CALCULO DE ALIMENTADOR AL 75% DE FACTOR DE DEMANDA DE TABLERO SALAS 15-16 HOSPITAL ESPAÑOL

CALCULO POR AMPACIDAD


W = 58300.69
W RAIZ(3) = 1.7321
=
I RAIZ(3)*ef*cos Ø COSØ = 0.85
ef = 220
I = ¿?
58300.69
=
I 323.89350101538

= 180.000 A
I

F.D.(100%) = 180.000 A 100% factor de demanda


F.D(75%) = 126.000 A 75% factor de demanda

CALCULO DE SECCION DEL COBRE POR DISTANCIA

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 100 MTS
I = 126.00 A
43647.5754010695 e% = 2 CAIDA
=
S 440 ef = 220 V

DEL
= 99.1990350024307 CONDUCTO
S R

Zefec con
CALIBRE PROPUESTO SECCION F.P. 0.85
4/0 107.2 0.244

CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321


e% =
10*ef Z = 0.244
I = 126.000
5325.00419893048 L = 100
e% =
2200 ef = 220

e% = ˃ 2%
2.42045645405931 4-(4/0 KCM); 1-6d
3F-1N-1d

Conductor seleccionado
CALIBRE PROPUESTO SECCION v
250 KCM 126.67 0.216

CALCULO DE CAIDA DE VOLTAJE

4713.93814331551
e% =
2200

e% = 2.1426991560525 ˃ 2%

considerando un factor de demanda del 75% 4-(250 KCM); 1-6d


3F-1N-1d

Conductor seleccionado
Zefec con
CALIBRE PROPUESTO SECCION F.P. 0.85
300 KCM 152.01 0.194

CALCULO DE CAIDA DE VOLTAJE

4233.81481390374
e% =
2200

e% = 1.92446127904716 ˂ 2%

considerando un factor de demanda del 75% 4-(300 KCM); 1-6d


3F-1N-1d
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
TAB A.A
ALIMENTADOR GRAL. DE LA SALA 1 12/26/2022
TIPO: NQ - 20 " MARCA: TABLERO: SERVICIO:
CAT: NQ30 - 4AB100 S SQUARE´D NQ 30 CIRCUITOS EUIPOS ELECTROMECANICOS DEL SISTEMA DE AIRE ACONDICIONADO - HBAK
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F-4H, 220/127 V, 60Hz 3P-90 AMP. CUARTO DE MAQUINAS SR. JOSE ALBERTO LOPEZ VAZQUEZ
ANALIS DE CARGA DE SALA 1
CONTACTOS
CHILLER UGAH-
DESCIPCION DE ESPACIO F & C5 y Alarma BOMBA CARCAMO CONTACTOS DE CONTACTOS DE
TABLERO SERVICIO CANTIDAD 01 220 V 3F- BAH-01 F&C 1 Y 2 UV-01 F&C 3 Y 4 EXT SERVICIO 220 DE SERVICIO SERVICIO ILUMINACION - CM F1 F2 F3 POTENCIA
EQUIPO ELECTRICO 6 Gases A.PLUVIAL V - EXT 127 V 220 V -
3H
CM
16080 1125 670 559.5 250 250 186.5 100 1270 660 180 360 60
WATTS WATTS WATTS WATTS WATTS WATTS WATTS watts WATTS WATTS WATTS WATTS WATTS

1 1 2 1 3 1 1 1 1 5 2 6 A B C W

5365.63 5365.63
CHILLER UGAH-01 1,3,5 AZOTEA 1 5365.63 5365.63
5365.63 5365.63
386.77 386.77
F&C 01 7,9 GANTRY 1 1
386.77 386.77
386.77 386.77
F&C 02 11, 13 TRATAMIENTO 1 1
386.77 386.77

VACIO 15 0.00

ALARMA GASES
17 CONTROL LINAC 200.00 200.00
MEDICINALES

BOMBA DE
19 CARCAMO 1 508.00 508.00
EXCEDENTE
VACIO 21 0.00
93 93.00
BOMBA EXT-01 23,25 PASILLO BUNKER 1
93 93.00
VACIO 27 0.00
VACIO 29 0.00
VACIO 31 0.00
VACIO 33 0.00
VACIO 35 0.00
VACIO 37 0.00
VACIO 39 0.00
VACIO 41 0.00

375.39 375.39
BAH-01 2,4,6 AZOTEA 1 375.39 375.39
375.39 375.39
186.70 186.70
MOTOR DE FLUJO
UV-01 8,10,12 1 186.70 186.70
C.M.
186.70 186.70
F&C 03 14 AREA DE CONTROL 1 250.00 250.00
F&C 04 16 AREA DE CPU 1 250.00 250.00
AREA DE
F&C 05 18 1 250.00 250.00
PLANEACION
VACIO 20 0.00
330.00 330.00
BOMBA EXT-02 22,24 VESTIDOR 1
330.00 330.00
CONTACTOS 127 26 CM 4.00 720 720.00
360.00 360.00
CONTACTOS 220 28,30 C.M. 2.00
360.00 360.00

