Comandos

en LMT

WILBERTH MORALES GARCIA

JESUS MARROQUIN DARDON


CONFIGURACION DE ALARMAS
EXTERNAS

BATERIAS EN DESCARGA:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=0,SW=ON,AID=65044,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65044, ANM="BATERIAS EN DESCARGA", ALVL=MAJOR, ASS=ENV;
Borrar alarma
SET ALMPORT: CN=0, SRN=0, SN=19, PN=0, SW=OFF;

FALLA DE RECTIFICADORES:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=1,SW=ON,AID=65047,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65047, ANM="FALLA DE RECTIFICADORES", ALVL=MAJOR, ASS=ENV;

ALTA TEMPERATURA:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=2,SW=ON,AID=65048,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65048, ANM="FALLA DE RECTIFICADORES", ALVL=MAJOR, ASS=ENV;

CONFIGURACION DE ALARMAS EN EXT-ALM1 (AC, MG OPERANDO, FALLA DE MG)


CORTE DE AC COMERCIAL:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=4,SW=ON,AID=65042,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65042, ANM="CORTE AC COMERCIAL", ALVL=MAJOR, ASS=ENV;

MG OPERANDO:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=5,SW=ON,AID=65045,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65045, ANM="MG OPERANDO", ALVL=MAJOR, ASS=ENV;

FALLA DE MG:
SET ALMPORT:CN=0,SRN=0,SN=19,PN=6,SW=ON,AID=65046,PT=BOOL,AVOL=HIGH;
SET ENVALMPARA: ALMID=65046, ANM="FALLA DE MG", ALVL=MAJOR, ASS=ENV;
LISTADO DE ALARMAS
EXTERNAS
LISTADO DE COMANDOS EN LMT
LISTADO DE COMANDOS EN LMT