:40 0:25
140, 3:30 2:00 1:25 1:00 0:45 0:30 0:25

Estudio de sobrecargas Página 35 de 198


Marzo 2017
Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:30 0:55
125, 24:00:00 24:00:00 24:00:00 3:20 1:40 1:00 0:40
130, 24:00:00 24:00:00 3:25 1:50 1:10 0:45 0:30
135, 24:00:00 3:30 1:55 1:15 0:50 0:35 0:25
140, 3:25 2:00 1:20 0:55 0:40 0:30 0:20

Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:25 0:50
125, 24:00:00 24:00:00 24:00:00 3:15 1:35 0:55 0:35
130, 24:00:00 24:00:00 3:20 1:45 1:05 0:40 0:25
135, 24:00:00 3:25 1:50 1:10 0:45 0:30 0:20
140, 3:20 1:55 1:15 0:50 0:35 0:25 0:20

Estudio de sobrecargas Página 36 de 198


Marzo 2017
Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:55 1:20 0:40
125, 24:00:00 24:00:00 24:00:00 3:10 1:30 0:50 0:30
130, 24:00:00 24:00:00 3:15 1:40 1:00 0:35 0:25
135, 24:00:00 3:20 1:45 1:05 0:45 0:30 0:20
140, 3:15 1:50 1:10 0:50 0:35 0:25 0:15

Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:10 0:35
125, 24:00:00 24:00:00 24:00:00 3:00 1:25 0:45 0:25
130, 24:00:00 24:00:00 3:10 1:30 0:55 0:30 0:20
135, 24:00:00 3:10 1:40 1:00 0:40 0:25 0:15
140, 3:10 1:45 1:05 0:45 0:30 0:20 0:15

Estudio de sobrecargas Página 37 de 198


Marzo 2017
Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:00 0:30
125, 24:00:00 24:00:00 24:00:00 2:55 1:15 0:35 0:20
130, 24:00:00 24:00:00 3:00 1:25 0:45 0:25 0:15
135, 24:00:00 3:05 1:35 0:55 0:35 0:20 0:10
140, 3:05 1:40 1:00 0:40 0:25 0:15 0:10

Cuadro de carga
ID XA19344001 Trafo 20 MVA 66 13,8 KV ONAN 16 ONAF1 20
Transformador SE El Paico T1 T-47800 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:50 0:20
125, 24:00:00 24:00:00 24:00:00 2:40 1:05 0:30 0:15
130, 24:00:00 24:00:00 2:55 1:15 0:40 0:20 0:10
135, 24:00:00 3:00 1:25 0:45 0:25 0:15 0:10
140, 3:00 1:30 0:55 0:35 0:20 0:10 0:05

Estudio de sobrecargas Página 38 de 198


Marzo 2017
1.8. SE LA ESPERANZA T-48500 T1 ID 40745
Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55
125, 24:00:00 24:00:00 24:00:00 2:35 1:35 1:00 0:40
130, 24:00:00 24:00:00 2:40 1:40 1:05 0:45 0:30
135, 24:00:00 2:40 1:40 1:10 0:50 0:35 0:25
140, 2:40 1:45 1:15 0:55 0:40 0:30 0:25

Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:25 0:50
125, 24:00:00 24:00:00 24:00:00 2:35 1:30 0:55 0:40
130, 24:00:00 24:00:00 2:40 1:35 1:05 0:45 0:30
135, 24:00:00 2:40 1:40 1:05 0:45 0:35 0:25
140, 2:40 1:40 1:10 0:50 0:40 0:30 0:20

Estudio de sobrecargas Página 39 de 198


Marzo 2017
Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50
125, 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55 0:35
130, 24:00:00 24:00:00 2:35 1:30 1:00 0:40 0:30
135, 24:00:00 2:35 1:35 1:05 0:45 0:30 0:25
140, 2:35 1:40 1:10 0:50 0:35 0:25 0:20

Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:15 0:45
125, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:35
130, 24:00:00 24:00:00 2:30 1:30 0:55 0:40 0:25
135, 24:00:00 2:30 1:35 1:00 0:40 0:30 0:20
140, 2:30 1:35 1:05 0:45 0:35 0:25 0:20

Estudio de sobrecargas Página 40 de 198


Marzo 2017
Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:10 0:40
125, 24:00:00 24:00:00 24:00:00 2:20 1:15 0:45 0:30
130, 24:00:00 24:00:00 2:25 1:25 0:50 0:35 0:25
135, 24:00:00 2:30 1:30 1:00 0:40 0:25 0:20
140, 2:30 1:30 1:00 0:45 0:30 0:20 0:15

Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35
125, 24:00:00 24:00:00 24:00:00 2:15 1:10 0:40 0:25
130, 24:00:00 24:00:00 2:20 1:20 0:50 0:30 0:20
135, 24:00:00 2:25 1:25 0:55 0:35 0:25 0:15
140, 2:25 1:30 1:00 0:40 0:30 0:20 0:15

Estudio de sobrecargas Página 41 de 198


Marzo 2017
Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:55 0:30
125, 24:00:00 24:00:00 24:00:00 2:10 1:05 0:35 0:20
130, 24:00:00 24:00:00 2:15 1:15 0:45 0:25 0:15
135, 24:00:00 2:20 1:20 0:50 0:30 0:20 0:15
140, 2:20 1:25 0:55 0:35 0:25 0:15 0:10

Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:25
125, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:30 0:20
130, 24:00:00 24:00:00 2:10 1:05 0:40 0:25 0:15
135, 24:00:00 2:15 1:15 0:45 0:30 0:20 0:10
140, 2:15 1:20 0:50 0:35 0:20 0:15 0:10

Estudio de sobrecargas Página 42 de 198


Marzo 2017
Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:40 0:20
125, 24:00:00 24:00:00 24:00:00 1:55 0:50 0:25 0:15
130, 24:00:00 24:00:00 2:00 1:00 0:35 0:20 0:10
135, 24:00:00 2:05 1:10 0:40 0:25 0:15 0:10
140, 2:10 1:15 0:45 0:30 0:20 0:10 0:05

Cuadro de carga
ID 40745 Rhona 12 MVA 66 23-13,2 KV ONAN 10 ONAF1 12
Transformador SE La Esperanza T1 T-48500 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:30 0:15
125, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:20 0:10
130, 24:00:00 24:00:00 1:55 0:55 0:25 0:15 0:05
135, 24:00:00 2:00 1:00 0:35 0:20 0:10 0:05
140, 2:00 1:05 0:40 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 43 de 198


Marzo 2017
1.9. SE LA MANGA T-48600 T1 ID 23018
Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:40 0:25
115, 24:00:00 24:00:00 6:10 1:25 0:45 0:30 0:20
120, 24:00:00 4:10 1:25 0:50 0:30 0:25 0:15
125, 3:25 1:25 0:50 0:35 0:25 0:20 0:15
130, 1:25 0:50 0:35 0:25 0:20 0:15 0:10
135, 0:50 0:35 0:30 0:20 0:15 0:15 0:10
140, 0:40 0:30 0:25 0:20 0:15 0:10 0:10

Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:40 0:25
115, 24:00:00 24:00:00 6:05 1:25 0:45 0:30 0:20
120, 24:00:00 4:05 1:25 0:45 0:30 0:20 0:15
125, 3:20 1:25 0:50 0:30 0:25 0:15 0:15
130, 1:20 0:50 0:35 0:25 0:20 0:15 0:10
135, 0:50 0:35 0:25 0:20 0:15 0:15 0:10
140, 0:35 0:30 0:20 0:15 0:15 0:10 0:10

Estudio de sobrecargas Página 44 de 198


Marzo 2017
Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:35 0:25
115, 24:00:00 24:00:00 6:05 1:20 0:40 0:25 0:20
120, 24:00:00 4:05 1:20 0:45 0:30 0:20 0:15
125, 3:20 1:20 0:45 0:30 0:20 0:15 0:10
130, 1:20 0:45 0:30 0:25 0:20 0:15 0:10
135, 0:50 0:35 0:25 0:20 0:15 0:10 0:10
140, 0:35 0:25 0:20 0:15 0:15 0:10 0:10

Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:35 0:20
115, 24:00:00 24:00:00 6:00 1:15 0:40 0:25 0:15
120, 24:00:00 4:00 1:15 0:40 0:25 0:20 0:15
125, 3:15 1:15 0:45 0:30 0:20 0:15 0:10
130, 1:15 0:45 0:30 0:20 0:15 0:10 0:10
135, 0:45 0:30 0:25 0:20 0:15 0:10 0:10
140, 0:35 0:25 0:20 0:15 0:10 0:10 0:05

Estudio de sobrecargas Página 45 de 198


Marzo 2017
Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:30 0:20
115, 24:00:00 24:00:00 5:55 1:10 0:35 0:20 0:15
120, 24:00:00 3:55 1:10 0:40 0:25 0:15 0:10
125, 3:10 1:15 0:40 0:25 0:20 0:15 0:10
130, 1:15 0:40 0:30 0:20 0:15 0:10 0:10
135, 0:45 0:30 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:25 0:20 0:15 0:10 0:10 0:05

Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:25 0:15
115, 24:00:00 24:00:00 5:45 1:05 0:30 0:20 0:10
120, 24:00:00 3:50 1:05 0:35 0:20 0:15 0:10
125, 3:05 1:10 0:35 0:25 0:15 0:10 0:05
130, 1:10 0:40 0:25 0:20 0:15 0:10 0:05
135, 0:40 0:30 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:20 0:15 0:15 0:10 0:05 0:05

Estudio de sobrecargas Página 46 de 198


Marzo 2017
Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45 0:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:50 0:25 0:10
115, 24:00:00 24:00:00 5:40 1:00 0:25 0:15 0:10
120, 24:00:00 3:40 1:00 0:30 0:20 0:10 0:05
125, 3:00 1:05 0:35 0:20 0:15 0:10 0:05
130, 1:05 0:35 0:25 0:15 0:10 0:05 0:05
135, 0:40 0:25 0:20 0:15 0:10 0:05 0:05
140, 0:30 0:20 0:15 0:10 0:10 0:05 0:05

Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:25
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:45 0:20 0:10
115, 24:00:00 24:00:00 5:30 0:50 0:25 0:10 0:05
120, 24:00:00 3:35 0:55 0:25 0:15 0:10 0:05
125, 2:55 1:00 0:30 0:20 0:10 0:05 0:05
130, 1:00 0:35 0:20 0:15 0:10 0:05 0:00
135, 0:35 0:25 0:15 0:10 0:05 0:05 0:00
140, 0:25 0:20 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 47 de 198


Marzo 2017
Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:25 0:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:15 0:05
115, 24:00:00 24:00:00 5:15 0:45 0:20 0:10 0:00
120, 24:00:00 3:25 0:50 0:25 0:10 0:05 0:00
125, 2:45 0:50 0:25 0:15 0:10 0:05 0:00
130, 0:55 0:30 0:20 0:10 0:05 0:05 0:00
135, 0:30 0:20 0:15 0:10 0:05 0:00 0:00
140, 0:25 0:15 0:10 0:05 0:05 0:00 0:00

Cuadro de carga
ID 23018 Rhona 10 MVA 66 13,8 KV ONAN 8 ONAF1 10
Transformador SE La Manga T1 T-48600 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15 0:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:25 0:05 0:00
115, 24:00:00 24:00:00 5:00 0:35 0:15 0:05 0:00
120, 24:00:00 3:10 0:40 0:20 0:10 0:00 0:00
125, 2:35 0:45 0:20 0:10 0:05 0:00 0:00
130, 0:50 0:25 0:15 0:10 0:05 0:00 0:00
135, 0:30 0:20 0:10 0:05 0:05 0:00 0:00
140, 0:20 0:15 0:10 0:05 0:00 0:00 0:00

Estudio de sobrecargas Página 48 de 198


Marzo 2017
1.10. SE LAS ARAÑAS T-48900 T3 ID40163
Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55
130, 24:00:00 24:00:00 24:00:00 2:35 1:30 1:00 0:40
135, 24:00:00 24:00:00 2:40 1:40 1:05 0:45 0:35
140, 24:00:00 2:45 1:45 1:10 0:50 0:35 0:30

Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
130, 24:00:00 24:00:00 24:00:00 2:30 1:30 1:00 0:40
135, 24:00:00 24:00:00 2:40 1:35 1:05 0:45 0:30
140, 24:00:00 2:40 1:40 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 49 de 198


Marzo 2017
Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
130, 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55 0:35
135, 24:00:00 24:00:00 2:35 1:35 1:00 0:40 0:30
140, 24:00:00 2:40 1:40 1:05 0:45 0:35 0:25

Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45
130, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:35
135, 24:00:00 24:00:00 2:30 1:30 1:00 0:40 0:25
140, 24:00:00 2:35 1:35 1:05 0:45 0:30 0:20

Estudio de sobrecargas Página 50 de 198


Marzo 2017
Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 1:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40
130, 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50 0:30
135, 24:00:00 24:00:00 2:25 1:25 0:55 0:35 0:25
140, 24:00:00 2:35 1:30 1:00 0:40 0:30 0:20

Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 9:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05 0:35
130, 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45 0:30
135, 24:00:00 24:00:00 2:25 1:20 0:50 0:35 0:20
140, 24:00:00 2:30 1:25 0:55 0:40 0:25 0:20

Estudio de sobrecargas Página 51 de 198


Marzo 2017
Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 8:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 1:00 0:30
130, 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40 0:25
135, 24:00:00 24:00:00 2:20 1:15 0:45 0:30 0:20
140, 24:00:00 2:25 1:25 0:50 0:35 0:25 0:15

Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 8:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:30
130, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35 0:20
135, 24:00:00 24:00:00 2:10 1:10 0:40 0:25 0:15
140, 24:00:00 2:20 1:20 0:50 0:30 0:20 0:15

Estudio de sobrecargas Página 52 de 198


Marzo 2017
Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 8:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25
130, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30 0:15
135, 24:00:00 24:00:00 2:05 1:05 0:35 0:20 0:15
140, 24:00:00 2:15 1:15 0:45 0:25 0:15 0:10

Cuadro de carga
ID40163 Rhona 12 MVA 66 25-15 KV ONAN 10 ONAF1 12
Transformador SE Las Arañas T3 T-48900 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 8:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:35 0:15
130, 24:00:00 24:00:00 24:00:00 1:45 0:50 0:25 0:10
135, 24:00:00 24:00:00 2:00 1:00 0:30 0:20 0:10
140, 24:00:00 2:05 1:05 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 53 de 198


Marzo 2017
1.11. SE LAS ARAÑAS T-49000 ATR1 ID ET91373
Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:25 2:15 1:30 1:00
130, 24:00:00 24:00:00 4:20 2:20 1:35 1:10 0:50
135, 24:00:00 4:15 2:20 1:40 1:10 0:55 0:40
140, 4:05 2:25 1:45 1:15 1:00 0:45 0:35

Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:20 2:10 1:25 1:00
130, 24:00:00 24:00:00 4:20 2:15 1:30 1:05 0:45
135, 24:00:00 4:10 2:20 1:35 1:10 0:50 0:40
140, 4:00 2:20 1:40 1:15 0:55 0:40 0:30

Estudio de sobrecargas Página 54 de 198


Marzo 2017
Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15
125, 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20 0:55
130, 24:00:00 24:00:00 4:15 2:10 1:30 1:00 0:45
135, 24:00:00 4:10 2:15 1:35 1:05 0:50 0:35
140, 4:00 2:20 1:35 1:10 0:55 0:40 0:30

Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:55 1:10
125, 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15 0:50
130, 24:00:00 24:00:00 4:10 2:10 1:25 0:55 0:40
135, 24:00:00 4:05 2:10 1:30 1:05 0:45 0:30
140, 3:55 2:15 1:35 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 55 de 198


Marzo 2017
Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05
125, 24:00:00 24:00:00 24:00:00 4:05 1:55 1:15 0:45
130, 24:00:00 24:00:00 4:05 2:05 1:20 0:55 0:35
135, 24:00:00 4:00 2:10 1:25 1:00 0:40 0:30
140, 3:50 2:10 1:30 1:05 0:45 0:35 0:25

Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05 0:40
130, 24:00:00 24:00:00 4:00 2:00 1:15 0:50 0:30
135, 24:00:00 3:55 2:05 1:20 0:55 0:40 0:25
140, 3:50 2:05 1:25 1:00 0:45 0:30 0:20

Estudio de sobrecargas Página 56 de 198


Marzo 2017
Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:35 0:50
125, 24:00:00 24:00:00 24:00:00 3:55 1:45 1:00 0:35
130, 24:00:00 24:00:00 3:55 1:55 1:10 0:45 0:30
135, 24:00:00 3:50 2:00 1:15 0:50 0:35 0:20
140, 3:45 2:00 1:20 0:55 0:40 0:25 0:20

Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 3:45 1:40 0:55 0:30
130, 24:00:00 24:00:00 3:50 1:45 1:05 0:40 0:25
135, 24:00:00 3:45 1:55 1:10 0:45 0:30 0:20
140, 3:40 1:55 1:15 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 57 de 198


