Está en la página 1de 9

CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG

TD1A TD1A TD1A TD1A TD1A TD1A TD1A TD1A TD1A TD1A TD1A TD1A
ITEM DESCRIPCION P.U. (W) TD1A-C1 TD1A-C2 TD1A-C3 TD1A-C4 TD1A-C5 TD1A-C6 TD1A-C7 TD1A-C8 TD1A-C9 TD1A-C10 TD1A-C11 TD1A-C12
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 10
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 3 3 4
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 8 7
4 TOMACORRIENTES 1x100W 100.00 10 7 4
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00 3 4
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00 17 21
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00
11 RESERVA TIPO 2 500.00
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 0 0 0 14
POTENCIA INSTALADA (KW) 1.19 0.45 1.00 0.34 0.60 0.70 0.45 0.40 0.72 0.21 1.47 0.00
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 1.19 0.45 1.00 0.34 0.60 0.70 0.45 0.40 0.72 0.21 1.47 0.00
CORRIENTE CON 30% DE RESERVA (A) 5.08 1.92 4.27 1.43 2.56 2.99 1.92 1.71 3.06 0.89 6.28 0.00
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD TG-TD1A TG-TD1B TG-TDM TG-TDB


POTENCIA INSTALADA (KW) 16.84 52.94 22.77 13.50
FACTOR DE DEMANDA (%) 80% 80% 80% 80%
DEMANDA MAXIMA (KW) 13.47 42.35 18.22 10.80
CORRIENTE CON 30% DE RESERVA (A) 71.91 226.04 22.77 57.64
DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 64 94 6 10
CAIDA DE TENSION (V) 4.55 7.50 0.34 0.89
CAIDA DE TENSION (%) 2.07 3.41 0.15 0.40
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2) 3-1x25 3-1x70 3-1x10 3-1x10

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD1A TD1A TD1A TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B
ITEM DESCRIPCION P.U. (W) TD1A-C13 TD1A-C14 TD1A-C15 TD1B-C1 TD1B-C2 TD1B-C3 TD1B-C4 TD1B-C5 TD1B-C6 TD1B-C7 TD1B-C8 TD1B-C9
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 14 2 16
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 1 8 8
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 5 4
4 TOMACORRIENTES 1x100W 100.00 7 11
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1
11 RESERVA TIPO 2 500.00 2
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00 1
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00 1
20 TSD-C2 1808.00 1
21 TSD-C3 1808.00 1
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 0 0 0 0
POTENCIA INSTALADA (KW) 1.00 1.00 0.00 0.00 0.00 0.00 0.84 0.74 0.70 1.10 0.58 0.90
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 1.00 1.00 7.32 1.81 1.81 1.81 0.84 0.74 0.70 1.10 0.58 0.90
CORRIENTE CON 30% DE RESERVA (A) 4.27 4.27 31.27 7.72 7.72 7.72 3.57 3.15 2.99 4.70 2.49 3.83
DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 12.00 58.00 35.00 53.00
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V) 0.93 1.11 0.67 1.01
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%) 0.42 0.50 0.30 0.46
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2) 10 10 10 10

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B TD1B
ITEM DESCRIPCION P.U. (W) TD1B-C10 TD1B-C11 TD1B-C12 TD1B-C13 TD1B-TD-2B TD1B-TD-3A TD1B-TD-3B TD1B-TD-A TD1B-C14 TD1B-C15 TD1B-C16
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 8
4 TOMACORRIENTES 1x100W 100.00 8 8
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00 17
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1
11 RESERVA TIPO 2 500.00 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00 1
16 TD-3A 3406.00 1
17 TD-3B 2953.00 1
18 TD-A 21500.00 1
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 15 0 0
POTENCIA INSTALADA (KW) 0.80 0.80 0.34 1.87 0.00 0.00 0.00 0.00 0.00 1.00 0.50
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 0.80 0.80 0.34 1.87 9.50 3.41 2.95 21.50 0.00 1.00 0.50
CORRIENTE CON 30% DE RESERVA (A) 3.42 3.42 1.43 7.98 40.55 14.54 12.61 91.80 0.00 4.27 2.13
DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 10.00 40.00 33.00 35.00
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V) 1.00 1.44 1.03 3.18
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%) 0.46 0.65 0.47 1.44
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2) 10 10 10 25

