INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152


Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

ELABORÓ REVISÓ APROBÓ


FECHA OBJETO
Iniciales Iniciales Iniciales/Cargo

TMK / LU SN/VPO
MAR. 2010 Emisión Original MR MS/VPO
/ PPC

903-HM150-E01-GUD-152_REV0.DOCX 1 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Índice

Página

1.  PROPÓSITO .................................................................................................. 3 


2.  ALCANCE ....................................................................................................... 3 
3.  INSTRUCCIONES .......................................................................................... 3 
3.1  Descripción ..................................................................................................... 3 
3.1.1  Tabla Datos de entrada .................................................................................. 3 
3.1.2  Tabla Parámetros de cálculo .......................................................................... 4 
3.2  Utilización ....................................................................................................... 5 
3.2.1  Bloque de decisión ......................................................................................... 5 
3.2.2  Bloque de acción ............................................................................................ 6 
4.  DESARROLLO DEL MÉTODO DE DIMENSIONAMIENTO ........................... 8 
4.1  Intensidad máxima admisible por el cable en servicio permanente .............. 10 
4.1.1  Premisas ....................................................................................................... 10 
4.1.2  Desarrollo ..................................................................................................... 11 
4.1.3  Capacidad de carga en régimen permanente – Flujogramas ....................... 11 
4.1.4  Capacidad de carga en régimen permanente – Datos de entrada ............... 13 
4.1.5  Capacidad de carga en régimen permanente – Parámetros de cálculo ....... 16 
4.2  Intensidad máxima admisible en cortocircuito durante un tiempo
determinado .................................................................................................. 17 
4.2.1  Premisas ....................................................................................................... 17 
4.2.2  Desarrollo ..................................................................................................... 17 
4.2.3  Sección admisible por cortocircuito – Flujograma ........................................ 20 
4.2.4  Sección admisible por cortocircuito - Datos de entrada ............................... 23 
4.2.5  Sección admisible por cortocircuito – Parámetros de cálculo ....................... 24 
4.3  Caída de tensión........................................................................................... 25 
4.3.1  Premisas ....................................................................................................... 25 
4.3.2  Desarrollo ..................................................................................................... 25 
4.3.3  Caída de Tensión – Flujograma.................................................................... 28 
4.3.4  Caída de Tensión – Datos de entrada .......................................................... 29 
4.3.5  Caída de Tensión – Parámetros de cálculo .................................................. 30 
5.  REFERENCIAS ............................................................................................ 31 
ANEXO I: INTENSIDAD MÁXIMA ADMISIBLE POR EL CABLE EN SERVICIO
PERMANENTE ............................................................................................. 33 
ANEXO II: TABLAS DECARACTERÍSTICAS DE CABLES ...................................... 38 
ANEXO III: IMPEDANCIAS TIPICAS DE CABLES ................................................... 39 

903-HM150-E01-GUD-152_REV0.DOCX 2 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

1. PROPÓSITO

Establecer los lineamientos para el dimensionamiento de los cables, a utilizarse


en los proyectos en el área de Ingeniería Eléctrica.

Este instructivo está desarrollado para ser utilizado como base en un programa
informático de cálculo de cables. No obstante, puede ser utilizado como guía
para cálculo manual.

2. ALCANCE

Este documento contempla el dimensionamiento de cables en el rango de


tensión de aislamiento 0,6/1kV a 18/30kV. Para cables de instrumentación y
control ver el documento “Especificación de Cables de Instrumentación y
Control” N° 903-HM160-I41-GUD-061.

3. INSTRUCCIONES

3.1 Descripción

Cada flujograma descriptivo de un método de cálculo en este instructivo tiene


dos tablas asociadas.

3.1.1 Tabla Datos de entrada

Indica los campos a completar (columna 2, “Campo”) para poder continuar con
el cálculo. Los campos están agrupados según afinidad (columna 1, “Grupo”).
Para cada campo se indican los datos que se tiene como opción (columna 4,
“Dato”) y cada campo tiene un número de referencia (columna 3, “N° ref. Dato
de Entrada”).

903-HM150-E01-GUD-152_REV0.DOCX 3 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

3.1.2 Tabla Parámetros de cálculo

Se listan en esta tabla todos los parámetros que se encuentran en el flujograma


(columna 1, “Parámetro”). Otorga una descripción de cada uno (columna 2,
“Descripción”), su unidad de medición (columna 3, “Unidad”), la fuente del valor
a asignar al parámetro (columna 4, “Fuente”) y los datos de entrada que se
necesitan para calcularlo (columna 5, “Datos de entrada”), referidos a la
columna 3 de la tabla Datos de entrada.

903-HM150-E01-GUD-152_REV0.DOCX 4 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

3.2 Utilización

Para realizar el cálculo elegido, en primer lugar se debe completar la tabla de


Datos de entrada. Para cada Campo que aplique al caso, se elige el dato que
corresponda:

• Ejemplo:

Tabla de “Datos de entrada” de cálculo por corriente


admisible

Conductor: Unipolar Trebolillo


Tensión nominal: 0,6/1 kV
Material conductor: Cobre
Aislamiento: PVC
etc.

Se comienza a recorrer el flujograma correspondiente. Al avanzar por los


distintos bloques, se pueden encontrar dos casos.

3.2.1 Bloque de decisión

Es el bloque en forma romboidal, que efectúa una pregunta, otorgando dos


posibilidades de respuesta. Estas respuestas se encuentran fácilmente con los
datos seleccionados en la tabla “Datos de entrada” o a partir de algún parámetro
calculado previamente.

903-HM150-E01-GUD-152_REV0.DOCX 5 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

• Ejemplo:

En el flujograma de cálculo por corriente admisible se encuentra un bloque que pregunta


si el cable está tendido bajo cubierta:

De la tabla “Datos de entrada” correspondiente, según se había seleccionado


previamente:

Se sigue el flujo por la rama “SI”

3.2.2 Bloque de acción

Es el bloque de forma rectangular, que indica una acción a llevar a cabo, como
obtener un parámetro mediante un cálculo, o extraer un parámetro de una tabla.
Él o los parámetros indicados en el bloque se debe/n ubicar en la tabla
“Parámetros de cálculo”. En la misma, se indica en la columna 4, “Fuente”, de
dónde se obtiene el valor del parámetro, y en la columna5, “Datos de entrada”,
qué datos hacen falta para obtenerlo. Esta última columna, “Datos de entrada”,
hace referencia a la columna 3, “N° ref. Dato de entrada”, de la tabla “Datos de
entrada”.

903-HM150-E01-GUD-152_REV0.DOCX 6 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

903-HM150-E01-GUD-152_REV0.DOCX 7 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4. DESARROLLO DEL MÉTODO DE DIMENSIONAMIENTO

En el flujograma de la figura 1 se representa en forma general el método a


utilizar para el dimensionamiento de cables según IEC / DIN VDE. Tal como allí
se expone, existen tres criterios para calcular la sección del conductor de
acuerdo a las características eléctricas de la carga a alimentar, al tipo de cable
y a la forma de instalación. Dichos criterios se explican en la sección 5, y son:

903-HM150-E01-GUD-152_REV0.DOCX 8 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

a. Criterio de Intensidad máxima admisible en servicio permanente,


desarrollado en la subsección 4.1. Se tomó como base lo establecido por
las normas DIN VDE en lugar de IEC debido a que las normas IEC en
cuanto a cables de media tensión no logran unicidad de criterio, y en
cuanto a cables de baja tensión sólo desarrollan un procedimiento para
instalaciones domiciliarias en BT.

b. Criterio de Intensidad máxima admisible en Cortocircuito durante un tiempo


determinado, desarrollado en la subsección 4.2. Se tomó como base lo
establecido en la norma IEC 60949 “Cálculo de corrientes de cortocircuito
térmicamente admisibles, teniendo en cuenta efectos de disipación de calor
no adiabáticos”. Este cálculo se debe realizar no sólo en los conductores
de fase, sino también en los conductores de retorno (neutro, tierra), si
existen.

c. Criterio de Caída de Tensión, desarrollado en la subsección 4.3. Se realiza


la verificación de la caída de tensión en el cable en el arranque y en
servicio permanente mediante las fórmulas electrotécnicas conocidas. La
corrección del valor de la resistencia se realiza según norma IEC, los
valores de reactancia se toman como promedio de valores de catálogos de
distintos proveedores.

En el Anexo I se presenta una guía que facilita la interpretación de las tablas


presentadas en las subsecciones 4.1, 4.2 y 4.3.

903-HM150-E01-GUD-152_REV0.DOCX 9 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 1 Flujograma general

Referencias : Inicio

Iad: Corriente admisible.


ICC: Corriente de cortocircuito.
Cu : Caída de Tensión: Criterio a
Cálculo por Iad

Selecciona cable
de catálogo según
sección obtenido

Incrementa
sección
Criterio b
Cálculo por ICC

No ¿Verifica
Criterio b?

Si

Selecciona cable Criterio C


de catálogo según
sección obtenida Cálculo por Cu

Incremento No ¿Verifica
Sección Criterio C?

Si

Fin

4.1 Intensidad máxima admisible por el cable en servicio permanente

4.1.1 Premisas

Se deben seguir los pasos indicados en los flujogramas a1 y a2


correspondiente al criterio, utilizando las tablas A1 y A2 como se explica en el
Anexo I.

903-HM150-E01-GUD-152_REV0.DOCX 10 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Como valores de corriente admisible para cables no contemplados en las


normas de referencia, se toman los promedios de los valores dados por distintos
fabricantes, para cada tipo de cable. Este caso se da en los cables XLPE 2,3/3,3
kV.

Cuando el cable está cubierto por una protección en forma de media caña se
debe aplicar un factor de corrección de 0,9.

Cuando el cable está tendido dentro de un tubo se debe aplicar un factor de


corrección de 0,85.

En el anexo I se analizan los fundamentos del método aquí utilizado.

4.1.2 Desarrollo

Se deben seguir los pasos indicados en los flujogramas a1, a2 y a3, utilizando
las tablas A1 y A2.

El método descrito consiste en calcular la sección del cable por capacidad


térmica en régimen permanente.

4.1.3 Capacidad de carga en régimen permanente – Flujogramas

Referencias: Tabla A1 “Datos de entrada”.


Tabla A2 “Parámetros de cálculo”.

903-HM150-E01-GUD-152_REV0.DOCX 11 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 2 Flujograma a1 – Obtención Factor de corrección.

903-HM150-E01-GUD-152_REV0.DOCX 12 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 3 Flujograma a2 – Elección de la sección

4.1.4 Capacidad de carga en régimen permanente – Datos de entrada

Tabla A1 “Datos de entrada”

N° ref. Dato de
Grupo Campo Datos
Entrada
1 Unipolar CC
3 Unipolares Trebolillo
3 Unipolares en fila
Tripolar/Tetrapolar
Multi x 5
Cable Multi x 7
Conductores 1
Multi x 10
Multi x 14
Multi x 19
Multi x 24
Multi x 40
Multi x 61

903-HM150-E01-GUD-152_REV0.DOCX 13 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

N° ref. Dato de
Grupo Campo Datos
Entrada
0,6/1 kV
3,6/6 kV
2 6/10 kV
Tensión
nominal 12/20 kV
18/30 kV
Material Cobre
3
Cable conductor Aluminio
XLPE / 90°C
PVC
Aislamiento 4
Papel impregnado
Papel impregnado
Protección Armado
5
cables Sin Armar
Caño
Protección Bajo cubierta, aire
6
externa intermedio
Ninguna
1
2
3
4
Exterior
5
N° de sistemas 7
6
7
8
9
10
k8 8 Valor manual
I calculada 9 Valor manual
Factor de
10
carga Valor manual
En aire
Tendido 11
Enterrado
Temperatura
12 Valor manual
ambiente
1
2
3
4
Tendido
5
Tipo de tendido 6
13
en aire 7
8
9
10
11
12

903-HM150-E01-GUD-152_REV0.DOCX 14 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

N° ref. Dato de
Grupo Campo Datos
Entrada
13
14
15
16
Tipo de tendido
13 17
en aire
18
19
20
21
1
2
N° de Capas 14
3
6
Temp. del
15 Valor manual
terreno
0,7
Resistividad
1
térmica del 16
1,5
terreno
2,5
1-1
Tendido 1-4
1-10
2-1
2-3
2-5
Configuración 17
2-8
2-10
3-1
3-3
3-6
3-10
1
Tipo de tendido 2
18
enterrado 3
4
90
80
Temp. Máxima
19 70
de operación
65
60

903-HM150-E01-GUD-152_REV0.DOCX 15 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.1.5 Capacidad de carga en régimen permanente – Parámetros de cálculo

Tabla A2 “Parámetros de cálculo”.

