Documentos de Académico
Documentos de Profesional
Documentos de Cultura
IDGE - ESTUDIOS ELECTRICOS - PART1 - v3
IDGE - ESTUDIOS ELECTRICOS - PART1 - v3
ENERGÉTICA
IDGE
POWER SOLUTIONS
ESTUDIOS DE OPERATIVIDAD
DE LA CTE IQUITOS
ÍNDICE
1. INTRODUCCIÓN ........................................................................................................ 5
2. OBJETIVO .................................................................................................................. 6
3. INFORMACIÓN UTILIZADA ....................................................................................... 7
3.1. Descripción del Proyecto .............................................................................................. 7
3.2. Periodo de Estudio ....................................................................................................... 10
3.3. Oferta del Sistema Eléctrico Iquitos ........................................................................... 10
3.4. Demanda del Sistema Eléctrico Iquitos ..................................................................... 11
4. METODOLOGÍA ....................................................................................................... 13
4.1. Tolerancia a la Circulación de la Corriente de Secuencia Negativa ....................... 13
4.2. Análisis de Flujo de Potencia ...................................................................................... 13
4.3. Análisis de Cortocircuito ............................................................................................. 14
4.4. Determinación del Tiempo Crítico de Despeje de Falla ........................................... 14
4.5. Análisis de Estabilidad Transitoria ............................................................................. 14
5. CRITERIOS TÉCNICOS ............................................................................................ 15
6. EXIGENCIAS DE DISEÑO ........................................................................................ 16
6.1. Tolerancia a Corrientes de Secuencia Inversa .......................................................... 16
7. ANÁLISIS EN ESTADO ESTACIONARIO ................................................................. 18
7.1. Flujo de Potencia en Operación Normal .................................................................... 18
7.1.1. Caso Base – Sin Proyecto ......................................................................................... 18
7.1.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 19
7.1.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 20
7.2. Cortocircuito en Estado Estacionario ........................................................................ 22
7.2.1. Caso Base – Sin Proyecto ......................................................................................... 22
7.2.2. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 22
7.2.3. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 23
7.2.4. Máxima Generación 2024 .......................................................................................... 24
8. TIEMPOS CRÍTICOS DE DESPEJE DE FALLA ........................................................ 25
8.1.1. Periodo 1 con C.T.E. Iquitos 9 MW............................................................................ 25
8.1.2. Periodo 2 con C.T.E. Iquitos 12 MW ......................................................................... 27
8.1.3. Resultados Tiempos Críticos de Despeje de Falla .................................................... 29
9. ESTABILIDAD TRANSITORIA ANTE FALLAS ......................................................... 30
10. ESTABILIDAD DE FRECUENCIA ............................................................................. 33
10.1. Eventos Importantes en el Año 2015 .......................................................................... 33
10.2. Criterio para los Relés de Umbral de Frecuencia ..................................................... 35
10.2.1. Primer umbral de rechazo .......................................................................................... 35
10.2.2. Numero de etapas ..................................................................................................... 35
10.2.3. Temporización............................................................................................................ 35
ÍNDICE DE CUADROS
ÍNDICE DE FIGURAS
1. INTRODUCCIÓN
El proyecto comprende la instalación de una central eléctrica con una capacidad total de salida
de 12 MW a 10.5 kV - 60 Hz, 0.8 factor de potencia, Potencia Continua. Una máquina adicional
será cómo reserva, para mantenimientos y/o reparaciones de cualquier de las otras máquinas.
Cables de MT
Todos los equipos tienen la capacidad para operar 24/7 (24 horas/7 días por semana), menos
durante mantenimiento, por lo que se usa la máquina de reserva. Los generadores operarán a
480 Volt – 60Hz
2. OBJETIVO
3. INFORMACIÓN UTILIZADA
En la Figura 3.1, se muestra el diagrama unifilar del área de influencia considerada en el estudio,
la C.T.E. Iquitos se encuentra encerrado con líneas de color azul.
El proyecto comprende la instalación de 15 generadores con potencia nominal 1.25 MVA cada
uno, factor de potencia de 0.8 y tensión nominal 0.48 kV. Además contará con dos
transformadores de 6.6 MVA (2x3.3 MVA) y un transformador de 3.3 MVA, la relación de
transformación es 10.5/0.48 kV en la C.T.E. Iquitos y la conexión al Sistema Eléctrico Iquitos se
realizará en la celda de reserva “BAO907” (Barra Wartsila G20MW) en 10.5 kV mediante cables
N2XSY de capacidad 354 A y 531 A.
Los transformadores elevadores de la C.T.E. Iquitos son de 3.3 MVA KNAF, 10.5 ± 2x 4.76%/0.48
kV, con rangos de taps ±9.52%. En el siguiente Cuadro se muestran los parámetros de los
transformadores del Sistema Eléctrico Iquitos y de la C.T.E. Iquitos.