Marzo 2017
Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:15 0:35
125, 24:00:00 24:00:00 24:00:00 3:40 1:30 0:45 0:25
130, 24:00:00 24:00:00 3:40 1:40 0:55 0:30 0:20
135, 24:00:00 3:40 1:45 1:05 0:40 0:25 0:15
140, 3:30 1:50 1:10 0:45 0:30 0:20 0:10

Cuadro de carga
ID ET91373 Crompton G. 50MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR1 T-49000 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:05 0:25
125, 24:00:00 24:00:00 24:00:00 3:30 1:20 0:40 0:20
130, 24:00:00 24:00:00 3:35 1:30 0:50 0:25 0:15
135, 24:00:00 3:30 1:40 0:55 0:35 0:20 0:10
140, 3:25 1:45 1:05 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 58 de 198


Marzo 2017
1.12. SE LAS ARAÑAS T-49100 ATR2 IDET91371
Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:25 2:15 1:30 1:00
130, 24:00:00 24:00:00 4:20 2:20 1:35 1:10 0:50
135, 24:00:00 4:15 2:20 1:40 1:10 0:55 0:40
140, 4:05 2:25 1:45 1:15 1:00 0:45 0:35

Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:20 2:10 1:25 1:00
130, 24:00:00 24:00:00 4:20 2:15 1:30 1:05 0:45
135, 24:00:00 4:10 2:20 1:35 1:10 0:50 0:40
140, 4:00 2:20 1:40 1:15 0:55 0:40 0:30

Estudio de sobrecargas Página 59 de 198


Marzo 2017
Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15
125, 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20 0:55
130, 24:00:00 24:00:00 4:15 2:10 1:30 1:00 0:45
135, 24:00:00 4:10 2:15 1:35 1:05 0:50 0:35
140, 4:00 2:20 1:35 1:10 0:55 0:40 0:30

Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:55 1:10
125, 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15 0:50
130, 24:00:00 24:00:00 4:10 2:10 1:25 0:55 0:40
135, 24:00:00 4:05 2:10 1:30 1:05 0:45 0:30
140, 3:55 2:15 1:35 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 60 de 198


Marzo 2017
Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05
125, 24:00:00 24:00:00 24:00:00 4:05 1:55 1:15 0:45
130, 24:00:00 24:00:00 4:05 2:05 1:20 0:55 0:35
135, 24:00:00 4:00 2:10 1:25 1:00 0:40 0:30
140, 3:50 2:10 1:30 1:05 0:45 0:35 0:25

Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05 0:40
130, 24:00:00 24:00:00 4:00 2:00 1:15 0:50 0:30
135, 24:00:00 3:55 2:05 1:20 0:55 0:40 0:25
140, 3:50 2:05 1:25 1:00 0:45 0:30 0:20

Estudio de sobrecargas Página 61 de 198


Marzo 2017
Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:35 0:50
125, 24:00:00 24:00:00 24:00:00 3:55 1:45 1:00 0:35
130, 24:00:00 24:00:00 3:55 1:55 1:10 0:45 0:30
135, 24:00:00 3:50 2:00 1:15 0:50 0:35 0:20
140, 3:45 2:00 1:20 0:55 0:40 0:25 0:20

Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 3:45 1:40 0:55 0:30
130, 24:00:00 24:00:00 3:50 1:45 1:05 0:40 0:25
135, 24:00:00 3:45 1:55 1:10 0:45 0:30 0:20
140, 3:40 1:55 1:15 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 62 de 198


Marzo 2017
Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:15 0:35
125, 24:00:00 24:00:00 24:00:00 3:40 1:30 0:45 0:25
130, 24:00:00 24:00:00 3:40 1:40 0:55 0:30 0:20
135, 24:00:00 3:40 1:45 1:05 0:40 0:25 0:15
140, 3:30 1:50 1:10 0:45 0:30 0:20 0:10

Cuadro de carga
IDET91371 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Las Arañas ATR2 T-49100 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:05 0:25
125, 24:00:00 24:00:00 24:00:00 3:30 1:20 0:40 0:20
130, 24:00:00 24:00:00 3:35 1:30 0:50 0:25 0:15
135, 24:00:00 3:30 1:40 0:55 0:35 0:20 0:10
140, 3:25 1:45 1:05 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 63 de 198


Marzo 2017
1.13. SE LEYDA T-49200 T1 ID18954
Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:35 1:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 2:00 1:15
120, 24:00:00 24:00:00 24:00:00 4:50 2:10 1:20 0:55
125, 24:00:00 24:00:00 4:40 2:15 1:25 1:00 0:40
130, 24:00:00 4:25 2:15 1:30 1:05 0:45 0:35
135, 4:05 2:15 1:35 1:10 0:50 0:35 0:30
140, 2:15 1:35 1:10 0:55 0:40 0:30 0:25

Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 2:00 1:10
120, 24:00:00 24:00:00 24:00:00 4:50 2:05 1:20 0:50
125, 24:00:00 24:00:00 4:35 2:10 1:25 0:55 0:40
130, 24:00:00 4:20 2:15 1:30 1:00 0:45 0:30
135, 4:05 2:15 1:30 1:05 0:50 0:35 0:25
140, 2:15 1:35 1:10 0:50 0:40 0:30 0:20

Estudio de sobrecargas Página 64 de 198


Marzo 2017
Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:25 1:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:55 1:05
120, 24:00:00 24:00:00 24:00:00 4:45 2:00 1:15 0:45
125, 24:00:00 24:00:00 4:35 2:05 1:20 0:55 0:35
130, 24:00:00 4:15 2:10 1:25 1:00 0:40 0:30
135, 4:00 2:10 1:30 1:05 0:45 0:35 0:25
140, 2:10 1:30 1:05 0:50 0:35 0:25 0:20

Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 1:50 1:00
120, 24:00:00 24:00:00 24:00:00 4:40 1:55 1:10 0:45
125, 24:00:00 24:00:00 4:30 2:00 1:15 0:50 0:35
130, 24:00:00 4:15 2:05 1:20 0:55 0:40 0:25
135, 3:55 2:10 1:25 1:00 0:40 0:30 0:20
140, 2:10 1:30 1:05 0:45 0:35 0:25 0:20

Estudio de sobrecargas Página 65 de 198


Marzo 2017
Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:40 0:55
120, 24:00:00 24:00:00 24:00:00 4:35 1:50 1:05 0:40
125, 24:00:00 24:00:00 4:25 1:55 1:10 0:45 0:30
130, 24:00:00 4:10 2:00 1:15 0:50 0:35 0:25
135, 3:55 2:05 1:20 0:55 0:40 0:25 0:20
140, 2:05 1:25 1:00 0:45 0:30 0:25 0:15

Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:25 1:35 0:50
120, 24:00:00 24:00:00 24:00:00 4:25 1:45 1:00 0:35
125, 24:00:00 24:00:00 4:20 1:50 1:05 0:40 0:25
130, 24:00:00 4:05 1:55 1:10 0:45 0:30 0:20
135, 3:50 2:00 1:15 0:50 0:35 0:25 0:15
140, 2:00 1:20 0:55 0:40 0:30 0:20 0:15

Estudio de sobrecargas Página 66 de 198


Marzo 2017
Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:25 0:40
120, 24:00:00 24:00:00 24:00:00 4:20 1:35 0:50 0:30
125, 24:00:00 24:00:00 4:10 1:45 1:00 0:35 0:20
130, 24:00:00 4:00 1:50 1:05 0:40 0:25 0:15
135, 3:45 1:55 1:10 0:45 0:30 0:20 0:15
140, 1:55 1:15 0:50 0:35 0:25 0:15 0:10

Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:15 0:35
120, 24:00:00 24:00:00 24:00:00 4:10 1:30 0:45 0:25
125, 24:00:00 24:00:00 4:05 1:35 0:55 0:30 0:15
130, 24:00:00 3:50 1:45 1:00 0:35 0:20 0:15
135, 3:40 1:50 1:05 0:40 0:25 0:20 0:10
140, 1:50 1:10 0:45 0:30 0:20 0:15 0:10

Estudio de sobrecargas Página 67 de 198


Marzo 2017
Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 0:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:05 0:25
120, 24:00:00 24:00:00 24:00:00 4:00 1:20 0:35 0:15
125, 24:00:00 24:00:00 3:55 1:30 0:45 0:25 0:15
130, 24:00:00 3:45 1:35 0:55 0:30 0:20 0:10
135, 3:30 1:40 1:00 0:35 0:25 0:15 0:10
140, 1:45 1:05 0:40 0:30 0:20 0:10 0:05

Cuadro de carga
ID18954 Rhona 12,5 MVA 115 13,8 KV ONAN 10 ONAF 12.5
Transformador SE Leyda T1 T-49200 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 12,5 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 0:50 0:15
120, 24:00:00 24:00:00 24:00:00 3:50 1:05 0:25 0:10
125, 24:00:00 24:00:00 3:45 1:20 0:35 0:20 0:10
130, 24:00:00 3:35 1:30 0:45 0:25 0:15 0:05
135, 3:25 1:35 0:55 0:30 0:20 0:10 0:05
140, 1:40 1:00 0:35 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 68 de 198


Marzo 2017
1.14. SE MARCHIGÜE T-15400 T2 ID 7320054.0
Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05
125, 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15 0:50
130, 24:00:00 24:00:00 4:15 2:05 1:20 0:55 0:35
135, 24:00:00 4:15 2:10 1:25 1:00 0:40 0:30
140, 4:05 2:10 1:30 1:00 0:45 0:35 0:25

Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:45 1:05
125, 24:00:00 24:00:00 24:00:00 4:10 1:55 1:10 0:45
130, 24:00:00 24:00:00 4:15 2:00 1:15 0:50 0:35
135, 24:00:00 4:10 2:05 1:20 0:55 0:40 0:30
140, 4:00 2:10 1:25 1:00 0:45 0:30 0:25

Estudio de sobrecargas Página 69 de 198


Marzo 2017
Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 4:05 1:50 1:05 0:40
130, 24:00:00 24:00:00 4:10 2:00 1:15 0:50 0:35
135, 24:00:00 4:10 2:00 1:20 0:55 0:35 0:25
140, 4:00 2:05 1:25 1:00 0:40 0:30 0:20

Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:40 0:55
125, 24:00:00 24:00:00 24:00:00 4:00 1:45 1:05 0:40
130, 24:00:00 24:00:00 4:05 1:55 1:10 0:45 0:30
135, 24:00:00 4:05 2:00 1:15 0:50 0:35 0:25
140, 3:55 2:05 1:20 0:55 0:40 0:30 0:20

Estudio de sobrecargas Página 70 de 198


Marzo 2017
Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:30 0:50
125, 24:00:00 24:00:00 24:00:00 3:55 1:40 1:00 0:35
130, 24:00:00 24:00:00 4:00 1:50 1:05 0:40 0:25
135, 24:00:00 4:00 1:55 1:10 0:45 0:30 0:20
140, 3:55 2:00 1:15 0:50 0:35 0:25 0:20

Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 3:50 1:35 0:55 0:30
130, 24:00:00 24:00:00 3:55 1:45 1:00 0:40 0:25
135, 24:00:00 3:55 1:50 1:05 0:45 0:30 0:20
140, 3:50 1:55 1:15 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 71 de 198


Marzo 2017
Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:20 0:40
125, 24:00:00 24:00:00 24:00:00 3:45 1:30 0:50 0:30
130, 24:00:00 24:00:00 3:50 1:40 0:55 0:35 0:20
135, 24:00:00 3:50 1:45 1:00 0:40 0:25 0:15
140, 3:45 1:50 1:10 0:45 0:30 0:20 0:15

Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:10 0:35
125, 24:00:00 24:00:00 24:00:00 3:35 1:25 0:40 0:25
130, 24:00:00 24:00:00 3:45 1:30 0:50 0:30 0:20
135, 24:00:00 3:45 1:40 0:55 0:35 0:20 0:15
140, 3:40 1:45 1:05 0:40 0:25 0:20 0:10

Estudio de sobrecargas Página 72 de 198


Marzo 2017
Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:00 0:25
125, 24:00:00 24:00:00 24:00:00 3:30 1:15 0:35 0:20
130, 24:00:00 24:00:00 3:40 1:25 0:45 0:25 0:15
135, 24:00:00 3:40 1:35 0:50 0:30 0:20 0:10
140, 3:35 1:40 1:00 0:35 0:25 0:15 0:10

Cuadro de carga
ID 7320054.0 Tusan 10 MVA 66 24-14,4 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T2 T-15400 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:50 0:20
125, 24:00:00 24:00:00 24:00:00 3:20 1:05 0:30 0:15
130, 24:00:00 24:00:00 3:30 1:15 0:35 0:20 0:10
135, 24:00:00 3:30 1:25 0:45 0:25 0:15 0:10
140, 3:25 1:35 0:50 0:30 0:20 0:10 0:05

Estudio de sobrecargas Página 73 de 198


Marzo 2017
1.15. SE MELIPILLA T-50200 T1 ID20590
Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:55 0:35
115, 24:00:00 24:00:00 5:10 1:45 1:00 0:40 0:25
120, 24:00:00 3:55 1:45 1:00 0:40 0:30 0:20
125, 3:20 1:40 1:05 0:45 0:30 0:25 0:20
130, 1:40 1:05 0:45 0:35 0:25 0:20 0:15
135, 1:05 0:45 0:35 0:25 0:20 0:15 0:15
140, 0:45 0:35 0:30 0:20 0:20 0:15 0:10

Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:55 0:30
115, 24:00:00 24:00:00 5:05 1:45 0:55 0:35 0:25
120, 24:00:00 3:50 1:40 1:00 0:40 0:25 0:20
125, 3:15 1:40 1:00 0:40 0:30 0:20 0:15
130, 1:35 1:00 0:45 0:30 0:25 0:20 0:15
135, 1:00 0:45 0:35 0:25 0:20 0:15 0:10
140, 0:45 0:35 0:25 0:20 0:15 0:15 0:10

Estudio de sobrecargas Página 74 de 198


Marzo 2017
Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:50 0:30
115, 24:00:00 24:00:00 5:00 1:40 0:55 0:35 0:20
120, 24:00:00 3:50 1:35 0:55 0:35 0:25 0:20
125, 3:15 1:35 1:00 0:40 0:25 0:20 0:15
130, 1:35 1:00 0:40 0:30 0:20 0:15 0:10
135, 1:00 0:40 0:30 0:25 0:20 0:15 0:10
140, 0:45 0:30 0:25 0:20 0:15 0:10 0:10

Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:45 0:25
115, 24:00:00 24:00:00 4:55 1:35 0:50 0:30 0:20
120, 24:00:00 3:45 1:35 0:50 0:35 0:25 0:15
125, 3:10 1:30 0:55 0:35 0:25 0:20 0:15
130, 1:30 0:55 0:40 0:25 0:20 0:15 0:10
135, 0:55 0:40 0:30 0:20 0:15 0:15 0:10
140, 0:40 0:30 0:25 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 75 de 198


Marzo 2017
Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:40 0:25
115, 24:00:00 24:00:00 4:50 1:30 0:45 0:25 0:15
120, 24:00:00 3:40 1:30 0:50 0:30 0:20 0:15
125, 3:05 1:25 0:50 0:35 0:25 0:15 0:10
130, 1:25 0:50 0:35 0:25 0:20 0:15 0:10
135, 0:55 0:35 0:25 0:20 0:15 0:10 0:10
140, 0:40 0:30 0:20 0:15 0:15 0:10 0:05

Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:35 0:20
115, 24:00:00 24:00:00 4:45 1:20 0:40 0:25 0:15
120, 24:00:00 3:30 1:20 0:45 0:25 0:15 0:10
125, 3:00 1:20 0:45 0:30 0:20 0:15 0:10
130, 1:20 0:50 0:30 0:20 0:15 0:10 0:05
135, 0:50 0:35 0:25 0:20 0:15 0:10 0:05
140, 0:35 0:25 0:20 0:15 0:10 0:10 0:05

Estudio de sobrecargas Página 76 de 198


Marzo 2017
Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:30 0:15
115, 24:00:00 24:00:00 4:35 1:15 0:35 0:20 0:10
120, 24:00:00 3:25 1:15 0:40 0:25 0:15 0:10
125, 2:50 1:15 0:40 0:25 0:15 0:10 0:05
130, 1:15 0:45 0:30 0:20 0:15 0:10 0:05
135, 0:45 0:30 0:20 0:15 0:10 0:05 0:05
140, 0:35 0:25 0:20 0:15 0:10 0:05 0:05

Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50 0:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:25 0:10
115, 24:00:00 24:00:00 4:25 1:05 0:30 0:15 0:05
120, 24:00:00 3:15 1:10 0:35 0:20 0:10 0:05
125, 2:45 1:10 0:35 0:25 0:15 0:10 0:05
130, 1:10 0:40 0:25 0:15 0:10 0:05 0:05
135, 0:40 0:30 0:20 0:15 0:10 0:05 0:00
140, 0:30 0:20 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 77 de 198


