WEG Guia de Instalacao mt6000 8000ie Quick Guide English
WEG Guia de Instalacao mt6000 8000ie Quick Guide English
1. Installation and Startup Guide 2. Unpacking the Unit 2. Press the spring and insert the USB stick into HMI. 6. EasyBuilder Pro Software
Unpack and check the delivery. If damage is found, Settings
Read these instructions carefully before installing, notify the supplier. Launch EasyBuilder Pro software, select your project
operating or perform maintenance in this file, press F7 shortcut key to open the download dialog
equipment. box: Select Ethernet > IP tab > Enter your HMI IP >
(1)
Click Download to download this project file to HMI.
This document covers the installation of If use MT6070iE, please select USB cable.
(2)
MT6000/8000iE Series HMI, for the detailed (please refer to EasyBuilder Pro User Manual
specifications and operation, please refer to brochure for software operation details).
and EasyBuilder Pro user manual.
(5) (3) 4. Power Connections
Install environment: (6) (4)
MT6000/8000iE Series HMI is
NEMA rating
NEMA 4 rated (indoor only).
1. Installation instruction, 2-sided A4 *1
2. Human machine interface *1
The MT6000/8000iE Series 3. Power connector *1
has been tested to conform
to European CE requirements.
4. Brackets & screws *1 pack
This means that the circuitry is 5. USB stick clamp & tying strap *1
designed to resist the effects 6. Fuse 1.25 A/250 V 5*20mm *1
Electrical environment
of electrical noise. This does 7. Communication Connections
not guarantee noise immunity Note! Note!
in severe cases. Proper wire Place the operator panel on a stable surface during 1. COM1 and COM3 (RS485) 2 W support MPI
routing and grounding will installation. Dropping it or letting it fall may cause
insure proper operation.
187.5K, please use one at one time.
damage. 2. COM1 (RS485) / COM3 (RS485) with isolation
(1) Make sure that the displays Note!
protection. (N/A for MT6070iE).
are installed correctly and 1. Connect positive DC line to the ‘+’ terminal and
that the operating limits are
3. Installation Instructions the DC ground to the ‘-’ terminal.
COM1 RS232, 9 Pin, Male, D-sub
followed. Avoid installing Secure the operator panel in position, using all the
2. Please do not connect HMI with PLC and PC
units in environments where fastening holes and the provided brackets
simultaneously to prevent potential difference from
severe mechanical vibration or and screws:
destroying USB ports of HMI and PC. PIN# Symbol COM1 (RS232)
shocks are present.
(2) Do not operate the unit 1 Not used
in areas subject to explosion (A)
5. System Settings
hazards due to flammable When HMI is powered up and displays image, 2 RxD Received data
gases, vapors or dusts. click the system setting button (default system pass- 3 TxD Transmitted data
Environmental
(3) Do not install the unit
(B)
Cutout
considerations word: 111111). It is necessary to connect the HMI to
where acid gas, such as SO2 4 Not used
your network through a RJ45 cable (N/A for MT6070iE).
exists.
5 GND Ground
(4) This device should be
mounted in the vertical 6 Not used
position and for use on the flat
surface enclosure. Type A (mm) B (mm) 7 RTS Ready to send output
(5) Conform to UL 508 MT6070iE 192 138 8 CTS Clear to send input
(ISBN 0-7629-0404-6) machi-
ne safety for use in Pollution MT8070iE 192 138 Go to the Network tab, you may choose to auto get 9 Not used
Degree 2 Environment. DHCP IP, or designate your own IP.
MT8100iE 260 202