S-03
Cab_S-04
B_CATMAK-05
0.0400 km tr2_AuxWartsilaG20MW
1.5MVA 10.5/0.4KV Dyn11_5.92% Cab_AuxWartsilaG20MW
N2XSY 8.7/15KV 3x240 mm2
S-04
0.0400 km tr2_AuxCATMAK-05
1.6MVA 10.5/0.4KV Dyn11_6%
tr2_AuxCATMAK
1.6MVA 10.5/0.4KV Dyn11_6% Cab_ServAuxi
0
N2XSY 3-1x185 mm2
0.0300 km Cab_WARTSILA-Nº05
0
AuxWARTSILAG20MW
AuxCAT MAK-05
0.1200 km Cab_CATMAK-05
0
~
N2XSY 6/10KV 3x120 mm2
AuxCAT MAK
SG
0.0400 km
B_CATMAK 01-02
0.0500 km
WARTSILA-Nº05
~
CAT MAK-05
SG
Cab_WARTSILA-Nº06
N2XSY 8.7/15KV 3x240 mm2
Cab_CATMAK-Nº02 0.1150 km
~
N2XSY 3-1x240 mm2
SG
Breaker/Switch
0.0500 km
~
SG
WARTSILA-Nº06
WARTSILA-WARTSILA G20MW
N2XSY 8.7/15KV 3x240 mm2
S-07
SG
0.0260 km
DESARROLLO
WARTSILA-Nº07
1.0MVA 10.5/0.4KV Dyn11_7.20% 6/10KV-1992 3x500 mm2 ALU
AuxSKODA
B_W ARTSILA
WARTSILA-Nº04
Cab_S-08
N2XSY 3-1x70 mm2
1250 A 0.0400 km
S-08
GESTIÓN ENERGÉTICA
Max353.8Amp(1)
N2XSY 8.7/15KV 3x185 mm2
0.0700 km
Cab_PSE NORTE
N2XSY 3-1x70 mm2
PSE NORTE 0.0400 km
~
B_G1-G3
G01
SG
tr2_CTE-IQUITOS01 Cab_WARTSILA-Nº03
3.3MVA 10.5/0.48KV Dyn11_9.73% 6/10KV-1992 3x300 mm2 ALU
GR_01
EPLI SAC_01 0.0400 km
3.0MVA 10.5/0.4KV Yd5_5.81%
B_G1-G6
~
~
~
G02
SG
SG
SG
1
CAT 3516-Nº01
WARTSILA-Nº03
0 Cab_RESERVA
~
~
N2XSY 3-1x70 mm2
G03
SG
SG
RESERVA 0.0400 km
B_SKODA
CAT 3516-Nº05
0.0150 km
GR_02
0.5000 km
~
~
B_G4-G6
G04
SG
SG
tr2_CTE-IQUITOS02 0.0400 km
N2XSY 8.7/15KV 3x240 mm2
CAT 3516-Nº06
1
~
~
G05
SG
SG
Cab_S-02
WARTSILA-Nº02
1
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
CAT 3512B-PM16
~
GR_03
G06
S-02
SG
EPLI SAC_03
2.5MVA 10.5/0.4KV Dyn11_5.81%
~
SG
Cab_WARTSILA-Nº01
6/10KV-1992 3x70 mm2 ALU
GRUPOS RAPIDOS
0.0300 km
CAT 3512B-PM17
1
~
~
SG
SG
~
B_G7-G9
G07
SG
tr2_CTE-IQUITOS03
0.0350 km
Cab_S-10
WARTSILA-Nº01
CAT 3512B-PM19
Max530.7Amp
3.3MVA 10.5/0.48KV Dyn11_9.73% N2XSY 8.7/15KV 3x120 mm2
0.0400 km
B_G7-G12
0.5000 km
~
G08
N2XSY 8.7/15KV 3x240 mm2
S-10
SG
T-3
SKODA-CAT-Nº3
1
N2XSY 8.7/15KV 3x120 mm2
~
G09
Página 9
SG
0
~
SG
T-4 T-6
1.0MVA 10.1/0.4KV Dyn11_7.11% 1.5MVA 10.5/0.4KV Dyn11_5.4%
CAT 3516-Nº03
~
~
B_G10-G12
G10
SG
SG
0.0600 km
POWER SOLUTIONS
CAT 3516-Nº02
GENERAL MOTOR
(1)
~
~
G11
SG
SG
T-6(1)
GM-Nº1
Line(2)
N2XSY 8.7/15KV 3x120 mm2
~
G12
SG
0.0400 km
0.0400 km
Max353.8Amp
1
~
SG
T-6(2)
1.0MVA 10.5/0.4KV Dyn11_7.14%
CAT 3516-Nº04
Cab_S-11
N2XSY 8.7/15KV 3x185 mm2
~
B_G13-G15
B_G13-G15(1)
G13
SG tr2_CTE-IQUITOS05 0.0400 km
3.3MVA 10.5/0.48KV Dyn11_9.73%
1
S-11
TR2_CUMMINSNº1
2.0MVA 10.5/0.4KV Dyn11_6%
~
G14
SG
Cab_S-06
N2XSY 8.7/15KV 3x120 mm2
1
~
0.0400 km
SG
1
~
C.T.E. IQUITOS
G15
CUMMINS-Nº1
S-06
SG
Figura 3.1 – Diagrama Unifilar del Proyecto
tr2_AuxWartsila Cab_AuxWartsila
0.2540 km
AuxWARTSILA
SR522.9KV
Breaker/Switch(1)
Tr2-SR5 Cab_S-01
7.0MVA 22.9/10KV Ynd5_5.85% N2XSY 8.7/15KV 3x120 mm2
0.0400 km
S-01
SR-5
Cab_SR-4
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
PowerFactory 15.1.7
SR-4
SANTA_ROSA60KV
T-03
BARRA_A_10.5KV
Z_SR
T-04
7.5MVA 60/10KV Ynd5_7.20%
Serv.Aux
-4
SR-2
Cab_SR-2
IQUITOS60KV
0.0400 km T-01
C.T .E. IQUIT OS
Cab_T-01
IQUITOS10.5KV
0.0380 km
N2XSY 8.7/15KV 3x500 mm2
BARRA ALSTOM-SET IQUITOS
Cab_SR-6
060_CT Iquitos - Iquitos
0
0.0540 km
Cab_SR-1
0
Annex:
Cab_SR-9
N2XSY 8.7/15KV 3x120 mm2
0.0400 km
SR-9
BARRA_B_10.5KV
Project: EOCTEIQ
9/16/2015
Graphic: RED_IQUIT OS
DIgSILENT
INGENIERÍA
DESARROLLO
GESTIÓN ENERGÉTICA
La demanda de los alimentadores del sistema Eléctrico Iquitos para el año 2015, fue
proporcionada por la Empresa Electro Oriente, esta información se detalla en el siguiente cuadro.