ILUMINACION - CM 32 4.00 240.00 240.00

F&C 06 34 CUARTO UPS 1 250.00


250
VACIO 36 0.00

VACIO 38 0.00

VACIO 40 0.00

VACIO 42 0.00
0.00
0.00
0.00

WATTS 8512.27 7504.50 7547.50 23564.26

TOTAL EN WATTS = 23564.26


KW = 23.56
8512.27 100
7547.50 88.666 -11.333908168 23564.26
I =
381.05117767

I= = 61.840147164

FT= 1
FA= 1

IC = 61.840147

AMPERES

INTERRUPTOR PRINCIPAL AL 100% DE DEMANDA


0.00 A ≥ A 100% I 77.30 A
DEMANDA

ANALISIS DE CALIBRE DE ALIMENTADOR PRINCIPAL DE TABLERO

LONGITUD 155 W = 21207.83


CAlIBRE ACTUAL 1/0 AWG RAIZ(3) = 1.7321 55.6561324476177 69.57016555952
SECCION MM2 53.48 MM2 COSØ = 0.85
Z EFECTIVA A 0.85 DE F.P. 0.411 IMPEDANCIA ef = 220
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

21207.8348134524
=
I 323.89350101538

= 65.48
I

CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION

2*RAIZ(3)*L*I RAIZ(3) = 1.7321 2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 155 MTS e%*ef L = 155
I = 65.48 A I = 65.48
35157.3732201618 e% = 2 CAIDA 35157.3732201618 e% = 2
=
S 440 ef = 220 V 440 ef = 220

SECCION DEL SECCION DEL


S
= 79.90 CONDUCTOR
79.9031209549132
CONDUCTOR

I M P E D A N C I A =Z e f e c c o n
CALIBRE PROPUESTO AWG SECCION F.P. 0.85 CALIBRE PROPUESTO KCM SECCION IMPEDANCIA=Zefec con F.P. 0.85

4/0 107 0.242 250 127 0.213


CALCULO DE CAIDA DE VOLTAJE CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 RAIZ(3)*Z*I*L RAIZ(3) = 1.7321


e% =
10*ef Z = 0.242 10*ef Z = 0.213
I = 65.478 I = 65.478
4254.04215963958 L = 155 4348.17319116453 L = 180
e% =
2200 ef = 220 2200 ef = 220

e% = 1.9336555271089 ≤ 2% 1.97644235962024 ≤ 2%

ANALISIS DE POTENCIA REAL SOPORTADA POR CALIBRE 4/0 CON 155 MTS DE LONGITUD

LONGITUD 155 MTS W = 21207.83


CAlIBRE ACTUAL 4/0 AWG RAIZ(3) = 1.7321
SECCION MM2 107 MM2 COSØ = 0.85
Z EFECTIVA A 0.85 DE F.P. 0.242 IMPEDANCIA ef = 220
I = ¿?
ILUMINACION

VOLTAJE DE REFERNCIA
OPERACIÓN SISTEMA FASES CANTIDAD BUNKER

LUMINARIAS C12 127 1F-1N 0 3 CAL. 12


LUMINARIAS C13 127 1F-1N 1 8 CAL. 12
LUMINARIAS C14 127 1F-1N 1 6 CAL. 12
LUMINARIAS C15 127 1F-1N 1 5 CAL. 12
LUMINARIAS C16 127 1F-1N 1 8 CAL. 12
CONTROL LINAC 127 1F-1N 1 DETERMINAR CARGA
CLOSET DE CPU'S 127 1F-1N 1 DETERMINAR CARGA
CUARTO DE CONTROL-
PLANEACION DE 127 1F-1N 1 DETERMINAR CARGA
TRATAMIENTO
POTENCIA
(WATTS) TOTAL
ILUMINACION

VOLTAJE DE
OPERACIÓN SISTEMA
PUERTA DE ACCESO 127 1F-1N

C01 CITB-JUNTO A PUERTAS DE ACCESO


DENTRO AREA DE EQUIPO ELEKTA Y AREA DE
C02
BUNKER

C03 CONTROL DE LINAC

C04 CLOSET DE CPU'S


CONTACTOS PARA LASER EN MUROS Y UNO EN
C05
PLAFON
C06 ALIMENTACIÓN PARA CITB

C07 ALIMENTACIÓN A SOLENOIDES

C08 ALIMENTACION PUERTA METALICA

C09 ALIMENTACIÓN SEMAFORO

ALIMENTACION PARA BOTONES DE PARO


C10 (INTERRUPTORES TERMOMAGNETICOS CON
BOBINA DE DISPARO)

C11 LUMINARIAS 600 LUX/M2 DIMEABLE

C12 LUMINARIAS 200 LUX/M2 (LINAC)