Marzo 2017
Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:20
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:45 0:15 0:05
115, 24:00:00 24:00:00 4:15 0:55 0:25 0:10 0:05
120, 24:00:00 3:05 1:00 0:30 0:15 0:05 0:00
125, 2:35 1:00 0:30 0:20 0:10 0:05 0:00
130, 1:05 0:35 0:20 0:15 0:10 0:05 0:00
135, 0:40 0:25 0:15 0:10 0:05 0:05 0:00
140, 0:25 0:20 0:15 0:10 0:05 0:00 0:00

Cuadro de carga
ID20590 Rhona 25 MVA 115 13,8 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla T1 T-50200 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:20 0:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:10 0:00
115, 24:00:00 24:00:00 4:00 0:40 0:15 0:05 0:00
120, 24:00:00 2:55 0:50 0:20 0:10 0:05 0:00
125, 2:25 0:55 0:25 0:15 0:05 0:00 0:00
130, 0:55 0:30 0:20 0:10 0:05 0:00 0:00
135, 0:35 0:20 0:15 0:10 0:05 0:00 0:00
140, 0:25 0:15 0:10 0:05 0:05 0:00 0:00

Estudio de sobrecargas Página 78 de 198


Marzo 2017
1.16. SE MELIPILLA T-50300 T2 IDXA1689A001
Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:20
130, 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:30 0:55
135, 24:00:00 24:00:00 24:00:00 3:30 1:40 1:00 0:40
140, 24:00:00 24:00:00 3:50 1:50 1:10 0:45 0:30

Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:15
130, 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:30 0:50
135, 24:00:00 24:00:00 24:00:00 3:25 1:40 1:00 0:40
140, 24:00:00 24:00:00 3:50 1:50 1:05 0:45 0:30

Estudio de sobrecargas Página 79 de 198


Marzo 2017
Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:15
130, 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:25 0:50
135, 24:00:00 24:00:00 24:00:00 3:25 1:35 0:55 0:35
140, 24:00:00 24:00:00 3:45 1:45 1:05 0:40 0:30

Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:10
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:55 1:20 0:45
135, 24:00:00 24:00:00 24:00:00 3:20 1:35 0:55 0:35
140, 24:00:00 24:00:00 3:45 1:45 1:00 0:40 0:30

Estudio de sobrecargas Página 80 de 198


Marzo 2017
Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:05
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:50 1:20 0:45
135, 24:00:00 24:00:00 24:00:00 3:15 1:30 0:50 0:30
140, 24:00:00 24:00:00 3:40 1:40 1:00 0:35 0:25

Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:00
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:15 0:40
135, 24:00:00 24:00:00 24:00:00 3:10 1:25 0:50 0:30
140, 24:00:00 24:00:00 3:35 1:35 0:55 0:35 0:25

Estudio de sobrecargas Página 81 de 198


Marzo 2017
Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:55
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:10 0:35
135, 24:00:00 24:00:00 24:00:00 3:05 1:20 0:45 0:25
140, 24:00:00 24:00:00 3:30 1:30 0:50 0:30 0:20

Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 0:50
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:05 0:30
135, 24:00:00 24:00:00 24:00:00 3:00 1:15 0:40 0:25
140, 24:00:00 24:00:00 3:25 1:25 0:45 0:30 0:20

Estudio de sobrecargas Página 82 de 198


Marzo 2017
Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:45
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:55 0:30
135, 24:00:00 24:00:00 24:00:00 2:55 1:10 0:35 0:20
140, 24:00:00 24:00:00 3:20 1:20 0:45 0:25 0:15

Cuadro de carga
IDXA1689A001 Trafo 50MVA 110 66 KV ONAN 40 ONAF1 50
Transformador SE Melipilla T2 T-50300 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:35
130, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 0:50 0:25
135, 24:00:00 24:00:00 24:00:00 2:45 1:00 0:30 0:15
140, 24:00:00 24:00:00 3:15 1:15 0:40 0:20 0:15

Estudio de sobrecargas Página 83 de 198


Marzo 2017
1.17. SE PORTEZUELO T-51800 T1 IDET91372
Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:25 2:15 1:30 1:00
130, 24:00:00 24:00:00 4:20 2:20 1:35 1:10 0:50
135, 24:00:00 4:15 2:20 1:40 1:10 0:55 0:40
140, 4:05 2:25 1:45 1:15 1:00 0:45 0:35

Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
125, 24:00:00 24:00:00 24:00:00 4:20 2:10 1:25 1:00
130, 24:00:00 24:00:00 4:20 2:15 1:30 1:05 0:45
135, 24:00:00 4:10 2:20 1:35 1:10 0:50 0:40
140, 4:00 2:20 1:40 1:15 0:55 0:40 0:30

Estudio de sobrecargas Página 84 de 198


Marzo 2017
Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15
125, 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20 0:55
130, 24:00:00 24:00:00 4:15 2:10 1:30 1:00 0:45
135, 24:00:00 4:10 2:15 1:35 1:05 0:50 0:35
140, 4:00 2:20 1:35 1:10 0:55 0:40 0:30

Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:55 1:10
125, 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15 0:50
130, 24:00:00 24:00:00 4:10 2:10 1:25 0:55 0:40
135, 24:00:00 4:05 2:10 1:30 1:05 0:45 0:30
140, 3:55 2:15 1:35 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 85 de 198


Marzo 2017
Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05
125, 24:00:00 24:00:00 24:00:00 4:05 1:55 1:15 0:45
130, 24:00:00 24:00:00 4:05 2:05 1:20 0:55 0:35
135, 24:00:00 4:00 2:10 1:25 1:00 0:40 0:30
140, 3:50 2:10 1:30 1:05 0:45 0:35 0:25

Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05 0:40
130, 24:00:00 24:00:00 4:00 2:00 1:15 0:50 0:30
135, 24:00:00 3:55 2:05 1:20 0:55 0:40 0:25
140, 3:50 2:05 1:25 1:00 0:45 0:30 0:20

Estudio de sobrecargas Página 86 de 198


Marzo 2017
Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:35 0:50
125, 24:00:00 24:00:00 24:00:00 3:55 1:45 1:00 0:35
130, 24:00:00 24:00:00 3:55 1:55 1:10 0:45 0:30
135, 24:00:00 3:50 2:00 1:15 0:50 0:35 0:20
140, 3:45 2:00 1:20 0:55 0:40 0:25 0:20

Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 3:45 1:40 0:55 0:30
130, 24:00:00 24:00:00 3:50 1:45 1:05 0:40 0:25
135, 24:00:00 3:45 1:55 1:10 0:45 0:30 0:20
140, 3:40 1:55 1:15 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 87 de 198


Marzo 2017
Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:15 0:35
125, 24:00:00 24:00:00 24:00:00 3:40 1:30 0:45 0:25
130, 24:00:00 24:00:00 3:40 1:40 0:55 0:30 0:20
135, 24:00:00 3:40 1:45 1:05 0:40 0:25 0:15
140, 3:30 1:50 1:10 0:45 0:30 0:20 0:10

Cuadro de carga
ID ET91372 Crompton G. 50 MVA 110 66 KV ONAN 40 ONAF 50
Transformador SE Portezuelo T1 T-51800 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 50, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:05 0:25
125, 24:00:00 24:00:00 24:00:00 3:30 1:20 0:40 0:20
130, 24:00:00 24:00:00 3:35 1:30 0:50 0:25 0:15
135, 24:00:00 3:30 1:40 0:55 0:35 0:20 0:10
140, 3:25 1:45 1:05 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 88 de 198


Marzo 2017
1.18. SE PORTEZUELO T-52900 T3 ID20591
Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:25 2:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 5:00 2:10 1:20
125, 24:00:00 24:00:00 24:00:00 5:30 2:15 1:30 1:00
130, 24:00:00 24:00:00 5:40 2:25 1:35 1:05 0:45
135, 24:00:00 5:30 2:30 1:40 1:10 0:50 0:40
140, 5:10 2:30 1:45 1:15 0:55 0:45 0:30

Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:55 2:05 1:15
125, 24:00:00 24:00:00 24:00:00 5:25 2:15 1:25 0:55
130, 24:00:00 24:00:00 5:35 2:20 1:30 1:05 0:45
135, 24:00:00 5:25 2:25 1:40 1:10 0:50 0:35
140, 5:10 2:30 1:40 1:15 0:55 0:40 0:30

Estudio de sobrecargas Página 89 de 198


Marzo 2017
Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:55 2:00 1:15
125, 24:00:00 24:00:00 24:00:00 5:20 2:10 1:20 0:55
130, 24:00:00 24:00:00 5:30 2:15 1:30 1:00 0:40
135, 24:00:00 5:25 2:25 1:35 1:05 0:45 0:35
140, 5:05 2:25 1:40 1:10 0:50 0:40 0:30

Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:55 1:10
125, 24:00:00 24:00:00 24:00:00 5:15 2:05 1:15 0:50
130, 24:00:00 24:00:00 5:30 2:15 1:25 0:55 0:40
135, 24:00:00 5:20 2:20 1:30 1:00 0:45 0:30
140, 5:00 2:25 1:35 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 90 de 198


Marzo 2017
Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:50 1:05
125, 24:00:00 24:00:00 24:00:00 5:10 2:00 1:10 0:45
130, 24:00:00 24:00:00 5:25 2:10 1:20 0:50 0:35
135, 24:00:00 5:15 2:15 1:25 1:00 0:40 0:30
140, 5:00 2:20 1:30 1:05 0:45 0:30 0:25

Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 1:45 0:55
125, 24:00:00 24:00:00 24:00:00 5:05 1:55 1:05 0:40
130, 24:00:00 24:00:00 5:20 2:05 1:15 0:50 0:30
135, 24:00:00 5:10 2:10 1:20 0:55 0:35 0:25
140, 4:55 2:15 1:30 1:00 0:40 0:30 0:20

Estudio de sobrecargas Página 91 de 198


Marzo 2017
Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:35 0:50
125, 24:00:00 24:00:00 24:00:00 5:00 1:50 1:00 0:35
130, 24:00:00 24:00:00 5:15 2:00 1:10 0:45 0:25
135, 24:00:00 5:05 2:05 1:15 0:50 0:35 0:20
140, 4:50 2:10 1:25 0:55 0:40 0:25 0:20

Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:30 0:45
125, 24:00:00 24:00:00 24:00:00 4:55 1:40 0:55 0:30
130, 24:00:00 24:00:00 5:05 1:50 1:05 0:40 0:25
135, 24:00:00 5:00 2:00 1:10 0:45 0:30 0:20
140, 4:45 2:05 1:20 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 92 de 198


Marzo 2017
Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:20 0:35
125, 24:00:00 24:00:00 24:00:00 4:45 1:35 0:45 0:25
130, 24:00:00 24:00:00 5:00 1:45 0:55 0:30 0:20
135, 24:00:00 4:55 1:55 1:05 0:40 0:25 0:15
140, 4:40 2:00 1:15 0:45 0:30 0:20 0:10

Cuadro de carga
ID 20591 Rhona 10,35 MVA 66 23-13,8 KV ONAN 8 ONAF 10
Transformador SE Portezuelo T3 T-52900 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:05 0:25
125, 24:00:00 24:00:00 24:00:00 4:35 1:25 0:40 0:20
130, 24:00:00 24:00:00 4:50 1:35 0:50 0:25 0:15
135, 24:00:00 4:45 1:45 1:00 0:35 0:20 0:10
140, 4:30 1:55 1:05 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 93 de 198


Marzo 2017
1.19. SE QUELENTARO T-18400 T5 ID7320065
Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:25 0:50
130, 24:00:00 24:00:00 24:00:00 4:20 1:40 0:55 0:35
135, 24:00:00 24:00:00 5:15 1:50 1:00 0:40 0:30
140, 24:00:00 6:25 2:00 1:10 0:45 0:30 0:25

Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
130, 24:00:00 24:00:00 24:00:00 4:20 1:35 0:55 0:35
135, 24:00:00 24:00:00 5:10 1:45 1:00 0:40 0:25
140, 24:00:00 6:20 1:55 1:05 0:45 0:30 0:20

Estudio de sobrecargas Página 94 de 198


Marzo 2017
Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:20 0:45
130, 24:00:00 24:00:00 24:00:00 4:15 1:35 0:50 0:30
135, 24:00:00 24:00:00 5:10 1:45 1:00 0:35 0:25
140, 24:00:00 6:20 1:55 1:05 0:40 0:30 0:20

Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50 1:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:15 0:40
130, 24:00:00 24:00:00 24:00:00 4:10 1:30 0:50 0:30
135, 24:00:00 24:00:00 5:05 1:40 0:55 0:35 0:25
140, 24:00:00 6:15 1:50 1:00 0:40 0:25 0:20

Estudio de sobrecargas Página 95 de 198


Marzo 2017
Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:15 0:40
130, 24:00:00 24:00:00 24:00:00 4:10 1:25 0:45 0:30
135, 24:00:00 24:00:00 5:00 1:35 0:50 0:30 0:20
140, 24:00:00 6:15 1:45 1:00 0:35 0:25 0:20

Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 0:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:10 0:35
130, 24:00:00 24:00:00 24:00:00 4:05 1:20 0:40 0:25
135, 24:00:00 24:00:00 4:55 1:35 0:50 0:30 0:20
140, 24:00:00 6:10 1:45 0:55 0:35 0:25 0:15

Estudio de sobrecargas Página 96 de 198


Marzo 2017
Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35 0:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:05 0:30
130, 24:00:00 24:00:00 24:00:00 3:55 1:15 0:40 0:25
135, 24:00:00 24:00:00 4:50 1:30 0:45 0:25 0:20
140, 24:00:00 6:05 1:40 0:50 0:30 0:20 0:15

Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:45
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:05 0:55 0:25
130, 24:00:00 24:00:00 24:00:00 3:50 1:10 0:35 0:20
135, 24:00:00 24:00:00 4:45 1:25 0:40 0:25 0:15
140, 24:00:00 6:00 1:35 0:50 0:30 0:20 0:10

Estudio de sobrecargas Página 97 de 198


Marzo 2017
Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:50 0:25
130, 24:00:00 24:00:00 24:00:00 3:45 1:05 0:30 0:15
135, 24:00:00 24:00:00 4:40 1:15 0:35 0:20 0:15
140, 24:00:00 5:55 1:30 0:45 0:25 0:15 0:10

Cuadro de carga
ID 7320065 Tusan 13 MVA 110 24-14,4 KV ONAN 10 ONAF1 13
Transformador SE Quelentaro T5 T-18400 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 13, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 0:30
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:45 0:20
130, 24:00:00 24:00:00 24:00:00 3:35 0:55 0:25 0:15
135, 24:00:00 24:00:00 4:35 1:10 0:35 0:20 0:10
140, 24:00:00 5:50 1:20 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 98 de 198


Marzo 2017
1.20. SE RAPEL T-50100 T3 ID18968
Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 2:15
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 2:30 1:45
140, 24:00:00 24:00:00 24:00:00 5:35 2:40 1:55 1:25

Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 2:10
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 2:25 1:40
140, 24:00:00 24:00:00 24:00:00 5:30 2:40 1:50 1:20

Estudio de sobrecargas Página 99 de 198


Marzo 2017
Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 2:10
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 2:20 1:35
140, 24:00:00 24:00:00 24:00:00 5:25 2:35 1:45 1:20

Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 2:05
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 2:20 1:35
140, 24:00:00 24:00:00 24:00:00 5:25 2:30 1:45 1:15

Estudio de sobrecargas Página 100 de 198


Marzo 2017
Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 2:00
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:25 2:15 1:30
140, 24:00:00 24:00:00 24:00:00 5:20 2:25 1:40 1:10

Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:55
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:20 2:10 1:25
140, 24:00:00 24:00:00 24:00:00 5:15 2:25 1:35 1:05

Estudio de sobrecargas Página 101 de 198


Marzo 2017
Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:50
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:05 1:20
140, 24:00:00 24:00:00 24:00:00 5:10 2:20 1:30 1:00

Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:40
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 2:00 1:15
140, 24:00:00 24:00:00 24:00:00 5:05 2:15 1:25 0:55

Estudio de sobrecargas Página 102 de 198


Marzo 2017
Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:35
135, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:50 1:05
140, 24:00:00 24:00:00 24:00:00 5:00 2:05 1:20 0:50

Cuadro de carga
ID 18968 Rhona 10MVA 66 13,2 KV ONAN 8 ONAF 10
Transformador SE Rapel T3 T-50100 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:25
135, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:45 1:00
140, 24:00:00 24:00:00 24:00:00 4:55 2:00 1:15 0:45

Estudio de sobrecargas Página 103 de 198


Marzo 2017
1.21. SE RAPEL T-52600 T1 ID 21796
Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:35 1:00
130, 24:00:00 24:00:00 24:00:00 2:45 1:40 1:05 0:45
135, 24:00:00 24:00:00 2:45 1:45 1:10 0:50 0:35
140, 24:00:00 2:45 1:50 1:15 0:55 0:40 0:30

Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:30 1:00
130, 24:00:00 24:00:00 24:00:00 2:40 1:35 1:05 0:45
135, 24:00:00 24:00:00 2:45 1:40 1:10 0:50 0:35
140, 24:00:00 2:45 1:45 1:15 0:55 0:40 0:30