4. METODOLOGÍA
Según la norma ANSI, la capacidad térmica de corto tiempo del rotor se calcula de acuerdo a la
siguiente expresión:
(I2)2 x t = n
Siendo:
De acuerdo a la Norma ANSI C37.102.1987, las maquinas con potencias nominales menores a
800 MVA pueden soportar en forma permanente corrientes de secuencia negativa del orden del
10% de la corriente nominal.
Igualmente, la misma norma específica que la constante de tiempo (I2/I0)2.t de los generadores
con potencias menores a 800 MVA es de 40 s.
durante el proceso de cálculo. La solución del problema de flujo de potencia permite obtener
principalmente los siguientes resultados:
Los análisis de flujo de potencia, se realizan en condiciones normales de operación con la C.T.E.
Iquitos en los Periodo 1 con 9 MW y Periodo 2 con 12 MW.
El cálculo de las corrientes de cortocircuito se realiza según la norma IEC60909 2001, para fallas
bifásicas a tierra, monofásicas y trifásicas en las barras del Sistema Eléctrico Iquitos. Este
análisis se realizará para las situaciones de máxima, media y mínima demanda para el año 2015.
Los resultados del análisis de cortocircuito, se presentan en cuadros y salidas graficas del
DIGSILENT. Asimismo se simula el escenario de máxima generación, con todos los generadores
operando, con el fin de calcular las mayores corrientes de cortocircuito.
Para ello, se aplicó una falla trifásica en la barra de alta tensión del transformador elevador de la
C.T.E. Iquitos durante 100 ms, luego se procedió a incrementarlo hasta que el generador
perdiese el sincronismo.
El análisis se realiza para las situaciones de máxima, media y mínima demanda en los periodos
1 y 2.
Para encontrar desde el punto de vista dinámico, el impacto que puede producir sobre el sistema
la ocurrencia de disturbios de magnitud importante, tales como cortocircuitos, se analizan los
siguientes casos:
Falla monofásica con recierre exitoso en la línea Iquitos – Santa Rosa 60 kV, al 1% de
la línea desde la S.E. Iquitos.
5. CRITERIOS TÉCNICOS
Los criterios técnicos para el análisis en estado estacionario se describen a continuación y han
sido obtenidas del documento “Procedimiento técnico del COES, PR-20 - Ingreso, modificación
y retiro de instalaciones del SEIN”, aprobado mediante Resolución OSINERGMIN Nº 035-2013-
OS/CD del 14 de marzo de 2013.
Tensión
Estado Normal: debe estar dentro del rango ± 5 % de las tensiones nominales de los
equipos instalados en las subestaciones, principalmente transformadores de potencia.
Asimismo, en el caso de las barras del sistema de transmisión, las tensiones en Estado
Normal deben estar en el rango de ± 2.5 % de las tensiones de operación.
Sobrecargas
Estado Normal: no se admite sobrecargas ni en líneas ni en transformadores de
potencia.
6. EXIGENCIAS DE DISEÑO
Se simula una falla bifásica sin contacto a tierra en los bornes de generación 0.48 kV y en el lado
de alta tensión del generador elevador 10.5 kV, determinándose el cual de los casos se obtiene
una mayor corriente de secuencia inversa.
DIgSILENT
2.323
0.002 s
Y = 2.212 p.u.
1.836
1.350
0.863
0.376
-0.111
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G04: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.
G13: Negative-Sequence Current, Magnitude in p.u.
SEC_INVERSA Date:
Annex: /1
DIgSILENT
1.466
0.002 s
Y = 1.396 p.u.
1.159
0.852
0.545
0.237
-0.070
-0.100 0.119 0.339 0.558 0.777 [s] 0.997
G01: Negative-Sequence Current, Magnitude in p.u.
G07: Negative-Sequence Current, Magnitude in p.u.
G10: Negative-Sequence Current, Magnitude in p.u.
SEC_INVERSA Date:
Annex: /1
I2 tiempo
Falla en: Tensión (kV)
(p.u.) (segundos)
Lado de Baja Tensión 0.48 2.212 8.18
Lado de Alta Tensión 10.5 1.396 20.53
En el cuadro anterior se observa, que la falla que produce mayor incremento de corriente de
secuencia negativa, es la falla bifásica en 0.48 kV y éste tolerará dicha corriente de 2.212 p.u.
por 8.18 segundos.
De acuerdo a los resultados este tiempo de tolerancia de 8.18 segundos, aún bajo la hipótesis
que la corriente inversa no decrece con el tiempo, supera ampliamente cualquier tiempo
razonable que pudiera ser asignado para un esquema de respaldo.
Las simulaciones se realizaron utilizando el programa Digsilent Versión 15.1.7, los análisis
incluyen las situaciones con proyecto y sin proyecto (Periodo 1 y 2), en las condiciones de
máxima, media y mínima demanda para el año 2015.
Se ha simulado los flujos de potencia para la configuración sin la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, están dentro de los rangos
aceptables de operación normal ±5%.
b) Respecto a las sobrecargas del Sistema Eléctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, líneas de transmisión y transformadores:
Del cuadro anterior se observa que las sobrecargas en cables, líneas y transformadores son
menores al 100%.
En el Anexo A1, se puede observar los resultados de las simulaciones de flujo de potencia sin
proyecto.
Se ha simulado los flujos de potencia para la configuración con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, están dentro de los rangos
aceptables de operación normal ±5%.
b) Respecto a las sobrecargas del Sistema Eléctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, líneas de transmisión y transformadores:
Tensión PERIODO 1
Línea / Transformador Nominal Máxima Media Mínima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.26 9.33 22.85
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.71 17.31
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.92 4.62 35.30
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.88 39.74 9.15 20.52
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.02 61.39 5.02 61.36 5.02 61.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 5.01 53.02 5.01 53.00 5.01 52.95
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 17.45 61.54 15.67 55.25 6.76 23.81
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.55 4.71 32.61
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.28 4.62 31.96
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.64 80.07 2.64 80.03 2.64 79.96
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 0.02 0.46 0.02 0.46 0.02 0.46
Del cuadro anterior se observa que las sobrecargas en líneas y transformadores son menores al
100%.