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD2A TD2A TD2A TD2A TD2A TD2A TD2A TD2A TD2A TD2A TD2A TD2B TD2B
ITEM DESCRIPCION P.U. (W) TD2A-c1 TD2A-c2 TD2A-c3 TD2A-c4 TD2A-c5 TD2A-c6 TD2A-c7 TD2A-c8 TD2A-c9 TD2A-c10 TD2A-c11 TD2B-c1 TD2B-c2
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 14
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 8 6 3
4 TOMACORRIENTES 1x100W 100.00 16 14 9 4 10
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00 4
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00 1
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1
11 RESERVA TIPO 2 500.00 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 3 0 0 0 0
POTENCIA INSTALADA (KW) 1.60 0.34 0.81 0.05 1.40 0.13 0.90 0.40 0.00 1.00 0.50 1.00 0.60
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 1.60 0.34 0.81 0.05 1.40 0.13 0.90 0.40 0.00 1.00 0.50 1.00 0.60
CORRIENTE CON 30% DE RESERVA (A) 6.83 1.43 3.45 0.20 5.98 0.54 3.84 1.71 0.00 4.27 2.13 4.27 2.56
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD2B TD2B TD2B TD2B TD2B TD2B TD2B TD2B TD2B TD2B TD3A TD3A
ITEM DESCRIPCION P.U. (W) TD2B-c3 TD2B-c4 TD2B-c5 TD2B-c6 TD2B-c7 TD2B-c8 TD2B-c9 TD2B-c10 TD2B-c11 TD2B-c12 TD3A-c1 TD3A-c2
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 1 18 8
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 11 12 1 6
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 8 6 2
4 TOMACORRIENTES 1x100W 100.00 13 5 5
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00 8
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00 2
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1
11 RESERVA TIPO 2 500.00 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 4 0 0 0 0
POTENCIA INSTALADA (KW) 1.20 0.91 0.93 1.30 1.11 0.50 0.45 0.00 1.00 0.50 0.50 0.40
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 1.20 0.91 0.93 1.30 1.11 0.50 0.45 0.00 1.00 0.50 0.50 0.40
CORRIENTE CON 30% DE RESERVA (A) 5.12 3.88 3.98 5.55 4.74 2.13 1.91 0.00 4.27 2.13 2.13 1.69
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD3A TD3A TD3A TD3A TD3B TD3B TD3B TD3B TD3B TD3B TD3B
ITEM DESCRIPCION P.U. (W) TD3A-c3 TD3A-c4 TD3A-c5 TD3A-c6 TD3B-c1 TD3B-c2 TD3B-c3 TD3B-c4 TD3B-c5 TD3B-c6 TD3B-c7 TD3B-c8
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 4
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 1
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 5 6
4 TOMACORRIENTES 1x100W 100.00 8 4 3 2
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00 1
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1 1
11 RESERVA TIPO 2 500.00 1 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 0 3 0 0
POTENCIA INSTALADA (KW) 0.21 0.80 1.00 0.50 0.40 0.30 0.30 0.20 0.25 0.00 1.00 0.50
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 0.21 0.80 1.00 0.50 0.40 0.30 0.30 0.20 0.25 0.00 1.00 0.50
CORRIENTE CON 30% DE RESERVA (A) 0.90 3.42 4.27 2.13 1.71 1.30 1.28 0.85 1.06 0.00 4.27 2.13
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TSDC1 TSDC1 TSDC1 TSDC1 TSDC2 TSDC2 TSDC2 TSDC2 TSDC3 TSDC3 TSDC3
ITEM DESCRIPCION P.U. (W) TSDC1-c1 TSDC1-c2 TSDC1-c3 TSDC1-c4 TSDC2-c1 TSDC2-c2 TSDC2-c3 TSDC2-c4 TSDC3-c1 TSDC3-c2 TSDC3-c3
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 1 1 1
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 1 1 1
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00
4 TOMACORRIENTES 1x100W 100.00 2 2 2
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00
10 RESERVA TIPO 1 1000.00 1 1 1
11 RESERVA TIPO 2 500.00 1 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 0 0 0
POTENCIA INSTALADA (KW) 0.20 0.11 1.00 0.50 0.20 0.11 1.00 0.50 0.20 0.11 1.00
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 0.20 0.11 1.00 0.50 0.20 0.11 1.00 0.50 0.20 0.11 1.00
CORRIENTE CON 30% DE RESERVA (A) 0.85 0.46 4.27 2.13 0.85 0.46 4.27 2.13 0.85 0.46 4.27
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V)
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TSDC3 TDA TDA TDA TDA TDM TDM TDM TDM TDM TDM
ITEM DESCRIPCION P.U. (W) TSDC3-c4 TDA-c1 TDA-c2 TDA-c3 TDA-c4 TDM-c1 TDM-c2 TDM-c3 TDM-c4 TDM-c5 TDM-c6
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 9
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00
4 TOMACORRIENTES 1x100W 100.00 8
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00 10 13
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00 1 1
10 RESERVA TIPO 1 1000.00 1 1
11 RESERVA TIPO 2 500.00 1 1 1
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 0 0 0 0 0 0
POTENCIA INSTALADA (KW) 0.50 10.00 10.00 1.00 0.50 0.50 0.80 1.10 1.43 1.00 0.50
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
DEMANDA MAXIMA (KW) 0.50 10.00 10.00 1.00 0.50 0.50 0.80 1.10 1.43 1.00 0.50
CORRIENTE CON 30% DE RESERVA (A) 2.13 42.70 42.70 4.27 2.13 2.15 3.42 4.70 6.11 4.27 2.13
DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 12.00 12.00
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V) 1.27 1.27
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%) 0.58 0.58
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2) 10 10

