ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FD-FA
1. Colocar dimensiones de la viga continua
30.0 cm
3 Ø 3/4 '' As Positivo 5.04 cm² Verificar As min y As max
80.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
8.40 cm²
40.0 cm
As Negativo 11.04 cm² Cumple con As min y As max
9 Ø 1/2 '' 190.0 cm
11.04 cm²
ACERO TRANSVERSAL
sadm Suelo = 15.000 Tn/m² REFUERZO NEGATIVO
s diseño = 22.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 7.20 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
Ø barra = 1/2 ''
80.0 cm 1/2 '' @ 0.2 Ø estribo = 3/8 ''
recub. = 7.50 cm
80.0 cm d = 30.91 cm
M = 7.20 Tn-m
40.0 cm a = 1.486 cm
As = 6.31 cm²
190.0 cm Ø barra = 1/2 ''
As = 1.267 cm²
22.50 Tn/m @= 20.00
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 38.344 Tn > 24.541 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 190.00 cm
d= 30.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 27.73 cm S = 27.00 cm □Ø 3/8 '' @ 0.27
S ≤ 30.00 cm
30.0 cm
4 Ø 3/4 '' As Positivo 9.20 cm² Cumple con As min y As max
80.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
9.20 cm²
40.0 cm
As Negativo 14.93 cm² Cumple con As min y As max
8 Ø 5/8 '' 180.0 cm
14.93 cm²
30.0 cm
3 Ø 3/4 '' As Positivo 5.01 cm² Verificar As min y As max
80.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
8.40 cm²
40.0 cm
As Negativo 11.52 cm² Cumple con As min y As max
10 Ø 1/2 '' 180.0 cm
11.52 cm²