En el Anexo A2, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el año de ingreso.
Se ha simulado los flujos de potencia para la configuración con la C.T.E. Iquitos, de los casos
analizados podemos concluir los siguientes puntos importantes:
Del cuadro anterior se observa que las tensiones en el sistema, están dentro de los rangos
aceptables de operación normal ±5%.
d) Respecto a las sobrecargas del Sistema Eléctrico, en el siguiente cuadro se presenta el nivel
de carga (%) y los MVA en cables, líneas de transmisión y transformadores:
Tensión PERIODO 2
Línea / Transformador Nominal Máxima Media Mínima
[kV] [MVA] [%] [MVA] [%] [MVA] [%]
BARRA ALSTOM-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 22.00 53.89 18.48 45.27 9.34 22.89
Cab_T-01 N2XSY 8.7/15KV 3x500 mm2 11.09 40.82 9.32 34.29 4.72 17.34
Cab_T-02 N2XSY 8.7/15KV 3x120 mm2 10.87 83.24 9.13 69.93 4.62 35.36
IQUITOS-SANTA ROSA 60KV 060_CT Iquitos - Iquitos 21.14 47.34 17.89 39.75 9.16 20.56
Max353.8Amp(1) N2XSY 8.7/15KV 3x185 mm2 5.26 64.32 5.26 64.33 5.26 64.30
Max530.7Amp N2XSY 8.7/15KV 3x240 mm2 7.90 83.49 7.90 83.50 7.89 83.46
WARTSILA G20MW-SET IQUITOS N2XSY 8.7/15KV 3x500 mm2 - - - - - -
WARTSILA-WARTSILA G20MW N2XSY 8.7/15KV 3x240 mm2 18.47 65.12 16.35 57.66 9.60 33.84
T-01 14MVA 60/10KV Ynd5_8.7% 11.08 75.66 9.32 63.56 4.72 32.67
T-02 14MVA 60/10KV Ynd5_8.88% 10.86 74.15 9.13 62.29 4.62 32.01
tr2_CTE-IQUITOS01 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS02 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.87 2.77 83.87 2.77 83.84
tr2_CTE-IQUITOS03 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS04 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.82 2.77 83.83 2.77 83.79
tr2_CTE-IQUITOS05 3.3MVA 10.5/0.48KV Dyn11_9.73% 2.77 83.95 2.77 83.96 2.77 83.92
Del cuadro anterior se observa que las sobrecargas en líneas y transformadores son menores al
100%.
En el Anexo A3, se puede observar los resultados de las simulaciones de flujo de potencia con
proyecto para el año de ingreso.
Las simulaciones se realizaron con el programa Digsilent Versión 15.1.7, para las situaciones
con proyecto y sin proyecto, en las condiciones de máxima, media y mínima demanda para el
año 2015.
En el Anexo B, C y D, se pueden observar los resultados de las simulaciones del cálculo de las
corrientes de cortocircuito, para fallas bifásicas a tierra, monofásicas y trifásicas respectivamente.
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifásicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.9 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentarían
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del cálculo de las
corrientes de cortocircuito para la situación con proyecto en el periodo 1:
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifásicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.24 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentarían
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del cálculo de las
corrientes de cortocircuito para la situación con proyecto en el periodo 2:
De los resultados se concluye que se obtuvieron mayores corrientes de cortocircuito ante fallas
trifásicas, en la barra Wartsila G20MW se observa que la corriente de cortocircuito alcanza
valores de 25.53 kA, el cual supera la capacidad de ruptura de 25 kA.
En las otras barras el nivel de cortocircuito es menor a los 26 kA, por tanto no presentarían
problemas con el equipo existente de 31.5 kA.
En el siguiente cuadro se presentan los resultados de las simulaciones del cálculo de las
corrientes de cortocircuito para la situación de máxima generación (todos los generadores
operando) en la situación con y sin proyecto:
Considerando la operación de todos los generadores, se deberá considerar para el diseño de los
equipos la corriente de cortocircuito de 37 kA en la barra de 10.5 kV (celdas resaltadas de color
rojo).
Secuencia de Simulación:
Se aplicó una falla trifásica en el punto de conexión de la C.T.E. Iquitos en 10.5 kV durante 100
ms, luego se procedió a incrementarlo hasta que el generador perdiese el sincronismo. El análisis
se realiza para las situaciones de máxima, media y mínima demanda para el periodo 1 (con
C.T.E. 9 MW) y periodo 2 (con C.T.E. 12 MW).