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70
CALCULOS ELECTRICOS DEL SISTEMA ELECTRICO TABLEROS DISTRIBUCION TG
TD-B TD-B TD-B TD-B TD-B
TOTAL TOTAL kW
ITEM DESCRIPCION P.U. (W) TDB-c1 TDB-c2 TDB-c3 TDB-c4 TDB-c5
1 LUMINARIA ADOSADA CON LAMPARAS LINEALES LED 2 x 28W, 220 V. 56.00 99 5.54
2 LUMINARIA CIRCULAR ADOSADA CON LAMPARAS 2 X 26 W, 220 V. 52.00 61 3.17
3 LUMINARIA ADOSADA CON LÁMPARAS LINEALES LED 3 X 14 W, 220 V 42.00 76 3.19
4 TOMACORRIENTES 1x100W 100.00 162 16.20
5 LUMINARIA SUSPENDIDA CIRCULAR CON LAMPARAS LED 1 X 150 W, 220 V. 150.00 19 2.85
6 LUMINARIA ADOSADA EN PARED CON LAMPARA 1 X 25 W, 220 V. 25.00 4 0.10
7 LUMINARIA ORNAMENTAL EN PISO CON LAMPARA 1 X 70 W - 45°, 220 V. 70.00 38 2.66
8 LUMINARIA CON POSTE Y LAMPARA LED 1 X 110 W, 220 V. 110.00 40 4.40
9 SALIDA DE FUERZA ASCENSOR 10 kW 10000.00 2 20.00
10 RESERVA TIPO 1 1000.00 1 12 12.00
11 RESERVA TIPO 2 500.00 1 13 6.50
12 ELECTROBOMBA DE AGUA POTABLE 4 kW 4000.00 1 1 1 3 12.00
13 ELECTROBOMBA DE AGUA CONTRA INCENDIOS 5 kW 5000.00 0 0.00
14 TD-2A 7323.00
15 TD-2B 9498.00
16 TD-3A 3406.00
17 TD-3B 2953.00
18 TD-A 21500.00
19 TSD-C1 1808.00
20 TSD-C2 1808.00
21 TSD-C3 1808.00
22 LUCES DE EMERGENCIA 0.00 0 0 0 0 0 39 0.00
POTENCIA INSTALADA (KW) 4.00 4.00 4.00 1.00 0.50 88.41 88.62
FACTOR DE DEMANDA (%) 100% 100% 100% 100% 100% F.S.= 0.90
DEMANDA MAXIMA (KW) 4.00 4.00 4.00 1.00 0.50 79.57
CORRIENTE CON 30% DE RESERVA (A) 17.08 17.08 17.08 4.27 2.13
DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 12.00 12.00 12.00
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (V) 0.51 0.51 0.51
CAIDA DE TENSION DE CARGA A SU RESPECTIVO TD (%) 0.23 0.23 0.23
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2) 10 10 10

CALCULOS ELECTRICOS DEL ALIMENTADORES ENTRE TG Y TD


POTENCIA INSTALADA (KW)
FACTOR DE DEMANDA (%)
DEMANDA MAXIMA (KW)
CORRIENTE CON 30% DE RESERVA (A)
DISTANCIA DE CARGA A SU RESPECTIVO TD (m)
CAIDA DE TENSION (V)
CAIDA DE TENSION (%)
CONDUCTOR ALIMENTADORES TIPO NYY, 1 KV (mm2)

RESUMEN CALCULOS ELECTRICOS


ITEM DESCRIPCION D.M.
1 DEMANDA TOTAL (KW) 79.57
2 DEMANDA TOTAL (KVA) 83.76
3 CORRIENTE (A) 220.08
4 DISTANCIA DE CARGA A SU RESPECTIVO TD (m) 16.00
5 CAIDA DE TENSION (V) 1.24
6 CAIDA DE TENSION (%) 0.57
7 POTENCIA DE LA SUBESTACION (KVA) 100.00
CONDUCTOR ALIMENTADORES TIPO N2XOH 1 KV (mm2) 3-1x70