Estudio de sobrecargas Página 104 de 198


Marzo 2017
Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55
130, 24:00:00 24:00:00 24:00:00 2:35 1:35 1:00 0:40
135, 24:00:00 24:00:00 2:40 1:40 1:05 0:45 0:35
140, 24:00:00 2:40 1:45 1:10 0:50 0:35 0:25

Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50
130, 24:00:00 24:00:00 24:00:00 2:30 1:30 0:55 0:40
135, 24:00:00 24:00:00 2:35 1:35 1:05 0:45 0:30
140, 24:00:00 2:40 1:40 1:10 0:50 0:35 0:25

Estudio de sobrecargas Página 105 de 198


Marzo 2017
Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:45
130, 24:00:00 24:00:00 24:00:00 2:30 1:25 0:55 0:35
135, 24:00:00 24:00:00 2:30 1:30 1:00 0:40 0:30
140, 24:00:00 2:35 1:35 1:05 0:45 0:30 0:25

Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:10 0:40
130, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:30
135, 24:00:00 24:00:00 2:30 1:25 0:55 0:35 0:25
140, 24:00:00 2:30 1:30 1:00 0:40 0:30 0:20

Estudio de sobrecargas Página 106 de 198


Marzo 2017
Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05 0:35
130, 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45 0:30
135, 24:00:00 24:00:00 2:25 1:20 0:50 0:35 0:20
140, 24:00:00 2:25 1:25 0:55 0:40 0:25 0:20

Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00 0:30
130, 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40 0:25
135, 24:00:00 24:00:00 2:15 1:15 0:45 0:30 0:20
140, 24:00:00 2:20 1:20 0:50 0:35 0:25 0:15

Estudio de sobrecargas Página 107 de 198


Marzo 2017
Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:40
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:25
130, 24:00:00 24:00:00 24:00:00 2:05 1:00 0:35 0:20
135, 24:00:00 24:00:00 2:10 1:10 0:40 0:25 0:15
140, 24:00:00 2:15 1:15 0:45 0:30 0:20 0:10

Cuadro de carga
ID 21796 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T1 T-52600 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30
125, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45 0:20
130, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30 0:15
135, 24:00:00 24:00:00 2:05 1:00 0:35 0:20 0:10
140, 24:00:00 2:10 1:10 0:40 0:25 0:15 0:10

Estudio de sobrecargas Página 108 de 198


Marzo 2017
1.22. SE RAPEL T-52700 T2 ID22830
Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50
140, 24:00:00 24:00:00 24:00:00 2:40 1:30 1:00 0:40

Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:10
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
140, 24:00:00 24:00:00 24:00:00 2:35 1:30 0:55 0:40

Estudio de sobrecargas Página 109 de 198


Marzo 2017
Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:05
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:15 0:45
140, 24:00:00 24:00:00 24:00:00 2:35 1:25 0:55 0:35

Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:05
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45
140, 24:00:00 24:00:00 24:00:00 2:30 1:25 0:50 0:35

Estudio de sobrecargas Página 110 de 198


Marzo 2017
Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 1:00
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40
140, 24:00:00 24:00:00 24:00:00 2:25 1:20 0:50 0:30

Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:55
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:05 0:40
140, 24:00:00 24:00:00 24:00:00 2:25 1:15 0:45 0:30

Estudio de sobrecargas Página 111 de 198


Marzo 2017
Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:50
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35
140, 24:00:00 24:00:00 24:00:00 2:20 1:10 0:40 0:25

Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:45
135, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30
140, 24:00:00 24:00:00 24:00:00 2:15 1:05 0:40 0:25

Estudio de sobrecargas Página 112 de 198


Marzo 2017
Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:40
135, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:25
140, 24:00:00 24:00:00 24:00:00 2:05 1:00 0:35 0:20

Cuadro de carga
ID 22830 Rhona 30 MVA 66 66 KV ONAN 20 ONAF1 25 ONAF2 30
Transformador SE Rapel T2 T-52700 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
130, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:35
135, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25
140, 24:00:00 24:00:00 24:00:00 2:00 0:55 0:30 0:15

Estudio de sobrecargas Página 113 de 198


Marzo 2017
1.23. SE SANTA ROSA T-53500 T1 ID87070
Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:50 2:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 6:10 2:35 1:45
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:50 1:55 1:25
140, 24:00:00 24:00:00 24:00:00 3:00 2:05 1:30 1:10

Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:45 2:20
130, 24:00:00 24:00:00 24:00:00 24:00:00 6:05 2:35 1:45
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:50 1:20
140, 24:00:00 24:00:00 24:00:00 2:55 2:00 1:30 1:05

Estudio de sobrecargas Página 114 de 198


Marzo 2017
Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:45 2:15
130, 24:00:00 24:00:00 24:00:00 24:00:00 6:00 2:30 1:40
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:50 1:20
140, 24:00:00 24:00:00 24:00:00 2:50 1:55 1:25 1:05

Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:40 2:10
130, 24:00:00 24:00:00 24:00:00 24:00:00 6:00 2:25 1:35
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:45 1:15
140, 24:00:00 24:00:00 24:00:00 2:50 1:55 1:20 1:00

Estudio de sobrecargas Página 115 de 198


Marzo 2017
Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:35 2:05
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:55 2:20 1:30
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:40 1:10
140, 24:00:00 24:00:00 24:00:00 2:45 1:50 1:20 0:55

Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30 2:00
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:50 2:15 1:25
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:35 1:05
140, 24:00:00 24:00:00 24:00:00 2:40 1:45 1:15 0:55

Estudio de sobrecargas Página 116 de 198


Marzo 2017
Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:55
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:40 2:10 1:20
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:30 1:00
140, 24:00:00 24:00:00 24:00:00 2:35 1:40 1:10 0:50

Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:45
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:35 2:05 1:15
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:25 0:55
140, 24:00:00 24:00:00 24:00:00 2:30 1:35 1:05 0:45

Estudio de sobrecargas Página 117 de 198


Marzo 2017
Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:35
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:30 1:55 1:05
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:20 0:50
140, 24:00:00 24:00:00 24:00:00 2:25 1:30 1:00 0:40

Cuadro de carga
ID 87070 Rhona 20 MVA 66 24-13,8 KV ONAN 16 ONAF 20
Transformador SE Santa Rosa T1 T-53500 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 20, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:25
130, 24:00:00 24:00:00 24:00:00 24:00:00 5:20 1:45 0:55
135, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:10 0:40
140, 24:00:00 24:00:00 24:00:00 2:20 1:25 0:50 0:30

Estudio de sobrecargas Página 118 de 198


Marzo 2017
1.24. SE EL PEUMO T-47900 RESERVA FRÍA PARA PROYECTO ID 73200300
Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 5:15 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 7:45 1:30 0:50 0:30
130, 24:00:00 24:00:00 24:00:00 1:40 0:55 0:35 0:25
135, 24:00:00 24:00:00 1:45 1:00 0:40 0:30 0:20
140, 9:25 1:50 1:05 0:40 0:30 0:25 0:20

Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 5:10 1:20 0:40
125, 24:00:00 24:00:00 24:00:00 7:45 1:30 0:45 0:30
130, 24:00:00 24:00:00 24:00:00 1:40 0:50 0:35 0:25
135, 24:00:00 24:00:00 1:45 0:55 0:35 0:25 0:20
140, 9:25 1:50 1:00 0:40 0:30 0:20 0:15

Estudio de sobrecargas Página 119 de 198


Marzo 2017
Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 5:05 1:15 0:40
125, 24:00:00 24:00:00 24:00:00 7:40 1:25 0:45 0:30
130, 24:00:00 24:00:00 24:00:00 1:35 0:50 0:30 0:20
135, 24:00:00 24:00:00 1:45 0:55 0:35 0:25 0:20
140, 9:20 1:50 1:00 0:40 0:30 0:20 0:15

Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 5:00 1:15 0:35
125, 24:00:00 24:00:00 24:00:00 7:35 1:25 0:40 0:25
130, 24:00:00 24:00:00 24:00:00 1:30 0:45 0:30 0:20
135, 24:00:00 24:00:00 1:40 0:55 0:35 0:25 0:15
140, 9:15 1:45 1:00 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 120 de 198


Marzo 2017
Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:55 1:10 0:35
125, 24:00:00 24:00:00 24:00:00 7:35 1:20 0:40 0:25
130, 24:00:00 24:00:00 24:00:00 1:30 0:45 0:30 0:20
135, 24:00:00 24:00:00 1:35 0:50 0:30 0:20 0:15
140, 9:15 1:40 0:55 0:35 0:25 0:20 0:15

Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:05 0:30
125, 24:00:00 24:00:00 24:00:00 7:30 1:15 0:35 0:20
130, 24:00:00 24:00:00 24:00:00 1:25 0:40 0:25 0:15
135, 24:00:00 24:00:00 1:30 0:45 0:30 0:20 0:15
140, 9:10 1:40 0:50 0:35 0:25 0:15 0:10

Estudio de sobrecargas Página 121 de 198


Marzo 2017
Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30 0:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:00 0:25
125, 24:00:00 24:00:00 24:00:00 7:20 1:10 0:35 0:20
130, 24:00:00 24:00:00 24:00:00 1:20 0:40 0:25 0:15
135, 24:00:00 24:00:00 1:30 0:45 0:25 0:20 0:10
140, 9:05 1:35 0:50 0:30 0:20 0:15 0:10

Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20 0:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 0:50 0:25
125, 24:00:00 24:00:00 24:00:00 7:15 1:05 0:30 0:15
130, 24:00:00 24:00:00 24:00:00 1:15 0:35 0:20 0:15
135, 24:00:00 24:00:00 1:20 0:40 0:25 0:15 0:10
140, 9:00 1:30 0:45 0:30 0:20 0:15 0:10

Estudio de sobrecargas Página 122 de 198


Marzo 2017
Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 0:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:25 0:45 0:20
125, 24:00:00 24:00:00 24:00:00 7:05 0:55 0:25 0:15
130, 24:00:00 24:00:00 24:00:00 1:05 0:30 0:20 0:10
135, 24:00:00 24:00:00 1:15 0:35 0:20 0:15 0:10
140, 8:55 1:25 0:40 0:25 0:15 0:10 0:05

Cuadro de carga
ID 732003001 Tusan 10 MVA 66 23 KV ONAN 8 ONAF1 10
Transformador SE El Peumo Reserva fría para proyecto T-
47900 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 0:35 0:15
125, 24:00:00 24:00:00 24:00:00 6:55 0:50 0:20 0:10
130, 24:00:00 24:00:00 24:00:00 1:00 0:25 0:15 0:10
135, 24:00:00 24:00:00 1:10 0:30 0:20 0:10 0:05
140, 8:50 1:20 0:40 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 123 de 198


Marzo 2017
1.25. SE EL PEUMO T-54137 T1 ID7320154
Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:50
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 2:00 1:15
125, 24:00:00 24:00:00 24:00:00 4:10 2:05 1:20 0:55
130, 24:00:00 24:00:00 4:05 2:10 1:25 1:00 0:45
135, 24:00:00 4:00 2:15 1:30 1:05 0:45 0:35
140, 3:50 2:15 1:35 1:10 0:50 0:40 0:30

Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:55 1:10
125, 24:00:00 24:00:00 24:00:00 4:05 2:00 1:20 0:50
130, 24:00:00 24:00:00 4:05 2:05 1:25 1:00 0:40
135, 24:00:00 3:55 2:10 1:30 1:00 0:45 0:35
140, 3:45 2:10 1:30 1:05 0:50 0:35 0:30

Estudio de sobrecargas Página 124 de 198


Marzo 2017
Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:50 1:10
125, 24:00:00 24:00:00 24:00:00 4:00 2:00 1:15 0:50
130, 24:00:00 24:00:00 4:00 2:05 1:20 0:55 0:40
135, 24:00:00 3:50 2:05 1:25 1:00 0:40 0:30
140, 3:45 2:10 1:30 1:05 0:45 0:35 0:25

Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:45 1:05
125, 24:00:00 24:00:00 24:00:00 4:00 1:55 1:10 0:45
130, 24:00:00 24:00:00 3:55 2:00 1:15 0:50 0:35
135, 24:00:00 3:50 2:05 1:20 0:55 0:40 0:30
140, 3:40 2:05 1:25 1:00 0:45 0:30 0:25

Estudio de sobrecargas Página 125 de 198


Marzo 2017
Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:30
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:40 1:00
125, 24:00:00 24:00:00 24:00:00 3:55 1:50 1:05 0:40
130, 24:00:00 24:00:00 3:50 1:55 1:10 0:45 0:30
135, 24:00:00 3:45 2:00 1:15 0:50 0:35 0:25
140, 3:35 2:00 1:20 0:55 0:40 0:30 0:20

Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:35 0:50
125, 24:00:00 24:00:00 24:00:00 3:45 1:45 1:00 0:35
130, 24:00:00 24:00:00 3:45 1:50 1:05 0:45 0:30
135, 24:00:00 3:40 1:55 1:15 0:50 0:35 0:20
140, 3:30 2:00 1:20 0:55 0:35 0:25 0:20

Estudio de sobrecargas Página 126 de 198


Marzo 2017
Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:25 0:45
125, 24:00:00 24:00:00 24:00:00 3:40 1:35 0:55 0:30
130, 24:00:00 24:00:00 3:40 1:45 1:00 0:40 0:25
135, 24:00:00 3:35 1:50 1:10 0:45 0:30 0:20
140, 3:25 1:55 1:15 0:50 0:35 0:25 0:15

Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:20 0:40
125, 24:00:00 24:00:00 24:00:00 3:35 1:30 0:50 0:25
130, 24:00:00 24:00:00 3:35 1:40 0:55 0:35 0:20
135, 24:00:00 3:30 1:45 1:00 0:40 0:25 0:15
140, 3:20 1:50 1:10 0:45 0:30 0:20 0:15

Estudio de sobrecargas Página 127 de 198


Marzo 2017
Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:10 0:30
125, 24:00:00 24:00:00 24:00:00 3:25 1:20 0:40 0:20
130, 24:00:00 24:00:00 3:25 1:30 0:50 0:30 0:15
135, 24:00:00 3:25 1:35 0:55 0:35 0:20 0:15
140, 3:15 1:40 1:00 0:40 0:25 0:15 0:10

Cuadro de carga
ID7320154 Tusan 30 MVA 69 25-15,3 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE El Peumo T1 T-54137 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 0:40
120, 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:00 0:25
125, 24:00:00 24:00:00 24:00:00 3:15 1:10 0:35 0:15
130, 24:00:00 24:00:00 3:15 1:20 0:40 0:20 0:10
135, 24:00:00 3:15 1:30 0:50 0:30 0:15 0:10
140, 3:10 1:35 0:55 0:35 0:20 0:15 0:05

Estudio de sobrecargas Página 128 de 198


Marzo 2017
1.26. SE ISLA DE MAIPO T-20000 T1 ID 18340
Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:30 0:55
120, 24:00:00 24:00:00 24:00:00 2:30 1:35 1:00 0:40
125, 24:00:00 24:00:00 2:30 1:35 1:05 0:45 0:35
130, 6:40 2:30 1:40 1:10 0:50 0:35 0:25
135, 2:25 1:40 1:10 0:50 0:40 0:30 0:25
140, 1:40 1:15 0:55 0:40 0:30 0:25 0:20

Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55
120, 24:00:00 24:00:00 24:00:00 2:30 1:30 1:00 0:40
125, 24:00:00 24:00:00 2:25 1:30 1:00 0:45 0:30
130, 6:40 2:25 1:35 1:05 0:45 0:35 0:25
135, 2:20 1:35 1:10 0:50 0:35 0:30 0:20
140, 1:35 1:10 0:55 0:40 0:30 0:25 0:20

Estudio de sobrecargas Página 129 de 198


Marzo 2017
Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
120, 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55 0:35
125, 24:00:00 24:00:00 2:25 1:30 1:00 0:40 0:30
130, 6:35 2:20 1:30 1:00 0:45 0:30 0:25
135, 2:20 1:35 1:05 0:45 0:35 0:25 0:20
140, 1:35 1:10 0:50 0:40 0:30 0:20 0:15

Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45
120, 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50 0:30
125, 24:00:00 24:00:00 2:20 1:25 0:55 0:35 0:25
130, 6:30 2:20 1:25 1:00 0:40 0:30 0:20
135, 2:15 1:30 1:00 0:45 0:30 0:25 0:15
140, 1:30 1:05 0:45 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 130 de 198


Marzo 2017
Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40
120, 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45 0:30
125, 24:00:00 24:00:00 2:15 1:20 0:50 0:35 0:20
130, 6:25 2:15 1:25 0:55 0:35 0:25 0:20
135, 2:10 1:25 1:00 0:40 0:30 0:20 0:15
140, 1:25 1:00 0:45 0:30 0:25 0:20 0:15

Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00 0:35
120, 24:00:00 24:00:00 24:00:00 2:05 1:10 0:40 0:25
125, 24:00:00 24:00:00 2:10 1:15 0:45 0:30 0:20
130, 6:20 2:10 1:20 0:50 0:35 0:25 0:15
135, 2:05 1:20 0:55 0:40 0:25 0:20 0:15
140, 1:25 1:00 0:40 0:30 0:20 0:15 0:10

