REPORTE DE HALLAZGOS INTERVENTORIA

INCIDENCIAS/MANTENIMIENTO
ORDEN FECHA
400182177-400207527 TIPO REVISION: Mantenimiento 17/08/2022
MANTENIMIENTO REVISION
TOLIMA SUR -
SECTOR: CONTRATISTA: HESEGO FECHA DE INFORME 30/08/2022
CHAPARRAL

REALIZADO POR: SEBASTIAN VARON

APOYOS
No. APOYO No. APOYO
TIPO SERIE CONJUNTO COORDENADAS
(Plano) (Terreno)
CHAPA 12*510 4.17587679 -
65240149 65240149 10411531 B6+B6SM+ST2
KgF 74.94119309
CHAPA 12*510
65244861 65244861 10404835 B12SM 4,176139 -74,941056
KgF
4.17652918 -
2360632 2360632 HORMIGON 2842 B7SM+V02
74.94092589
HORMIGON B77T+B6SM+TB27+ST2+ 4.1766337 -
65243229 65243229 827
12*750F V02/2S31AR+MCD1+AP 74.94079051
HORMIGON 4.17660426 -
65244144 65244144 3124 2B76T+V02
12*750F 74.94072773
HORMIGON 4.17704283 -
65244489 65244489 271 B72E+B6FSM+ST2
12*1050F 74.94044289
HORMIGON 4.17650205 -
65244136 65244136 991 B6+B6SM
12*750F 74.939998568
HORMIGON 4.17708609 -
65243131 65243131 1253 B71
14*1050 KgF 74.94033079
HORMIGON 4.17758879 -
65244888 65244888 1532 B72E+B59FSM+ST2
14*1050 KgF 74.94014577
B56SM+TB37+ST2+2S3+ 4.17758093 -
2057212 2057212 HORMIGON NV
S32+AP 74.940506
HORMIGON 4.17810067 -
65244128 65244128 1455 B72ED
14*1350 KgF 74.93980412
HORMIGON 4.1788192 -
65244047 65244047 1666 C151+B151+B76T+ST2
14*1350 KgF 74.93944106
DESCRIPCION OT(PARTE)
SUBESTACION VENTANA CTO 1 ESPINAL , sector vda dindalito municipio de espinal.
NODOS:65244047-65244128-2057212-65244888-65243131-65244136-65244489-65244144-65244144-65240149-65244861-236063-652432292.
Cambio de estructuras en la red MT y postes.

REGISTRO FOTOGRAFICO

NODO 65240149 ESTRUCTURA B6+B6SM+ST2 ,SE EVIDENCIA TRANSICION DE RED SEMIAISLADA A RED ABIERTA ACSR SIN DPS.

F123-DSE V.01
10-02-2020
NODO 65240149 ESTRUCTURA B6+B6SM, CONDUCTORES ENTIZADOS , SPT CON DISTANCIA MENOR A 1 METRO DE LA BASE DE EL APOYO

NODO 65244861 ESTRUCTURA B12SM

NODO 65244861 ESTRUCTURA B12SM, CONDUCTOR ASEGURADO CON ALAMBRE GALVANIZADO DESNUDO ( SEGÚN NORMA VIGENTE CELSIA, SE DEBE
REALIZAR CON ALAMBRE AISLADO )

F123-DSE V.01
10-02-2020
NODO 2360632 ESTRUCTURA B7SM+V02 SIN PLACA DE MARCACION DE APOYO

NODO 2360632 ESTRUCTURA B7SM+V02

NODO 65243229 ESTRUCTURA B77T+B6SM+TB27+ST2+V02/2S31AR+MCD1+AP

F123-DSE V.01
10-02-2020
NODO 65243229 ESTRUCTURA B77T+B6SM+TB27+ST2+V02/2S31AR+MCD1+AP

NODO 65244144 ESTRUCTURA 2B76T+V02

NODO 65244144 ESTRUCTURA 2B76T+V02 APOYO DESAPLOMADO.

F123-DSE V.01
10-02-2020
NODO 65244489 ESTRUCTURA B72E+B6FSM+ST2

NODO 65244489 ESTRUCTURA B72E+B6FSM+ST2

NODO 65244136 ESTRUCTURA B6SM+B6

F123-DSE V.01
10-02-2020
NODO 65244136 ESTRUCTURA B6SM+B6 TRANSICION DE RED SIN DPS

NODO 65244888 ESTRUCUTRA B72E+B59FSM+ST2

NODO 65244888 ESTRUCUTRA B72E+B59FSM+ST2

F123-DSE V.01
10-02-2020
NODO 2057212 B56SM+TB37+ST2+2S3+S32+AP, SIN MARCACION DE APOYO

NODO 2057212 B56SM+TB37+ST2+2S3+S32+AP

NODO65244128 ESTRUCTURA B72ED

F123-DSE V.01
10-02-2020
|

NODO65244128 ESTRUCTURA B72ED

NODO 65244047 ESTRUCTURA C151+B151+B76T+ST2

NODO 65244047 ESTRUCTURA C151+B151+B76T+ST2

F123-DSE V.01
10-02-2020
NODO 65244047 ESTRUCTURA C151+B151+B76T+ST2 CONDUCTOR ASEGURADO CON ALAMBRE GALVANIZADO DESNUDO ( SEGÚN NORMA VIGENTE CELSIA,
SE DEBE REALIZAR CON ALAMBRE AISLADO )

TIPO DE HALLAZGO: TIPO NC COD


NC 1: Apoyo (Poste)
NO CONFORME (NC)
NC 2: Armado

ACTUALIZADO EN BDI NC 3: Sistema de puesta a tierra (SPT)

SI OTRAS:
CONCLUSIONES:
Se realiza visita de recibo técnico al contratista HESEGO , se evidencia lo siguiente:
Se verifica instalación de estructuras de MT y Actualizacion en BDI.
Las no conformidades encontradas en terreno se detallan en este informe.
NC: 1. NODO 65240149 ESTRUCTURA B6+B6SM+ST2, se evidencia transición de red semiaislada a red abierta ACSR sin DPS.
Conductores entizados, SPT con distancia menor a 1 METRO de la base del apoyo
2. NODO 65244861 ESTRUCTURA B12SM, conductor asegurado con alambre galvanizado desnudo (según NORMA VIGENTE
CELSIA vigente, se debe realizar con alambre aislado)
3. NODO 2360632 ESTRUCTURA B7SM+V02 sin placa de marcación de apoyo
4. NODO 65244144 ESTRUCTURA 2B76T+V02 apoyo desaplomado.
5. NODO 65244136 ESTRUCTURA B6SM+B6 transición de red sin DPS
6. NODO 2057212 B56SM+TB37+ST2+2S3+S32+AP, sin marcación de apoyo
7. NODO 65244047 ESTRUCTURA C151+B151+B76T+ST2 conductor asegurado con alambre galvanizado desnudo (según
NORMA VIGENTE CELSIA vigente, se debe realizar con alambre aislado)
Se recomienda solucionar hallazgos conforme a la norma de construcción de redes de CELSIA.