Figura 8.1 – Tiempo Crítico de Despeje de Falla – Máxima Demanda (9 MW) – tc=180 ms
DIgSILENT
90.32 115.5
55.56
73.65
-4.333
56.98
-64.23
40.31
-124.1
23.64 -184.0
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
6.968 WARTSILA-Nº03: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-Nº04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-Nº02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-Nº1: Rotor angle with reference to reference machine angle in deg
1.381 10.39
7.036
1.083
3.681
0.784
0.326
0.486
-3.030
0.187 -6.385
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-Nº01: Total Active Power in MW
WARTSILA-Nº02: Total Active Power in MW
-0.111 WARTSILA-Nº03: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-Nº04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-Nº05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-Nº06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-Nº07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-Nº02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-Nº1: Total Active Power in MW
Figura 8.2 – Tiempo Crítico de Despeje de Falla – Media Demanda (9 MW) – tc=190 ms
DIgSILENT
300.00 159.5
119.2
200.00
78.86
100.00
38.53
0.00
-1.800
-100.00 -42.13
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
-200.00 WARTSILA-Nº03: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-Nº04: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg CATMAK-Nº02: Rotor angle with reference to reference machine angle in deg
G11: Rotor angle with reference to reference machine angle in deg CUMMINS-Nº1: c:firel
1.004 22.44
14.47
0.779
6.508
0.554
-1.459
0.329
-9.425
0.105 -17.39
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
WARTSILA-Nº01: Total Active Power in MW
WARTSILA-Nº02: Total Active Power in MW
-0.120 WARTSILA-Nº03: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-Nº04: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-Nº05: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-Nº06: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-Nº07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-Nº02: Total Active Power in MW
G13: m:Psum:bus1 CUMMINS-Nº1: m:Psum:bus1
Figura 8.3 – Tiempo Crítico de Despeje de Falla – Mínima Demanda (9 MW) – tc=200 ms
DIgSILENT
186.9 97.03
69.45
148.9
41.88
110.9
14.30
72.91 -13.28
-40.86
34.93 -0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
WARTSILA-Nº03: c:firel
-3.057 WARTSILA-Nº04: c:firel
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-Nº05: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg CATMAK-Nº02: c:firel
G10: Rotor angle with reference to reference machine angle in deg CUMMINS-Nº1: c:firel
1.003 13.22
8.610
0.764
4.003
0.525
-0.605
0.286
-5.212
0.047 -9.819
-0.100 1.920 3.940 5.960 7.980 [s] 10.000
WARTSILA-Nº01: Total Active Power in MW
WARTSILA-Nº02: Total Active Power in MW
-0.191 WARTSILA-Nº03: m:Psum:bus1
-0.100 1.920 3.940 5.960 7.980 [s] 10.000 WARTSILA-Nº04: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-Nº05: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-Nº06: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-Nº07: Total Active Power in MW
G10: Total Active Power in MW CATMAK-Nº02: m:Psum:bus1
G13: m:Psum:bus1 CUMMINS-Nº1: m:Psum:bus1
Figura 8.4 – Tiempo Crítico de Despeje de Falla – Máxima Demanda (12 MW) – tc=180 ms
DIgSILENT
150.5 55.60
35.15
122.1
14.69
93.83
-5.762
65.52
-26.22
37.21
-46.67
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
8.900 WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-Nº02: Rotor angle with reference to reference machine angle in deg
1.321 16.15
10.69
1.001
5.235
0.681
-0.223
0.362
-5.681
0.042
-11.14
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
-0.278 WARTSILA-Nº01: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº02: Active Power in MW
G01: Active Power in MW WARTSILA-Nº03: Active Power in MW
G04: Active Power in MW WARTSILA-Nº04: Active Power in MW
G07: Active Power in MW WARTSILA-Nº05: Active Power in MW
G10: Active Power in MW WARTSILA-Nº06: Active Power in MW
G13: Active Power in MW WARTSILA-Nº07: Active Power in MW
Figura 8.5 – Tiempo Crítico de Despeje de Falla – Media Demanda (12 MW) – tc=185 ms
DIgSILENT
132.0 34.03
20.95
106.9
7.866
81.74
-5.217
56.61
-18.30
31.48
-31.38
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
6.354 WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-Nº03: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº04: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg CATMAK-Nº02: c:firel
1.345 12.41
8.489
1.012
4.568
0.679
0.648
0.346
-3.273
0.013
-7.194
-0.100 1.920 3.940 5.959 7.979 [s] 9.999
-0.320 WARTSILA-Nº01: Total Active Power in MW
-0.100 1.920 3.940 5.959 7.979 [s] 9.999 WARTSILA-Nº02: Total Active Power in MW
G01: Total Active Power in MW WARTSILA-Nº03: Total Active Power in MW
G04: Total Active Power in MW WARTSILA-Nº04: Total Active Power in MW
G07: Total Active Power in MW WARTSILA-Nº05: Total Active Power in MW
G10: Total Active Power in MW WARTSILA-Nº06: Total Active Power in MW
G13: Total Active Power in MW WARTSILA-Nº07: Total Active Power in MW
Figura 8.6 – Tiempo Crítico de Despeje de Falla – Mínima Demanda (12 MW) – tc=190 ms
DIgSILENT
169.1 52.82
36.66
136.3
20.49
103.6
4.326
70.80
-11.84
38.04
-28.01
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
5.275 WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-Nº02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
0.962 9.810
6.239
0.744
2.667
0.525
-0.904
0.307
-4.475
0.089
-8.046
-0.100 1.919 3.939 5.958 7.977 [s] 9.997
-0.130 WARTSILA-Nº01: Total Active Power in MW
-0.100 1.919 3.939 5.958 7.977 [s] 9.997 WARTSILA-Nº02: m:Psum:bus1
G01: Total Active Power in MW WARTSILA-Nº03: m:Psum:bus1
G04: Total Active Power in MW WARTSILA-Nº04: m:Psum:bus1
G07: Total Active Power in MW WARTSILA-Nº05: m:Psum:bus1
G10: Total Active Power in MW WARTSILA-Nº06: m:Psum:bus1
G13: Total Active Power in MW WARTSILA-Nº07: Total Active Power in MW
De las simulaciones se concluye que el menor valor del tiempo crítico de despeje de falla es de
180 ms en el escenario de máxima demanda, y se encuentra entre 185 ms-190 ms en el
escenario de media demanda y entre190 ms-200 ms en el escenario de mínima demanda, los
tiempos obtenidos son mayores al tiempo normal de operación de las protecciones, igual a 100
ms.
Tiempo Crítico
CASO Escenario Conclusión
(ms)
Máxima Demanda 180 >100ms
Con CT.E Iquitos 9 MW Media Demanda 190 >100ms
Mínima Demanda 200 >100ms
Máxima Demanda 180 >100ms
Con CT.E Iquitos 12 MW Media Demanda 185 >100ms
Mínima Demanda 190 >100ms
Falla monofásica con recierre exitoso en la línea Iquitos – Santa Rosa 60 kV, al 1% de
la línea desde la S.E. Iquitos.