C13 LUMINARIAS 50 LUX/M2 DIMEABLE

DICROICAS AZULES PARA AMBIENTACIÓN-


C14
DIMEABLE

C15 PLANEACIÓN DEL TRATAMIENTO-400 LUX/M2

C16 CONTROL LINAC Y CLOSET'S DE CPU'S 400 LUX/M2

PASILLO BUNKER ACCESO A SALA DE


C17
TRATAMIENTOLUMINARIAS 200 LUX/M2

C18 AREA DE PLANEACION DEL TRATAMIENTO


CR01 ARRIBA EN PLAFON DENTRO AREA DE EQUIPO
ELEKTA

MONITOR(X1) FRENTE A PUERTA METALICA Y


CR02 DENTRO DE AREA DE PLANTA DE TRATAMIENTO

CR03 CLOSET DE CPU´S


ILUMINACION

FASES CANTIDAD REFERNCIA BUNKER


1 1 CAL. 10
NOTAS
CANTIDAD
3 CONTACTOS

6 CONTACTOS

15 CONTACTOS ESTE CIRCUITOS SE DIVIDIRA EN 3 CIRCUITOS


SEPARADOS
6 CONTACTOS

4 CONTACTOS

1 SALIDA

1 ELIMINADO

1 SALIDA

1 SALIDA

1 SALIDA

ESTE CIRCUITO EN PLANO ME LO MARCA COMO


3 ILUMINACIÓN-GANTRY
C12
ILUMINACIÓN- ESTE CIRCUITO EN PLANO ME LO MARCA COMO
6
PRINCIPAL C14
ILUMINACIÓN-
8
SECUNDARIA

ESTE CIRCUITO EN PLANO ME LO MARCA COMO


5 ILUMINACIÓN
C15

HACER PROPUESTA- NO REFLEJADO EN CUADRO DE CIRCUITOS 127


?
ILUMINACIÓN VAC
HACER PROPUESTA-
?
ILUMINACIÓN

8 ILUMINACIÓN

13 CONTACTOS ESTE CIRCUITOS SE DIVIDIRA EN 3 CIRCUITOS


SEPARADOS
3 CONTACTOS
REGULADOS

14
CONTACTOS
REGULADOS
6 CONTACTOS
REGULADOS
SISTEMA
3F-4H 2207127 V

IDENTIFICACION TABLERO UBICACIÓN


C01 C01 CITB-JUNTO A PUERTAS DE ACCESO
DENTRO AREA DE EQUIPO ELEKTA Y AREA DE
C02 C02
BUNKER

C03_01 C03 CONTROL DE LINAC

C03_02 C04 CONTROL DE LINAC

C03_03 C05 CONTROL DE LINAC

C04 C06 CLOSET DE CPU'S


CONTACTOS PARA LASER EN MUROS Y UNO EN
C05 C07
PLAFON
C06 C08 ALIMENTACIÓN PARA CITB

C07_01 C09 AREA DE PLANEACION DEL TRATAMIENTO

C07_02 C10 AREA DE PLANEACION DEL TRATAMIENTO

C07_03 C11 AREA DE PLANEACION DEL TRATAMIENTO

C08 C12 ALIMENTACION PUERTA METALICA

C09 C13 ALIMENTACIÓN SEMAFORO

ALIMENTACION PARA BOTONES DE PARO


C10 C14 (INTERRUPTORES TERMOMAGNETICOS CON
BOBINA DE DISPARO)

C11 C15 LUMINARIAS 600 LUX/M2

C12 C16 LUMINARIAS 200 LUX/M2 (LINAC)

C13 C17 LUMINARIAS 50-100 LUX/M2 DIMEABLE

DICROICAS AZULES PARA AMBIENTACIÓN-


C14 C18 DIMEABLE 50-100 LUX/M2

C15 C19 PLANEACIÓN DEL TRATAMIENTO-400 LUX/M2

SALIDA PARA UPS DE 10 KVA PARA TABLERO


C16 C20
REGULADO 220V
LUMINARIAS PASILLO BUNKER ACCESO A SALA DE
C17 C21
TRATAMIENT 200 LUX/M2

SALIDA PARA UPS DE 10 KVA PARA TABLERO


C18 C22
REGULADO 220V

C18 CONTROL LINAC Y CLOSET'S DE CPU'S 400 LUX/M2


C23
SALIDA PARA UPS DE 10 KVA PARA TABLERO
C24
REGULADO 220V
C25 LIBRE
C26 LIBRE
C27 LIBRE
C28 LIBRE
C29 LIBRE

C30 LIBRE

C31 LIBRE

C32 LIBRE

C33 LIBRE
C34 LIBRE
C35 LIBRE
C36 LIBRE
C37 LIBRE
C38 LIBRE
C39 LIBRE
C40 LIBRE
C41 LIBRE
C42 LIBRE
FASES CANTIDAD REFERNCIA BUNKER
1 1 CAL. 10

CANTIDAD NOTAS
3 CONTACTOS

6 CONTACTOS

5 CONTACTOS
ESTE CIRCUITOS SE DIVIDIRA EN 3 CIRCUITOS
5 CONTACTOS
SEPARADOS
5 CONTACTOS

6 CONTACTOS

4 CONTACTOS

1 SALIDA

4 CONTACTOS

ESTE CIRCUITOS SE DIVIDIRA EN 3 CIRCUITOS


5 CONTACTOS
SEPARADOS

4 CONTACTOS

1 SALIDA

1 SALIDA

1 SALIDA

ESTE CIRCUITO EN PLANO ME LO MARCA COMO


3 ILUMINACIÓN-GANTRY
C12
ILUMINACIÓN- ESTE CIRCUITO EN PLANO ME LO MARCA COMO
6
PRINCIPAL C14
ILUMINACIÓN-
8
SECUNDARIA

ESTE CIRCUITO EN PLANO ME LO MARCA COMO


5 ILUMINACIÓN C15

HACER PROPUESTA- NO REFLEJADO EN CUADRO DE CIRCUITOS 127


?
ILUMINACIÓN VAC

1 SALIDA TRIFASICA
8 ILUMINACIÓN

1 SALIDA TRIFASICA

HACER PROPUESTA-
?
ILUMINACIÓN

1 SALIDA TRIFASICA

LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE

LIBRE LIBRE

LIBRE LIBRE

LIBRE LIBRE

LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LIBRE LIBRE
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

