CARGAS POR NIVEL CALZ. MEXICO TACUBA 362

Nivel NIVEL (1) PoPo (1) CM (2) CVMAX (3) CV ACC (4) CV INS (1+2) (1+3) (1+4)
TINACOS 18.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AZOTEA 18.08 23.00 150.00 33.00 22.00 5.00 206.00 195.00 178.00
N5 15.40 118.00 110.00 54.00 29.00 22.00 282.00 257.00 250.00
N4 12.71 118.00 110.00 54.00 29.00 22.00 282.00 257.00 250.00
N3 10.03 118.00 110.00 54.00 29.00 22.00 282.00 257.00 250.00
N2 7.34 118.00 110.00 54.00 29.00 22.00 282.00 257.00 250.00
N1 4.67 118.00 110.00 54.00 29.00 22.00 282.00 257.00 250.00
P.B 1.90 218.00 145.00 56.00 30.00 24.00 419.00 393.00 387.00
EST. SOT -1.80 136.00 116.00 80.00 33.00 14.00 332.00 285.00 266.00
CAJÓN CIM -1.64 244.51 244.51 244.51 244.51

S 967.00 1205.51 439.00 230.00 153.00 2611.51 2402.51 2325.51


2367.00 2158.00 2081.00
ANALISIS SISMICO

Nivel Hi (m) Wi (ton) WiHi Fi (ton) Vi (ton) Mvolt


TINACOS 18.98 0.00 0.00 0.00 0.00 ALTURA ACUMULADA NO
0.00
AZOTEA 18.08 195.00 3525.60 82.11 1484.52
82.11
N5 15.40 257.00 3956.52 92.14 1418.56
174.25
N4 12.71 257.00 3266.47 76.07 966.90
250.33
N3 10.03 257.00 2576.43 60.00 601.53
310.33
N2 7.34 257.00 1886.38 43.93 322.46
354.26
N1 4.67 257.00 1198.91 27.92 130.25
382.18
P.B 1.90 393.00 746.70 17.39 33.04
399.57
S 1873.00 17157.00 4957.27

C= 0.32 CONSIDERADO DEACUERDO AL ESTUDIO DE MECANICA DE SUELOS X= 12.60


Q= 1.50 Z= 25.00
c.s.= 0.213 ATOT= 315.00
PRESIONES DE CONTACTO
Df = 1.64 m. Cargas Verticales su
g= 1.54 m. sm = 8.29 Ton/m^2 11.61

Asentamientos
s= 7.38 Ton/m^2
Presión de Compensación sd = 2.53 Ton/m^2
Ds = 4.85 s perm= 1.86 NO SE ACEPTA, COLOCAR PILOTES
Dsf = Ds-sperm = 2.99 Ton/m^2 PRESION NETA FALTANTE POR ASENTAMIENTOS

e= 2.06 m SI CONSIDERAR
Sismo
sx = 11.93 Ton/m^2 13.13
sz = 10.13 Ton/m^2 11.14

DISEÑO DE LOSA RIGE SISMO slosafondo x = 10.11 Ton/m^2 FACTORIZADO POR 1.1
slosafondo x = 8.13 Ton/m^2 FACTORIZADO POR 1.1

Pilotes PROMEDIO COMPENS NETA FALTANTE


Esfuerzo total estatico = 11.61 t/m2 2.53 t/m2 2.99 t/m2 12.06 t/m2 CAP. PILOTE =
Esfuerzo prom dinámico = 12.13 t/m2 2.53 t/m2 2.99 t/m2 12.59 t/m2 CAP. PILOTE =
Lado o diámetro del Pilote = 80 cm 1 PESO X PILOTE = 17.13 t
Perimetro del pilote = 2.51 m
Longitud efectiva = 14.20 m Peso equiv. estático = 3800 t
Superficie lateral = 35.7 m2 Peso equiv. dinámico = 3966 t