Figura 9.1 – Falla 1ɸ con Recierre Exitoso LT Iquitos – Sta. Rosa en Máxima Demanda
DIgSILENT
18.23 5.562
3.049
18.10
0.537
17.97
-1.975
17.84
-4.488
17.71
-7.000
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
17.57 WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº02: Rotor angle with reference to reference machine angle in deg
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº03: Rotor angle with reference to reference machine angle in deg
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº04: Rotor angle with reference to reference machine angle in deg
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: Rotor angle with reference to reference machine angle in deg
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: Rotor angle with reference to reference machine angle in deg
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
60.66 2.468
2.204
60.52
1.940
60.38
1.675
60.24 1.411
1.146
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.11
WARTSILA-Nº01: Active Power in MW
WARTSILA-Nº02: Active Power in MW
WARTSILA-Nº03: Active Power in MW
WARTSILA-Nº04: Active Power in MW
59.97 WARTSILA-Nº05: Active Power in MW
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº06: Active Power in MW
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-Nº07: Active Power in MW
DIgSILENT
1.05 23.00
1.01
19.00
0.97
15.00
0.93
11.00
0.89
0.85 7.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 3.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-Nº3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW
Figura 9.2 – Falla 1ɸ con Recierre Exitoso LT Iquitos – Sta. Rosa en Mínima Demanda
DIgSILENT
15.09 0.472
-1.605
15.01
-3.682
14.94
-5.759
14.86
-7.837
14.78
-9.914
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
14.71 WARTSILA-Nº01: Rotor angle with reference to reference machine angle in deg
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº02: c:firel
G01: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº03: c:firel
G04: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº04: c:firel
G07: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº05: c:firel
G10: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº06: c:firel
G13: Rotor angle with reference to reference machine angle in deg WARTSILA-Nº07: Rotor angle with reference to reference machine angle in deg
60.41 6.574
6.005
60.33
5.435
60.24
4.866
60.15 4.296
3.727
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
60.07
WARTSILA-Nº01: Total Active Power in MW
WARTSILA-Nº02: m:Psum:bus1
WARTSILA-Nº03: m:Psum:bus1
WARTSILA-Nº04: m:Psum:bus1
59.98 WARTSILA-Nº05: m:Psum:bus1
-0.100 1.919 3.938 5.956 7.975 [s] 9.994 WARTSILA-Nº06: m:Psum:bus1
B_WARTSILA G20MW: Electrical Frequency in Hz WARTSILA-Nº07: Total Active Power in MW
DIgSILENT
1.04 12.00
1.02
10.00
1.00
8.00
0.98
6.00
0.96
0.94 4.00
-0.100 1.919 3.938 5.956 7.975 [s] 9.994
BARRA_A_10.5KV: u1, Magnitude in p.u.
BARRA_B_10.5KV: u1, Magnitude in p.u.
B_ALSTOM: u1, Magnitude in p.u.
B_CATMAK 01-02: u1, Magnitude in p.u.
B_CATMAK-05: u1, Magnitude in p.u.
B_G1-G6: u1, Magnitude in p.u.
B_G13-G15(1): u1, Magnitude in p.u.
B_G7-G12: u1, Magnitude in p.u. 2.00
B_SKODA: u1, Magnitude in p.u. -0.100 1.919 3.938 5.956 7.975 [s] 9.994
B_WARTSILA: u1, Magnitude in p.u. BARRA ALSTOM-SET IQUITOS: Total Active Power/Terminal i in MW
B_WARTSILA G20MW: u1, Magnitude in p.u. IQUITOS-SANTA ROSA 60KV: Total Active Power/Terminal i in MW
CAT-Nº3 10.5KV: u1, Magnitude in p.u. Max353.8Amp: Total Active Power/Terminal i in MW
GRUPOS RAPIDOS: u1, Magnitude in p.u. Max353.8Amp(1): Total Active Power/Terminal j in MW
IQUITOS10.5KV: u1, Magnitude in p.u. Max530.7Amp: Total Active Power/Terminal i in MW
IQUITOS60KV: u1, Magnitude in p.u. WARTSILA G20MW-SET IQUITOS: m:Psum:bus2
PCONEX_CTE: u1, Magnitude in p.u. WARTSILA-CATMAK: Total Active Power/Terminal j in MW
SANTA_ROSA60KV: u1, Magnitude in p.u. WARTSILA-WARTSILA G20MW: Total Active Power/Terminal j in MW
De las simulaciones observamos que el ángulo del rotor, potencia de los generadores, potencia
en líneas y tensiones se estabilizan en el periodo de simulación de 10 segundos.
De acuerdo al evento la generación total pre-falla es 27.75 MW, el cual corresponde al escenario
de mínima demanda. Antes de ocurrir algún rechazo automático de generación o carga la
frecuencia es mayor a 59.8 Hz y menor a 60.02 Hz.
En el segundo caso, evaluaremos la salida del generador GT Cat Mak N° 2, en la siguiente figura
se muestra la evolución en el tiempo de la frecuencia:
De acuerdo al evento la generación total pre-falla es 22.8 MW, el cual corresponde al escenario
de mínima demanda. Antes de ocurrir algún rechazo automático de generación o carga la
frecuencia es mayor a 59.5 Hz y menor a 60.02 Hz.
Por último, tenemos algunos de los eventos importantes, en la siguiente figura se muestra la
evolución en el tiempo de la frecuencia:
Al igual que los primeros eventos podemos verificar que la frecuencia pre-falla se encuentra entre
59.6 Hz y 60.1 Hz.
Por tanto, concluimos que la frecuencia pre-falla (operación normal) es mayor a 59.5 Hz.
El primer umbral de frecuencia no debe estar cercano a la frecuencia nominal del sistema,
permitiendo de esta manera la respuesta natural del sistema ante la variación de la generación.
