Comportamiento de la corriente de
cortocircuito de un Generador Sncrono:
Comportamiento de la corriente de
cortocircuito de un Generador Sncrono:
Xd(t)
Xd
X'd
X''d
Generador
Falla trifsica:
Transformador
Lnea
R
I/kA
1.0
-0.02
-0.01
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.04
0.05
0.06
0.07
0.08
t/s
0.0
-1.0
Line1:m:I:bus1:A A
Line1:m:I:bus1:B B
Line1:m:I:bus1:C C
p.u.
0.5
0.0
-0.02
-0.01
0.00
0.01
0.02
0.03
t/s
-0.5
-1.0
Line1:m:u:bus1:B B
Line1:m:u:bus1:A A
Line1:m:u:bus1:C C
Falla trifsica:
Fasores previa a la falla
Va
Va
Ic
Ia
Ia
Ic
Vb
Vc
Vb
Ib
Vc
Ib
Generador
Transformador
Lnea
R
I/kA
0.5
0.0
-0.025
-0.000
0.025
0.050
0.075
0.100
0.125
0.150
0.075
0.100
0.125
0.150
t/s
-0.5
-1.0
Line1:m:I:bus1:A A
Line1:m:I:bus1:B B
Line1:m:I:bus1:C C
p.u.
1.0
-0.025
-0.000
0.025
0.050
t/s
0.0
-1.0
Line1:m:u:bus1:B B
Line1:m:u:bus1:A A
Line1:m:u:bus1:C C
Va
Va
Ia
Ia
Ic
Ic
Ib
Vc
Vb
Vc
Vb
Ib
Generador
Transformador
Lnea
R
I/kA
1.0
0.0
-0.03
-0.02
-0.01
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.04
0.05
0.06
0.07
0.08
0.09
0.10
t/s
-1.0
Line1:m:I:bus1:A A
Line1:m:I:bus1:B B
Line1:m:I:bus1:C C
p.u.
1.0
-0.03
-0.02
-0.01
0.00
0.01
0.02
0.03
t/s
0.0
-1.0
Line1:m:u:bus1:B B
Line1:m:u:bus1:A A
Line1:m:u:bus1:C C
Generador
Transformador
Lnea
R
I/kA
1.0
-0.03
-0.02
-0.01
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
t/s
0.0
-1.0
Line1:m:I:bus1:A A
Line1:m:I:bus1:B B
Line1:m:I:bus1:C C
IE*/kA
0.5
0.0
-0.03
-0.02
-0.01
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
-0.02
-0.01
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
t/s
-0.5
-1.0
IE*
p.u.
1.0
0.5
-0.03
t/s
0.0
-0.5
-1.0
Line1:m:u:bus1:B B
Line1:m:u:bus1:A A
Line1:m:u:bus1:C C
Generador
Transformador
Lnea
R
I/A
300
200
100
0
0.06
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.22
0.24
0.16
0.18
0.20
0.22
0.24
-100
t/s
-200
-300
Line1:m:I:bus1:A A
Line1:m:I:bus1:B B
Line1:m:I:bus1:C C
p.u.
1.0
0.0
0.06
0.08
0.10
0.12
0.14
t/s
-1.0
Line1:m:u:bus1:B B
Line1:m:u:bus1:A A
Line1:m:u:bus1:C C
10
Generador
Transformador
Lnea
DIgSILENT
R
40.00
0.021 s
39.709 kA
0.475 s
14.543 kA
20.00
0.00
0.029 s
1.241 kA
-20.00
0.483 s
-9.609 kA
-40.00
-0.1000
0.0200
GS1: Phase Current A in kA
GS1: Phase Current B in kA
GS1: Phase Current C in kA
0.1400
0.2600
0.3799
[s]
0.4999
11
R
S
T
R
S
T
Falla monofsica
S.E. A
S.E. B
12
R
S
T
R
S
T
Desconexin monofsica
S.E. A
S.E. B
13
R
S
T
S.E. A
R
S
T
S.E. B
Recierre exitoso
(Si la falla no es permanente y el arco elctrico secundario se extingue)
14
S.E. A
R
T
Falla monofsica
15
S.E. B
T
Desconexin monofsica
16
S.E. B
17
S.E. A
R
T
Recierre exitoso
Si la falla no es permanente y el arco elctrico
secundario se extingue, el banco de
compensacin serie queda puenteada por un
tiempo razonable para identificar que la falla fue
eliminada.
18
S.E. B
T
Ciclo de recierre exitoso
Apertura automtica del interruptor
del banco de compensacin serie:
19