Capacidad de carga Qf = f p L = 124.91 t FR=1.0 ,Qu (estático) = 124.9 t No. Pilotes = 30 521

GENERAL SOSTENES ROCHA 84 - 202, COL DANIEL GARZA, 11830 MEXICO, D.F. TEL/FAX 52 73 00 40 26 14 44 87, CORREO
ELECTRONICO: cafelingenieria@prodigy.net.mx
PAG 2 DE 6

f = fricción promedio del fuste FR=1.0 ,Qu (dinámico) = 124.9 t No. Pilotes = 32 544
en condiciones no drenadas= 3.5 t/m2
Se deberan colocar 32 pilotes distribuidos uniformemente de 80 cm

GENERAL SOSTENES ROCHA 84 - 202, COL DANIEL GARZA, 11830 MEXICO, D.F. TEL/FAX 52 73 00 40 26 14 44 87, CORREO
ELECTRONICO: cafelingenieria@prodigy.net.mx
PAG 3 DE 6

ANALISIS ESTATICO PARA STAAD Q=1.0 (DESPLAZAMIENTOS)

Nivel Hi (m) Wi (ton) WiHi Fi (ton) Vi (ton) Mvolt


TINACOS 18.98 0.00 0.00 0.00 0.00
0.00
AZOTEA 18.08 195.00 3525.60 123.16 2226.78
123.16
N5 15.40 257.00 3956.52 138.22 2127.84
261.38
N4 12.71 257.00 3266.47 114.11 1450.34
375.49
N3 10.03 257.00 2576.43 90.00 902.29
465.49
N2 7.34 257.00 1886.38 65.90 483.70
531.39
N1 4.67 257.00 1198.91 41.88 195.38
573.27
P.B 1.90 393.00 746.70 26.09 49.56
599.36
S 1873.00 17157.00 7435.90

C= 0.32 CONSIDERADO DEACUERDO AL ESTUDIO DE MECANICA DE SUELOS


Q= 1.00
c.s.= 0.320

LONG INERCIA CENTRO C.G. Excent I=Io+SAdy^2 S


X 12.60 4167.5 6.30 6.30 0.00 4167.5 #DIV/0!
Z 25.00 16406.3 12.50 12.50 0.00 16406.3 #DIV/0!

X 6.3
Z 0.0
X 6.3 X 6.3
-Z 12.5 2 3 4 Z 12.5

LX = 12.60 C

-X 6.3 1 6 5 -X 6.3
-Z 12.5 LZ = 25.0 Z 12.5
-X 6.3
Z 0.0
Calculo de esfuerzos estáticos en los puntos
MVx MVz

0 0
Punto Ix Iz dx dz Dsx Dsz Dsest Dsprom Dstotal
Centroide 4167 16406 0.0 0.0 0.0 0.0 0.0 5.76 5.76
1 -6.3 -12.5 0.0 0.0 0.0 5.76 5.76
2 6.3 -12.5 0.0 0.0 0.0 5.76 5.76
3 6.3 0.0 0.0 0.0 0.0 5.76 5.76
4 6.3 12.5 0.0 0.0 0.0 5.76 5.76
5 -6.3 12.5 0.0 0.0 0.0 5.76 5.76

6 -6.3 0.0 0.0 0.0 0.0 5.76 5.76


PRESION NETA MAX, CONSIDERANDO EXCENTRICIDAD EN EL PUNTO MAS DESFAVORABLE 5.76
Calculo de esfuerzos dinámicos en los puntos
MVx MVz
4957 4957
Punto Ix Iz dx dz Dsx Dsz Dsest Dssismo+ Dssismo-
Centroide 4167 16406 0.0 0.0 0.0 0.0 5.76 5.76 5.76
1 6.3 12.5 8.6 6.0 5.76 14.39 -2.87
2 6.3 12.5 8.6 6.0 5.76 14.39 -2.87
3 6.3 0.0 7.5 2.2 5.76 13.25 -1.74
4 6.3 12.5 8.6 6.0 5.76 14.39 -2.87
5 6.3 12.5 8.6 6.0 5.76 14.39 -2.87
6 6.3 0.0 7.5 2.2 5.76 13.25 -1.74