Datos de
Parámetro Descripción Unidad Fuente (1)
entrada
VDE 0276-1000 T10
k1 Factor de agrupamiento en aire - 13 , 14 y 7
VDE 0276-1000 T11
Factor de corrección por
k2 - VDE 0276-1000 T12 4 , 12 y 19
temperatura ambiente
Factor de corrección por
k3 - VDE 0276-1000 T13 1 y 11
multiconductor
Factor de corrección por
k4 - Automático 6
tendido bajo cubierta con aire
Factor de corrección por
k5 - Automático 6
tendido en caño
Factor de corrección por
VDE 0276-1000 T4 4 , 15 , 16 ,
k6 temperatura y resistencia -
VDE 0276-1000 T5 17 , 10 y 19
térmica del terreno
VDE 0276-1000 T6
Factor de corrección por VDE 0276-1000 T7 4 , 16 , 7 , 10
k7 -
agrupamiento enterrado VDE 0276-1000 T8 y 18
VDE 0276-1000 T9
Factor de corrección a criterio
K8 - - -
de proyectista
ktot Factor de corrección total - Fórmula en flujograma 8
Icorr Corriente del circuito corregida A Fórmula en flujograma 9
Sección del conductor por
mm2 Tabla secciones -
Sad corriente admisible
VDE 0276-603 T14 H3-G-23
VDE 0276-603 T14 H5-G-22
VDE 0276-603 T15 H3-G-24
VDE 0276-603 T15 H5-G-23
VDE 0276-620 T6 H3-C-22
VDE 0276-620 T7 H3-C-23
VDE 0276-620 T8 H4-C-22
VDE 0276-620 T9 H4-C-23
VDE 0276-620 T7 H5-C-25
VDE 0276-620 T8 H5-C-26 1,2,3,4y
Ti Tabla de corrientes admisibles -
VDE 0276-620 T7 H6-C-26 11
VDE 0276-620 T8 H6-C-27
VDE 0276-621 T6 H3-C-17
VDE 0276-621 T7 H3-C-18
VDE 0276-621 T8 H3-C-18
VDE 0276-621 T9 H3-C-19
VDE 0276-621 T10 H3-C-19
VDE 0276-621 T11 H3-C-20
VDE 0276-621 T11 H4-C-21
VDE 0276-621 T12 H4-C-22

(1): Estructura: (n° norma) T(tabla) H(n° de hoja)

903-HM150-E01-GUD-152_REV0.DOCX 16 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.2 Intensidad máxima admisible en cortocircuito durante un tiempo


determinado

4.2.1 Premisas

En el método de cálculo tradicional, se asume que el efecto del cortocircuito en


el conductor se produce en condiciones adiabáticas, siendo retenido todo el
calor en el mismo.

Sin embargo, en condiciones reales hay intercambio de calor con los materiales
adyacentes. A partir de esto, se puede tomar cierta ventaja teniendo en cuenta
parte de este efecto no adiabático.

Según [6], se incorpora al cálculo una corrección que permite un incremento del
5% como mínimo en la corriente admisible por cortocircuito, para los cables de
potencia de uso común. Esta corrección es válida para cualquier duración del
cortocircuito, y las condiciones asumidas en las fórmulas corresponden al peor
caso.

4.2.2 Desarrollo

Se deben seguir los pasos indicados en los flujogramas b1, b2 y b3, utilizando
las tablas B1 y B2 como se explica en el Anexo II.

El método descrito consiste en:

a) Calcular la corriente de cortocircuito adiabática.


b) Calcular el factor de modificación que tiene en cuenta el efecto no adiabático.
c) Multiplicar a) y b) para obtener la corriente de cortocircuito admisible.

4.2.2.1 Corriente de cortocircuito admisible

I = ε ⋅ IAD (b.1)
Donde:

I: corriente de cortocircuito admisible (A).


IAD : corriente de cortocircuito calculada por método adiabático (A).
ε: factor para admitir las pérdidas de calor en los componentes
adyacentes. Para cálculo adiabático ε = 1.

903-HM150-E01-GUD-152_REV0.DOCX 17 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.2.2.2 Cálculo de la corriente de cortocircuito adiabática

⎛θ f + β ⎞
I AD ⋅ t = K 2 ⋅ S cc ⋅ ln⎜⎜ ⎟
2 2
⎟ (b.2)
⎝ θi + β ⎠
Con:
σ c ⋅ ( β + 20) ⋅ 10 −12
K= (b.3)
ρ 20
Donde:
IAD: corriente de cortocircuito calculada por método adiabático (A).
t: duración del cortocircuito (s).
K: constante dependiente del material del elemento conductor.
(A.s1/2/mm2).
Scc : área seccional del elemento conductor (mm2).
θf : temperatura final (°C).
θi : temperatura inicial (°C).
β: inversa del coeficiente de temperatura de resistencia del elemento
conductor a 0 °C. Ver Tabla I [6] (Anexo II).
σc : Calor específico volumétrico del elemento conductor. A 20°C
(J/K.m3). Ver Tabla I [6] (Anexo II).
ρ20 : resistividad eléctrica del elemento conductor a 20°C (Ω.m). Ver
Tabla I [6] (Anexo II).

4.2.2.3 Cálculo del factor no adiabático para conductores y pantallas de


alambres espaciados

t ⎛ t ⎞
ε = 1+ F ⋅ A⋅ + F 2 ⋅ B ⋅ ⎜⎜ ⎟⎟ (b.4)
S cc ⎝ S cc ⎠
Donde:
F: factor que tiene en cuenta el contacto térmico imperfecto entre
conductor o alambres y materiales no metálicos adyacentes.

Alambres de pantalla aislados no embebidos en el material: F = 0,5


Recomendado: F = 0,7
Cables con aceite: F = 1

A; B: constantes empíricas

C1 σi
A= (mm 2 /s) 1/2 ; C1 = 2464 mm/m (b.5)
σc ρi

C2 ⎛ σ i ⎞
B= ⎜ ⎟⎟ (mm 2 /s) ; C 2 = 1,22 K.m.mm 2 /J (b.6)
σ c ⎜⎝ ρ i ⎠
903-HM150-E01-GUD-152_REV0.DOCX 18 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

σc : Calor específico volumétrico del elemento conductor a 20°C


(J/K.m3). Ver Tabla I [6] (Anexo II).
σi : Calor específico volumétrico de los materiales envolventes o
adyacentes no metálicos. A 20°C (J/K.m3). Ver Tabla I [6] (Anexo II)
ρi : Resistividad térmica de los materiales envolventes o adyacentes no
metálicos (K.m/W) Valores sugeridos en Tabla II [6] (Anexo II).

4.2.2.4 Cálculo del factor no adiabático para vainas, pantallas y alambres

( )2
(
ε = 1 + 0,61 ⋅ M ⋅ t − 0,069 ⋅ M ⋅ t + 0,0043 ⋅ M ⋅ t )
3
(b.7)
⎛ σ2 σ 3 ⎞⎟
⎜ +
⎜ ρ ρ 3 ⎟⎠

(s −1/2 )
2
M= F (b.8)
2 ⋅ σ 1 ⋅ δ ⋅ 10 −3

Donde:

σ2 , σ3: Calor específico volumétrico de los medios a cada lado de la


vaina, pantalla o armadura (J/K.m3). Valores sugeridos en Tabla II [6]
(Anexo II).
ρ2 , ρ3: Resistividad térmica de los medios a cada lado de la vaina,
pantalla o armadura (K.m/W). Valores sugeridos en Tabla II [6] (Anexo II).
σ1: Calor específico volumétrico de la vaina, pantalla o armadura
(J/K.m3). Valores sugeridos en Tabla II [6] (Anexo II).
δ: espesor de la pantalla, vaina o armadura (mm).

4.2.2.5 Áreas de vainas, pantallas y alambres para ser usadas en la fórmula


adiabática

4.2.2.5.1 Vaina tubular

S = π ⋅ d ⋅δ (mm2 ) (b.9)

Donde:
D: diámetro medio de la pantalla (mm)
δ: espesor de la vaina (mm)

Nota: para vaina corrugada, d = ( Dint + Dext ) / 2

4.2.2.5.2 Cintas longitudinales

Fórmula a utilizar para un solape menor al 10%.

S = ω ⋅δ (mm2 ) (b.10)

903-HM150-E01-GUD-152_REV0.DOCX 19 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Donde:
ω: ancho de la cinta (mm)
δ: espesor de la cinta (mm)

4.2.2.5.3 Cintas helicoidales

Se asume que la corriente fluye en el sentido de la hélice.

S = n ⋅ω ⋅δ (mm2 ) (b.11)
Donde:

n: número de cintas
ω: ancho de la cinta (mm)
δ: espesor de la cinta (mm)

4.2.2.5.4 Alambres en contacto

Se toma δ como el diámetro de un alambre.

4.2.2.5.5 Tejido de alambre

Se toma δ como dos veces el diámetro del alambre del tejido.

4.2.3 Sección admisible por cortocircuito – Flujograma

Referencias: Tabla B1 “Datos de entrada”.


Tabla B2 “Parámetros de cálculo”.

903-HM150-E01-GUD-152_REV0.DOCX 20 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 4 Flujograma b1 – Cálculo de corriente de cortocircuitos admisible


según IEC 60949.

903-HM150-E01-GUD-152_REV0.DOCX 21 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 5 Flujograma b2 – Interruptor limitador.

Fig. 6 Flujograma b3 – Verificación de corriente admisible.

903-HM150-E01-GUD-152_REV0.DOCX 22 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.2.4 Sección admisible por cortocircuito - Datos de entrada

Tabla B1 “Datos de entrada”

N° ref. Dato
Componente Campo Datos
de entrada
Cobre
Cable Material conductor 1
Aluminio
Plomo
Acero
Material 2
Bronce
Aluminio
Papel impregnado en cables tipo sólidos
Papel impregnado en cables en aceite
Aceite
PE
Material en
3 XLPE
contacto Interior
PVC V≤3kV
PVC V>3kV
EPR V≤3kV
EPR V>3kV
Goma butílica
Goma (natural)
Material de fibras
Protección
Protección de goma en sándwich
Neoprene
Material en PVC V≤35kV
4 PVC V>35kV
contacto Exterior
PVC/bitumen o cobertura de aluminio
corrugado
XLPE semiconductor
EPR semiconductor
Ninguno
Pantalla de Si
alambres no
5
embebidos en el No
material
δ (espesor) 6 Valor manual
Sp 14 Valor manual
θi 7 Valor manual
θf 8 Valor manual
t (tiempo duración
9
falla) Valor manual
Energía limitada 10 Valor manual
General Icc monofásico 11 Valor manual
Icc trifásico 12 Valor manual
Cable monofásico
Tipo conductor 13 Cable trifásico
Protección

903-HM150-E01-GUD-152_REV0.DOCX 23 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.2.5 Sección admisible por cortocircuito – Parámetros de cálculo

Tabla B2 “Parámetros de cálculo”


