Declarar alarmas en GSM

// General de CA:
SET
BTSENVALMPORT:IDTYPE=BYNAME,BTSNAME="173658",CN=0,SRN=0,SN=18,PN=0,SW=OPEN,AID=65033,PT=BOOL,AVO
L=LOW;
// Fuerza Menor
SET
BTSENVALMPORT:IDTYPE=BYNAME,BTSNAME="173658",CN=0,SRN=0,SN=18,PN=1,SW=OPEN,AID=65036,PT=BOOL,AVO
L= LOW;
//Fuerza Mayor
SET
BTSENVALMPORT:IDTYPE=BYNAME,BTSNAME="173658",CN=0,SRN=0,SN=18,PN=2,SW=OPEN,AID=65035,PT=BOOL,AVO
L= LOW;
//Alta Temperatura
SET
BTSENVALMPORT:IDTYPE=BYNAME,BTSNAME="173658",CN=0,SRN=0,SN=18,PN=4,SW=OPEN,AID=65046,PT=BOOL,AVO
L= LOW;
//Puerta Abierta
SET
BTSENVALMPORT:IDTYPE=BYNAME,BTSNAME="173658",CN=0,SRN=0,SN=19,PN=0,SW=OPEN,AID=65037,PT=BOOL,AVO
L=HIGH;

Se pueden declarar las alarmas en las tarjetas UEIU (Slot 18) ó UPEU (Slot 19).
BOOL significa que los valores son 1 ó 0.
AVOL significa la lógica. Se pueden invertir las lógicas (LOW/HIGH).  

 
 
 
Las alarmas para ambos sitios ya están cargadas físicamente en los equipos.
 

 
Declarar alarmas en UMTS
3G: Se ejecuta en cada NodoB
SET ENVALMPARA:ALMID=65033,ANM="ALARMA GENERAL DE CA",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:ALMID=65036,ANM="ALARMA FUERZA MENOR",ALVL=MAJOR,ASS=ENV;
SET ENVALMPARA:ALMID=65035,ANM="ALARMA FUERZA MAYOR",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:ALMID=65046,ANM="ALTA TEMPERATURA INCENDIO",ALVL=CRITICAL,ASS=ENV;
SET ENVALMPARA:ALMID=65037,ANM="ALARMA PUERTA ABIERTA",ALVL=CRITICAL,ASS=ENV;

SET ENVALMPARA:ALMID=65038,ANM="ALARMA GENERADOR EN SERVICIO",ALVL=CRITICAL,ASS=ENV;


SET ALMPORT:CN=0,SRN=0,SN=19,PN=0,SW=ON,AID=65038,PT=BOOL,AVOL=HIGH;

SET ENVALMPARA:ALMID=65049,ANM="ALARMA BAJO NIVEL DE COMBUSTIBLE",ALVL=CRITICAL,ASS=ENV;


SET ALMPORT:CN=0,SRN=0,SN=19,PN=1,SW=ON,AID=65049,PT=BOOL,AVOL=HIGH;

SET ENVALMPARA:ALMID=65039,ANM="ALARMA FALLA DE GENERADOR",ALVL=CRITICAL,ASS=ENV;


SET ALMPORT:CN=0,SRN=0,SN=19,PN=2,SW=ON,AID=65039,PT=BOOL,AVOL=HIGH;

SET ALMPORT:CN=0,SRN=0,SN=19,PN=0,SW=ON,AID=65033,PT=BOOL,AVOL=HIGH;
SET ALMPORT:CN=0,SRN=0,SN=19,PN=1,SW=ON,AID=65036,PT=BOOL,AVOL=HIGH;
SET ALMPORT:CN=0,SRN=0,SN=19,PN=2,SW=ON,AID=65035,PT=BOOL,AVOL=HIGH;
SET ALMPORT:CN=0,SRN=0,SN=19,PN=2,SW=ON,AID=65046,PT=BOOL,AVOL=HIGH;
SET ALMPORT:CN=0,SRN=0,SN=19,PN=3,SW=ON,AID=65037,PT=BOOL,AVOL=HIGH;

Se pueden declarar las alarmas en las tarjetas UEIU (Slot 18) ó UPEU (Slot 19).
BOOL significa que los valores son 1 ó 0.
AVOL significa la lógica. Se pueden invertir las lógicas (LOW/HIGH).  