ANALIS DE CARGA DE SALA 1

BOTONES DE PARO
DESCIPCION DE EQUIPO CONTACTO CONTACTO MONOFASICO TORRE DE ILUMINACION L U M I N A R I A 6 0 0 LUMINARIA LU M IN AR I A 4 00 PUE RT A M ET ALIC A
ESPACIO TABLERO SERVICIO CANTIDAD LUMINARIA 200 LUX/M2 CITB PARA ACCIONAR BOBINAS UPS TRIFASICO F1 F2 F3 POTENCIA
ELECTRICO MONOFASICO DE SERVICIO PARA LASER (INDICADOR) LUX/M2 50-100 LUX/M2 LUX/M2 MAGNETIZADA
DE DISPARO

300 400 10 60 80 18 18 750 500 300 10000


WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS
127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 220 V

CONTACTOS CUARTO DE GANTRY 1 3 3 900 900.00

3 5 5 1500 1500.00
CONTACTOSCONTROL LINAC
5 5 5 1500 1500.00
CONTACTOSCONTROL LINAC
CONTACTOS LASER 7 4 4 1600 1600.00

C O NT A CT OS AR EA DE 9 4 4 1200 1200.00
PLANEACIÓN DEL TRATAMIENTO

CONTACTOS AREA DE PLANEACIÓN DEL 11 4 4 1200 1200.00


TRATAMIENTO

13 1 1 10 10.00
ALIMENTACIÓN SEMAFORO

I L UM I NA CI Ó N GAN TR Y- 6 00
15 3 3 180 180.00
LUX/M2 CONPAGADOR ESCALERA

17 8 8 640 640.00
ILUMINACIÓN SECUNDARIA 50-100
LUX/M2(DIMEABLE)

19 PROPUESTA PENDIENTE 12 216 216.00


ILUMINACIÓN PLANEACIÓN DEL
TRATAMIENTO 400 LUX/M2

I L UM I NA CI Ó N PAS ILLO BU NKE R 21 9 9 162 162.00


200 LUX/M2 (QUINTO SISTEMA)

I L UM I NA CI Í ON CO NT ROL L INA C 23 PROPUESTA PENDIENTE 12 216 216.00


400 LUX/M2

I L UM I NA CI Í ON CL OS ET DE 25 PROPUESTA PENDIENTE 4 72 72.00


CPU'S 400 LUX/M3
27 0.00
29 0.00
31 0.00
33 0.00
35 0.00
37 0.00
39 0.00
41 0.00

CONTACTOS SALA DE TRATAMIENTO


2 6 6 1800 1800.00
LINAC
4 5 6 1800 1800.00
CONTACTOSCONTROL LINAC
6 6 6 1800 1800.00
CONTACTOS CLOSET DE CPU'S
8 1 1 750 750.00
ALIMENTACIÓN PARA C I T B - S A L I D A

CONTACTOS AREA DE PLANEACIÓN DEL 10 5 5 1500 1500.00


TRATAMIENTO
ALIMENTACIÓN PUERTA
METALICA 12 1 1 500 500.00

14 1 1 300 300.00
ALIMENTACIÓN BOTONES DE PARO(INT,
TERM, CON BOBINA DE DISPARO)

ILUMINACIÓN PRINCIPAL 200 LUX/M2 16 6 6 108 108.00


(LINAC)

18 5 5 400 400.00
ILUMINACION AZUL CON DICROICAS
PARA AMBIENTACIÓN
20 3336.84 3336.84
ALIMENTACIÓN DE UPS PARA TABLERO
22 1 1 3336.84 3336.84
REGULADO 1O KVA´S
24 3336.84 3336.84
26 0.00
28 0.00
30 0.00
32 0.00
34 0.00
36 0.00
38 0.00
40 0.00
42 0.00
0.00

WATTS 8984.84 9786.84 9592.84 28364.51


LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

TOTAL EN WATTS = 28364.51


KW = 28.36

28364.51
I =
381.051177665153

I= = 74.437533286979

FT= 1
FA= 1

IC = 74.44

AMPERES

INTERRUPTOR PRINCIPAL AL 100% DE DEMANDA


106.00 A ≥ A
I = 74.44 A
100% DEMANDA

ANALISIS DE CALIBRE DE ALIMENTADOR PRINCIPAL DE TABLERO

LONGITUD 150 W = 28364.51


CAlIBRE ACTUAL 1/0 AWG RAIZ(3) = 1.7321
SECCION MM2 53.48 MM2 COSØ = 0.9
Z EFECTIVA A 0.85 DE F.P. 0.411 IMPEDANCIA ef = 220
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

28364.5097214924
=
I 342.946059898638

= 82.71
I

CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION

2*RAIZ(3)*L*I RAIZ(3) = 1.7321 2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 150 MTS e%*ef L = 150
I = 82.71 A I = 0.00
42976.5298810491 e% = 2 CAIDA 0 e% = 2
=
S 440 ef = 220 V 440 ef = 220

SECCION DEL SECCION DEL


= 97.6739315478388 0
S CONDUCTOR CONDUCTOR

IMPEDANCIA=Zefec con F.P.


