Está en la página 1de 6

CALCULO DE LA RED DOMICILIARIA DE AGUA POTABLE

TRAMO CAUDAL CAUDAL LONG N° COEF N° COEF N° COEF N° COEF LONG LONG J J
INSTALADOMAX PROB DIAM VELOC REAL CODO CODO TEE TEE TEE TEE VALV VALV EQUIV TOTAL UNIT TOT
(l/m) (l/m) (mm) (m/s) (m) DIR DIR LAT/BIL LAT/BIL GLO GLO (m) (m) (m/m) (mca)

MAP - A 113 45.2 25 1.54 0.5 1.0 0.73 1.0 0.40 1.52 6.77 1.13 1.63 0.0977 0.16
A - LLJ 20 13.7 13 1.72 0.5 1.0 0.36 0.20 0.76 3.44 0.36 0.86 0.2707 0.23
A-B 93 39.5 25 1.34 5.3 0.73 1.0 0.40 1.52 6.77 0.40 5.70 0.0773 0.44
B-C 33 19.4 25 0.66 1.0 1.0 0.73 0.40 1.0 1.52 1.0 6.77 9.02 10.02 0.0221 0.22
C - LO 8 7.3 13 0.92 0.5 1.0 0.36 0.20 0.76 3.44 0.36 0.86 0.0896 0.08
C-D 25 16.0 25 0.54 0.7 0.73 1.0 0.40 1.52 6.77 0.40 1.10 0.0158 0.02
D - WC 10 8.5 13 1.07 0.5 1.0 0.36 0.20 0.76 3.44 0.36 0.86 0.1173 0.10
D - BO 15 11.2 13 1.41 0.7 2.0 0.36 0.20 0.76 3.44 0.72 1.42 0.1913 0.27
B-E 60 29.2 25 0.99 4.0 0.73 1.0 0.40 1.52 6.77 0.40 4.40 0.0455 0.20
E-F 33 19.4 25 0.66 1.0 0.73 0.40 1.0 1.52 1.0 6.77 8.29 9.29 0.0221 0.21
F - LO 8 7.3 13 0.92 0.5 1.0 0.36 0.20 0.76 3.44 0.36 0.86 0.0896 0.08
F-G 25 16.0 25 0.54 0.7 0.73 1.0 0.40 1.52 6.77 0.40 1.10 0.0158 0.02
G - WC 10 8.5 13 1.07 0.5 1.0 0.36 0.20 0.76 3.44 0.36 0.86 0.1173 0.10
G - BO 15 11.2 13 1.41 0.7 2.0 0.36 0.20 0.76 3.44 0.72 1.42 0.1913 0.27
E-H 27 16.9 25 0.57 5.3 2.0 0.73 1.0 0.40 1.52 6.77 1.86 7.16 0.0174 0.12
H - LP 12 9.6 13 1.21 0.5 1.0 0.36 0.20 0.76 1.0 3.44 3.80 4.30 0.1462 0.63
H - MLAV 15 11.2 13 1.41 0.5 2.0 0.36 0.20 0.76 1.0 3.44 4.16 4.66 0.1913 0.89
SUBTOTALES 16 6 2 4

CELDAS RESALTADAS EN AMARILLO: DATOS QUE DEBE PROPORCIONAR EL USUARIO


PRIMERA COTA PIEZOMETRICA INICIAL = COTA DE TERRENO EN SOLERA FRENTE AL MEDIDOR + PRESIÓN RED PÚBLICA (14mca)
PIEZOMETPIEZOMET COTA PRESION
INICIAL FINAL ARTEF DISPONIB
(m) (m) (m) (mca)

14.00 13.84 13.84


13.84 13.61 0.70 12.91
13.84 13.40 13.40
13.40 13.18 13.18
13.18 13.10 0.70 12.40
13.18 13.16 13.16
13.16 13.06 0.40 12.66
13.40 13.13 2.00 11.13
13.40 13.20 13.20
13.20 12.99 12.99
12.99 12.92 0.70 12.22
12.99 12.98 12.98
12.98 12.88 0.40 12.48
12.98 12.71 2.00 10.71
13.20 13.08 13.08
13.08 12.45 12.45
13.08 12.18 0.70 11.48
1.22
CALCULO DE LA RED DOMICILIARIA DE AGUA POTABLE CALIENTE
TRAMO CAUDAL CAUDAL LONG N° N° N° N° LONG LONG J J PIEZOMETPIEZOMET
INSTALADOMAX PROB DIAM VELOC REAL CODO TEE TEE VALV EQUIV TOTAL UNIT TOT INICIAL FINAL
(l/m) (l/m) (mm) (m/s) (m) DIR LAT/BIL GLO (m) (m) (m/m) (mca) (m) (m)

CALEFONT - E 35 20.2 19 1.19 0.5 1.0 1.09 1.59 0.0876 0.14 13.40 13.26
E - LP 12 9.6 13 1.21 0.5 2.0 1.0 4.16 4.66 0.1462 0.68 13.26 12.58
E-F 23 15.1 19 0.89 5.0 4.0 1.0 1.0 7.40 12.40 0.0528 0.65 13.26 12.61
F - Lº 8 7.3 13 0.92 0.5 1.0 0.36 0.86 0.0896 0.08 12.61 12.53
F - Bº 15 11.2 13 1.41 2.0 4.0 1.44 3.44 0.1913 0.66 12.61 11.95

CELDAS RESALTADAS EN AMARILLO: DATOS QUE DEBE PROPORCIONAR EL USUARIO


COTA PRESION
ARTEF DISPONIB
(m) (mca)

13.26
0.70 11.88
12.61
0.70 11.83
2.00 9.95