Estudio de sobrecargas Página 131 de 198


Marzo 2017
Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30
120, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35 0:20
125, 24:00:00 24:00:00 2:00 1:10 0:40 0:25 0:15
130, 6:15 2:05 1:15 0:45 0:30 0:20 0:15
135, 2:00 1:15 0:50 0:35 0:25 0:15 0:10
140, 1:20 0:55 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45 0:20
120, 24:00:00 24:00:00 24:00:00 1:50 0:55 0:30 0:15
125, 24:00:00 24:00:00 1:55 1:00 0:35 0:20 0:10
130, 6:10 1:55 1:05 0:40 0:25 0:15 0:10
135, 1:55 1:10 0:45 0:30 0:20 0:15 0:10
140, 1:15 0:50 0:35 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 132 de 198


Marzo 2017
Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25 0:10
125, 24:00:00 24:00:00 1:45 0:55 0:30 0:15 0:10
130, 6:00 1:50 1:00 0:35 0:20 0:10 0:05
135, 1:50 1:05 0:40 0:25 0:15 0:10 0:05
140, 1:10 0:45 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID 18340 Rhona 25 MVA 110-66 12,5 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Isla De Maipo T1 T-20000 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25 0:10
120, 24:00:00 24:00:00 24:00:00 1:30 0:35 0:15 0:05
125, 24:00:00 24:00:00 1:35 0:45 0:25 0:10 0:05
130, 5:55 1:40 0:50 0:30 0:15 0:10 0:05
135, 1:40 0:55 0:35 0:20 0:10 0:05 0:00
140, 1:00 0:40 0:25 0:15 0:10 0:05 0:00

Estudio de sobrecargas Página 133 de 198


Marzo 2017
1.27. SE MELIPILLA T-45500 T3 ID44630
Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 6:05 1:45 0:55
115, 24:00:00 24:00:00 24:00:00 4:50 1:45 1:00 0:40
120, 24:00:00 24:00:00 4:10 1:50 1:05 0:40 0:30
125, 24:00:00 3:40 1:50 1:10 0:45 0:30 0:25
130, 3:20 1:50 1:10 0:50 0:35 0:25 0:20
135, 1:45 1:10 0:50 0:35 0:30 0:20 0:15
140, 1:10 0:50 0:40 0:30 0:25 0:20 0:15

Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 6:00 1:40 0:55
115, 24:00:00 24:00:00 24:00:00 4:45 1:45 1:00 0:35
120, 24:00:00 24:00:00 4:05 1:45 1:00 0:40 0:30
125, 24:00:00 3:35 1:45 1:05 0:45 0:30 0:20
130, 3:15 1:45 1:05 0:45 0:35 0:25 0:20
135, 1:45 1:10 0:50 0:35 0:25 0:20 0:15
140, 1:10 0:50 0:35 0:30 0:20 0:15 0:15

Estudio de sobrecargas Página 134 de 198


Marzo 2017
Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:55 1:35 0:50
115, 24:00:00 24:00:00 24:00:00 4:40 1:40 0:55 0:35
120, 24:00:00 24:00:00 4:00 1:40 1:00 0:35 0:25
125, 24:00:00 3:35 1:45 1:00 0:40 0:30 0:20
130, 3:10 1:40 1:05 0:45 0:30 0:25 0:15
135, 1:40 1:05 0:45 0:35 0:25 0:20 0:15
140, 1:05 0:50 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:50 1:30 0:45
115, 24:00:00 24:00:00 24:00:00 4:35 1:35 0:50 0:30
120, 24:00:00 24:00:00 3:55 1:35 0:55 0:35 0:25
125, 24:00:00 3:30 1:40 1:00 0:40 0:25 0:20
130, 3:10 1:40 1:00 0:40 0:30 0:20 0:15
135, 1:40 1:05 0:45 0:30 0:25 0:15 0:15
140, 1:05 0:45 0:35 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 135 de 198


Marzo 2017
Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:45 1:20 0:40
115, 24:00:00 24:00:00 24:00:00 4:30 1:30 0:45 0:25
120, 24:00:00 24:00:00 3:50 1:30 0:50 0:30 0:20
125, 24:00:00 3:25 1:35 0:55 0:35 0:25 0:15
130, 3:05 1:35 0:55 0:40 0:25 0:20 0:15
135, 1:35 1:00 0:40 0:30 0:20 0:15 0:10
140, 1:00 0:45 0:30 0:25 0:15 0:15 0:10

Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:35 1:15 0:35
115, 24:00:00 24:00:00 24:00:00 4:25 1:20 0:40 0:25
120, 24:00:00 24:00:00 3:45 1:25 0:45 0:25 0:15
125, 24:00:00 3:20 1:30 0:50 0:30 0:20 0:15
130, 3:00 1:30 0:55 0:35 0:25 0:15 0:10
135, 1:30 0:55 0:35 0:25 0:20 0:15 0:10
140, 1:00 0:40 0:30 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 136 de 198


Marzo 2017
Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:25 1:05 0:30
115, 24:00:00 24:00:00 24:00:00 4:15 1:15 0:35 0:20
120, 24:00:00 24:00:00 3:40 1:20 0:40 0:25 0:15
125, 24:00:00 3:10 1:20 0:45 0:25 0:15 0:10
130, 2:55 1:25 0:50 0:30 0:20 0:15 0:10
135, 1:25 0:50 0:35 0:25 0:15 0:10 0:05
140, 0:55 0:35 0:25 0:20 0:15 0:10 0:05

Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:15 0:55 0:20
115, 24:00:00 24:00:00 24:00:00 4:05 1:05 0:30 0:15
120, 24:00:00 24:00:00 3:30 1:10 0:35 0:20 0:10
125, 24:00:00 3:05 1:15 0:40 0:25 0:15 0:10
130, 2:45 1:20 0:45 0:25 0:15 0:10 0:05
135, 1:20 0:45 0:30 0:20 0:15 0:10 0:05
140, 0:50 0:35 0:25 0:15 0:10 0:05 0:05

Estudio de sobrecargas Página 137 de 198


Marzo 2017
Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 5:00 0:45 0:15
115, 24:00:00 24:00:00 24:00:00 3:55 0:55 0:20 0:10
120, 24:00:00 24:00:00 3:20 1:00 0:30 0:15 0:05
125, 24:00:00 2:55 1:10 0:35 0:20 0:10 0:05
130, 2:40 1:10 0:40 0:25 0:15 0:10 0:05
135, 1:15 0:40 0:25 0:15 0:10 0:05 0:05
140, 0:45 0:30 0:20 0:15 0:10 0:05 0:00

Cuadro de carga
ID44630 Rhona 30 MVA 115 25-13,4 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Melipilla T3 T-45500 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 0:30 0:05
115, 24:00:00 24:00:00 24:00:00 3:40 0:40 0:15 0:05
120, 24:00:00 24:00:00 3:05 0:50 0:20 0:10 0:00
125, 24:00:00 2:45 1:00 0:30 0:15 0:05 0:00
130, 2:30 1:05 0:35 0:20 0:10 0:05 0:00
135, 1:05 0:35 0:20 0:15 0:10 0:05 0:00
140, 0:40 0:25 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 138 de 198


Marzo 2017
1.28. SE MELIPILLA T-50400 RESERVA FRÍA ID17353
Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:30 0:55
120, 24:00:00 24:00:00 24:00:00 2:30 1:35 1:00 0:40
125, 24:00:00 24:00:00 2:30 1:35 1:05 0:45 0:35
130, 6:40 2:30 1:40 1:10 0:50 0:35 0:25
135, 2:25 1:40 1:10 0:50 0:40 0:30 0:25
140, 1:40 1:15 0:55 0:40 0:30 0:25 0:20

Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55
120, 24:00:00 24:00:00 24:00:00 2:30 1:30 1:00 0:40
125, 24:00:00 24:00:00 2:25 1:30 1:00 0:45 0:30
130, 6:40 2:25 1:35 1:05 0:45 0:35 0:25
135, 2:20 1:35 1:10 0:50 0:35 0:30 0:20
140, 1:35 1:10 0:55 0:40 0:30 0:25 0:20

Estudio de sobrecargas Página 139 de 198


Marzo 2017
Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50
120, 24:00:00 24:00:00 24:00:00 2:25 1:25 0:55 0:35
125, 24:00:00 24:00:00 2:25 1:30 1:00 0:40 0:30
130, 6:35 2:20 1:30 1:00 0:45 0:30 0:25
135, 2:20 1:35 1:05 0:45 0:35 0:25 0:20
140, 1:35 1:10 0:50 0:40 0:30 0:20 0:15

Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45
120, 24:00:00 24:00:00 24:00:00 2:20 1:20 0:50 0:30
125, 24:00:00 24:00:00 2:20 1:25 0:55 0:35 0:25
130, 6:30 2:20 1:25 1:00 0:40 0:30 0:20
135, 2:15 1:30 1:00 0:45 0:30 0:25 0:15
140, 1:30 1:05 0:45 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 140 de 198


Marzo 2017
Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:10 0:40
120, 24:00:00 24:00:00 24:00:00 2:15 1:15 0:45 0:30
125, 24:00:00 24:00:00 2:15 1:20 0:50 0:35 0:20
130, 6:25 2:15 1:25 0:55 0:35 0:25 0:20
135, 2:10 1:25 1:00 0:40 0:30 0:20 0:15
140, 1:25 1:00 0:45 0:30 0:25 0:20 0:15

Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:05 1:00 0:35
120, 24:00:00 24:00:00 24:00:00 2:05 1:10 0:40 0:25
125, 24:00:00 24:00:00 2:10 1:15 0:45 0:30 0:20
130, 6:20 2:10 1:20 0:50 0:35 0:25 0:15
135, 2:05 1:20 0:55 0:40 0:25 0:20 0:15
140, 1:25 1:00 0:40 0:30 0:20 0:15 0:10

Estudio de sobrecargas Página 141 de 198


Marzo 2017
Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:55 0:30
120, 24:00:00 24:00:00 24:00:00 2:00 1:00 0:35 0:20
125, 24:00:00 24:00:00 2:00 1:10 0:40 0:25 0:15
130, 6:15 2:05 1:15 0:45 0:30 0:20 0:15
135, 2:00 1:15 0:50 0:35 0:25 0:15 0:10
140, 1:20 0:55 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45 0:20
120, 24:00:00 24:00:00 24:00:00 1:50 0:55 0:30 0:15
125, 24:00:00 24:00:00 1:55 1:00 0:35 0:20 0:10
130, 6:10 1:55 1:05 0:40 0:25 0:15 0:10
135, 1:55 1:10 0:45 0:30 0:20 0:15 0:10
140, 1:15 0:50 0:35 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 142 de 198


Marzo 2017
Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25 0:10
125, 24:00:00 24:00:00 1:45 0:55 0:30 0:15 0:10
130, 6:00 1:50 1:00 0:35 0:20 0:10 0:05
135, 1:50 1:05 0:40 0:25 0:15 0:10 0:05
140, 1:10 0:45 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID17353 Rhona 25 MVA 110 66 KV ONAN 15 ONAF1 20 ONAF2 25
Transformador SE Melipilla Reserva fría T-50400 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 25, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25 0:10
120, 24:00:00 24:00:00 24:00:00 1:30 0:35 0:15 0:05
125, 24:00:00 24:00:00 1:35 0:45 0:25 0:10 0:05
130, 5:55 1:40 0:50 0:30 0:15 0:10 0:05
135, 1:40 0:55 0:35 0:20 0:10 0:05 0:00
140, 1:00 0:40 0:25 0:15 0:10 0:05 0:00

Estudio de sobrecargas Página 143 de 198


Marzo 2017
1.29. SE MELIPILLA T-MÓVIL RESERVA FRÍA ID XA1957A001
Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 50, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:20
105, 24:00:00 24:00:00 24:00:00 5:40 2:15 1:20 0:45
110, 24:00:00 24:00:00 3:45 2:00 1:15 0:45 0:25
115, 24:00:00 3:00 1:50 1:10 0:45 0:25 0:15
120, 2:30 1:40 1:10 0:45 0:30 0:20 0:10
125, 1:30 1:05 0:45 0:30 0:20 0:15 0:10
130, 1:00 0:45 0:30 0:20 0:15 0:10 0:10
135, 0:45 0:30 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:20 0:15 0:10 0:10 0:05 0:05

Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 55, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 1:15
105, 24:00:00 24:00:00 24:00:00 5:35 2:10 1:15 0:40
110, 24:00:00 24:00:00 3:40 1:55 1:10 0:40 0:20
115, 24:00:00 2:55 1:45 1:10 0:40 0:25 0:15
120, 2:25 1:35 1:05 0:40 0:25 0:15 0:10
125, 1:30 1:00 0:40 0:25 0:15 0:10 0:10
130, 1:00 0:40 0:25 0:20 0:15 0:10 0:05
135, 0:40 0:30 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:20 0:15 0:10 0:10 0:05 0:05

Estudio de sobrecargas Página 144 de 198


Marzo 2017
Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 60, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 1:05
105, 24:00:00 24:00:00 24:00:00 5:25 2:05 1:05 0:35
110, 24:00:00 24:00:00 3:35 1:50 1:05 0:35 0:20
115, 24:00:00 2:50 1:40 1:05 0:35 0:20 0:15
120, 2:20 1:30 1:00 0:35 0:20 0:15 0:10
125, 1:25 1:00 0:40 0:25 0:15 0:10 0:05
130, 0:55 0:40 0:25 0:15 0:10 0:10 0:05
135, 0:35 0:25 0:15 0:15 0:10 0:05 0:05
140, 0:25 0:20 0:15 0:10 0:10 0:05 0:05

Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 65, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 1:00
105, 24:00:00 24:00:00 24:00:00 5:20 1:55 1:00 0:25
110, 24:00:00 24:00:00 3:25 1:45 1:00 0:30 0:15
115, 24:00:00 2:45 1:35 0:55 0:30 0:15 0:10
120, 2:15 1:25 0:55 0:35 0:20 0:10 0:10
125, 1:20 0:55 0:35 0:20 0:15 0:10 0:05
130, 0:50 0:35 0:20 0:15 0:10 0:05 0:05
135, 0:35 0:25 0:15 0:10 0:10 0:05 0:05
140, 0:25 0:15 0:10 0:10 0:05 0:05 0:05

Estudio de sobrecargas Página 145 de 198


Marzo 2017
Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 70, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:50
105, 24:00:00 24:00:00 24:00:00 5:10 1:50 0:50 0:20
110, 24:00:00 24:00:00 3:20 1:35 0:50 0:25 0:10
115, 24:00:00 2:35 1:30 0:50 0:25 0:15 0:10
120, 2:10 1:20 0:50 0:30 0:15 0:10 0:05
125, 1:15 0:50 0:30 0:15 0:10 0:05 0:05
130, 0:45 0:30 0:20 0:15 0:10 0:05 0:05
135, 0:30 0:20 0:15 0:10 0:05 0:05 0:05
140, 0:20 0:15 0:10 0:10 0:05 0:05 0:00

Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 75, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:35
105, 24:00:00 24:00:00 24:00:00 5:00 1:35 0:40 0:15
110, 24:00:00 24:00:00 3:10 1:30 0:40 0:20 0:10
115, 24:00:00 2:30 1:20 0:45 0:20 0:10 0:05
120, 2:05 1:15 0:45 0:25 0:15 0:10 0:05
125, 1:10 0:45 0:25 0:15 0:10 0:05 0:05
130, 0:40 0:25 0:15 0:10 0:05 0:05 0:00
135, 0:25 0:15 0:10 0:10 0:05 0:05 0:00
140, 0:20 0:15 0:10 0:05 0:05 0:05 0:00

Estudio de sobrecargas Página 146 de 198


Marzo 2017
Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 80, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:20
105, 24:00:00 24:00:00 24:00:00 4:45 1:25 0:30 0:10
110, 24:00:00 24:00:00 3:00 1:15 0:30 0:15 0:05
115, 24:00:00 2:20 1:10 0:35 0:15 0:10 0:05
120, 1:55 1:05 0:35 0:20 0:10 0:05 0:05
125, 1:05 0:35 0:20 0:10 0:05 0:05 0:00
130, 0:35 0:20 0:15 0:10 0:05 0:05 0:00
135, 0:20 0:15 0:10 0:05 0:05 0:00 0:00
140, 0:15 0:10 0:05 0:05 0:05 0:00 0:00

Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 85, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:10
105, 24:00:00 24:00:00 24:00:00 4:30 1:05 0:15 0:05
110, 24:00:00 24:00:00 2:45 1:05 0:20 0:10 0:05
115, 24:00:00 2:10 1:00 0:25 0:10 0:05 0:00
120, 1:45 1:00 0:25 0:15 0:05 0:05 0:00
125, 0:55 0:30 0:15 0:10 0:05 0:00 0:00
130, 0:30 0:15 0:10 0:05 0:05 0:00 0:00
135, 0:20 0:10 0:10 0:05 0:05 0:00 0:00
140, 0:15 0:10 0:05 0:05 0:00 0:00 0:00