GENERAL SOSTENES ROCHA 84 - 202, COL DANIEL GARZA, 11830 MEXICO, D.F. TEL/FAX 52 73 00 40 26 14 44 87, CORREO
ELECTRONICO: cafelingenieria@prodigy.net.mx
PAG 4 DE 6

PROMEDIO 14.01 -2.49


MAX 14.39 -2.87
INCREMENTO EN EL ESFUERZO SISMICO 8.63

GENERAL SOSTENES ROCHA 84 - 202, COL DANIEL GARZA, 11830 MEXICO, D.F. TEL/FAX 52 73 00 40 26 14 44 87, CORREO
ELECTRONICO: cafelingenieria@prodigy.net.mx
PAG 5 DE 6

PROFUNDIDAD DE EXCAVACIÓN

Edificio: CALZ. MEXICO TACUBA 362

Losa Tapa 0.12 m. (espesor)

Losa Fondo 0.20 m. (espesor)

h= 2.40 m. Alt Contratrabes invertidas= 1.20 m.

h' = 2.08 m. Long.Contratrabes = 162.00 m.

Ancho Contratrabes = 0.20 m.

Contratrabes = 93.31 t.

Losa Fondo = 151.20 t. Intersecciones 0 (Dados)

244.51 t. (PESO DE LA SUBESTRUCTURA)

Peso = 2081.00 t. (SIN CONSIDERAR LA SUBESTRUCTURA)

Peso Total = 2325.51 t. (TODO EL EDIFICIO)

Area= 315.00 m^2

sactuante sneta Prof Total Nivel Losa Tapa Alt.Cajon

H: Altura del cajón 7.38 - 4.85 = 1.64 - 1.80 = -0.16 m.


H=
1.54

gsuelo

NOTA: EN ESTA CONSIDERACIÓN SE TOMA EN CUENTA EL NIVEL DE AGUA FREÁTICA A -

COMO LO INDICA EL ESTUDIO DE MECANICA DE SUELOS.

POR TANTO; EL CAJON TENDRA UNA ALTURA TOTAL DE: -0.16 m.

PROFUNDIDAD DE EXCAVACIÓN CON PLANTILLA: 1.69 m.

GENERAL SOSTENES ROCHA 84 - 202, COL. DANIEL GARZA 11830 MEXICO D.F. TEL/FAX 52 73 00 40 26
14 44 87, CORREO ELECTRONICO cafelingenieria@prodigy.net.mx
PAG 6 DE 6

REVISIÓN DE CAJÓN DE CIMENTACIÓN

Edificio: PLUTARCO ELÍAS CALLES 1383

PROPIEDADES DEL CAJÓN DE CIMENTACIÓN

Losa Tapa 0.09 m. (espesor, losacero)

Losa Fondo 0.20 m. (espesor)

NPT (-) = 2.20 m. Largo del desplante= 24.56 m.

Df (-)= 2.40 m. Ancho del desplante = 11.64 m.

Área = 285.88 m2.

PROPIEDADES DEL TERRENO

γm = 1.60 t/m3.
q adm = 7.00 t/m2.

DESCARGAS DE LA ESTRUCTURA
CONDICIÓN DE CARGA VERTICAL

NTC-01 (PP+SCM+CVm) = 2713.00 t. (SE CONSIDERA LA SUBESTRUCTURA)

PRESIÓN DE CONTACTO = 9.49 t/m2

COMPENSACIÓN = 3.84 t/m2

PRESIÓN NETA = 5.65 t/m2

CONCLUSIÓN: EL TERRENO TIENE SUFICIENTE CAPACIDAD