Pará- Datos de
Descripción Unidad Ubicación
metro entrada
Constante dependiente del material del A √s
K Fórmula b.3 -
conductor /mm2
Inversa del coeficiente de temperatura de
β K Tabla I 1o2
resistencia a 0°C
θi Temperatura inicial °C Ingresos manuales 7
θf Temperatura final °C Ingresos manuales 8
t Duración del cortocircuito s Ingresos manuales 9
Espesor de la cubierta, pantalla o
δ mm Ingresos manuales 6
armadura
Calor específico volumétrico del material
σi J/(K m3) Tabla II 4
no metálico envolvente
Resistividad térmica del material no
ρi K m/W Tabla II 4
metálico envolvente
Calor específico volumétrico del
σc J/(K m3) Tabla I 1o2
componente conductor a 20°C
Calor específico volumétrico de la
σ1 J/(K m3) Tabla II 4
cubierta, pantalla o armadura
Resistividad térmica del medio en el lado
ρ2 K m/W Tabla II 3
interno de la cubierta, pantalla o armadura
Calor específico volumétrico del medio en
σ2 el lado interno de la cubierta, pantalla o J/(K m3) Tabla II 3
armadura
Resistividad térmica del medio del lado
ρ3 externo de la cubierta, pantalla o K m/W Tabla II 4
armadura
Calor específico volumétrico del medio del
σ3 lado externo de la cubierta, pantalla o J/(K m3) Tabla II 4
armadura
Factor que considera imperfecciones en el
F - Tabla IV 4y5
contacto térmico
Sección mínima del tipo de cable
Smín mm2 Tabla secciones -
seleccionado
2
Scc Sección de cálculo de corto mm Tabla secciones -
Área de la sección transversal de la
Sp mm2 Ingresos manuales 14
protección
Densidad de energía del interruptor
I2 t A2 s Ingresos manuales 10
limitador
Densidad de energía adiabática admisible
IAD2 t A2 s Fórmula b.2 7,8
por el cable
Factor para cálculo de vaina, pantallas y
M 1/√s Fórmula b.8 -
alambres
Factor de corrección por efecto no
ε - Fórmula b.4 o b.7 -
adiabático
Resistencia eléctrica del elemento
ρ20 Ω.m Tabla I 1o2
conductor
A Constante empírica A √(mm2/s) Fórmula b.5 -
B Constante empírica B mm2/s Fórmula b.6 -

903-HM150-E01-GUD-152_REV0.DOCX 24 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.3 Caída de tensión

4.3.1 Premisas

Para la verificación del cable por caída de tensión se emplea el siguiente cálculo:

En condiciones nominales

ΔU n = k ⋅ I n ⋅ Long ⋅ ( R ⋅ cosϕn + X ⋅ senϕn ) (c.1)


Donde:

⎧ 2 sistema monofásico
k =⎨
⎩ 3 sistema trifásico

In: Corriente nominal de la carga (A)


Long: Longitud del cable (m)
R: Resistencia del conductor por unidad de longitud (Ω/m)
X: Reactancia del conductor (Ω/m)

En el arranque

ΔU arr = k ⋅ l arr ⋅ Long ⋅ ( R ⋅ cosϕ arr + X ⋅ senϕ arr ) (c.2)

Donde:
Iarr: Corriente de arranque
Para este cálculo se debe corregir el valor de la resistencia del conductor en
corriente alterna para la máxima temperatura de operación del cable, mediante
los factores de proximidad y de efecto pelicular, a partir del valor de resistencia
en corriente continua a 20°C según [7] (Anexo II). Para dicha corrección se
toma el método según [8].

Para los valores de reactancia de los conductores se utiliza el promedio entre


los distintos valores de reactancias presentados por diferentes proveedores de
cables en sus catálogos, refiriéndolos a frecuencia y temperatura de operación.

4.3.2 Desarrollo

Se deben seguir los pasos indicados en los flujogramas c1 y c2, utilizando las
tablas C1 y C2 como se explica en el Anexo I.

4.3.2.1 Resistencia del conductor en corriente alterna

La resistencia por unidad de longitud del conductor a su máxima temperatura


de operación está dada por la siguiente fórmula

903-HM150-E01-GUD-152_REV0.DOCX 25 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

R = R '⋅(1 + y s + y p ) (c.3)

Y para cables en caños de acero


[
R = R '⋅ 1 + 1,5( y s + y p )] (c.4)

Donde:

R: Resistencia del conductor a la máxima temperatura de operación.


R’ : Resistencia del conductor a la máxima temperatura de operación en
corriente continua.
Ys : Factor de corrección por efecto pelicular.
Yp : Factor de corrección por proximidad.

4.3.2.2 Resistencia del conductor en corriente continua

La resistencia por unidad de longitud del conductor a su máxima temperatura


de operación en corriente continua está dada por:

R' = R0 ⋅ [1 + α 20 ⋅ (θ − 20)] (c.5)

Donde:

R0 : Resistencia del conductor en corriente continua a 20°C (Ω/m). El valor


de R0 se obtiene de [7] (Anexo II).
α20 : Coeficiente de temperatura del material a 20°C.
θ: Máxima temperatura de operación, determinada por el tipo de
aislamiento a ser usado (°C).

4.3.2.3 Factor de corrección por efecto pelicular

Está dado por:


xs4
ys = (c.6)
192 + 0,8 ⋅ xs4
Con:

8⋅π ⋅ f
xs2 = ⋅ 10 − 7 ⋅ k s (c.7)
R'
Donde:

f : Frecuencia de red (Hz).


ks : Coeficiente experimental, de [8] (Anexo II).

903-HM150-E01-GUD-152_REV0.DOCX 26 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

4.3.2.4 Factor de corrección por proximidad

4.3.2.4.1 Cable bipolar o 2 unipolares

Está dado por:

2,9 ⋅ x 4p
⎛ dc ⎞
2

yp = ⎜ ⎟ (c.8)
192 + 0,8 ⋅ x p ⎝ s ⎠
4

Con:
8 ⋅ π ⋅ f −7
x 2p = 10 ⋅ k p (c.9)
R'
Donde:

dc : Diámetro del conductor (mm).


s: Separación entre ejes de los conductores (mm).
kp : Coeficiente experimental, de [8] (Anexo II).

4.3.2.4.2 Cable tripolar o 3 unipolares

4.3.2.4.2.1 Para cables de conductores circulares

⎡ ⎤
4 ⎢2 2 ⎥
x ⎛ dc ⎞ ⎢ ⎛ dc ⎞ 1,18 ⎥
yp = ⎜ ⎟ 0,312 ⋅ ⎜ ⎟ +
p
(c.10)
192 + 0,8 ⋅ x 4p ⎝ s ⎠ ⎢ ⎝ ⎠
s x 4 ⎥
⎢ p
+ 0, 27 ⎥
⎢⎣ 192 + 0,8 ⋅ x 4p ⎥⎦

Con:

8 ⋅ π ⋅ f −7
x 2p = 10 ⋅ k p (c.11)
R'
Donde:

dc : Diámetro del conductor (mm).


kp : Coeficiente experimental, de [8] (Anexo II).
s: Distancia entre ejes del conductor (mm)
Nota: Para cables en disposición coplanar, “s” es el espaciamiento entre
fases adyacentes. Cuando el espaciamiento entre fases adyacentes no
es igual, la distancia será tomada como

s = s1 ⋅ s 2 (c.12)

903-HM150-E01-GUD-152_REV0.DOCX 27 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Donde:

s1;s2 : Distancia entre la fase central y las extremas.

4.3.2.4.2.2 Para cables sectoriales

En el caso de multiconductores sectoriales, el valor de yp será 2/3 del


calculado para cable con conductores circulares.
Con:

dc = dx = Diámetro de un conductor circular equivalente de igual sección y


grado de compactación (mm).
s = (dx + t ) (mm)

Donde:

t: Espesor de la aislamiento entre conductores. (mm)


kp : Coeficiente experimental, [8] (Anexo II).

4.3.3 Caída de Tensión – Flujograma

Referencias: Tabla C1 “Datos de entrada”.


Tabla C2 “Parámetros de cálculo”.

Fig. 7 Flujograma c1 – Corrección de resistencia según IEC 60287 1-1.

903-HM150-E01-GUD-152_REV0.DOCX 28 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Fig. 8 Flujograma c2 – Cálculo de caída de tensión.

4.3.4 Caída de Tensión – Datos de entrada

Tabla C1 “Datos de entrada”

N° ref. Dato
Grupo Campo Datos
de entrada
1
2
Clase 1
5
Cable
6
Cu
Conductor 2
Al
Temperatura ambiente 3 Valor manual
50 Hz
Frecuencia 4
60 Hz
Cable Redondo
Tipo de conductor 5 Hueco
Sectorizado

903-HM150-E01-GUD-152_REV0.DOCX 29 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Disposición de los Trenzado


6
conductores Segmentado
Seco e impregnado
Cable Condiciones 7
No seco
Separación entre cond. 8 Valor manual
Unipolar
Conductores 9
Tripolar
Diámetro exterior 19 Valor manual
Monofásico
Sistema 10
Trifásico
Longitud 11 Valor manual
Cos ϕn 12 Valor manual
Circuito Cos ϕarr 13 Valor manual
Un 14 Valor manual
In 15 Valor manual
Iarr 16 Valor manual
Δu n ad 17 Valor manual
Δu arr ad 18 Valor manual

4.3.5 Caída de Tensión – Parámetros de cálculo

Tabla C2 “Parámetros de cálculo”.

Datos
Parámetro Descripción Unidad Fuente de
entrada
Tabla 1, 2, 3 y 4 -
Ro Resistencia del conductor a 20°C Ω/m 1y2
IEC 228
Tabla 1-IEC 287-1-
α20°C Coeficiente de temperatura a 20°C K
1
2
Factor para el cálculo de efecto Tabla 2-IEC 287-1-
ks - 5, 6 y 7
pelicular 1
Factor para el cálculo de efecto Tabla 2-IEC 287-1-
kp - 5, 6 y 7
proximidad 1
k Factor de caída de tensión - Automático 10
In Corriente en condiciones normales A Ingresos manuales 15
Iarr Corriente en el arranque (motor) A Ingresos manuales 16
Un Tensión nominal del sistema V Ingresos manuales 14
SΔu Sección según caída de tensión mm2 Tabla secciones -
Sección mínima del tipo de cable
Smín mm2 Tabla secciones -
seleccionado
Caída de tensión porcentual
Δu n ad % Ingresos manuales 17
admisible en condiciones normales
Caída de tensión porcentual
Δu arr ad % Ingresos manuales 18
admisible en el arranque (motores)
Resistencia del conductor a la
R' Ω/m Fórmula c.3 -
máxima temperatura de operación
Coeficiente de factor de corrección
Xs - Fórmula c.7 4
por efecto pelicular

903-HM150-E01-GUD-152_REV0.DOCX 30 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

Datos
Parámetro Descripción Unidad Fuente de
entrada
Factor de corrección por efecto
Ys - Fórmula c.6 -
pelicular
Coeficiente del factor de corrección
Xp - Fórmula c.9 4
por proximidad
Fórmula c.8
Yp Factor de corrección por proximidad - 19 y 8
Fórmula c.10
Resistencia del conductor a la Fórmula c.3
R Ω/m 9
máxima temperatura de operación Fórmula c.4
Tabla fabricante
(en su defecto,
X Reactancia del cable a 50Hz Ω/m obtener los valores 9
según lo mostrado
en el anexo III)
Reactancia del cable a la frecuencia
Xc Ω/m Fórmula 4
de utilización
15 , 11 y
Δu n Caída de tensión nominal V Fórmula c.1
13
16 , 11 y
Δu arr Caída de tensión en el arranque V Fórmula c.2
13

Δu n % Caída de tensión nominal porcentual % Fórmula 14

Caída de tensión en el arranque


Δu arr % % Fórmula 14
porcentual

5. REFERENCIAS

[1] DIN VDE 0276-1000:1995 Power cables –Part 1000: Current-carrying


capacity, general, conversion factors
[2] DIN VDE 0271:1997 PVC-insulated and sheathed power cables for rated
voltages up to and including Uo/U (Um) 3,6/6 (7,2) kV
[3] DIN VDE 0276-603:2000 Distribution cables of nominal voltages U0/U 0,6/1
kV
[4] DIN VDE 0276-620:1996 Distribution cables of nominal voltages U0/U 3,6/6 V
to 20,8/36 kV
[5] DIN VDE 0276-621:1997 Energieverteilungskabel mit getränkter
Papierisolierung für Mittelspannung
[6] IEC 60949:1988 Calculation of thermally permissible short-circuit currents,
taking into account non-adiabatic heating effects
[7] IEC 60228:2004 Conductors of insulated cables
[8] IEC 60287 1-1:2001 Current rating equations (100 % load factor) and
calculation of losses
[9] INEDON 903-HM160-I41-GUD-061 Especificación Técnica de Cables de
Instrumentación y Control

903-HM150-E01-GUD-152_REV0.DOCX 31 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

[10] IEC 60502-1:2004 Power cables with extruded insulation and their
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 1
[11] IEC 60502-2:2004 Power cables with extruded insulation and their
accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 2
[12] IEC 60909-2:2008(E) Short-circuit currents in three-phase a.c. systems. Part
2: Data of electrical equipment for short-circuit current calculations.