CALIBRE PROPUESTO AWG SECCION IMPEDANCIA=Zefec con F.P. 0.85 CALIBRE PROPUESTO KCM SECCION 0.85

4/0 107 0.242 250 127 0.213

CALCULO DE CAIDA DE VOLTAJE CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 RAIZ(3)*Z*I*L RAIZ(3) = 1.7321


e% =
10*ef Z = 0.242 10*ef Z = 0.213
I = 82.708 I = 82.708
5200.16011560694 L = 150 4577.00043233173 L = 150
e% =
2200 ef = 220 2200 ef = 220

e% = ≤ 2% ≤ 2%
2.3637091434577 2.08045474196897
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

ANALISIS DE POTENCIA REAL SOPORTADA POR CALIBRE 4/0 CON 150 MTS DE LONGITUD

LONGITUD 150 MTS W = 28364.51


CAlIBRE ACTUAL 4/0 AWG RAIZ(3) = 1.7321
SECCION MM2 107 MM2 COSØ = 0.9
Z EFECTIVA A 0.85 DE F.P. 0.242 IMPEDANCIA ef = 220
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

28364.5097214924
=
I 342.946059898638

= 82.71 A
I

CALCULO DE SECCION DEL COBRE POR DISTANCIA

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 150 MTS
I = 82.71 A
42976.5298810491 e% = 2 CAIDA
=
S 440 ef = 220 V

SECCION DEL
= 97.67 MM2
S CONDUCTOR

Z e f e c c o n F .P .
CALIBRE PROPUESTO SECCION 0.85 80.60 A X 220 X1.73=30.68 KW KVA=30.68 KW / F,P,= 30.68/0.85=36.08 KVA
4/0 107 0.242

CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 36.08 X 0.30 F.S.= 46.91 KVA


e% =
10*ef Z = 0.242
I = 82.708
5200.16011560694 L = 150
e% =
2200 ef = 220
TRANSFORMADOR 3F-4H DELTA ESTRELA= 50 KVA
e% = ≤ 2%
2.36

CON EL CALIBRE 4/0 AWG Y 160 METROS DE LONGITUD DEL ALIMENTADOR EL CONDUCTOR TIENE LA CAPACIDAD DE SUMINISTRAR una demanda de 27643 WATTS 3f-4h CON UN AMPERAJE POR FASE DE 80.60 A
Vp Vs
EQUIPO ELEKTA 220 480
TABLEROS 220/127
ELEKTA 6 KV 220/127 KV

HVAC AIRE
ACONDICIONADO
GOTT 220 V

KVA DE TR 220 A CONSIDERAR

KVA DE TRANSFORMADOR ACTUAL


GLOBAL
DEMANDA KW ARRANQUE(1.25) RESERVA(30%)

112
28 39.2 47.04 KVA

28 39.2 47.04 KVA

TOTAL 168

IC (1,40) 235.2

RESERVA(20%) N/A

TOTAL 235.2

0 A CONSIDERAR 235.2 KVA

ORMADOR ACTUAL 300 KVA

TOTAL 535.2 0

600 KVA
CAPACIDAD DEL 750
TRANSFORMADOR KVA
VOLTAJE DEVANADO PRIM: 6 KVp
VOLTAJE DEVANADO SEC: 0.22 KVs

AMP. EN PRIMARIO KVA/ (1.73*KVp)


AMP. EN PRIMARIO 72.25 A

FACTORES DE REDUCCION DE POTENCIA

F1 0.97 TEMPERATURA EN SUBSUELO


F2 0.68 AGRUPACION JUNTOS O SEPARACION ENTRE ELLOS DE CENTRO A CENTRO
F3 1 RESISTIVIDAD TERMICA DE LA TIERRA EN RELACION CON EL AREA DEL CONDUCTOR (MM2) Y LA PROFUNDIDAD DE LOS CONDUCUTORES
F4 0.98 FACTOR DE LA PROFUNDIDAD PARA DETERMINAR VALOR DE DERRATEO

Ic= I/(F1*F2*F3*F4)
Ic= 111.78 A

SECCION EN BASE A TABLA 310-60(C)(77) DETALLE 2

SECCION DE 33.6 mm2 Cal. 2 AWG 90°C (155 A) AMPACIDAD DE 5001-35000 VOLTS
CORRIENTE DE CORTO CIRCUITO

ISC=(K X A)/(RAIZ (t))

K= Constante que depende del material del conductor relacionado con la temperatura inical y final asociadas con las condiciones del cable durante el corto circuito
136 (cobre= 136; aluminio=87)
A= 36 Sección transversal del conductor
t= 1 Duración del corto circuito, para cables de MV usar 1 segundo

ISC= 4.896 KA
Evaluación por caída de Tensión- regulación de tensión
REACTANCIA
RESISTENCIA INDUCTIVA
CORRIENTE ALTERNA
R (OHM/KM) XL (OHM/KM)
CONDUIT PVC O
CONDUIT DE PVC
Evaluando valor aproximado de caida de tension con base en la impedancia del condcutor ALUMINIO
TABLA 1
Ɵ= F.P.=COS(Ɵ) SEN (Ɵ) SECCION CALIBRE R XL Z
Z= 1 0
Zef= Rcos(Ɵ) + Xsen(Ɵ) SEN= 0.53 0.95 0.31
COS= 0.85 F.P. 0.9 0.44 2 0.6671 0.17 Z= 0.657135
R= TABLA 1 0.85 0.53 1/0 0.4195 0.155 Z= 0.438725
X= TABLA 1 0.8 0.6 2/0 0.3331 0.149 Z= 0.362105
F.P= COS( 0.75 0.66 4/0 0.2103 0.138 Z= 0.251895
I= 111.78 0.7 0.71
LONGITUD EN (KM)= 0.30
V f-f- 6000.00
EVALUACION DE CAIDA DE TENSION