Estudio de sobrecargas Página 147 de 198


Marzo 2017
Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 90, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:00
105, 24:00:00 24:00:00 24:00:00 4:05 0:45 0:10 0:00
110, 24:00:00 24:00:00 2:25 0:45 0:10 0:05 0:00
115, 24:00:00 1:55 0:45 0:15 0:05 0:00 0:00
120, 1:35 0:45 0:20 0:10 0:05 0:00 0:00
125, 0:45 0:20 0:10 0:05 0:05 0:00 0:00
130, 0:25 0:15 0:10 0:05 0:00 0:00 0:00
135, 0:15 0:10 0:05 0:05 0:00 0:00 0:00
140, 0:10 0:05 0:05 0:00 0:00 0:00 0:00

Cuadro de carga
ID XA1957A001 Trafo 30MVA 110-66 24-13,2 KV OF 30
Transformador SE Melipilla Reserva fría T-Móvil Grado de carga inicial de 95, %
Refrigeración tipo OF Transformador con una potencia de 30 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:05 0:00
105, 24:00:00 24:00:00 24:00:00 3:30 0:15 0:00 0:00
110, 24:00:00 24:00:00 2:05 0:25 0:05 0:00 0:00
115, 24:00:00 1:35 0:30 0:10 0:00 0:00 0:00
120, 1:20 0:35 0:10 0:05 0:00 0:00 0:00
125, 0:35 0:15 0:05 0:05 0:00 0:00 0:00
130, 0:15 0:10 0:05 0:00 0:00 0:00 0:00
135, 0:10 0:05 0:05 0:00 0:00 0:00 0:00
140, 0:10 0:05 0:00 0:00 0:00 0:00 0:00

Estudio de sobrecargas Página 148 de 198


Marzo 2017
1.30. SE PADRE HURTADO T-24500 RESERVA FRÍA PARA PROYECTO ID37463
Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 2:00 1:15
130, 24:00:00 24:00:00 24:00:00 4:40 2:10 1:20 0:55
135, 24:00:00 24:00:00 4:55 2:15 1:30 1:00 0:45
140, 24:00:00 5:00 2:20 1:35 1:05 0:50 0:35

Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:45
125, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:55 1:10
130, 24:00:00 24:00:00 24:00:00 4:40 2:05 1:20 0:50
135, 24:00:00 24:00:00 4:55 2:15 1:25 1:00 0:40
140, 24:00:00 5:00 2:20 1:30 1:05 0:45 0:35

Estudio de sobrecargas Página 149 de 198


Marzo 2017
Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:40
125, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:50 1:10
130, 24:00:00 24:00:00 24:00:00 4:35 2:00 1:15 0:50
135, 24:00:00 24:00:00 4:50 2:10 1:25 0:55 0:40
140, 24:00:00 4:55 2:15 1:30 1:00 0:45 0:30

Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:35
125, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:50 1:05
130, 24:00:00 24:00:00 24:00:00 4:30 2:00 1:10 0:45
135, 24:00:00 24:00:00 4:45 2:05 1:20 0:50 0:35
140, 24:00:00 4:55 2:15 1:25 1:00 0:40 0:30

Estudio de sobrecargas Página 150 de 198


Marzo 2017
Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:30
125, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:45 1:00
130, 24:00:00 24:00:00 24:00:00 4:25 1:55 1:10 0:45
135, 24:00:00 24:00:00 4:45 2:00 1:15 0:50 0:35
140, 24:00:00 4:50 2:10 1:20 0:55 0:40 0:25

Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 1:25
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 1:40 0:55
130, 24:00:00 24:00:00 24:00:00 4:20 1:50 1:05 0:40
135, 24:00:00 24:00:00 4:40 2:00 1:10 0:45 0:30
140, 24:00:00 4:45 2:05 1:20 0:50 0:35 0:25

Estudio de sobrecargas Página 151 de 198


Marzo 2017
Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:20
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:30 0:50
130, 24:00:00 24:00:00 24:00:00 4:15 1:45 1:00 0:35
135, 24:00:00 24:00:00 4:35 1:55 1:05 0:40 0:25
140, 24:00:00 4:40 2:00 1:15 0:45 0:30 0:20

Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:10
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:25 0:40
130, 24:00:00 24:00:00 24:00:00 4:10 1:35 0:50 0:30
135, 24:00:00 24:00:00 4:30 1:45 1:00 0:35 0:25
140, 24:00:00 4:35 1:55 1:10 0:45 0:30 0:20

Estudio de sobrecargas Página 152 de 198


Marzo 2017
Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:00
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:15 0:35
130, 24:00:00 24:00:00 24:00:00 4:00 1:30 0:45 0:25
135, 24:00:00 24:00:00 4:20 1:40 0:55 0:30 0:20
140, 24:00:00 4:30 1:50 1:05 0:40 0:25 0:15

Cuadro de carga
ID37463 Rhona 30MVA 115 25-13,4KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Padre Hurtado Reserva fría para proyecto
T-24500 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
120, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:50
125, 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:05 0:30
130, 24:00:00 24:00:00 24:00:00 3:50 1:20 0:40 0:20
135, 24:00:00 24:00:00 4:15 1:35 0:50 0:25 0:15
140, 24:00:00 4:25 1:45 0:55 0:35 0:20 0:10

Estudio de sobrecargas Página 153 de 198


Marzo 2017
1.31. SE PAPELERA TALAGANTE T-54103 T1 ID 47700
Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:40 0:25
115, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:30 0:20
120, 24:00:00 24:00:00 1:40 0:45 0:30 0:20 0:15
125, 24:00:00 1:35 0:45 0:30 0:25 0:20 0:15
130, 1:30 0:45 0:30 0:25 0:20 0:15 0:10
135, 0:45 0:35 0:25 0:20 0:15 0:15 0:10
140, 0:35 0:25 0:20 0:15 0:15 0:10 0:10

Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:40 0:25
115, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:25 0:20
120, 24:00:00 24:00:00 1:40 0:45 0:30 0:20 0:15
125, 24:00:00 1:30 0:45 0:30 0:20 0:15 0:15
130, 1:25 0:45 0:30 0:25 0:20 0:15 0:10
135, 0:45 0:30 0:25 0:20 0:15 0:10 0:10
140, 0:35 0:25 0:20 0:15 0:15 0:10 0:10

Estudio de sobrecargas Página 154 de 198


Marzo 2017
Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:40 0:25
115, 24:00:00 24:00:00 24:00:00 1:40 0:40 0:25 0:20
120, 24:00:00 24:00:00 1:35 0:40 0:30 0:20 0:15
125, 24:00:00 1:30 0:45 0:30 0:20 0:15 0:10
130, 1:25 0:45 0:30 0:20 0:15 0:15 0:10
135, 0:45 0:30 0:25 0:20 0:15 0:10 0:10
140, 0:30 0:25 0:20 0:15 0:10 0:10 0:10

Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:35 0:20
115, 24:00:00 24:00:00 24:00:00 1:35 0:40 0:25 0:15
120, 24:00:00 24:00:00 1:30 0:40 0:25 0:20 0:15
125, 24:00:00 1:25 0:40 0:30 0:20 0:15 0:10
130, 1:20 0:45 0:30 0:20 0:15 0:10 0:10
135, 0:45 0:30 0:20 0:15 0:15 0:10 0:10
140, 0:30 0:25 0:20 0:15 0:10 0:10 0:05

Estudio de sobrecargas Página 155 de 198


Marzo 2017
Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:35 0:20
115, 24:00:00 24:00:00 24:00:00 1:30 0:35 0:20 0:15
120, 24:00:00 24:00:00 1:25 0:40 0:25 0:15 0:10
125, 24:00:00 1:25 0:40 0:25 0:20 0:15 0:10
130, 1:20 0:40 0:25 0:20 0:15 0:10 0:10
135, 0:40 0:30 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:20 0:15 0:15 0:10 0:10 0:05

Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30 0:15
115, 24:00:00 24:00:00 24:00:00 1:25 0:35 0:20 0:15
120, 24:00:00 24:00:00 1:20 0:35 0:20 0:15 0:10
125, 24:00:00 1:20 0:35 0:25 0:15 0:10 0:10
130, 1:15 0:40 0:25 0:20 0:15 0:10 0:05
135, 0:40 0:25 0:20 0:15 0:10 0:10 0:05
140, 0:30 0:20 0:15 0:10 0:10 0:05 0:05

Estudio de sobrecargas Página 156 de 198


Marzo 2017
Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25 0:15
115, 24:00:00 24:00:00 24:00:00 1:20 0:30 0:15 0:10
120, 24:00:00 24:00:00 1:15 0:30 0:20 0:15 0:10
125, 24:00:00 1:15 0:35 0:20 0:15 0:10 0:05
130, 1:10 0:35 0:25 0:15 0:10 0:10 0:05
135, 0:35 0:25 0:20 0:15 0:10 0:05 0:05
140, 0:25 0:20 0:15 0:10 0:10 0:05 0:05

Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:10 0:25 0:10
115, 24:00:00 24:00:00 24:00:00 1:10 0:25 0:15 0:10
120, 24:00:00 24:00:00 1:10 0:30 0:15 0:10 0:05
125, 24:00:00 1:10 0:30 0:20 0:15 0:10 0:05
130, 1:05 0:35 0:20 0:15 0:10 0:05 0:05
135, 0:35 0:25 0:15 0:10 0:10 0:05 0:00
140, 0:25 0:20 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 157 de 198


Marzo 2017
Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50 0:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:20 0:05
115, 24:00:00 24:00:00 24:00:00 1:00 0:20 0:10 0:05
120, 24:00:00 24:00:00 1:00 0:25 0:15 0:10 0:05
125, 24:00:00 1:00 0:30 0:15 0:10 0:05 0:00
130, 1:00 0:30 0:20 0:10 0:10 0:05 0:00
135, 0:30 0:20 0:15 0:10 0:05 0:05 0:00
140, 0:20 0:15 0:10 0:10 0:05 0:00 0:00

Cuadro de carga
ID 47700 Rhona 30 MVA 6623-13,2 KV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Papelera Talagante T1 T-54103 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:20
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35 0:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 0:45 0:10 0:00
115, 24:00:00 24:00:00 24:00:00 0:50 0:15 0:05 0:00
120, 24:00:00 24:00:00 0:55 0:20 0:10 0:05 0:00
125, 24:00:00 0:55 0:25 0:15 0:05 0:05 0:00
130, 0:55 0:25 0:15 0:10 0:05 0:00 0:00
135, 0:30 0:20 0:10 0:10 0:05 0:00 0:00
140, 0:20 0:15 0:10 0:05 0:05 0:00 0:00

Estudio de sobrecargas Página 158 de 198


Marzo 2017
1.32. SE QUELENTARO T-51900, T-52000, T-52100 ATR123 IDET91361-2-3
Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:10 2:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:15 2:10 1:25
120, 24:00:00 24:00:00 24:00:00 5:00 2:15 1:30 1:00
125, 24:00:00 24:00:00 4:40 2:20 1:35 1:05 0:45
130, 24:00:00 4:20 2:20 1:35 1:10 0:50 0:40
135, 4:00 2:20 1:40 1:15 0:55 0:40 0:30
140, 2:20 1:40 1:15 1:00 0:45 0:35 0:25

Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:05 2:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:10 2:05 1:20
120, 24:00:00 24:00:00 24:00:00 4:55 2:15 1:25 1:00
125, 24:00:00 24:00:00 4:35 2:15 1:30 1:05 0:45
130, 24:00:00 4:15 2:20 1:35 1:05 0:50 0:35
135, 4:00 2:20 1:35 1:10 0:55 0:40 0:30
140, 2:20 1:40 1:15 0:55 0:45 0:35 0:25

Estudio de sobrecargas Página 159 de 198


Marzo 2017
Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:00 1:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:05 2:00 1:15
120, 24:00:00 24:00:00 24:00:00 4:55 2:10 1:20 0:55
125, 24:00:00 24:00:00 4:35 2:10 1:25 1:00 0:40
130, 24:00:00 4:15 2:15 1:30 1:05 0:45 0:35
135, 3:55 2:15 1:35 1:10 0:50 0:35 0:25
140, 2:15 1:35 1:10 0:55 0:40 0:30 0:25

Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:55 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:00 1:55 1:10
120, 24:00:00 24:00:00 24:00:00 4:50 2:05 1:15 0:50
125, 24:00:00 24:00:00 4:30 2:10 1:20 0:55 0:40
130, 24:00:00 4:10 2:10 1:25 1:00 0:40 0:30
135, 3:50 2:10 1:30 1:05 0:45 0:35 0:25
140, 2:10 1:35 1:10 0:50 0:40 0:30 0:20

Estudio de sobrecargas Página 160 de 198


Marzo 2017
Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:55 1:50 1:05
120, 24:00:00 24:00:00 24:00:00 4:45 2:00 1:10 0:45
125, 24:00:00 24:00:00 4:25 2:05 1:15 0:50 0:35
130, 24:00:00 4:05 2:05 1:20 0:55 0:40 0:25
135, 3:45 2:05 1:25 1:00 0:45 0:30 0:20
140, 2:10 1:30 1:05 0:45 0:35 0:25 0:20

Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:45 0:55
120, 24:00:00 24:00:00 24:00:00 4:35 1:50 1:05 0:40
125, 24:00:00 24:00:00 4:20 1:55 1:10 0:45 0:30
130, 24:00:00 4:00 2:00 1:15 0:50 0:35 0:25
135, 3:40 2:05 1:20 0:55 0:40 0:30 0:20
140, 2:05 1:25 1:00 0:45 0:30 0:25 0:15

Estudio de sobrecargas Página 161 de 198


Marzo 2017
Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:35 0:50
120, 24:00:00 24:00:00 24:00:00 4:30 1:45 1:00 0:35
125, 24:00:00 24:00:00 4:10 1:50 1:05 0:40 0:25
130, 24:00:00 3:55 1:55 1:10 0:45 0:30 0:20
135, 3:35 2:00 1:15 0:50 0:35 0:25 0:15
140, 2:00 1:20 0:55 0:40 0:30 0:20 0:15

Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:25 0:40
120, 24:00:00 24:00:00 24:00:00 4:20 1:35 0:50 0:25
125, 24:00:00 24:00:00 4:05 1:45 1:00 0:35 0:20
130, 24:00:00 3:45 1:50 1:05 0:40 0:25 0:15
135, 3:30 1:50 1:10 0:45 0:30 0:20 0:15
140, 1:55 1:15 0:50 0:35 0:25 0:15 0:10

Estudio de sobrecargas Página 162 de 198


Marzo 2017
Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:15 0:30
120, 24:00:00 24:00:00 24:00:00 4:10 1:25 0:40 0:20
125, 24:00:00 24:00:00 3:55 1:35 0:50 0:30 0:15
130, 24:00:00 3:40 1:40 1:00 0:35 0:20 0:10
135, 3:25 1:45 1:05 0:40 0:25 0:15 0:10
140, 1:50 1:10 0:45 0:30 0:20 0:15 0:05

Cuadro de carga
ID ET91361-2-3 Crompton G. 195MVA 220110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro ATR1/2/3 T-51900, T-52000,
T-52100 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:00 0:20
120, 24:00:00 24:00:00 24:00:00 4:00 1:15 0:30 0:15
125, 24:00:00 24:00:00 3:45 1:25 0:40 0:20 0:10
130, 24:00:00 3:30 1:30 0:50 0:30 0:15 0:05
135, 3:15 1:40 1:00 0:35 0:20 0:10 0:05
140, 1:40 1:05 0:40 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 163 de 198


Marzo 2017
1.33. SE QUELENTARO T-52200 RESERVA FRÍA ID ET 91364
Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:10 2:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:15 2:10 1:25
120, 24:00:00 24:00:00 24:00:00 5:00 2:15 1:30 1:00
125, 24:00:00 24:00:00 4:40 2:20 1:35 1:05 0:45
130, 24:00:00 4:20 2:20 1:35 1:10 0:50 0:40
135, 4:00 2:20 1:40 1:15 0:55 0:40 0:30
140, 2:20 1:40 1:15 1:00 0:45 0:35 0:25

Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:05 2:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:10 2:05 1:20
120, 24:00:00 24:00:00 24:00:00 4:55 2:15 1:25 1:00
125, 24:00:00 24:00:00 4:35 2:15 1:30 1:05 0:45
130, 24:00:00 4:15 2:20 1:35 1:05 0:50 0:35
135, 4:00 2:20 1:35 1:10 0:55 0:40 0:30
140, 2:20 1:40 1:15 0:55 0:45 0:35 0:25

Estudio de sobrecargas Página 164 de 198


Marzo 2017
Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 5:00 1:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:05 2:00 1:15
120, 24:00:00 24:00:00 24:00:00 4:55 2:10 1:20 0:55
125, 24:00:00 24:00:00 4:35 2:10 1:25 1:00 0:40
130, 24:00:00 4:15 2:15 1:30 1:05 0:45 0:35
135, 3:55 2:15 1:35 1:10 0:50 0:35 0:25
140, 2:15 1:35 1:10 0:55 0:40 0:30 0:25

Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:55 1:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 5:00 1:55 1:10
120, 24:00:00 24:00:00 24:00:00 4:50 2:05 1:15 0:50
125, 24:00:00 24:00:00 4:30 2:10 1:20 0:55 0:40
130, 24:00:00 4:10 2:10 1:25 1:00 0:40 0:30
135, 3:50 2:10 1:30 1:05 0:45 0:35 0:25
140, 2:10 1:35 1:10 0:50 0:40 0:30 0:20

Estudio de sobrecargas Página 165 de 198


Marzo 2017
Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:55 1:50 1:05
120, 24:00:00 24:00:00 24:00:00 4:45 2:00 1:10 0:45
125, 24:00:00 24:00:00 4:25 2:05 1:15 0:50 0:35
130, 24:00:00 4:05 2:05 1:20 0:55 0:40 0:25
135, 3:45 2:05 1:25 1:00 0:45 0:30 0:20
140, 2:10 1:30 1:05 0:45 0:35 0:25 0:20

Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:45 0:55
120, 24:00:00 24:00:00 24:00:00 4:35 1:50 1:05 0:40
125, 24:00:00 24:00:00 4:20 1:55 1:10 0:45 0:30
130, 24:00:00 4:00 2:00 1:15 0:50 0:35 0:25
135, 3:40 2:05 1:20 0:55 0:40 0:30 0:20
140, 2:05 1:25 1:00 0:45 0:30 0:25 0:15

Estudio de sobrecargas Página 166 de 198


Marzo 2017
Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:35 0:50
120, 24:00:00 24:00:00 24:00:00 4:30 1:45 1:00 0:35
125, 24:00:00 24:00:00 4:10 1:50 1:05 0:40 0:25
130, 24:00:00 3:55 1:55 1:10 0:45 0:30 0:20
135, 3:35 2:00 1:15 0:50 0:35 0:25 0:15
140, 2:00 1:20 0:55 0:40 0:30 0:20 0:15

Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 1:25 0:40
120, 24:00:00 24:00:00 24:00:00 4:20 1:35 0:50 0:25
125, 24:00:00 24:00:00 4:05 1:45 1:00 0:35 0:20
130, 24:00:00 3:45 1:50 1:05 0:40 0:25 0:15
135, 3:30 1:50 1:10 0:45 0:30 0:20 0:15
140, 1:55 1:15 0:50 0:35 0:25 0:15 0:10

Estudio de sobrecargas Página 167 de 198


Marzo 2017
Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:15 0:30
120, 24:00:00 24:00:00 24:00:00 4:10 1:25 0:40 0:20
125, 24:00:00 24:00:00 3:55 1:35 0:50 0:30 0:15
130, 24:00:00 3:40 1:40 1:00 0:35 0:20 0:10
135, 3:25 1:45 1:05 0:40 0:25 0:15 0:10
140, 1:50 1:10 0:45 0:30 0:20 0:15 0:05

Cuadro de carga
ID ET 91364 Crompton G. 65 MVA 220 110 KV ONAN 60 ONAF 65
Transformador SE Quelentaro Reserva fría T-
52200 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 65, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:00 0:20
120, 24:00:00 24:00:00 24:00:00 4:00 1:15 0:30 0:15
125, 24:00:00 24:00:00 3:45 1:25 0:40 0:20 0:10
130, 24:00:00 3:30 1:30 0:50 0:30 0:15 0:05
135, 3:15 1:40 1:00 0:35 0:20 0:10 0:05
140, 1:40 1:05 0:40 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 168 de 198


Marzo 2017
1.34. SE ISLA DE MAIPO T3 T-24400 ID 11111
Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:50 0:30
120, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:35 0:25
125, 24:00:00 24:00:00 1:55 1:00 0:35 0:25 0:20
130, 24:00:00 1:55 1:00 0:40 0:30 0:20 0:15
135, 1:50 1:00 0:40 0:30 0:25 0:20 0:15
140, 1:05 0:45 0:30 0:25 0:20 0:15 0:10

Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:50 0:30
120, 24:00:00 24:00:00 24:00:00 1:55 0:55 0:35 0:25
125, 24:00:00 24:00:00 1:55 0:55 0:35 0:25 0:20
130, 24:00:00 1:50 1:00 0:40 0:25 0:20 0:15
135, 1:50 1:00 0:40 0:30 0:20 0:15 0:15
140, 1:00 0:40 0:30 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 169 de 198


Marzo 2017
Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45 0:30
120, 24:00:00 24:00:00 24:00:00 1:50 0:50 0:30 0:20
125, 24:00:00 24:00:00 1:50 0:55 0:35 0:25 0:15
130, 24:00:00 1:50 0:55 0:35 0:25 0:20 0:15
135, 1:45 1:00 0:40 0:25 0:20 0:15 0:10
140, 1:00 0:40 0:30 0:20 0:15 0:15 0:10

Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:45 0:25
120, 24:00:00 24:00:00 24:00:00 1:45 0:45 0:30 0:20
125, 24:00:00 24:00:00 1:45 0:50 0:30 0:20 0:15
130, 24:00:00 1:45 0:55 0:35 0:25 0:15 0:15
135, 1:45 0:55 0:35 0:25 0:20 0:15 0:10
140, 0:55 0:40 0:30 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 170 de 198


Marzo 2017
Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:40 0:25
120, 24:00:00 24:00:00 24:00:00 1:40 0:45 0:25 0:15
125, 24:00:00 24:00:00 1:45 0:50 0:30 0:20 0:15
130, 24:00:00 1:40 0:50 0:30 0:20 0:15 0:10
135, 1:40 0:55 0:35 0:25 0:20 0:15 0:10
140, 0:55 0:35 0:25 0:20 0:15 0:10 0:10

Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:35 0:20
120, 24:00:00 24:00:00 24:00:00 1:35 0:40 0:25 0:15
125, 24:00:00 24:00:00 1:40 0:45 0:25 0:20 0:10
130, 24:00:00 1:40 0:50 0:30 0:20 0:15 0:10
135, 1:35 0:50 0:30 0:20 0:15 0:10 0:10
140, 0:50 0:35 0:25 0:20 0:15 0:10 0:05

Estudio de sobrecargas Página 171 de 198


Marzo 2017
Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:30 0:15
120, 24:00:00 24:00:00 24:00:00 1:30 0:35 0:20 0:15
125, 24:00:00 24:00:00 1:30 0:40 0:25 0:15 0:10
130, 24:00:00 1:35 0:45 0:25 0:20 0:10 0:10
135, 1:30 0:45 0:30 0:20 0:15 0:10 0:05
140, 0:50 0:30 0:25 0:15 0:10 0:10 0:05

Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:15 0:25 0:15
120, 24:00:00 24:00:00 24:00:00 1:20 0:30 0:20 0:10
125, 24:00:00 24:00:00 1:25 0:35 0:20 0:15 0:10
130, 24:00:00 1:25 0:40 0:25 0:15 0:10 0:05
135, 1:25 0:45 0:25 0:20 0:15 0:10 0:05
140, 0:45 0:30 0:20 0:15 0:10 0:05 0:05

Estudio de sobrecargas Página 172 de 198


Marzo 2017
Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55 0:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:05 0:20 0:10
120, 24:00:00 24:00:00 24:00:00 1:15 0:30 0:15 0:05
125, 24:00:00 24:00:00 1:20 0:30 0:20 0:10 0:05
130, 24:00:00 1:20 0:35 0:20 0:15 0:10 0:05
135, 1:20 0:40 0:25 0:15 0:10 0:05 0:05
140, 0:40 0:25 0:20 0:15 0:10 0:05 0:00

Cuadro de carga
id 11111 Rhona 18 24 30MVA 66 25_15kV ONAN 18 ONAF1 24 ONAF2 30
Transformador SE Isla De Maipo T3 T-24400 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 30, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:40 0:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 0:55 0:15 0:05
120, 24:00:00 24:00:00 24:00:00 1:05 0:25 0:10 0:05
125, 24:00:00 24:00:00 1:10 0:30 0:15 0:05 0:00
130, 24:00:00 1:15 0:30 0:20 0:10 0:05 0:00
135, 1:15 0:35 0:20 0:15 0:10 0:05 0:00
140, 0:40 0:25 0:15 0:10 0:05 0:05 0:00

Estudio de sobrecargas Página 173 de 198


Marzo 2017
1.35. SE ISLA DE MAIPO T-19800 T2 ID 79745
Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 50, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:05 0:35
120, 24:00:00 24:00:00 24:00:00 3:05 1:15 0:40 0:30
125, 24:00:00 24:00:00 3:00 1:15 0:45 0:30 0:20
130, 24:00:00 2:55 1:20 0:45 0:35 0:25 0:20
135, 2:45 1:20 0:50 0:35 0:25 0:20 0:15
140, 1:25 0:50 0:35 0:30 0:20 0:15 0:15

Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 55, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:00 1:05 0:35
120, 24:00:00 24:00:00 24:00:00 3:00 1:10 0:40 0:25
125, 24:00:00 24:00:00 3:00 1:15 0:45 0:30 0:20
130, 24:00:00 2:55 1:20 0:45 0:30 0:25 0:15
135, 2:45 1:20 0:50 0:35 0:25 0:20 0:15
140, 1:20 0:50 0:35 0:25 0:20 0:15 0:15

Estudio de sobrecargas Página 174 de 198


Marzo 2017
Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 60, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:55 1:00 0:35
120, 24:00:00 24:00:00 24:00:00 3:00 1:05 0:35 0:25
125, 24:00:00 24:00:00 2:55 1:10 0:40 0:25 0:20
130, 24:00:00 2:50 1:15 0:45 0:30 0:20 0:15
135, 2:40 1:20 0:45 0:30 0:25 0:20 0:15
140, 1:20 0:50 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 65, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40 0:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:50 0:55 0:30
120, 24:00:00 24:00:00 24:00:00 2:55 1:05 0:35 0:20
125, 24:00:00 24:00:00 2:50 1:10 0:40 0:25 0:20
130, 24:00:00 2:45 1:10 0:40 0:30 0:20 0:15
135, 2:40 1:15 0:45 0:30 0:20 0:15 0:10
140, 1:15 0:45 0:30 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 175 de 198


Marzo 2017
Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 70, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:55 0:30
120, 24:00:00 24:00:00 24:00:00 2:50 1:00 0:30 0:20
125, 24:00:00 24:00:00 2:45 1:05 0:35 0:25 0:15
130, 24:00:00 2:40 1:10 0:40 0:25 0:20 0:15
135, 2:35 1:10 0:40 0:30 0:20 0:15 0:10
140, 1:15 0:45 0:30 0:25 0:15 0:15 0:10

Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 75, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 0:50 0:25
120, 24:00:00 24:00:00 24:00:00 2:45 0:55 0:30 0:20
125, 24:00:00 24:00:00 2:40 1:00 0:35 0:20 0:15
130, 24:00:00 2:40 1:05 0:35 0:25 0:15 0:10
135, 2:30 1:10 0:40 0:25 0:20 0:15 0:10
140, 1:10 0:40 0:30 0:20 0:15 0:10 0:10

Estudio de sobrecargas Página 176 de 198


Marzo 2017
Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 80, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 0:45 0:20
120, 24:00:00 24:00:00 24:00:00 2:35 0:50 0:25 0:15
125, 24:00:00 24:00:00 2:35 0:55 0:30 0:20 0:10
130, 24:00:00 2:35 1:00 0:35 0:20 0:15 0:10
135, 2:25 1:05 0:35 0:25 0:15 0:10 0:10
140, 1:05 0:40 0:25 0:20 0:15 0:10 0:05

Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 85, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 2:30 0:45 0:20 0:10
125, 24:00:00 24:00:00 2:30 0:50 0:25 0:15 0:10
130, 24:00:00 2:25 0:55 0:30 0:20 0:10 0:05
135, 2:20 1:00 0:35 0:20 0:15 0:10 0:05
140, 1:00 0:35 0:25 0:15 0:10 0:10 0:05

Estudio de sobrecargas Página 177 de 198


Marzo 2017
Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 90, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 0:30 0:15
120, 24:00:00 24:00:00 24:00:00 2:20 0:40 0:20 0:10
125, 24:00:00 24:00:00 2:20 0:45 0:25 0:15 0:05
130, 24:00:00 2:20 0:50 0:25 0:15 0:10 0:05
135, 2:15 0:55 0:30 0:20 0:15 0:10 0:05
140, 1:00 0:35 0:20 0:15 0:10 0:05 0:05

Cuadro de carga
ID 79745 Bonar Long 11,2 MVA 66 12 KV ONAN 8 ONAF1 10 ONAF2 11.2
Transformador SE Isla De Maipo T2 T-19800 Grado de carga inicial de 95, %
Refrigeración tipo ONAF2 Transformador con una potencia de 11,2 MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:30 0:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:25 0:10
120, 24:00:00 24:00:00 24:00:00 2:05 0:30 0:15 0:05
125, 24:00:00 24:00:00 2:10 0:40 0:20 0:10 0:05
130, 24:00:00 2:10 0:45 0:25 0:15 0:05 0:05
135, 2:10 0:50 0:25 0:15 0:10 0:05 0:00
140, 0:55 0:30 0:20 0:15 0:10 0:05 0:00

Estudio de sobrecargas Página 178 de 198


Marzo 2017
1.36. SE LAS ARAÑAS T-18880 T4 ID 72221
Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 50, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:30 0:50
120, 24:00:00 24:00:00 24:00:00 5:10 1:40 0:55 0:40
125, 24:00:00 24:00:00 5:20 1:50 1:00 0:40 0:30
130, 24:00:00 5:10 1:55 1:05 0:45 0:35 0:25
135, 4:55 2:00 1:10 0:50 0:35 0:30 0:20
140, 2:05 1:15 0:50 0:40 0:30 0:25 0:20

Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 55, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:25 0:50
120, 24:00:00 24:00:00 24:00:00 5:10 1:35 0:55 0:35
125, 24:00:00 24:00:00 5:15 1:45 1:00 0:40 0:30
130, 24:00:00 5:10 1:55 1:05 0:45 0:30 0:25
135, 4:55 2:00 1:10 0:45 0:35 0:25 0:20
140, 2:00 1:10 0:50 0:40 0:30 0:25 0:20

Estudio de sobrecargas Página 179 de 198


Marzo 2017
Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 60, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:25 0:45
120, 24:00:00 24:00:00 24:00:00 5:05 1:35 0:50 0:35
125, 24:00:00 24:00:00 5:10 1:40 0:55 0:40 0:25
130, 24:00:00 5:05 1:50 1:00 0:40 0:30 0:25
135, 4:50 1:55 1:05 0:45 0:35 0:25 0:20
140, 2:00 1:10 0:50 0:35 0:30 0:20 0:15

Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 65, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 1:20 0:40
120, 24:00:00 24:00:00 24:00:00 5:00 1:30 0:50 0:30
125, 24:00:00 24:00:00 5:05 1:40 0:55 0:35 0:25
130, 24:00:00 5:00 1:45 1:00 0:40 0:30 0:20
135, 4:45 1:50 1:05 0:45 0:30 0:25 0:20
140, 1:55 1:10 0:45 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 180 de 198


Marzo 2017
Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 70, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:25 1:15 0:40
120, 24:00:00 24:00:00 24:00:00 4:50 1:25 0:45 0:30
125, 24:00:00 24:00:00 5:00 1:35 0:50 0:35 0:25
130, 24:00:00 4:55 1:40 0:55 0:35 0:25 0:20
135, 4:40 1:45 1:00 0:40 0:30 0:20 0:15
140, 1:50 1:05 0:45 0:30 0:25 0:20 0:15

Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 75, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:05 0:35
120, 24:00:00 24:00:00 24:00:00 4:45 1:15 0:40 0:25
125, 24:00:00 24:00:00 4:55 1:25 0:45 0:30 0:20
130, 24:00:00 4:50 1:35 0:50 0:35 0:25 0:15
135, 4:35 1:40 0:55 0:40 0:25 0:20 0:15
140, 1:45 1:00 0:40 0:30 0:25 0:15 0:10

Estudio de sobrecargas Página 181 de 198


Marzo 2017
Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 80, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:25 0:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:00 0:30
120, 24:00:00 24:00:00 24:00:00 4:35 1:10 0:35 0:20
125, 24:00:00 24:00:00 4:45 1:20 0:45 0:25 0:15
130, 24:00:00 4:40 1:30 0:50 0:30 0:20 0:15
135, 4:30 1:35 0:55 0:35 0:25 0:15 0:10
140, 1:40 1:00 0:40 0:30 0:20 0:15 0:10

Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 85, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:55 0:50 0:25
120, 24:00:00 24:00:00 24:00:00 4:25 1:05 0:30 0:20
125, 24:00:00 24:00:00 4:35 1:15 0:40 0:25 0:15
130, 24:00:00 4:35 1:25 0:45 0:30 0:20 0:10
135, 4:20 1:30 0:50 0:30 0:20 0:15 0:10
140, 1:35 0:55 0:35 0:25 0:20 0:10 0:10