903-HM150-E01-GUD-152_REV0.DOCX 32 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

ANEXO I: INTENSIDAD MÁXIMA ADMISIBLE POR


EL CABLE EN SERVICIO PERMANENTE

903-HM150-E01-GUD-152_REV0.DOCX 33 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

1.1 Fundamentos

El objeto al definir la corriente admisible de un cable es evitar que la


temperatura alcanzada por el mismo en régimen estacionario supere el valor
máximo establecido en [10] u [11] según el tipo de aislamiento del mismo.

La norma IEC (en [8]) presenta un método para el cálculo de corriente


admisible en servicio permanente para cables eléctricos, considerando
condiciones ambientales y de tendido, pero no obtiene resultados, es una
norma puramente teórica. La norma VDE muestra valores de corrientes
admisibles (en [2], [3], [4] y [5]) y valores de factores de corrección para
distintas condiciones de tendidos (en [1]) calculados a partir del método
presentado en [8].

La norma VDE estableció experimentalmente la validez del procedimiento aquí


presentado para los cables mostrados en la Tabla 1 [1] (Anexo II). En dicha
tabla, en la columna 1, se listan los cables para los que fueron realizados los
cálculos; en la columna 2 se listan los cables equivalentes a los de la columna
1, para los cuales los mismos resultados son aplicables. La equivalencia está
dada con un 1% de tolerancia en los márgenes operativos de cada tipo de
cable.

Otros puntos considerados en la norma de referencia:

- Corrientes admisibles del conductor según [8].


- Resistencias térmicas calculadas en base a [8].
− Se consideran las pérdidas producidas por la resistencia del conductor. Para
la conexión de las cubiertas metálicas se considera el peor caso aplicable, el
de ambos extremos puestos a tierra.
− Las pérdidas dieléctricas se consideran sólo en cables de PVC 6/10kV, con
εr.tgδ= 0,8 (εr: permitividad relativa, tgδ: factor de pérdidas). Para el resto de los
cables son despreciables.

Se analizan:

− Tipo de servicio
− Tipo de tendido
− Condiciones ambientales

Se deben revisar estas condiciones y efectuar correcciones según se explica


en los puntos referentes a tendido en tierra y a tendido en aire.
La corriente es sinusoidal equilibrada con frecuencia de 50 Hz.

903-HM150-E01-GUD-152_REV0.DOCX 34 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

1.1.1 Tendido en tierra

Se define como factor de carga a la relación entre la carga media y la carga


máxima en por ciento.
Se define como grado de carga a la relación entre la carga media y la carga
máxima, en por unidad.
Se considera como condición de servicio a la corriente en función del tiempo
según el perfil de carga típico de las compañías distribuidoras de energía
eléctrica.

Según se muestra en la tabla 2 de la norma DIN VDE 0276-1000:1995-06, las


corrientes nominales dadas en las tablas tienen validez para corriente nominal
con un factor de carga fc=70% cuando el cable es tendido en tierra, para otro
factor de carga corregir según tablas.

Se define como profundidad de tendido a la distancia entre la superficie del


terreno y el eje central longitudinal del grupo de cables.

La profundidad de tendido considerada aquí es de 0,7m. A mayor profundidad


de tendido, menor capacidad de corriente. Sin embargo, entre 0,7 y 1,2 m de
profundidad se considera como nula esta variación, dado que las variaciones
de temperatura y resistividad se compensan.

Un efecto a tener en cuenta, no contemplado por los factores de corrección, es


el producido por la secuencia de fases en el tendido. La secuencia sugerida
para aplicar las correcciones aquí propuestas es:

—L1-L2-L3 — L1-L2-L3 — L1-L2-L3 —

La polución del terreno aumenta la resistividad específica, por lo que se debe


proceder a un movimiento de suelo antes de la colocación del cable.
La resistividad será mayor para terrenos no compactados, o terrenos con
raíces para el valor de resistividad en el caso húmedo.

1.1.2 Tendido en aire

En este caso, a diferencia de lo desarrollado para tendido en tierra, se


considera un factor de carga del 100%, debido a que las constantes térmicas
son chicas, por lo tanto el estado de carga anterior no influye.

El efecto de la radiación solar afecta a los cables, por lo que se recomienda


cubrirlos para evitar considerar su efecto en los cálculos.

903-HM150-E01-GUD-152_REV0.DOCX 35 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

1.1.3 Tendido en tierra

En la tabla 2 [1] (Anexo II, página) se presenta una guía para obtener la
corriente corregida eligiendo los factores de corrección adecuados.

Los valores de corriente admisible de cables tendidos en tierra se toman de las


tablas correspondientes de [2], [3], [4] y [5] (Anexo II). Estos valores están
dados para un factor de carga de 70%, para una resistividad térmica específica
del terreno de 1 K.m/W, para una temperatura del terreno de 20°C, y para una
profundidad de enterrado de 0,7 a 1,2 m.

En función de las características del tendido se definen los factores f1 y f2,


tablas 4 a 9 [1] (Anexo II).

Se debe considerar la temperatura del terreno sin el efecto que produce la


presencia del cable. Esta temperatura va normalmente de 5 a 20°C.Se tiene en
cuenta en el análisis el secado que se produce alrededor del cable. Se define
como condición normal arena mojada hasta 25°C con una resistividad de 1
Km/W.
Los cables multipolares se deben corregir según tabla 13 [1] (Anexo II).

Para obtener la capacidad de carga en un tendido en tierra se tienen diversos


casos, los cuales se resumen en la aplicación de los factores f1 y f2, mediante
lo cual se tiene un error de a lo sumo un 3%.

1.1.4 Tendido en aire

En la tabla 3 [1] (Anexo II) se presenta una guía para obtener la corriente
corregida para tendidos en aire.

Los valores de corriente admisible de cables tendidos en aire se toman de las


tablas correspondientes de [2], [3], [4] y [5] (Anexo II). Son aplicables para
operación continua trifásica a una temperatura ambiente de 30°C.

Se debe considerar como temperatura ambiente a la temperatura del aire sin el


efecto que produce la presencia del cable cargado. Esta temperatura es de
30°C para las corrientes volcadas en las tablas, para valores diferentes se debe
corregir según tabla 12 [1] (Anexo II).

No obstante lo dicho en el punto anterior, cuando los cables se encuentran


dentro de un recinto, la disipación térmica de los mismos puede provocar una
elevación de temperatura del aire significativa. En este caso se corrige según
tabla 12 [1] (Anexo II) con el valor de temperatura corregido por el efecto de los
cables.

903-HM150-E01-GUD-152_REV0.DOCX 36 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

La corrección para cables multiconductores se realiza mediante la tabla 13 [1]


(Anexo II).

903-HM150-E01-GUD-152_REV0.DOCX 37 de 39 INEDON
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

ANEXO II: TABLAS DECARACTERÍSTICAS DE


CABLES

903-HM150-E01-GUD-152_REV0.DOCX 38 de 39 INEDON
Table 1. relation between Cable Types and Those Types which are Mentioned in Cable Load Tables

Cable Types as per Load Cable Tables Related Constructive Types

Paper Impregnated Cable

PVC Cables

XLPE Cables
Table 2. Operating Conditions for Laying in Earth

Operating conditions for calculation of rated currents Operation under additional constraints

Type of service (see 5.3.1.1) Correction factors according tables 4


Load factor 0,7 and maximum load according tables for cable to 9
laying in earth
Installation conditions (see 5.3.1.2)
Laying in depth 0.7 m See 5.3.1.2.1

Arrangement Correction Factors:


1 Multiconductor cable - For grouping see tables 4, 5, 9.
- For multiconductor see table 13
1 Single conductor cable in DC system

3 single conductor cables in three phase system,


- For grouping see tables 4 to 7
treefoiled

3 single conductor cables in three phase system - For grouping see tables 4, 5, 8
laying adjacent with interspace of 7 cm
Laying in sand or excavation on earth and eventually covering Correction Factors:
with bricks, concrete plates or flat or till slightly curved, thin
- For cover plates with ventilation
plastic cover plates
openings see 5.3.1.2.3
- For installation in pipes see 5.3.1.2.4

Environmental Conditions (see 5.3.1.3). Correction factors:

- Soil temperature at installation depth of 20°C - According tables 4 to 9


- Specific thermal soil resistance of dry region: 1,0 K.m/W - According tables 4 to 9
- Specific thermal soil resistance of wet region: 2,5 K.m/W -

Bonding and earthing of sheaths and screens on both ends See 5.2
Table 3. Operating Conditions for Laying in Air

Operating conditions for calculation of rated currents Operation under additional constraints
Type of service (see 5.3.2.1) Continuous service shall be regarded
Continuous operation (load factor 1,0) according tables for either if load factor is smaller than
laying in air 1,0 or not.

Installation condition (see 5.3.2.2)


Arrangement Correction Factors:
1 Multiconductor cable - For grouping according table 11

1 Single conductor cable in DC system - For multiconductor cable according


table 13
3 single conductor cables in three phase system,
treefoiled - For grouping according table 10

3 single conductor cables in three phase - For grouping according table 10


system laying adjacent with interspace of d

Installation in air, i.e, the free heat exchange is guarantee by


means of:
- Distance to walls, roofs or decks of at least 2 cm.
- Interspace of horizontal adjacent laying cables is at least 2
times the cable diameter.
- Interspace of vertical adjacent laying cables of at least 2 of
cable diameter.
- Free space between vertically overlapped cable layers of at
least nearly 30 cm

Environmental conditions (see 5.3.2.3) Correction Factors:

- Ambient temperature: 30°C - According table 12


- Room dimensions big enough or ventilation so that ambient - According table 12
temperature does not rise up because of heat losses in cables
- Protection against direct heat radiation, etc. -

Bonding and earthing of sheaths and screens on both ends See 5.2
Table 4 DIN VDE 0276-1000:1995-06

660
Conversion factors f1, cables laid in ground
All cables (except PVC cables for 6/10 kV) (as per DIN VDE 0276-1000)
1 2 3 4 5 6

Permissible Soil Specific thermal resistance of soil K m/W


operating temperature 0.7 1.0 15 2.5
temperature Load factor Load factor Load factor Load factor
°C °C 0.50 0.60 0.70 0.85 1.00 0 50 0.60 0.70 0.85 1.00 0 50 0.60 0.70 0.85 1.00 0.5 to 1.00

90 5 1.24 1.21 1.18 1.13 1.07 1.11 1.09 1.07 1.03 1.00 0 99 0.98 0.97 0.96 0 94 0.89
10 1.23 1.19 1.16 1.11 1.05 1.09 1.07 1.05 1.01 0.98 0 97 0.96 0.95 0.93 0 91 0.86
15 1.21 1.17 1.14 1.08 1.03 1.07 1.05 1.02 0.99 0.95 0 95 0.93 0.92 0.91 0 89 0.84
20 1.19 1.15 1.12 1.06 1.00 1.05 1.02 1.00 0.96 0.93 0 92 0.91 0.90 0.88 0 86 0.81
25 1.02 1.00 0.98 0.94 0.90 0 90 0.88 0.87 0.85 0 84 0.78
30 0.95 0.91 0.88 0 87 0.86 0.84 0.83 0 81 0.75
35 0.82 0.80 0.78 0.72
40 0.68

80 5 1.27 1.23 1.20 1.14 1.08 1.12 1.10 1.07 1.04 1.00 0 99 0.98 0.97 0.95 0 93 0.88
10 1.25 1.21 1.17 1.12 1.06 1.10 1.07 1.05 1.01 0.97 0 97 0.95 0.94 0.92 0 91 0.85
15 1.23 1.19 1.15 1.09 1.03 1.07 1.05 1.03 0.99 0.95 0 94 0.93 0.92 0.90 0 88 0.82
20 1.20 1.17 1.13 1.07 1.01 1.05 1.03 1.00 0.96 0.92 0 91 0.90 0.89 0.87 0 85 0.78
25 1.03 1.00 0.97 0.93 0.89 0 88 0.87 0.86 0.84 0 82 0.75
30 0.95 0.91 0.86 0 85 0.84 0.83 0.81 0.78 0.72
35 0.80 0.77 0.75 0.68
40 0.64