CALIBRE= 2 CAIDA FASE-NEUTRO= ZEF*L*I CAIDA FASE-FASE= 1.73* CAIDA FASE NEUTRO
CAIDA FASE-NEUTRO= 22.036014065957 CAIDA FASE-FASE= 38.1223043

PORCENTAJE DE CAIDA DE TENSION

% CAIDA DE TENSION FASE-FASE= (CAIDA FASE-FASE*VOLTAJE DEL SISTEMA)*100


% CAIDA DE TENSION FASE-FASE= 0.6353717389017 %

CALIBRE= 1/0 CAIDA FASE-NEUTRO= ZEF*L*I CAIDA FASE-FASE= 1.73* CAIDA FASE NEUTRO
CAIDA FASE-NEUTRO= 14.711969794771 CAIDA FASE-FASE= 25.4517077

PORCENTAJE DE CAIDA DE TENSION

% CAIDA DE TENSION FASE-FASE= (CAIDA FASE-FASE*VOLTAJE DEL SISTEMA)*100


% CAIDA DE TENSION FASE-FASE= 0.4241951290826 %

CALIBRE= 2/0 CAIDA FASE-NEUTRO= ZEF*L*I CAIDA FASE-FASE= 1.73* CAIDA FASE NEUTRO
CAIDA FASE-NEUTRO= 12.142635643138 CAIDA FASE-FASE= 21.0067597

PORCENTAJE DE CAIDA DE TENSION

% CAIDA DE TENSION FASE-FASE= (CAIDA FASE-FASE*VOLTAJE DEL SISTEMA)*100


% CAIDA DE TENSION FASE-FASE= 0.3501126610438 %

CALIBRE= 4/0 CAIDA FASE-NEUTRO= ZEF*L*I CAIDA FASE-FASE= 1.73* CAIDA FASE NEUTRO
CAIDA FASE-NEUTRO= 8.446912374389 CAIDA FASE-FASE= 14.6131584

PORCENTAJE DE CAIDA DE TENSION


% CAIDA DE TENSION FASE-FASE= (CAIDA FASE-FASE*VOLTAJE DEL SISTEMA)*100
% CAIDA DE TENSION FASE-FASE= 0.2435526401282 %
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

ANALIS DE CARGA DE SALA 1

BOTONES DE PARO PARA


ESPACIO CONTACTO MONOFASICO DE CONTACTO MONOFASICO TORRE DE ILUMINACION LUMINARIA 50-100 PUERTA METALICA
DESCIPCION DE EQUIPO ELECTRICO SERVICIO CANTIDAD LUMINARIA 600 LUX/M2 LUMINARIA 400 LUX/M2 LUMINARIA 200 LUX/M2 CITB ACCIONAR BOBINAS DE UPS TRIFASICO F1 F2 F3 POTENCIA
TABLERO SERVICIO PARA LASER (INDICADOR) LUX/M2 MAGNETIZADA
DISPARO

300 400 10 60 80 18 18 750 500 300 10000


WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS
127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 127 V 220 V

26 0.00
28 0.00
30 0.00
32 0.00
34 0.00
36 0.00
38 0.00
40 0.00
42 0.00
0.00

WATTS 0.00 0.00 0.00 0.00


LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

TOTAL EN WATTS = 0.00


KW = 0.00

I =

I= = 640

FT= 1
FA= 1

IC = 721.00

AMPERES

INTERRUPTOR PRINCIPAL AL 100% DE DEMANDA


#DIV/0! A ≥ A
I = #DIV/0! A
100% DEMANDA

ANALISIS DE CALIBRE DE ALIMENTADOR PRINCIPAL DE TABLERO

LONGITUD 150 W = 274412.60


CAlIBRE ACTUAL 1/0 AWG RAIZ(3) = 1.73
SECCION MM2 53.48 MM2 COSØ = 0.85
Z EFECTIVA A 0.85 DE F.P. 0.411 IMPEDANCIA ef = 220
DISTANCIA DE ALIMENTADOR L = 20 MTS
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

274412.6
=
I 323.89350101538

= 847.23
I

= 1.25*I/(FT*FA)
IC

1059.04 3 cond. Portadores de


= 1 cond. X fase
IC 1.00 corriente

IC
= 1059.04 a
4 -6 c o n d . P o r t a d o r e s d e
2 cond. X fase
1059.04 corriente
=
IC 0.80

IC
= 1323.80 a

3 cond. X fase
1059.04 7 -9 c o n d . P o r t a d o r e s d e
=
IC 0.70 corriente