También se debe considerar que los umbrales de disparo de las protecciones de baja frecuencia
de las unidades de generación es la frecuencia de 57 Hz.
Del análisis de los eventos importantes ocurridos en ELOR se concluye que la frecuencia pre-
falla es mayor a 59.5 Hz, por tanto como primer umbral se utilizará la frecuencia de 59.0 Hz.
Siendo el primer umbral 59 Hz, el paso entre etapas será fijo e igual a -0.1 Hz, es decir el umbral
para la segunda etapa es 58.9 Hz, para la tercera etapa es 58.8 Hz, para la cuarta etapa es 58.7
Hz, para la quinta etapa es 58.6 Hz. El valor de -0.1 Hz es muy usual en sistemas de potencia y
puede considerarse estándar.
10.2.3. Temporización
La temporización es igual para todas las etapas, con el fin de permitir que el efecto causado por
el rechazo de cada etapa en la dinámica del sistema se efectivice antes de que actué la siguiente
etapa. Se ha seleccionado una temporización de 150 ms, en la selección de esta temporización
se tiene en cuenta la demora de los interruptores en abrir efectivamente (85 ms).
En el análisis se buscará rechazar la menor carga hasta que el sistema sea estable y la
frecuencia final se encuentre entre 59.5 Hz y 60.5 Hz.
Las características del rechazo de carga por derivada de frecuencia son similares a las de umbral
de frecuencia, con la diferencia de que para todas las etapas se tiene un umbral de frecuencia
común. El coordinamiento entre etapas se establece mediante los valores de la pendiente.
respuesta natural del sistema Iquitos, con este valor se esperaría una rápida acción de rechazo,
el cual se verifica en las simulaciones realizadas
Generación 9 MW Generación 12 MW
Indicador Máxima Media Mínima Máxima Media Mínima
Demanda Demanda Demanda Demanda Demanda Demanda
Total Carga (MW) 53.46 48.30 22.02 53.46 48.30 22.02
Total Generación (MW) 54.14 48.85 22.35 54.14 48.85 22.35
Pérdida de Generación (MW) 9.00 9.00 9.00 12.00 12.00 12.00
% Pérdida Generación/Carga 16.8% 18.6% 40.9% 22.4% 24.8% 54.5%
La salida de la C.T.E. Iquitos en mínima demanda representa el 40.9% y 54.5%, en estos casos
donde se presentan gran déficit de generación es necesario realizar rechazar más del porcentaje
para que el sistema pueda recuperar la frecuencia.
Número de Porcentaje de Rechazo Réles por Umbral Réles por Derivada de Frecuencia
Etapa en cada Etapa (*) Umbral (Hz) Temporización (s) Umbral (Hz/s) Temporización
1 8% 59.0 0.15 -0.9 0.12
2 5% 58.9 0.15 -0.7 0.12
3 4% 58.8 0.15 -0.7 0.12
4 4% 58.7 0.15
5 30% 58.6 0.15
(*) Porcentaje de carga para cualquier escenario (máxima, media y mínima demanda)
A continuación se verificará la actuación del ERCMF ante la salida de la C.T.E. Iquitos en los
caos de salida de la CTE con 9 MW y 12 MW en máxima, media y mínima demanda.
Figura 10.4 – Verificación del ERCMF en el Periodo 1 (C.T.E.I 9 MW) – Máxima Demanda
DIgSILENT
60.25
2.686 s
59.987 Hz
60.00
59.75
45.568 s
59.558 Hz
0.831 s
0.161 s Y = 59.500 Hz
59.50
59.25
0.332 s Y = 59.100 Hz
0.351 s
59.059 Hz
Y = 59.000 Hz
59.00
-0.100 9.920 19.94 29.96 39.98 [s] 50.00
WARTSILA-Nº05: Electrical Frequency in Hz
WARTSILA-Nº06: Electrical Frequency in Hz
WARTSILA-Nº07: Electrical Frequency in Hz
Figura 10.5 – Verificación del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Media Demanda
DIgSILENT
60.30
60.00
57.666 s
60.147 Hz
59.70
1.150 s
0.145 s Y = 59.500 Hz
59.40
0.532 s
0.281 s Y = 59.100 Hz
59.10
Y = 59.000 Hz
0.350 s
58.956 Hz Y = 58.900 Hz
Y = 58.800 Hz
58.80
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-Nº05: Electrical Frequency in Hz
WARTSILA-Nº06: Electrical Frequency in Hz
WARTSILA-Nº07: Electrical Frequency in Hz
Figura 10.6 – Verificación del ERCMF en el Periodo 1 (C.T.E.I 9 MW) - Mínima Demanda
DIgSILENT
63.25
Y = 63.000 Hz
2.706 s
62.957 Hz
62.00
60.75
0.977 s 11.513 s Y = 60.500 Hz
52.658 s
59.871 Hz
0.737 s
0.008 s Y = 59.500 Hz
59.50
0.656 s
0.092 s Y = 59.100 Hz
Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.492 s
58.25 0.196 s Y = 58.200 Hz
0.365 s
57.477 Hz
57.00
-0.100 11.92 23.94 35.96 47.98 [s] 59.99
WARTSILA-Nº05: n:fehz:bus1
WARTSILA-Nº06: n:fehz:bus1
WARTSILA-Nº07: Electrical Frequency in Hz
DIgSILENT
63.25
Y = 63.000 Hz
62.00
60.75
0.977 s Y = 60.500 Hz
0.049 s
0.020 s
0.008 s 0.737 s Y = 59.500 Hz
59.50
0.369 s
57.473 Hz
57.00
-0.100 0.485 1.071 1.656 2.241 [s] 2.827
WARTSILA-Nº05: n:fehz:bus1
WARTSILA-Nº06: n:fehz:bus1
WARTSILA-Nº07: Electrical Frequency in Hz
Figura 10.7 – Verificación del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Máxima Demanda
DIgSILENT
60.20
59.90
55.873 s
59.733 Hz
59.60