70 5 1.29 1.26 1.22 1.15 1.09 1.13 1.11 1.08 1.04 1.00 0 99 0.98 0.97 0.95 0 93 0.86
10 1.27 1.23 1.19 1.13 1.06 1.11 1.08 1.06 1.01 0.97 0 96 0.95 0.94 0.92 0 89 0.83
15 1.25 1.21 1.17 1.10 1.03 1.08 1.06 1.03 0.99 0.94 0 93 0.92 0.91 0.88 0 86 0.79
20 1.23 1.18 1.14 1.08 1.01 1.06 1.03 1.00 0.96 0.91 0 90 0.89 0.87 0.85 0 83 0.76
25 1.03 1.00 0.97 0.93 0.88 0 87 0.85 0.84 0.82 0.79 0.72
30 0.94 0.89 0.85 0 84 0.82 0.80 0.78 0.76 0.68
35 0.77 0.74 0.72 0.63
40 0.59
The conversion factor f1 must always be used with the conversion factor f2.
(continued)
Table 4 (continued) - DIN VDE 0276-1000:1995-06

1 2 3 4 5 6

Permissible Soil Specific thermal resistance of soil K · m/W


operating temperature 0.7 1.0 1.5 2.5
temperature Load factor Load factor Load factor Load factor
°C °C 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.5 to 1.00

65 5 1.31 1.27 1.23 1.16 1.09 1.14 1.11 1.09 1.04 1.00 0.99 0.98 0.96 0.94 0.92 0 85
10 1.29 1.24 1.20 1.14 1.06 1.11 1.09 1.06 1.02 0.97 0.96 0.95 0.93 0.91 0.89 0.82
15 1.26 1.22 1.18 1.11 1.04 1.09 1.06 1.03 0.98 0.94 0.93 0.91 0.90 0.88 0.85 0.78
20 1.24 1.20 1.15 1.08 1.01 1.06 1.03 1.00 0.95 0.90 0.90 0.88 0.86 0.84 0.82 0.74
25 1.03 1.00 0.97 0.92 0.87 0.86 0.84 0.83 0.80 0.78 0.70
30 0.94 0.89 0.83 0.82 0.81 0.79 0.77 0.74 0.65
35 0.75 0.72 0.70 0.60
40 0.55

60 5 1.33 1.28 1.24 1.17 1.10 1.15 1.12 1.09 1.05 1.00 0.99 0.98 0.96 0.94 0.92 0.84
10 1.30 1.26 1.21 1.14 1.07 1.12 1.09 1.06 1.02 0.97 0.96 0.94 0.93 0.90 0.88 0.80
15 1.28 1.23 1.19 1.12 1.04 1.09 1.06 1.03 0.98 0.93 0.92 0.91 0.89 0.87 0.84 0.76
20 1.25 1.21 1.16 1.09 1.01 1.06 1.03 1.00 0.95 0.90 0.89 0.87 0.86 0.83 0.80 0.72
25 1.03 1.00 0.97 0.92 0.86 0.85 0.83 0.82 0.79 0.76 0.67
30 0.93 0.88 0.82 0.81 0.79 0.78 0.75 0.72 0.62
35 0.73 0.70 0.67 0.57
40 0.51

With mass-impregnated cables, increasing the current rating at temperatures below 20 °C is subject to conditions. The conversion factor f1 must be applied only
together with conversion factor f2.

661
13
Table 5. DIN VDE 0276-1000:1995-06

662
Conversion factors f1, cables laid in ground, PVC cables for 6/10 kV (as per DIN VDE 0276-1000)
1 2 3 4 5 6 7 8

Number of Number Soil Specific thermal resistance of soil K · m/W


three- of three- tempe- 0.7 1.0 1.5 2.5
phase phase rature
Load factor Load factor Load factor Load factor
systems cables °C 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.5 to 1.0

1 1 1 5 1.31 1.27 1.23 1.16 1.09 1.14 1.12 1.09 1.05 1.00 0.99 0.98 0.96 0.94 0.92 0.85
10 1.29 1.25 1.21 1.14 1.07 1.12 1.09 1.06 1.02 0.97 0.96 0.95 0.93 0.91 0.89 0.81
15 1.27 1.22 1.18 1.11 1.04 1.09 1.06 1.03 0.98 0.94 0.93 0.91 0.90 0.87 0.85 0.77
20 1.24 1.20 1.15 1.08 1.01 1.06 1.03 1.00 0.95 0.90 0.89 0.88 0.86 0.84 0.81 0.73
25 1.03 1.00 0.97 0.92 0.87 0.86 0.84 0.83 0.80 0.77 0.69
30 0.94 0.89 0.83 0.82 0.80 0.79 0.76 0.73 0.64
35 0.75 0.72 0.70 0.59
40 0.54

4 3 3 5 1.29 1.24 1.20 1.13 1.06 1.11 1.08 1.05 1.01 0.96 0.95 0.94 0.93 0.90 0.88 0.81
10 1.26 1.22 1.17 1.11 1.03 1.08 1.05 1.03 0.98 0.93 0.92 0.91 0.89 0.87 0.84 0.77
15 1.24 1.19 1.15 1.08 1.00 1.05 1.03 0.99 0.95 0.90 0.89 0.87 0.86 0.83 0.81 0.73
20 1.21 1.17 1.12 1.05 0.97 1.03 0.99 0.96 0.91 0.86 0.85 0.84 0.82 0.79 0.77 0.68
25 0.99 0.96 0.93 0.88 0.83 0.82 0.80 0.78 0.76 0.73 0.64
30 0.90 0.84 0.79 0.78 0.76 0.74 0.71 0.68 0.59
35 0.70 0.67 0.64 0.53
40 0.47

10 5 6 5 1.26 1.21 1.17 1.10 1.03 1.08 1.05 1.02 0.97 0.93 0.92 0.90 0.89 0.86 0.84 0.76
10 1.23 1.19 1.14 1.07 1.00 1.05 1.02 0.99 0.94 0.89 0.88 0.87 0.85 0.83 0.80 0.72
15 1.21 1.16 1.12 1.04 0.96 1.02 0.99 0.96 0.91 0.86 0.85 0.83 0.81 0.79 0.76 0.68
20 1.18 1.14 1.09 1.01 0.93 0.99 0.96 0.93 0.87 0.82 0.81 0.79 0.77 0.75 0.72 0.63
25 0.96 0.93 0.89 0.84 0.78 0.77 0.75 0.73 0.70 0.68 0.58
30 0.86 0.80 0.74 0.73 0.71 0.69 0.66 0.63 0.52
35 0.64 0.61 0.58 0.46
40 0.38

Conversion factor f1 must be applied only together with conversion factor f2.
(continued)
Table 5 (continued) - DIN VDE 0276-1000:1995-06

1 2 3 4 5 6 7 8

Number of Number Soil Specific thermal resistance of soil K · m/W


three- of three- tempe- 0.7 1.0 1.5 2.5
phase phase rature
Load factor Load factor Load factor Load factor
systems cables °C 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.50 0.60 0.70 0.85 1.00 0.5 to 1.0

— 8 10 5 1.23 1.19 1.14 1.07 . 0.99 1.05 1.02 0.99 0.94 0.89 0.88 0.86 0.85 0.82 0.80 0.72
10 1.21 1.16 1.11 1.04 0.96 1.02 0.99 0.96 0.91 0.85 0.84 0.83 0.81 0.78 0.76 0 67
15 1.18 1.13 1.09 1.01 0.93 0.99 0.96 0.92 0.87 0.82 0.81 0.79 0.77 0.74 0.72 0.63
20 1.15 1.11 1.06 0.98 0.90 0.96 0.92 0.89 0.84 0.78 0.77 0.75 0.73 0.70 0.67 0.57
25 0.92 0.89 0.85 0.80 0.74 0.73 0.71 0.69 0.66 0.63 0.52
30 0.82 0.76 0.70 0.68 0.66 0.64 0 61 0.57 0.45
35 0.60 0.56 0.52 0.38
40 0.29

— 10 — 5 1.22 1.17 1.13 1.05 0.98 1.03 1.00 0.97 0.92 0.87 0.86 0.84 0.83 0.80 0.78 0.69
10 1.19 1.15 1.10 1.02 0.94 1.00 0.97 0.94 0.89 0.83 0.82 0.81 0.79 0.76 0.73 0.65
15 1.17 1.12 1.07 0.99 0.91 0.97 0.94 0.90 0.85 0.79 0.78 0.77 0.75 0.72 0.69 0.60
20 1.14 1.09 1.04 0.96 0.88 0.94 0.90 0.87 0.81 0.76 0.74 0.73 0.71 0.68 0.65 0.54
25 0.90 0.87 0.83 0.78 0.71 0.70 0.68 0.66 0.63 0.60 0.48
30 0.79 0.73 0.67 0.66 0.63 0.61 0.58 0.54 0.41
35 0.56 0.52 0.48 0.33
40 0.22

Arrangement of three-phase systems in column 1 Arrangement of three-phase systems in column 2 Arrangement of three-phase cables in column 3

Conversion factor f1 must be applied only together with conversion factor f2.

663
13
Table 6. DIN VDE 0276-1000:1995-06

664
Conversion factor f2, cables laid in ground
Single-core cables in three phase systems, trefoil formation (as per DIN VDE 0276-1000)
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
XLPE cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
6/10 kV
1 1.09 1.04 0.99 0.93 0.87 1.11 1.05 1.00 0.93 0.87 1.13 1.07 1.01 0.94 0.87 1.17 1.09 1.03 0.94 0.87
12/20 kV
2 0.97 0.90 0.84 0.77 0.71 0.98 0.91 0.85 0.77 0.71 1.00 0.92 0.86 0.77 0.71 1.02 0.94 0.87 0.78 0.71
18/30 kV
3 0.88 0.80 0.74 0.67 0.61 0.89 0.82 0.75 0.67 0.61 0.90 0.82 0.76 0.68 0.61 0.92 0.83 0.76 0.68 0.61
4 0.83 0.75 0.69 0.62 0.56 0.84 0.76 0.70 0.62 0.56 0.85 0.77 0.70 0.62 0.56 0.86 0.78 0.71 0.63 0.56
5 0.79 0.71 0.65 0.58 0.52 0.80 0.72 0.66 0.58 0.52 0.80 0.73 0.66 0.58 0.52 0.82 0.73 0.67 0.59 0.52
6 0.76 0.68 0.62 0.55 0.50 0.77 0.69 0.63 0.55 0.50 0.77 0.70 0.63 0.56 0.50 0.78 0.70 0.64 0.56 0.50
8 0.72 0.64 0.58 0.51 0.46 0.72 0.65 0.59 0.52 0.46 0.73 0.65 0.59 0.52 0.46 0.74 0.66 0.59 0.52 0.46
10 0.69 0.61 0.56 0.49 0.44 0.69 0.62 0.56 0.49 0.44 0.70 0.62 0.56 0.49 0.44 0.70 0.63 0.57 0.49 0.44
PVC cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
3.6/6 kV 1 1.01 1.02 0.99 0.93 0.87 1.04 1.05 1.00 0.93 0.87 1.07 1.06 1.01 0.94 0.87 1.11 1.08 1.01 0.94 0.87
6/10 kV 2 0.94 0.89 0.84 0.77 0.71 0.97 0.91 0.85 0.77 0.71 0.99 0.92 0.86 0.77 0.71 1.01 0.93 0.87 0.78 0.71
3 0.86 0.79 0.74 0.67 0.61 0.89 0.81 0.75 0.67 0.61 0.90 0.83 0.76 0.68 0.61 0.91 0.83 0.77 0.68 0.61
4 0.82 0.75 0.69 0.62 0.56 0.84 0.76 0.70 0.62 0.56 0.85 0.77 0.71 0.62 0.56 0.86 0.78 0.71 0.63 0.56
5 0.78 0.71 0.65 0.58 0.52 0.80 0.72 0.66 0.58 0.52 0.80 0.73 0.66 0.58 0.52 0.81 0.73 0.67 0.59 0.52
6 0.75 0.68 0.62 0.55 0.50 0.77 0.69 0.63 0.55 0.50 0.77 0.70 0.64 0.56 0.50 0.78 0.70 0.64 0.56 0.50
8 0.71 0.64 0.58 0.51 0.46 0.72 0.65 0.59 0.52 0.46 0.73 0.65 0.59 0.52 0.46 0.73 0.66 0.60 0.52 0.46
10 0.68 0.61 0.55 0.49 0.44 0.69 0.62 0.56 0.49 0.44 0.69 0.62 0.56 0.49 0.44 0.70 0.63 0.57 0.49 0.44