IC
= 1512.91 a

1059.04
= 4 cond. X fase
IC 0.50 7-9 cond. Portadores de corriente

IC
= 2118.08 a

CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 20 MTS
IC = 1059.04 A
tuberia conduit
= 73372.3529411765 e% = 1.00 % de caida a calcular metalico
S 220 ef = 220 V
3f-4h
SECCION DEL PARALELO e% z= total de cond.
= 333.510695187166 1000 kcm
S CONDUCTOR cond. X fase 1 0.119
1 cond. X fase 1 COND. X FASE 1.98 4
AREA= 333.510695187166

ampacidad en bandeja o tubo conduit ic


615 x 1 615.00 ≥ 1059.04 0

SECCION DEL PARALELO


CONDUCTOR cond. X fase 2
e% z= total de cond.
AREA= 208.444184491979 1000 0.119
2 COND. X FASE 1.24 8
area en tabla 304

ampacidad en bandeja o tubo conduit ic


615 x 2 1230.00 ≥ 1323.80 0

SECCION DEL PARALELO


CONDUCTOR cond. X fase 3

e% z= total de cond.
AREA= 158.814616755793 750 0.131
3 COND. X FASE 1.04 12
area en tabla 380

ampacidad en bandeja o tubo conduit ic


545 x 3 1635.00 ≥ 1512.91 1

SECCION DEL PARALELO


CONDUCTOR cond. X fase 4

e% z= total de cond.
AREA= 166.755347593583 1000 0.119
4 COND. X FASE 0.99 16

ampacidad en bandeja o tubo conduit ic


545 x 4 2180.00 2118.08 1

IMPEDANCIA=Zefec con F.P.


CALIBRE PROPUESTO AWG SECCION IMPEDANCIA=Zefec con F.P. 0.85 CALIBRE PROPUESTO KCM SECCION 0.85

4/0 107 0.242 250 127 0.213

CALCULO DE CAIDA DE VOLTAJE CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 RAIZ(3)*Z*I*L RAIZ(3) = 1.7321


e% =
10*ef Z = 0.242 10*ef Z = 0.213
I = 1059.039 I = 1059.039
8878.05470588235 L = 20 7814.15558823529 L = 20
e% =
2200 ef = 220 2200 ef = 220

e% = ≤ 2% ≤ 2%
4.03547941176471 3.55188890374332
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

ANALISIS DE POTENCIA REAL SOPORTADA POR CALIBRE 4/0 CON 20 MTS DE LONGITUD

LONGITUD 20 MTS W = 274412.60


CAlIBRE ACTUAL 4/0 AWG RAIZ(3) = 1.7321
SECCION MM2 107 MM2 COSØ = 0.85
Z EFECTIVA A 0.85 DE F.P. 0.242 IMPEDANCIA ef = 220
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

274412.6
=
I 323.89350101538

= 847.23 A
I

CALCULO DE SECCION DEL COBRE POR DISTANCIA

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 20 MTS
I = 847.23 A
58697.8823529412 e% = 2 CAIDA
=
S 440 ef = 220 V

SECCION DEL
= 133.40 MM2
S CONDUCTOR

CALIBRE PROPUESTO SECCION Zefec con F.P. 0.85 80.60 A X 220 X1.73=30.68 KW KVA=30.68 KW / F,P,= 30.68/0.85=36.08 KVA
4/0 107 0.242

CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 36.08 X 0.30 F.S.= 46.91 KVA


e% =
10*ef Z = 0.242
I = 847.231
7102.44376470588 L = 20
e% =
2200 ef = 220
TRANSFORMADOR 3F-4H DELTA ESTRELA= 50 KVA
e% = ≤ 2%
3.23

CON EL CALIBRE 4/0 AWG Y 160 METROS DE LONGITUD DEL ALIMENTADOR EL CONDUCTOR TIENE LA CAPACIDAD DE SUMINISTRAR una demanda de 27643 WATTS 3f-4h CON UN AMPERAJE POR FASE DE 80.60 A
LOVA PROYECTOS Y SERVICIOS ELECTRICOS S.A. DE C.V.
PROYECTO: FECHA:
CUADRO DE CARGAS
ALIMENTADOR GRAL. DE LA SALA 1 5/8/2020
TIPO: MARCA: TABLERO: SERVICIO:
NQ30 SQUARE´D NQ 30 CIRCUITOS ALUMBRADO Y CONTATOS
VOLTAJE: INT. PRINCIPAL: UBICACIÓN: REVISICIÓN:
3F,4H,220/127 V, 60Hz 3P-70 AMP. SALA 1 SR. JOSE ALBERTO LOPEZ VAZQUEZ

ANALISIS DE CALIBRE DE ALIMENTADOR PRINCIPAL DE TABLERO

LONGITUD 150 W = 195000.00 KVA KW RESERVA RESERVA-KVA 100 150


CAlIBRE ACTUAL 1/0 AWG RAIZ(3) = 1.73 150 150 130% 45.00 180

53.48 1 RESERVA EN AMPERES


SECCION MM2 MM2 COSØ = X FASE
Z EFECTIVA A 0.85 DE F.P. 0.411 IMPEDANCIA ef = 220 39.4114555964267
DISTANCIA DE ALIMENTADOR L = 20 MTS
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

