CALCULO DE ALIMENTADORES Y CAIDA DE TENSION

PUNTO TD-SG TD-AS TD-101 TD-201 TD-202 TD-301

SECCION (mm²) 16 16 16 16 16 16
ITM (AMP.) 3x80 3x30 2x63 2x63 2x63 2x63
Id (AMP.) 78.53 40.81 44.19 35.28 44.19 44.19
POT. M.D. (KW) 21.50 8.08 9.67 9.67 9.67 9.67
In (AMP.) 62.82 81.62 35.35 28.23 35.35 35.35
LONG. (m) 10.0 11.0 12.0 22.0 18.5 25.0

D V (V) 1.19 0.98 0.80 1.18 1.24 1.67


D V (%) 0.54 0.45 0.36 0.53 0.56 0.76
∑ (D V (%) ) 0.99
ES Y CAIDA DE TENSION
TD-302 TD-401 TD-402 TD-501 TD-502

16 16 16 16 16
2x63 2x63 2x63 2x63 2x63
44.19 44.19 44.19 50.51 50.51
9.67 9.67 9.67 10.67 10.67
35.35 35.35 35.35 40.40 40.40
21.5 28.0 24.5 31.0 27.5

1.44 1.87 1.64 2.37 2.10


0.65 0.85 0.74 1.08 0.96
< 2,5%
CUADRO DE CAIDA DE TENSION DEL TABLE
0.22 KV
ALIMENTADOR PUNTO SP I Nominal I Diseño Factor Corr. ITM (AMP)
Kw. Amp Amp Amp
DE MEDIDOR A
TG 23.98 70.01 87.51 1.00 3x90
TG
TENSION DEL TABLERO GENERAL : TG

Long. Seccion D V MAX.(%) D V (V) FORMACION


m mm2 1.5 Volt

9.85 16 0.74 1.63 3-1x16mm²N2XOH+1x16mm²NH-80(T)


CUADRO DE CARGAS DE
TD-501, TD-502
AREA DEL DEPARTAMENTO: 116.05 M2
ITEM DESCRIPCION A (M2) PI (KW) FD (P.U.) MD (KW)
1 Carga basica (Alumb. Y tomac.) 45.00 1.50 1.50
2 Carga adicional (Alumb. Y tomac.) 45.00 1.00 1.00
3 Carga adicional (Alumb. Y tomac.) 26.05 1.00 1.00
SUBTOTAL 116.05 3.50 3.50
N PN (KW)
3 Calentador 1.00 1.60 1.60 0.25 0.40
4 Lavadora-Secadora 1.00 2.50 2.50 0.25 0.63
5 Extractor cocina 1.00 0.15 0.15 1.00 0.15
6 Cocina 1.00 6.00 6.00 1.00 6.00
TOTAL 13.75 10.67
POTENCIA INSTALADA 13.75
MAXIMA DEMANDA 10.67
FACTOR DE SIMULTANEIDAD TOTAL 0.60
CARGA A CONTRATAR (PI x FS), MONOFASICO, 8.00 KW, 220V

CUADRO DE CARGAS DE
TD-201 A TD-402
AREA DEL DEPARTAMENTO: 81.60 M2
ITEM DESCRIPCION A (M2) PI (W) FD (P.U.) MD (W)
1 Carga basica (Alumb. Y tomac.) 45.00 1.50 1.50
2 Carga adicional (Alumb. Y tomac.) 36.60 1.00 1.00
SUBTOTAL 81.60 2.50 2.50
N PN (W)
3 Calentador 1.00 1.60 1.60 0.25 0.40
4 Lavadora-Secadora 1.00 2.50 2.50 0.25 0.63
5 Extractor cocina 1.00 0.15 0.15 1.00 0.15
6 Cocina 1.00 6.00 6.00 1.00 6.00
TOTAL 12.75 9.67
POTENCIA INSTALADA 12.75
MAXIMA DEMANDA 9.67
FACTOR DE SIMULTANEIDAD TOTAL 0.60
CARGA A CONTRATAR (PI x FS), MONOFASICO, 7.00 W, 220V