Estudio de sobrecargas Página 182 de 198


Marzo 2017
Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 90, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:45 0:20
120, 24:00:00 24:00:00 24:00:00 4:10 0:55 0:25 0:15
125, 24:00:00 24:00:00 4:25 1:05 0:35 0:20 0:10
130, 24:00:00 4:25 1:15 0:40 0:25 0:15 0:10
135, 4:15 1:25 0:45 0:30 0:20 0:10 0:05
140, 1:30 0:50 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID 72221 H. Siddeley 10 MVA 66 13,8 KV ONAN 8 ONAF 10
Transformador SE Las Arañas T4 T-18880 Grado de carga inicial de 95, %
Refrigeración tipo ONAN Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:15 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 3:55 0:45 0:20 0:10
125, 24:00:00 24:00:00 4:10 1:00 0:30 0:15 0:05
130, 24:00:00 4:10 1:10 0:35 0:20 0:10 0:05
135, 4:05 1:15 0:40 0:25 0:15 0:10 0:05
140, 1:25 0:45 0:30 0:20 0:10 0:05 0:05

Estudio de sobrecargas Página 183 de 198


Marzo 2017
1.37. SE MANDINGA T-49900 T1 ID 15662
Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 50, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:20 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:20 0:40
120, 24:00:00 24:00:00 24:00:00 5:00 1:25 0:45 0:30
125, 24:00:00 24:00:00 4:45 1:30 0:50 0:30 0:25
130, 24:00:00 4:20 1:35 0:55 0:35 0:25 0:20
135, 3:55 1:35 0:55 0:40 0:30 0:20 0:15
140, 1:40 1:00 0:40 0:30 0:25 0:20 0:15

Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 55, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:15 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:50 1:15 0:40
120, 24:00:00 24:00:00 24:00:00 5:00 1:25 0:45 0:30
125, 24:00:00 24:00:00 4:40 1:30 0:50 0:30 0:20
130, 24:00:00 4:20 1:35 0:50 0:35 0:25 0:20
135, 3:55 1:35 0:55 0:35 0:25 0:20 0:15
140, 1:35 1:00 0:40 0:30 0:20 0:15 0:15

Estudio de sobrecargas Página 184 de 198


Marzo 2017
Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 60, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:10 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:45 1:10 0:35
120, 24:00:00 24:00:00 24:00:00 4:55 1:20 0:40 0:25
125, 24:00:00 24:00:00 4:40 1:25 0:45 0:30 0:20
130, 24:00:00 4:15 1:30 0:50 0:30 0:25 0:15
135, 3:50 1:35 0:55 0:35 0:25 0:20 0:15
140, 1:35 0:55 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 65, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:05 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:40 1:05 0:35
120, 24:00:00 24:00:00 24:00:00 4:50 1:15 0:40 0:25
125, 24:00:00 24:00:00 4:35 1:20 0:45 0:25 0:20
130, 24:00:00 4:10 1:25 0:45 0:30 0:20 0:15
135, 3:45 1:30 0:50 0:35 0:25 0:15 0:15
140, 1:30 0:55 0:35 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 185 de 198


Marzo 2017
Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 70, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 4:00 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:35 1:00 0:30
120, 24:00:00 24:00:00 24:00:00 4:45 1:10 0:35 0:20
125, 24:00:00 24:00:00 4:30 1:20 0:40 0:25 0:15
130, 24:00:00 4:05 1:25 0:45 0:30 0:20 0:15
135, 3:45 1:25 0:50 0:30 0:20 0:15 0:10
140, 1:30 0:50 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 75, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:50 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:30 0:55 0:25
120, 24:00:00 24:00:00 24:00:00 4:40 1:05 0:30 0:20
125, 24:00:00 24:00:00 4:25 1:15 0:35 0:25 0:15
130, 24:00:00 4:05 1:20 0:40 0:25 0:20 0:10
135, 3:40 1:20 0:45 0:30 0:20 0:15 0:10
140, 1:25 0:50 0:30 0:25 0:15 0:10 0:10

Estudio de sobrecargas Página 186 de 198


Marzo 2017
Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 80, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:40 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:20 0:50 0:25
120, 24:00:00 24:00:00 24:00:00 4:30 1:00 0:30 0:15
125, 24:00:00 24:00:00 4:20 1:10 0:35 0:20 0:15
130, 24:00:00 4:00 1:15 0:40 0:25 0:15 0:10
135, 3:35 1:20 0:40 0:25 0:20 0:15 0:10
140, 1:20 0:45 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 85, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:30 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:10 0:45 0:20
120, 24:00:00 24:00:00 24:00:00 4:25 0:55 0:25 0:15
125, 24:00:00 24:00:00 4:15 1:00 0:30 0:20 0:10
130, 24:00:00 3:50 1:10 0:35 0:20 0:15 0:10
135, 3:30 1:15 0:40 0:25 0:15 0:10 0:05
140, 1:15 0:40 0:25 0:20 0:15 0:10 0:05

Estudio de sobrecargas Página 187 de 198


Marzo 2017
Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 90, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 4:00 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 4:15 0:45 0:20 0:10
125, 24:00:00 24:00:00 4:05 0:55 0:25 0:15 0:10
130, 24:00:00 3:45 1:00 0:30 0:20 0:10 0:05
135, 3:25 1:05 0:35 0:20 0:15 0:10 0:05
140, 1:10 0:40 0:25 0:15 0:10 0:05 0:05

Cuadro de carga
ID 15662 Rhona 8 MVA 69 13.8 KV ONAN 6 ONAF 8
Transformador SE Mandinga T1 T-49900 Grado de carga inicial de 95, %
Refrigeración tipo ONAF1 Transformador con una potencia de 8, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 0:30 0:10
120, 24:00:00 24:00:00 24:00:00 4:05 0:40 0:15 0:05
125, 24:00:00 24:00:00 3:55 0:50 0:20 0:10 0:05
130, 24:00:00 3:35 0:55 0:25 0:15 0:10 0:05
135, 3:15 1:00 0:30 0:20 0:10 0:05 0:00
140, 1:05 0:35 0:20 0:15 0:10 0:05 0:00

Estudio de sobrecargas Página 188 de 198


Marzo 2017
1.38. SE MARCHIGÜE T-50000 T1 ID570207
Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 50, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:10
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:45 1:20 0:45
120, 24:00:00 24:00:00 24:00:00 4:00 1:30 0:50 0:35
125, 24:00:00 24:00:00 4:05 1:35 0:55 0:40 0:30
130, 24:00:00 4:05 1:40 1:00 0:45 0:30 0:25
135, 3:55 1:45 1:05 0:45 0:35 0:25 0:20
140, 1:50 1:10 0:50 0:35 0:30 0:25 0:20

Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 55, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:15 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:40 1:15 0:45
120, 24:00:00 24:00:00 24:00:00 3:55 1:25 0:50 0:35
125, 24:00:00 24:00:00 4:00 1:35 0:55 0:35 0:25
130, 24:00:00 4:00 1:40 1:00 0:40 0:30 0:25
135, 3:55 1:45 1:00 0:45 0:35 0:25 0:20
140, 1:45 1:05 0:45 0:35 0:30 0:20 0:15

Estudio de sobrecargas Página 189 de 198


Marzo 2017
Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 60, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:05
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:35 1:15 0:40
120, 24:00:00 24:00:00 24:00:00 3:50 1:20 0:45 0:30
125, 24:00:00 24:00:00 3:55 1:30 0:50 0:35 0:25
130, 24:00:00 3:55 1:35 0:55 0:40 0:30 0:20
135, 3:50 1:40 1:00 0:40 0:30 0:25 0:20
140, 1:45 1:05 0:45 0:35 0:25 0:20 0:15

Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 65, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 3:05 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:30 1:10 0:40
120, 24:00:00 24:00:00 24:00:00 3:45 1:15 0:45 0:30
125, 24:00:00 24:00:00 3:50 1:25 0:50 0:35 0:25
130, 24:00:00 3:50 1:30 0:55 0:35 0:25 0:20
135, 3:45 1:35 1:00 0:40 0:30 0:20 0:15
140, 1:40 1:00 0:45 0:30 0:25 0:20 0:15

Estudio de sobrecargas Página 190 de 198


Marzo 2017
Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 70, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:55 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:20 1:05 0:35
120, 24:00:00 24:00:00 24:00:00 3:40 1:15 0:40 0:25
125, 24:00:00 24:00:00 3:45 1:20 0:45 0:30 0:20
130, 24:00:00 3:45 1:30 0:50 0:35 0:25 0:20
135, 3:40 1:35 0:55 0:40 0:30 0:20 0:15
140, 1:40 1:00 0:40 0:30 0:25 0:15 0:15

Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 75, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:45 0:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:10 1:00 0:30
120, 24:00:00 24:00:00 24:00:00 3:30 1:10 0:35 0:25
125, 24:00:00 24:00:00 3:40 1:15 0:45 0:30 0:20
130, 24:00:00 3:40 1:25 0:50 0:30 0:20 0:15
135, 3:35 1:30 0:50 0:35 0:25 0:20 0:15
140, 1:35 0:55 0:40 0:30 0:20 0:15 0:10

Estudio de sobrecargas Página 191 de 198


Marzo 2017
Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 80, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 3:00 0:50 0:30
120, 24:00:00 24:00:00 24:00:00 3:20 1:00 0:35 0:20
125, 24:00:00 24:00:00 3:30 1:10 0:40 0:25 0:15
130, 24:00:00 3:35 1:20 0:45 0:30 0:20 0:15
135, 3:30 1:25 0:50 0:35 0:25 0:15 0:10
140, 1:30 0:55 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 85, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:40
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:50 0:45 0:25
120, 24:00:00 24:00:00 24:00:00 3:10 0:55 0:30 0:15
125, 24:00:00 24:00:00 3:20 1:05 0:35 0:20 0:15
130, 24:00:00 3:25 1:10 0:40 0:25 0:15 0:10
135, 3:25 1:20 0:45 0:30 0:20 0:15 0:10
140, 1:25 0:50 0:35 0:25 0:15 0:10 0:05

Estudio de sobrecargas Página 192 de 198


Marzo 2017
Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 90, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:15
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:30 0:40 0:15
120, 24:00:00 24:00:00 24:00:00 2:55 0:50 0:25 0:10
125, 24:00:00 24:00:00 3:10 0:55 0:30 0:20 0:10
130, 24:00:00 3:15 1:05 0:35 0:20 0:15 0:05
135, 3:15 1:10 0:40 0:25 0:15 0:10 0:05
140, 1:20 0:45 0:30 0:20 0:15 0:10 0:05

Cuadro de carga
ID570207 Mitsubishi 10 MVA 66 24-13,8 KV ONAN 8 ONAF 10
Transformador SE Marchigüe T1 T-50000 Grado de carga inicial de 95, %
Refrigeración tipo ONAN Transformador con una potencia de 10, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:20
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 0:30 0:10
120, 24:00:00 24:00:00 24:00:00 2:40 0:40 0:20 0:10
125, 24:00:00 24:00:00 3:00 0:50 0:25 0:15 0:05
130, 24:00:00 3:05 1:00 0:30 0:20 0:10 0:05
135, 3:05 1:05 0:35 0:25 0:15 0:10 0:05
140, 1:10 0:40 0:25 0:20 0:10 0:05 0:00

Estudio de sobrecargas Página 193 de 198


Marzo 2017
1.39. SE PORTEZUELO T-17700 T2 ID30414
Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 50, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:50 1:10 0:40
120, 24:00:00 24:00:00 24:00:00 3:00 1:15 0:45 0:35
125, 24:00:00 24:00:00 3:05 1:20 0:50 0:35 0:25
130, 24:00:00 3:10 1:25 0:55 0:40 0:30 0:25
135, 3:05 1:30 1:00 0:40 0:30 0:25 0:20
140, 1:35 1:00 0:45 0:35 0:25 0:20 0:15

Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 55, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:05
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:30 1:00
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:45 1:05 0:40
120, 24:00:00 24:00:00 24:00:00 2:55 1:10 0:45 0:30
125, 24:00:00 24:00:00 3:05 1:20 0:50 0:35 0:25
130, 24:00:00 3:05 1:25 0:50 0:40 0:30 0:20
135, 3:05 1:30 0:55 0:40 0:30 0:25 0:20
140, 1:30 1:00 0:45 0:35 0:25 0:20 0:15

Estudio de sobrecargas Página 194 de 198


Marzo 2017
Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 60, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:20 0:55
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:40 1:00 0:40
120, 24:00:00 24:00:00 24:00:00 2:55 1:10 0:40 0:30
125, 24:00:00 24:00:00 3:00 1:15 0:45 0:35 0:25
130, 24:00:00 3:00 1:20 0:50 0:35 0:25 0:20
135, 3:00 1:25 0:55 0:40 0:30 0:25 0:15
140, 1:30 0:55 0:40 0:30 0:25 0:20 0:15

Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 65, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:50
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:15 0:50
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:35 1:00 0:35
120, 24:00:00 24:00:00 24:00:00 2:50 1:05 0:40 0:25
125, 24:00:00 24:00:00 2:55 1:10 0:45 0:30 0:20
130, 24:00:00 3:00 1:20 0:50 0:35 0:25 0:20
135, 2:55 1:20 0:50 0:35 0:30 0:20 0:15
140, 1:25 0:55 0:40 0:30 0:25 0:20 0:15

Estudio de sobrecargas Página 195 de 198


Marzo 2017
Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 70, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:10 0:45
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:25 0:55 0:30
120, 24:00:00 24:00:00 24:00:00 2:40 1:00 0:35 0:25
125, 24:00:00 24:00:00 2:50 1:10 0:40 0:30 0:20
130, 24:00:00 2:55 1:15 0:45 0:30 0:25 0:15
135, 2:50 1:20 0:50 0:35 0:25 0:20 0:15
140, 1:25 0:55 0:40 0:30 0:20 0:15 0:10

Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 75, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 2:00 0:40
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:20 0:50 0:30
120, 24:00:00 24:00:00 24:00:00 2:35 1:00 0:35 0:20
125, 24:00:00 24:00:00 2:45 1:05 0:40 0:25 0:15
130, 24:00:00 2:45 1:10 0:45 0:30 0:20 0:15
135, 2:45 1:15 0:45 0:30 0:25 0:15 0:10
140, 1:20 0:50 0:35 0:25 0:20 0:15 0:10

Estudio de sobrecargas Página 196 de 198


Marzo 2017
Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 80, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:45 0:35
115, 24:00:00 24:00:00 24:00:00 24:00:00 2:10 0:45 0:25
120, 24:00:00 24:00:00 24:00:00 2:25 0:55 0:30 0:20
125, 24:00:00 24:00:00 2:35 1:00 0:35 0:25 0:15
130, 24:00:00 2:40 1:05 0:40 0:25 0:20 0:10
135, 2:40 1:10 0:45 0:30 0:20 0:15 0:10
140, 1:15 0:45 0:35 0:25 0:20 0:15 0:10

Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 85, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:10
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:35 0:30
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:55 0:40 0:20
120, 24:00:00 24:00:00 24:00:00 2:15 0:45 0:25 0:15
125, 24:00:00 24:00:00 2:25 0:55 0:30 0:20 0:10
130, 24:00:00 2:30 1:00 0:35 0:25 0:15 0:10
135, 2:35 1:05 0:40 0:25 0:20 0:15 0:10
140, 1:10 0:45 0:30 0:20 0:15 0:10 0:05

Estudio de sobrecargas Página 197 de 198


Marzo 2017
Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 90, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:55
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:20 0:25
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:40 0:35 0:15
120, 24:00:00 24:00:00 24:00:00 2:00 0:40 0:20 0:10
125, 24:00:00 24:00:00 2:15 0:50 0:25 0:15 0:10
130, 24:00:00 2:25 0:55 0:30 0:20 0:10 0:05
135, 2:25 1:00 0:35 0:25 0:15 0:10 0:05
140, 1:05 0:40 0:25 0:20 0:15 0:10 0:05

Cuadro de carga
ID30414 Marelli 18 MVA 110 66 KV ONAN 15 ONAF 18
Transformador SE Portezuelo T2 T-17700 Grado de carga inicial de 95, %
Refrigeración tipo ONAN Transformador con una potencia de 15, MVA
Temperatura ambiente ºC
Grado de carga final% 10, 15, 20, 25, 30, 35, 40,
100, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00
105, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 0:35
110, 24:00:00 24:00:00 24:00:00 24:00:00 24:00:00 1:00 0:15
115, 24:00:00 24:00:00 24:00:00 24:00:00 1:25 0:25 0:10
120, 24:00:00 24:00:00 24:00:00 1:45 0:35 0:15 0:05
125, 24:00:00 24:00:00 2:00 0:40 0:20 0:10 0:05
130, 24:00:00 2:10 0:50 0:30 0:15 0:10 0:05
135, 2:15 0:55 0:30 0:20 0:15 0:05 0:00
140, 1:00 0:35 0:25 0:15 0:10 0:05 0:00

Estudio de sobrecargas Página 198 de 198


Marzo 2017

También podría gustarte