195000
=
I 381.051177665153

= 511.74
I

= 1.25*I/(FT*FA)
IC

639.68
= 1 cond. X fase
IC 1.00 3 cond. Portadores de corriente

IC
= 639.68 a

2 cond. X fase
639.68 4-6 cond. Portadores de corriente
=
IC 0.80

IC
= 799.60 a

3 cond. X fase
639.68
=
IC 0.70 7-9 cond. Portadores de corriente

IC
= 913.83 a

639.68
= 4 cond. X fase
IC 0.50 7-9 cond. Portadores de corriente

IC
= 1279.36 a

CALCULO DE SECCION DEL COBRE POR DISTANCIA- CAIDA DE TENSION

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 20 MTS
IC = 639.68 A
tuberia conduit
= 44318.1818181818 e% = 1.00 % de caida a calcular metalico
S 220 ef = 220 V
3f-4h
SECCION DEL PARALELO e% z= total de cond. CANALIZACION
S
= 201.446280991735
CONDUCTOR cond. X fase 1
1000 kcm 0.119
1 cond. X fase 1 COND. X FASE 1.20 4
AREA= 201.446280991735

ampacidad en bandeja o tubo conduit ic


615 x 1 615.00 ≥ 639.68 0
AMPACIDAD MINIMA DE CONDUCTOR
639.68
considerando dos tuberias, cada tuberia con 3 condcutores por fase para mantener factores de ft y fa con valor de 1.00

SECCION DEL PARALELO bandeja SECCION DEL PARALELO tuberias


CONDUCTOR cond. X fase 2 CONDUCTOR cond. X fase 2
1 2
e% z= total de cond. e% z= total de cond
AREA= 125.903925619835 500 KCM 0.154 ancho
AREA= 201.446280991735 350 kcm 0.187 diametro
0.97 8 2 0 cm p er al te d e 12 c m 0.94 8
area en tabla 304 2 COND. X FASE espacio 2.40 area en tabla 304 2 COND. X FASE 3"
mm
ampacidad en bandeja o tubo conduit ic ampacidad en bandeja o tubo conduit ic
430 x 2 860.00 ≥ 799.60 1 350 x 2 700.00 ≥ 639.68 1
AMPACIDAD MINIMA DE CONDUCTOR AMPACIDAD MINIMA DE CONDUCTOR
399.80 319.84

SECCION DEL PARALELO


CONDUCTOR cond. X fase 3

e% z= total de cond.
AREA= 95.926800472255 350 0.187
0.90 12
area en tabla 380 3 COND. X FASE

ampacidad en bandeja o tubo conduit ic


350 x 3 1050.00 ≥ 913.83 1
AMPACIDAD MINIMA DE CONDUCTOR
304.61

SECCION DEL PARALELO


CONDUCTOR cond. X fase 4

e% z= total de cond.
AREA= 100.723140495868 350 0.187
4 COND. X FASE 0.94 16

ampacidad en bandeja o tubo conduit ic


350 x 4 1400.00 1279.36 1
AMPACIDAD MINIMA DE CONDUCTOR
319.84

CALIBRE PROPUESTO AWG SECCION IMPEDANCIA=Zefec con F.P. 0.85 CALIBRE PROPUESTO KCM SECCION IMPEDANCIA=Zefec con F.P. 0.85

4/0 107 0.242 250 127 0.213

CALCULO DE CAIDA DE VOLTAJE CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 RAIZ(3)*Z*I*L RAIZ(3) = 1.7321


e% =
10*ef Z = 0.242 10*ef Z = 0.213
I = 639.678 I = 639.678
5362.5 L = 20 4719.88636363636 L = 20
e% =
2200 ef = 220 2200 ef = 220

e% = ≤ 2% ≤ 2%
2.4375 2.14540289256198

ANALISIS DE POTENCIA REAL SOPORTADA POR CALIBRE 4/0 CON 20 MTS DE LONGITUD

LONGITUD 20 MTS W = 195000.00


CAlIBRE ACTUAL 4/0 AWG RAIZ(3) = 1.7321
SECCION MM2 107 MM2 COSØ = 1
Z EFECTIVA A 0.85 DE F.P. 0.242 IMPEDANCIA ef = 220
I = ¿?
W
=
I RAIZ(3)*ef*cos Ø

W
=
I RAIZ(3)*ef*cos Ø

195000
=
I 381.051177665153

= 511.74 A
I

CALCULO DE SECCION DEL COBRE POR DISTANCIA

2*RAIZ(3)*L*I RAIZ(3) = 1.7321


=
S e%*ef L = 20 MTS
I = 511.74 A
35454.5454545454 e% = 2 CAIDA
=
S 440 ef = 220 V

SECCION DEL
= 80.58 MM2
S CONDUCTOR

CALIBRE PROPUESTO SECCION Zefec con F.P. 0.85 80.60 A X 220 X1.73=30.68 KW KVA=30.68 KW / F,P,= 30.68/0.85=36.08 KVA
4/0 107 0.242

CALCULO DE CAIDA DE VOLTAJE

RAIZ(3)*Z*I*L RAIZ(3) = 1.7321 36.08 X 0.30 F.S.= 46.91 KVA


e% =
10*ef Z = 0.242
I = 511.742
4290 L = 20
e% =
2200 ef = 220
TRANSFORMADOR 3F-4H DELTA ESTRELA= 50 KVA

e% = ≤ 2%
1.95

CON EL CALIBRE 4/0 AWG Y 160 METROS DE LONGITUD DEL ALIMENTADOR EL CONDUCTOR TIENE LA CAPACIDAD DE SUMINISTRAR una demanda de 27643 WATTS 3f-4h CON UN AMPERAJE POR FASE DE 80.60 A