Está en la página 1de 4

MEMORIA DE CALCULO

PROYECTO: INSTALACIONES ELECTRICAS DOMICILIARIAS


AREA TERRENO
AREA TECHADA1 PLANTA TRAS.
AREA TECHADA1 PLANTA
AREA TECHADA 2 PLANTA
TOTAL

312
17.43
157.55
156.6
332

AREA LIBRE

135.07

TOTAL

SEGN CNE 25 WATTS/M2 AREA TECHADA


C.I1 =

332 X 25 =

8,300 WATTS TECHADA

C.I2 =

1500 WATTS - TOMACORRIENTES

C.I.3 =

2000 WATTS x 0.3 = 600 WATTS (CARGA MOVIL, TERMA)

C.I.4 =

135 M2 x 5 W/M2 = 675.35 (A. L.)

C.I.5 =

1200 WATTS (TERMA 1,100 Wx 1 UNID.)

CARGA INSTALADA TOTAL

MD 1
MD 2
MD 3
MD 4
MD 5
MD 6

C.I.T. =

8,300 + 1500 + 600 + 675.35 + 1200

TOTAL =

12,275.35 WATTS

CI
2000

x
x

FD
MD
100%

9,075.55

35%

1200

100%

MD T

CALCULO DE LA SECCION DEL CONDUCTOR ALIMENTADOR

2000

3176.44

1200
6376.44

IN =

6376.44

WATTS

3 x 220 V. x 0.9
IN=

18.59 AMPERIOS

ID =

IS x IN

ID =

1.10 x 18.59 =

ID =

20 AMPERIOS

IS 25%
20.449 =

20

CONDUCTOR :
3- 10x 10 MM2 TW + 1 x 10 MM2 PVC 25 MM OP
CIRCUITOS ESPECIALES
CALENTADOR ELECTRICO :
IN =

MDT
V x COS O

IN=

1200 WATTS
220 x 1.0

= 5.45 AMPERIOS

ID =

1.12 x 5.45

= 6.10 AMPERIOS

CONDUCTOR 1.5 MM2 TW HASTA10 AMPERIOS


CIRCUITO DE ALUMBRADO
C.I1 =

25 W/M2 x 100 m2

I1 =

2500 = 14.20 AMPERIOS


220 x 0.9

C.I2 =

18 SALIDA MAX. X 100 m2

I1 =

1800 = 10.22 AMPERIOS


220 x 0.9

I1 > I2
I2 =

1.25 x 10.22 =

12.78 A. < 14.20 A. ------ MARGEN 25%

18 x 0.81 A.

= 14.58 A.

TOMACORRIENTES
IN =

WATTS (CARGA MOVIL, TERMA)

WATTS

< 14.20 A. ------ MARGEN 25%