The conversion factor f2 must be applied only together with conversion factor f1.
7
Table 6 (continued) DIN VDE 0276-1000:1995-06
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
Mass- load factor load factor load factor load factor
impregnated 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
cables
1 0.94 0.95 0.97 0.93 0.87 0.99 0.99 1.00 0.93 0.87 1.06 1.04 1.01 0.94 0.87 1.15 1.08 1.02 0.94 0.87
0.6/1 kV
2 0.88 0.88 0.84 0.77 0.71 0.93 0.91 0.85 0.77 0.71 0.97 0.92 0.86 0.77 0.71 1.01 0.93 0.87 0.78 0.71
3.6/6 kV
3 0.84 0.79 0.74 0.67 0.61 0.87 0.81 0.75 0.67 0.61 0.90 0.82 0.76 0.68 0.61 0.91 0.83 0.76 0.68 0.61
6/10 kV
12/20 kV 4 0.82 0.74 0.69 0.62 0.56 0.84 0.76 0.70 0.62 0.56 0.85 0.77 0.71 0.62 0.56 0.86 0.78 0.71 0.63 0.56
18/30 kV 5 0.78 0.70 0.65 0.58 0.52 0.79 0.72 0.65 0.58 0.52 0.80 0.73 0.66 0.58 0.52 0.81 0.73 0.67 0.59 0.52
6 0.75 0.68 0.62 0.55 0.50 0.76 0.69 0.63 0.55 0.50 0.77 0.70 0.63 0.56 0.50 0.78 0.70 0.64 0.56 0.50
8 0.71 0.64 0.58 0.51 0.46 0.72 0.64 0.58 0.52 0.46 0.72 0.65 0.59 0.52 0.46 0.73 0.66 0.59 0.52 0.46
10 0.68 0.61 0.55 0.49 0.44 0.69 0.61 0.56 0.49 0.44 0.69 0.62 0.56 0.49 0.44 0.70 0.62 0.56 0.49 0.44

The conversion factor f2 must be applied only together with conversion factor f1.

665
13
Table 7. DIN VDE 0276-1000:1995-06

666
Conversion factor f2, cables laid in ground
Single-core cables in three phase systems, trefoil formation (as per DIN VDE 0276-1000)
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
XLPE cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
6/10 kV 1 1.09 1.04 0.99 0.93 0.87 1.11 1.05 1.00 0.93 0.87 1.13 1.07 1.01 0.94 0.87 1.17 1.09 1.03 0.94 0.87
12/20 kV 2 1.01 0.94 0.89 0.82 0.75 1.02 0.95 0.89 0.82 0.75 1.04 0.97 0.90 0.82 0.75 1.06 0.98 0.91 0.83 0.75
18/30 kV
3 0.94 0.87 0.81 0.74 0.67 0.95 0.88 0.82 0.74 0.67 0.97 0.89 0.82 0.74 0.67 0.99 0.90 0.83 0.74 0.67
4 0.91 0.84 0.78 0.70 0.64 0.92 0.84 0.78 0.70 0.64 0.93 0.85 0.79 0.70 0.64 0.95 0.86 0.79 0.71 0.64
5 0.88 0.80 0.74 0.67 0.60 0.89 0.81 0.75 0.67 0.60 0.90 0.82 0.75 0.67 0.60 0.91 0.83 0.76 0.67 0.60
6 0.86 0.79 0.72 0.65 0.59 0.87 0.79 0.73 0.65 0.59 0.88 0.80 0.73 0.65 0.59 0.89 0.81 0.74 0.65 0.59
8 0.83 0.76 0.70 0.62 0.56 0.84 0.76 0.70 0.62 0.56 0.85 0.77 0.70 0.62 0.56 0.86 0.78 0.71 0.62 0.56
10 0.81 0.74 0.68 0.60 0.54 0.82 0.74 0.68 0.60 0.54 0.83 0.75 0.68 0.61 0.54 0.84 0.76 0.69 0.61 0.54

PVC cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
3.6/6 kV 1 1.01 1.02 0.99 0.93 0.87 1.04 1.05 1.00 0.93 0.87 1.07 1.06 1.01 0.94 0.87 1.11 1.08 1.01 0.94 0.87
6/10 kV 2 0.97 0.95 0.89 0.82 0.75 1.00 0.96 0.90 0.82 0.75 1.03 0.97 0.91 0.82 0.75 1.06 0.98 0.92 0.83 0.75
3 0.94 0.88 0.82 0.74 0.67 0.97 0.88 0.82 0.74 0.67 0.97 0.89 0.83 0.74 0.67 0.98 0.90 0.84 0.74 0.67
4 0.91 0.84 0.78 0.70 0.64 0.92 0.85 0.79 0.70 0.64 0.93 0.86 0.79 0.70 0.64 0.95 0.87 0.80 0.71 0.64
5 0.88 0.81 0.75 0.67 0.60 0.89 0.82 0.76 0.67 0.60 0.90 0.82 0.76 0.67 0.60 0.91 0.83 0.77 0.67 0.60
6 0.86 0.79 0.73 0.65 0.59 0.87 0.80 0.74 0.65 0.59 0.88 0.81 0.74 0.65 0.59 0.89 0.81 0.75 0.65 0.59
8 0.83 0.76 0.70 0.62 0.56 0.84 0.77 0.71 0.62 0.56 0.85 0.78 0.71 0.62 0.56 0.86 0.78 0.72 0.62 0.56
10 0.82 0.75 0.69 0.60 0.54 0.82 0.75 0.69 0.60 0.54 0.83 0.76 0.69 0.61 0.54 0.84 0.76 0.70 0.61 0.54

The conversion factor f2 must be applied only together with conversion factor f1.
(continued)
Table 7. (continued). DIN VDE 0276-1000:1995-06
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
Mass- load factor load factor load factor load factor
impregnated 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
cables 1 0.94 0.95 0.97 0.93 0.87 0.99 0.99 1.00 0.93 0.87 1.06 1.04 1.01 0.94 0.87 1.15 1.08 1.02 0.94 0.87
0.6/1 kV 2 0.90 0.91 0.88 0.82 0.75 0.95 0.94 0.89 0.82 0.75 1.00 0.96 0.89 0.82 0.75 1.05 0.97 0.90 0.83 0.75
3.6/6 kV 3 0.87 0.86 0.80 0.74 0.67 0.91 0.87 0.81 0.74 0.67 0.95 0.88 0.81 0.74 0.67 0.97 0.89 0.82 0.74 0.67
6/10 kV
4 0.86 0.82 0.76 0.70 0.64 0.89 0.83 0.77 0.70 0.64 0.91 0.83 0.77 0.70 0.64 0.92 0.84 0.78 0.71 0.64
12/10 kV
5 0.84 0.79 0.73 0.67 0.60 0.86 0.79 0.73 0.67 0.60 0.87 0.80 0.73 0.67 0.60 0.89 0.81 0.74 0.67 0.60
18/30 kV
6 0.83 0.77 0.71 0.65 0.59 0.84 0.77 0.71 0.65 0.59 0.85 0.78 0.71 0.65 0.59 0.86 0.78 0.72 0.65 0.59
8 0.80 0.73 0.67 0.62 0.56 0.81 0.74 0.68 0.62 0.56 0.82 0.74 0.68 0.62 0.56 0.83 0.75 0.68 0.62 0.56
10 0.78 0.71 0.65 0.60 0.54 0.79 0.71 0.65 0.60 0.54 0.80 0.72 0.66 0.61 0.54 0.81 0.73 0.66 0.61 0.54

The conversion factor f2 must be applied only together with conversion factor f1.

667
13
Table 8. DIN VDE 0276-1000:1995-06

668
Conversion factor f2, cables laid in ground
Single-core cables in three phase systems, flat formation (as per DIN VDE 0276-1000)
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5

XLPE cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
6/10 kV 1 1.08 1.05 0.99 0.91 0.85 1.13 1.07 1.00 0.92 0.85 1.18 1.09 1.01 0.92 0.85 1.19 1.11 1.03 0.93 0.85
12/20 kV 2 1.01 0.93 0.86 0.77 0.71 1.03 0.94 0.87 0.78 0.71 1.05 0.95 0.88 0.78 0.71 1.06 0.96 0.88 0.79 0.71
18/30 kV 3 0.92 0.84 0.77 0.69 0.62 0.93 0.85 0.77 0.69 0.62 0.95 0.86 0.78 0.69 0.62 0.96 0.86 0.79 0.69 0.62
4 0.88 0.80 0.73 0.65 0.58 0.89 0.80 0.73 0.65 0.58 0.90 0.81 0.74 0.65 0.58 0.91 0.82 0.74 0.65 0.58
5 0.84 0.76 0.69 0.61 0.55 0.85 0.77 0.70 0.61 0.55 0.87 0.78 0.70 0.62 0.55 0.87 0.78 0.71 0.62 0.55
6 0.82 0.74 0.67 0.59 0.53 0.83 0.75 0.68 0.60 0.53 0.84 0.75 0.68 0.60 0.53 0.85 0.76 0.69 0.60 0.53
8 0.79 0.71 0.64 0.57 0.51 0.80 0.71 0.65 0.57 0.51 0.81 0.72 0.65 0.57 0.51 0.81 0.72 0.65 0.57 0.51
10 0.77 0.69 0.62 0.55 0.49 0.78 0.69 0.63 0.55 0.49 0.78 0.70 0.63 0.55 0.49 0.79 0.70 0.63 0.55 0.49

PVC cables load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
3.6/6 kV 1 0.96 0.97 0.98 0.91 0.85 1.01 1.01 1.00 0.92 0.85 1.07 1.05 1.01 0.92 0.85 1.16 1.10 1.02 0.93 0.85
6/10 kV 2 0 92 0.89 0.86 0.77 0.71 0.96 0.94 0.87 0.78 0.71 1.00 0.95 0.88 0.78 0.71 1.05 0.97 0.89 0.79 0.71
3 0.88 0.84 0.77 0.69 0.62 0.91 0.85 0.78 0.69 0.62 0.95 0.86 0.79 0.69 0.62 0.96 0.87 0.79 0.69 0.62
4 0. 86 0.80 0.73 0.65 0.58 0.89 0.81 0.74 0.65 0.58 0.90 0.82 0.74 0.65 0.58 0.91 0.82 0.75 0.65 0.58
5 0.84 0.76 0.70 0.61 0.55 0.85 0.77 0.70 0.61 0.55 0.87 0.78 0.71 0.62 0.55 0.87 0.79 0.71 0.62 0.55
6 0.82 0.74 0.68 0.59 0.53 0.83 0.75 0.68 0.60 0.53 0.83 0.76 0.69 0.60 0.53 0.85 0.76 0.69 0.60 0.53
8 0.79 0.71 0.65 0.57 0.51 0.80 0.72 0.65 0.57 0.51 0.81 0.72 0.65 0.57 0.51 0.81 0.73 0.66 0.57 0.51
10 0.77 0.69 0.63 0.55 0.49 0.78 0.70 0.63 0.55 0.49 0.79 0.70 0.63 0.55 0.49 0.79 0.71 0.64 0.55 0.49

The conversion factor f2 must be applied only together with conversion factor f1.
(continued)
Table 8 (continued). DIN VDE 0276-1000:1995-06
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
Mass- load factor load factor load factor load factor
impregnated 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
cables 1 0.93 0.94 0.95 0.91 0.85 1.00 1.00 1.00 0.92 0.85 1.09 1.06 1.01 0.92 0.85 1.19 1.10 1.03 0.93 0.85
0.6/1 kV
2 0.89 0.89 0.86 0.77 0.71 0.95 0.93 0.87 0.78 0.71 1.01 0.95 0.88 0.78 0.71 1.05 0.97 0.89 0.79 0.71
3.6/6 kV
3 0.86 0.84 0.77 0.69 0.62 0.90 0.85 0.78 0.69 0.62 0.95 0.86 0.79 0.69 0.62 0.96 0.87 0.79 0.69 0.62
6/10 kV
4 0. 84 0.80 0.73 0.65 0.58 0.88 0.81 0.74 0.65 0.58 0.91 0.82 0.74 0.65 0.58 0.91 0.82 0.75 0.65 0.58
12/10 kV
18/30 kV 5 0.82 0.77 0.70 0.61 0.55 0.86 0.77 0.70 0.61 0.55 0.87 0.78 0.71 0.62 0.55 0.87 0.79 0.71 0.62 0.55
6 0.81 0.74 0.68 0.59 0.53 0.83 0.75 0.68 0.60 0.53 0.85 0.76 0.69 0.60 0.53 0.85 0.76 0.69 0.60 0.53
8 0.78 0.71 0.65 0.57 0.51 0.80 0.72 0.65 0.57 0.51 0.81 0.73 0.66 0.57 0.51 0.82 0.73 0.66 0.57 0.51
10 0.77 0.69 0.63 0.55 0.49 0.78 0.70 0.63 0.55 0.49 0.79 0.70 0.64 0.55 0.49 0.79 0.71 0.64 0.55 0.49

The conversion factor f2 must be applied only together with conversion factor f1.