CUADRO DE CARGAS DE
TD-SG
ITEM DESCRIPCION A (M2) FC(KW/M2) PI (KW) FD (P.U.) MD (KW)
1 Luz y tomac.
Servicios generales 302.32 0.01 3.02 1.00 3.02
N PN (KW)
2 Electrobomba consumo 2.00 1.87 3.73 0.50 1.87
3 Electrobomba desague 2.00 0.37 0.75 0.50 0.37
4 #REF! 2.00 0.80 1.60 1.00 1.60
5 #REF! 1.00 7.47 7.47 0.75 5.60
6 Puerta retractil 1.00 0.56 0.56 1.00 0.56
7 extractor inyector 2.00 1.57 3.13 1.00 3.13
8 montacargas neumatico 1.00 1.87 1.87 1.00 1.87
9 pequeñas cargas 10.00 0.35 3.50 1.00 3.50
TOTAL 25.62 21.52
POTENCIA INSTALADA 25.62
MAXIMA DEMANDA 21.52
FACTOR DE SIMULTANEIDAD TOTAL 0.75
CARGA A CONTRATAR (PI x FS), TRIFASICO, 20.00 W, 220V

CUADRO DE CARGAS DE
TD-101 (LOCAL COMERCIAL)
ITEM DESCRIPCION N PN (W) PI (W) FD(P.U.) MD (W)
1 Luz y tomac.
local comercial 185.29 0.025 4.63 1.00 4.63
N PN (KW)
2 Alarma 1.00 0.80 0.80 1.00 0.80
3 letrero luminoso 1.00 1.00 1.00 0.75 0.75
4 extractor, inyector 4.00 0.19 0.75 0.75 0.56
5 computo 10.00 0.20 2.00 0.75 1.50
6 pequeñas cargas 5.00 0.38 1.90 0.75 1.43
TOTAL 10.71 9.67
POTENCIA INSTALADA 10.71
MAXIMA DEMANDA 9.39
FACTOR DE SIMULTANEIDAD 0.60
CARGA A CONTRATAR (PI x FS), MONOFASICO, 7.00 W, 220V

CUADRO DE CARGAS DEL EDIFICIO


BANCO MEDIDORES F1
ITEM DESCRIPCION A (M2) MD de C/Tab. FD(P.U.) MD (KW)
1 TD-501 116.05 10.67 1.00 10.67
2 TD-502 111.01 10.67 0.65 6.94
3 TD-201 81.60 9.67 0.65 6.29
4 TD-202 75.16 9.67 0.40 3.87
5 TD-301 81.60 9.67 0.40 3.87
6 TD-302 75.16 9.67 0.30 2.90
7 TD-401 81.60 9.67 0.30 2.90
8 TD-402 75.16 9.67 0.30 2.90
9 TD-101 185.29 10.71 0.75 8.03
10 TD-SG 302.32 25.62 0.75 19.22
TOTAL 115.72 67.59
POTENCIA INSTALADA 115.72
MAXIMA DEMANDA 67.59

PARA LA CARGA A SOLICITAR, EDELNOR Y LUZ DEL SUR UTILIZAN VALORES DEL
FACTOR DE SIMULTANEIDAD GENERAL DE 0,6 A 0,7

NOTA:
PARA EL CONCESIONARIO SE SOLICITARA DE ACUERDO A LA LEY DE
CONCESIONES ELECTRICAS LAS SIGUIENTES CARGAS:

- 2 SUMINISTROS MONOFASICO POR UNA CARGA DE 8,00 KW PARA CADA UNO


DE LOS DEPARTAMENTOS (TD-501, TD-502)

- 6 SUMINISTROS MONOFASICO POR UNA CARGA DE 7,00 KW PARA CADA UNO


DE LOS DEPARTAMENTOS (TD-201 A TD-402)

- 1 SUMINISTRO MONOFASICO POR UNA CARGA DE 7,00 KW PARA EL LOCAL


COMERCIAL (TD-101)
- 1 SUMINISTROS TRIFASICO POR UNA CARGA DE 20.00 KW PARA SERVICIOS
GENERALES (TD-SG).

CARGA TOTAL A CONTRATAR = 85.00 KW