-*ESQUEMA UNILINEAL

AL.
"C-1" ALIMENTADOR "C-1"
3 x 8.37mm2 X.C.S
t.p.r.e. de 20mmØ
DUCTO t.p.r.s 63mmØ.
LARGO 20m.
COCINA
C6 t.p.r.e. de 20mmØ t.p.r.e. de 20mmØ

T.D.A "C-1"
TABLERO METALICO
2x50A
10KA IP 41
QUINCHO
C9
"C"
LIVING DORMITORIO BAÑO DORMITORIO ESPECIAL
C11
C8 C3

REPARTIDOR DE 75Amp.-10KA

1x6A
P P P P P P
D D D D D D 10KA
"C"
2X25A 2X40A 2X40A 2X40A 2X40A 2X16A
30mA 30mA 30mA 30mA 30mA 30mA

REPARTIDOR DE 75Amp.-10KA REPARTIDOR DE 75Amp.-10KA REPARTIDOR DE 75Amp.-10KA REPARTIDOR DE 75Amp.-10KA REPARTIDOR DE 75Amp.-10KA

2x10A 2x10A 2x10A 1x16A 1x16A 1x16A 1x20A 1x16A 1x20A 1x16A 1x16A
10KA 10KA 10KA 10KA 10KA 10KA 10KA 10KA 10KA 10KA 10KA RH RH
"C" "C" "C" "C" "C" "C" "C" "C" "C" "C" "C"
K1 K2
PLANTA DE CTES DEBILES
Esc: 1/50
K1 K2

1 2 3 4 5 6 7 8 9 10 11

DETALLE UNA CAJA

DETALLE DOS CAJAS DETALLE TRES CAJAS

DETALLE Nº1 - CAJAS ELECTRICAS


NOTAS:
-TODOS LOS ARTEFACTOS INDICADOS EN SIMBOLOGIA; MODELO Y MARCA ESTAN SUJETOS A LA
EN MOCHETA
APROBACION DEL ARQUITECTO Y/O PROPIETARIO.
-DONDE SE INDIQUEN MAS DE 7 CONDUCTORES, SE DEBERA CONSIDERAR DUCTO P.V.C. DE
25mm.Ø, SALVO INDICACION CONTRARIA EN PLANOS.
-SI EL SUB-ALIMENTADOR SOBREPASA LA LONGITUD INDICADA EN CUADROS DE CARGA, SE DEBERA
CALCULAR NUEVAMENTE LA CAIDA DE TENSIÓN Y ESTE NO DEBE EXCEDER EL 3%.
-TODAS LAS COTAS DE ILUMINACION Y ENCHUFES EN LAS CAPSULA SON EQUIVALENTES
EN TODO EL PROYECTO
INGENIERIA ELECTRICA
1x**A Galvarino Gallardo Nº1776 Providencia - Santiago Fono:2946 2031 Fax :2946 2033
xxKA E-mail : cgana@icgsa.cl, cconcha@icgsa.cl, planos@icgsa.cl

2x**A

xxKA

2x**A
P 30mA
D xxKA

FUS 2 Amp