669
13
Table 9. DIN VDE 0276-1000:1995-06

670
Conversion factor f2, cables laid in ground
Three-core cables in three-phase systems (as per DIN VDE 0276-1000)
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5

VPE cables1) load factor load factor load factor load factor
0.6/1 kV 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
6/10 kV 1 1.02 1.03 0.99 0.94 0.89 1.06 1.05 1.00 0.94 0.89 1.09 1.06 1.01 0.94 0.89 1.11 1.07 1.02 0.95 0.89
PVC cables1) 2 0.95 0.89 0.84 0.77 0.72 0.98 0.91 0.85 0.78 0.72 0.99 0.92 0.86 0.78 0.72 1.01 0.94 0.87 0.79 0.72
0.6/1 kV with 3 0.86 0.80 0.74 0.68 0.62 0.89 0.81 0.75 0.68 0.62 0.90 0.83 0.77 0.69 0.62 0.92 0.84 0.77 0.69 0.62
Sn ≥ 35 mm2 4 0.82 0.75 0.69 0.63 0.57 0.84 0.76 0.70 0.63 0.57 0.85 0.78 0.71 0.63 0.57 0.86 0.78 0.72 0.64 0.57
5 0.78 0.71 0.65 0.59 0.53 0.80 0.72 0.66 0.59 0.53 0.81 0.73 0.67 0.59 0.53 0.82 0.74 0.67 0.60 0.53
6 0.75 0.68 0.63 0.56 0.51 0.77 0.69 0.63 0.56 0.51 0.78 0.70 0.64 0.57 0.51 0.79 0.71 0.65 0.57 0.51
8 0.71 0.64 0.59 0.52 0.47 0.72 0.65 0.59 0.52 0.47 0.73 0.66 0.60 0.52 0.47 0.74 0.66 0.60 0.53 0.47
10 0.68 0.61 0.56 0.49 0.44 0.69 0.62 0.56 0.50 0.44 0.70 0.63 0.57 0.50 0.44 0.71 0.63 0.57 0.50 0.44

PVC cables1) load factor load factor load factor load factor
0.6/1 kV with 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
Sn < 35 mm2 1 0.91 0.92 0.94 0.94 0.89 0.98 0.99 1.00 0.94 0.89 1.04 1.03 1.01 0.94 0.89 1.13 1.07 1.02 0.95 0.89
3.6/6 kV 2 0.86 0.87 0.85 0.77 0.72 0.91 0.90 0.86 0.78 0.72 0.97 0.93 0.87 0.78 0.72 1.01 0.94 0.88 0.79 0.72
3 0.82 0.80 0.75 0.68 0.62 0.86 0.82 0.76 0.68 0.62 0.91 0.84 0.77 0.69 0.62 0.92 0.84 0.78 0.69 0.62
4 0.80 0.76 0.70 0.63 0.57 0.84 0.77 0.71 0.63 0.57 0.86 0.78 0.72 0.63 0.57 0.87 0.79 0.73 0.64 0.57
5 0.78 0.72 0.66 0.59 0.53 0.81 0.73 0.67 0.59 0.53 0.81 0.74 0.68 0.59 0.53 0.82 0.75 0.68 0.60 0.53
6 0.76 0.69 0.64 0.56 0.51 0.77 0.70 0.64 0.56 0.51 0.78 0.71 0.65 0.57 0.51 0.79 0.72 0.65 0.57 0.51
8 0.72 0.65 0.59 0.52 0.47 0.73 0.66 0.60 0.52 0.47 0.74 0.67 0.61 0.52 0.47 0.75 0.67 0.61 0.53 0.47
10 0.69 0.62 0.57 0.49 0.44 0.70 0.63 0.57 0.50 0.44 0.71 0.64 0.58 0.50 0.44 0.71 0.64 0.58 0.50 0.44
1)
The conversion factor f2 must be applied only together with conversion factor f1. In direct-current systems, these factors are
(continued) also valid for single-core cables for 0.6/1 kV.
Table 9 (continued).DIN VDE 0276-1000:1995-06
1 2 3 4 5 6
Type Number Specific thermal resistance of soil in K · m/W
of systems 0.7 1.0 1.5 2.5
Mass-impregna- load factor load factor load factor load factor
ted cables 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
Belted cables
0.6/1 kV 1 0.94 0.95 0.97 0.94 0.89 1.00 1.00 1.00 0.94 0.89 1.06 1.05 1.01 0.94 0.89 1.13 1.07 1.02 0.95 0.89
3.6/6 kv 2 0.89 0.89 0.85 0.77 0.72 0.94 0.92 0.86 0.78 0.72 0.99 0.93 0.87 0.78 0.72 1.01 0.94 0.88 0.79 0.72
Single lead
sheathed (SL) 3 0.84 0.81 0.76 0.68 0.62 0.89 0.83 0.77 0.68 0.62 0.91 0.84 0.78 0.69 0.62 0.92 0.85 0.79 0.69 0.62
cables 4 0.82 0.77 0.71 0.63 0.57 0.85 0.78 0.72 0.63 0.57 0.86 0.79 0.73 0.63 0.57 0.87 0.80 0.73 0.64 0.57
3.6/6 kV
6/10 kV 5 0.80 0.73 0.67 0.59 0.53 0.81 0.74 0.68 0.59 0.53 0.82 0.75 0.69 0.59 0.53 0.83 0.76 0.69 0.60 0.53
6 0.77 0.70 0.65 0.56 0.51 0.79 0.71 0.65 0.56 0.51 0.79 0.72 0.66 0.57 0.51 0.80 0.73 0.66 0.57 0.51
8 0.73 0.66 0.61 0.52 0.47 0.74 0.67 0.61 0.52 0.47 0.75 0.68 0.62 0.52 0.47 0.75 0.68 0.62 0.53 0.47
10 0.70 0.63 0.58 0.49 0.44 0.71 0.64 0.58 0.50 0.44 0.72 0.65 0.59 0.50 0.44 0.72 0.65 0.59 0.50 0.44
PVC cables load factor load factor load factor load factor
6/10 kV
0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00 0.5 0.6 0.7 0.85 1.00
Mass-impregna-
ted cables 1 0.90 0.91 0.93 0.96 0.91 0.98 0.99 1.00 0.96 0.91 1.05 1.04 1.03 0.97 0.91 1.14 1.09 1.04 0.97 0.91
Belted cables
6/10 kV 2 0.85 0.85 0.85 0.81 0.76 0.93 0.92 0.89 0.82 0.76 0.98 0.95 0.90 0.82 0.76 1.03 0.96 0.90 0.82 0.76
H cables 3 0.80 0.79 0.78 0.72 0.66 0.87 0.86 0.80 0.72 0.66 0.93 0.86 0.80 0. 73 0.66 0.95 0.87 0.81 0.73 0.66
6/10 kV
12/20 kV 4 0.77 0.77 0.74 0.67 0.61 0.85 0.81 0.75 0.67 0.61 0.89 0.82 0.75 0.68 0.61 0.90 0.82 0.76 0.68 0.61
18/30 kV 5 0.75 0.75 0.70 0.63 0.57 0.84 0.77 0.71 0.63 0.57 0.85 0.77 0.71 0.63 0.57 0.86 0.78 0.72 0.64 0.57
Single lead 6 0.74 0.73 0.67 0.60 0.55 0.81 0.74 0.68 0.60 0.55 0.82 0.74 0.68 0.61 0.55 0.83 0.75 0.69 0.61 0.55
sheathead (SL)
cables 8 0.73 0.69 0.63 0.56 0.51 0.77 0.70 0.64 0.56 0.51 0.77 0.70 0.64 0.57 0.51 0.78 0.71 0.64 0.57 0.51
12/20 kV 10 0.71 0.66 0.60 0.53 0.48 0.74 0.67 0.61 0.54 0.48 0.74 0.67 0.61 0.54 0.48 0.75 0.67 0.61 0.54 0.48
18/30 kV
The conversion factor f2 must be applied only together with conversion factor f1.

671
13
Table 10. DIN VDE 0276-1000:1995-06
Conversion factors for grouping in air1), single-core cables in three-phase systems (as
per DIN VDE 0276-1000)

1 2 3 4 5
Installation in flat formation Number of Number of
troughs/ systems2)
Spacing = racks horizontal
cable diameter d vertical 1 2 3

Laid d d
on the floor 1 0.92 0.89 0.88
a a ≥ 20 mm
Unperforated 1 0.92 0.89 0.88
cable troughs3)
≥ 300 mm 2 0.87 0.84 0.83

d d 3 0.84 0.82 0.81

a a ≥ 20 mm 6 0.82 0.80 0.79

Perforated 1 1.00 0.93 0.90


cable troughs3)
2 0.97 0.89 0.85
≥ 300 mm

d d 3 0.96 0.88 0.82

a a ≥ 20 mm 6 0.94 0.85 0.80

Cable racks4) 1 1.00 0.97 0.96

2 0.97 0.94 0.93


≥ 300 mm

d d 3 0.96 0.93 0.92

a a ≥ 20 mm 6 0.94 0.91 0.90

On racks or Number of Number of systems


on the wall or troughs vertical
on perforated cable horizontal 1 2 3
dd

troughs in vertical
configuration 1 0.94 0.91 0.89
≥ 225 mm
2 0.94 0.90 0.86
1) If the air temperature is increased by the heat loss of the cables in small buildings or because of high grouping, the
conversion factors for different air temperatures in Table 12 must also be used.
2) Factors as per DIN VDE 0255 (VDE 0255)

3) A cable trough is a continuous surface with raised edges but no cover. A cable trough is considered perforated if it is

perforated over at least 30 % of the entire surface area.


4) A cable rack is a support structure in which the supporting area is no more than 10% of the total area of the structure.

When cables with metal sheathing or shielding are laid flat, the increased sheathing or shielding losses act against the
reduced mutual heating when the spacing is increased. For this reason no information on reduction-free configurations can
be given.