59.30
2.626 s
0.205 s Y = 59.100 Hz
Y = 59.000 Hz
59.00
Y = 58.900 Hz
Y = 58.800 Hz
0.309 s
58.780 Hz
Y = 58.700 Hz
58.70
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-Nº05: Electrical Frequency in Hz
WARTSILA-Nº06: Electrical Frequency in Hz
WARTSILA-Nº07: Electrical Frequency in Hz
Figura 10.8 – Verificación del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Media Demanda
DIgSILENT
60.30
56.996 s
59.90 59.757 Hz
1.321 s
0.167 s Y = 59.100 Hz
59.10
Y = 59.000 Hz
Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
58.70
Y = 58.600 Hz
0.470 s
58.570 Hz Y = 58.500 Hz
58.30
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-Nº05: Electrical Frequency in Hz
WARTSILA-Nº06: Electrical Frequency in Hz
WARTSILA-Nº07: Electrical Frequency in Hz
Figura 10.9 – Verificación del ERCMF en el Periodo 2 (C.T.E.I 12 MW) - Mínima Demanda
DIgSILENT
61.00
Y = 60.500 Hz
3.851 s
59.932 Hz
60.00
48.168 s
59.588 Hz
1.881 s
0.007 s Y = 59.500 Hz
1.450 s
0.009 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
0.906 s
0.120 s Y = 58.200 Hz
58.00
57.00
0.306 s
56.478 Hz
56.00
-0.100 11.92 23.94 35.96 47.98 [s] 60.00
WARTSILA-Nº05: n:fehz:bus1
WARTSILA-Nº06: n:fehz:bus1
WARTSILA-Nº07: Electrical Frequency in Hz
DIgSILENT
61.00
Y = 60.500 Hz
60.00
0.056 s
0.009 s 1.450 s Y = 59.100 Hz
Y = 59.000 Hz
59.00 Y = 58.900 Hz
Y = 58.800 Hz
Y = 58.700 Hz
Y = 58.600 Hz
Y = 58.500 Hz
58.00
57.00
0.306 s
56.478 Hz
56.00
-0.100 0.570 1.240 1.910 2.580 [s] 3.250
WARTSILA-Nº05: n:fehz:bus1
WARTSILA-Nº06: n:fehz:bus1
WARTSILA-Nº07: Electrical Frequency in Hz
mínima frecuencia del alimentador R-5 actuaría. Se recomienda cambiar la temporización del
relé por mínima frecuencia del alimentador R-5 a 0.8 s.
Ante la pérdida de generación igual a 9 MW se debe rechazar 9.09 MW, 8.21 MW y 11.23 MW
en el escenario de máxima, media y mínima demanda respectivamente.
a) La falla bifásica en 0.48 kV produce una mayor corriente de secuencia negativa y éste
tolerará dicha corriente de 2.212 p.u. por 8.18 segundos. De acuerdo a los resultados este
tiempo de tolerancia de 8.18 segundos, aún bajo la hipótesis que la corriente inversa no
decrece con el tiempo, supera ampliamente cualquier tiempo razonable que pudiera ser
asignado para un esquema de respaldo.
e) De las simulaciones se concluye que el menor valor del tiempo crítico de despeje de falla es
180 ms, el tiempo determinado es mayor al tiempo normal de operación de las protecciones,
igual a 100 ms.
f) Ante una falla monofásica con recierre exitoso en la línea Iquitos-Santa Rosa 60 kV, no se
pierde sincronismo de las centrales, las tensiones, potencia y velocidad se estabilizan en el
periodo de simulación de 10 segundos.
i) Por lo mencionado, de los análisis eléctricos se concluye que las nuevas instalaciones que
conforman el proyecto “C.T.E. IQUITOS”, cumplen con el objetivo principal de brindar el
suministro de energía adicional de manera continua y confiable y no afecta la operación
actual de las demás instalaciones del proyecto.
12. ANEXOS
================================================
Anexo A – Flujo de Potencia
================================================
A1 – Caso Base
A1.1 Máxima Demanda
A1.2 Media Demanda
A1.3 Mínima Demanda
A2 – Periodo 1 – Con C.T.E. Iquitos 9 MW
A2.1 Máxima Demanda
A2.2 Media Demanda
A2.3 Mínima Demanda
A3 – Periodo 2 – Con C.T.E. Iquitos 12 MW
A3.1 Máxima Demanda
A3.2 Media Demanda
A3.3 Mínima Demanda
================================================
Anexo B – Cortocircuito Caso Base – Sin CTE Iquitos
================================================
B1 – Cortocircuito Bifásico a Tierra
B1.1 Máxima Demanda
B1.2 Media Demanda
B1.3 Mínima Demanda
B2 – Cortocircuito Monofásico
B2.1 Máxima Demanda
B2.2 Media Demanda
B2.3 Mínima Demanda
B3 – Cortocircuito Trifásico
B3.1 Máxima Demanda
B3.2 Media Demanda
B3.3 Mínima Demanda
================================================
Anexo C – Cortocircuito – Con CTE Iquitos – 9 MW
================================================
C1 – Cortocircuito Bifásico a Tierra
C1.1 Máxima Demanda
C1.2 Media Demanda
C1.3 Mínima Demanda
C2 – Cortocircuito Monofásico
C2.1 Máxima Demanda
C2.2 Media Demanda
C2.3 Mínima Demanda
C3 – Cortocircuito Trifásico
C3.1 Máxima Demanda
================================================
Anexo G - Escenario de Máxima Generación
================================================
G1 – Cortocircuito Trifásico
G1.1 Sin C.T.E. Iquitos
G1.2 Con C.T.E. Iquitos
================================================
Anexo H – Base de Datos Digsilent
================================================