(continued)

656
Table 10. (continued) - DIN VDE 0276-1000:1995-06
Conversion factors for grouping in air1), single-core cables in three-phase systems (as
per DIN VDE 0276-1000)

6 7 8 9 10

Installation in trefoil formation Number of Number of


troughs/ systems2)
Spacing = racks horizontal
2 · cable diameter d vertical 1 2 3
2d 2d
Laid
on the floor 1 0.98 0.96 0.94
a a ≥ 20 mm
Unperforated 1 0.98 0.96 0.94
cable troughs3)
2 0.95 0.91 0.87
≥ 300 mm

2d 2d 3 0.94 0.90 0.85

a a ≥ 20 mm 6 0.93 0.88 0.82

Perforated 1 1.00 0.98 0.96


cable troughs3)
2 0.97 0.93 0.89
≥ 300 mm

2d 2d
3 0.96 0.92 0.85

a a ≥ 20 mm 6 0.95 0.90 0.83

Cable racks4) 1 1.00 0.97 0.96


(cable gratings)
2 0.97 0.95 0.93
≥ 300 mm

2d 2d
3 0.96 0.94 0.90

a a ≥ 20 mm 6 0.95 0.93 0.87


On racks or Number of Number of systems
on the wall or troughs vertical
on perforated cable horizontal 1 2 3
2d

troughs in vertical
13

configuration 1 1.00 0.91 0.89


≥ 225 mm
2 1.00 0.90 0.86
1) If the air temperature is increased by the heat loss of the cables in small buildings or because of high grouping, the
conversion factors for different air temperatures in Table 12 must also be used.
2) Factors as in CENELEC Report R064.001 re HD 384,5.523:1991.

3) A cable trough is a continuous surface with raised edges but no cover. A cable trough is considered perforated if the

perforations cover at least 30 % of the entire surface area.


4) A cable rack is a support structure in which the supporting area is no more than 10 % of the total area of the structure.

Load reduction is not required when laying in bundles where the spacing of adjacent systems is at least four times the cable
diameter, as long as the ambient temperature is not increased by the heat loss (see footnote 1).

657
Table 11. DIN VDE 0276-1000:1995-06
Conversion factors for grouping in air1), multicore cables and single-core DC cables
(as per DIN VDE 0276-1000)

1 2 3 4 5 6 7

Installation Number of Number of cables


troughs/ horizontal4)
Spacing = racks
cable diameter d vertical 1 2 3 4 6

Laid d d
on the floor 1 0.97 0.96 0.94 0.93 0.90
a a ≥ 20 mm
Unperforated 1 0.97 0.96 0.94 0.93 0.90
cable troughs2)
2 0.97 0.95 0.92 0.90 0.86
≥ 300 mm

d d 3 0.97 0.94 0.91 0.89 0.84

a a ≥ 20 mm 6 0.97 0.93 0.90 0.88 0.83

Perforated 1 1.00 1.00 0.98 0.95 0.91


cable troughs2)
2 1.00 0.99 0.96 0.92 0.87
≥ 300 mm

d d 3 1.00 0.98 0.95 0.91 0.85

a a ≥ 20 mm 6 1.00 0.97 0.94 0.90 0.84

Cable racks3) 1 1.00 1.00 1.00 1.00 1.00


(cable gratings)
2 1.00 0.99 0.98 0.97 0.96
≥ 300 mm

d d 3 1.00 0.98 0.97 0.96 0.93

a a ≥ 20 mm 6 1.00 0.97 0.96 0.94 0.91

On racks or Number of Number of systems


on the wall or troughs vertical
on perforated horizontal 1 2 3 4 6
d d

cable troughs
in vertical 1 1.00 0.91 0.89 0.88 0.87
configuration ≥ 225 mm 2 1.00 0.91 0.88 0.87 0.85
1) If the air temperature is increased by the heat loss of the cables in small buildings or because of high grouping, the
conversion factors for different air temperatures in Table 12 must also be used.
2) A cable trough is a continuous surface with raised edges but no cover. A cable trough is considered perforated if it is
perforated over at least 30 % of the entire surface area.
3) A cable rack is a support structure in which the supporting area is no more than 10 % of the total area of the structure.

4) Factors as in CENELEC Report R064.001 re HD 384.5.523:1991.

Load reduction is not required where the horizontal or vertical spacing of adjacent cables is at least twice the cable
diameter, as long as the ambient temperature is not increased by the heat loss (see footnote 1).
(continued)

658
Table 11 (continued) - DIN VDE 0276-1000:1995-06
Conversion factors for grouping in air1), multicore cables and single-core d.c. systems
(as per DIN VDE 0276-1000)
8 9 10 11 12 13 14 15
Installation Number of Number of cables
troughs/racks horizontal4)
Mutual contact vertical 1 2 3 4 6 9
Laid
on the floor 1 0.97 0.85 0.78 0.75 0.71 0.68
a a ≥ 20 mm

Unperforated 1 0.97 0.85 0.78 0.75 0.71 0.68


cable troughs2) ≥ 300 mm
2 0.97 0.84 0.76 0.73 0.68 0.63

3 0.97 0.83 0.75 0.72 0.66 0.63


a a ≥ 20 mm
6 0.97 0.81 0.73 0.69 0.63 0.58

Perforated 1 1.00 0.88 0.82 0.79 0.76 0.73


cable troughs2)
≥ 300 mm

2 1.00 0.87 0.80 0.77 0.73 0.68

3 1.00 0.86 0.79 0.76 0.71 0.66


a a ≥ 20 mm
6 1.00 0.84 0.77 0.73 0.68 0.64

Cable racks3) 1 1.00 0.87 0.82 0.80 0.79 0.78


(cable gratings)
2 1.00 0.86 0.80 0.78 0.76 0.73
≥ 300 mm

3 1.00 0.85 0.79 0.76 0.73 0.70


a a ≥ 20 mm
6 1.00 0.83 0.76 0.73 0.69 0.66

Number of Number of cables


Perforated
troughs vertical
cable troughs
horizontal 1 2 3 4 6 9
vertical
configuration 1 1.00 0.88 0.82 0.78 0.73 0.72
≥ 225 mm
13

2 1.00 0.88 0.81 0.76 0.71 0.70

On racks or on the Number of cables


wall in vertical vertical
configuration 1 2 3 4 6 9

0.95 0.78 0.73 0.72 0.68 0.66


1) If the air temperature is increased by the heat loss of the cables in small buildings or because of high grouping, the conversion factors for
different air temperatures in Table 12 must also be used.
2) A cable trough is a continuous surface with raised edges but no cover. A cable trough is considered perforated if it is perforated over at least
30 % of the entire surface area.
3) A cable rack is a support structure in which the supporting area is no more than 10 % of the total area of the structure.
4) Factors as in CENELEC Report R064.001 re HD 384,5.523:1991.

Load reduction is not required where the horizontal or vertical spacing of adjacent systems is at least twice the cable diameter, so long as the
ambient temperatures are not increased by the heat loss (see footnote 1).

659
Table 12. Conversion Factors for Different Air Temperatures

Permissible Operating
Air Temperature in °C
Temperature °C

Table 13. Conversion factors1), for multicore cables with conductor cross-sections of 1.5 to 10
mm2 laid underground or in air

Number of Laid
In Air
loaded cores Underground

1) Conversion factors must be used when laid underground to the values and laid in air
Table 13. Inner Diameter of Cable Reels (Spools)

Constructive Type Inner reel diameter 1)

Cables without concentric conductors:

- Single conductor
- Multi conductor
- Multiconductor

Cables with concentric conductors

Outside cable diameter. Maximum values according tables 9 to 11 or manufacturer´s data


Nominal section of insulated conductors

1) There is no direct relationship between diameters as indicated here and those given in subsections 3 and 4 of main
section IV for bending radius regarded for cable installation purposes. Both of them are based on essentially different
material requirements.

Table 14. Rated Currents. Cables Laid in Earth

Insulation Material

Permissible operating
temper.

Type designation

Configuration

Number of loaded
conductors
Cross Section Cooper conductor rated current Aluminium conductor rated
in Amperes current in Amperes

1) Rated current in DC System with remote return conductors


Table 15. Rated Current. Cables Laid in Air

Insulation Material

Permissible operating
temper.

Type designation

Configuration

Number of loaded
conductors
Cross Section Cooper conductor rated current Aluminium conductor rated
in Amperes current in Amperes

1) Rated current in DC System with remote return conductors


Table 14. Rated Current. Cables Laid in Earth

Insulation Material XLPE

Permissible operating
temper.

Type designation

Configuration

Number of loaded
conductors
Cross Section Cooper conductor rated current Aluminium conductor rated
in Amperes current in Amperes

1) Rated current in DC System with remote return conductors


NOTE: Rated current also applicable for polyethylen jacketed cables.
Table 15. Rated Current. Cables Laid in Air

Insulation Material XLPE

Permissible operating
temper.

Type designation

Configuration

Number of loaded
conductors
Cross Section Cooper conductor rated current Aluminium conductor rated
in Amperes current in Amperes

1) Rated current in DC System with remote return conductors


NOTE: Rated current also applicable for polyethylen jacketed cables.
Table 5. Acronyms for Type Designation

Cables according to this main section are designated with:


- On acronyms according following shortcut:
Cables according to this specification
Aluminium conductors
Cooper conductors (without shortcut)
PVC Insulation
Common cooper shield
PVC jacket

- Number of conductors x conductor cross sections in mm2 and shield cross section separated by a
backslash (/)
- Conductor shape and type:
Round conductor
Stranded conductor
- Rated voltage Uo/U in kV.

Table 6. Rated Current. Cable Laid in Earth

Insulation Material

Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 7. Rated Current. Cables Laid in Air

Insulation Material

Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 8. Load Factor Definitions

Rated currents are calculated based upon a load profile which is often found in power distribution networks. Such
profiles are characterized with their 24 hours of maximum load and its load factor (see 24 hours cycle diagram).

Maximum load and load factor shall be extracted from 24 hours load profile or a reference load profile. The load
profile is a record of how load varies along a day of fault-free (undisturbed) operation. The average load is the
mean value of the 24 hours load profile; the load factor at any time is the quotient between instantaneous and
maximum load.

Load/Maximum Load Load Factor m

Time in Hours

Ratio Load to maximum load in %

Ratio of average to maximum load

24 H Load -Cycle and Load factor Calculation (Example)


Table 7. Outer Diameter (for preferred constructive types)

Outer diameter
Conductor Cross
Section

Table 8. Rated Current. Cables Laid in Earth.

Insulation Material

Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 9. Rated Current. Cables Laid in Air

Insulation Material

Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 10.Load Factor Definitions

Rated currents are calculated based upon a load profile which is often found in power distribution networks. Such
profiles are characterized with their 24 hours of maximum load and its load factor (see 24 hours cycle diagram).

Maximum load and load factor shall be extracted from 24 hours load profile or a reference load profile. The load
profile is a record of how load varies along a day of fault-free (undisturbed) operation. The average load is the
mean value of the 24 hours load profile; the load factor at any time is the quotient between instantaneous and
maximum load.

Load/Maximum Load Load Factor m

Time in Hours

Ratio Load to maximum load in %

Ratio of average to maximum load

24 H Load -Cycle and Load factor Calculation (Example)


Table 7. Rated Current. Cables Laid in Earth

Insulation XLPE

Permissible Operating Temper.

Type designation

Configuration

Cross Section
Cooper Conductor. Rated Current in A Aluminium Conductor. Rated Current in A

Values also valid for longitudinally watertight cables


Table 8. Rated Current. Cables Laid in Air

Insulation XLPE

Permissible Operating Temper.

Type designation

Configuration

Cross Section
Cooper Conductor. Rated Current in A Aluminium Conductor. Rated Current in A

Values also valid for longitudinally watertight cables


Table 6. Acronyms for Type designation

Cables are designated with:


- On Acronyms according following shortcut:
Cables according to this specification
Aluminium conductors
cooper conductors (without shortcut)
XLPE Insulating
Common cooper shield
cooper shield over each insulated conductor for multiconductor cable
PVC jacket
Polyethylen jacket

- Number of conductors x conductor cross sections in mm2 and shield cross section separated by a
backslash (/)
- Conductor shape and type:
Round conductor
Sector shaped conductor
Stranded conductor
Single (solid) conductor

Rated voltage Uo/U in kV

Table 7. Rated Current. Cables Laid in Earth

Insulation Material XLPE


Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 8. Current Rated. Cables Laid in Air

Insulation Material XLPE


Permissible operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 9. Load Factor Definitions

Rated currents are calculated based upon a load profile which is often found in power distribution networks. Such
profiles are characterized with their 24 hours of maximum load and its load factor (see 24 hours cycle diagram).

Maximum load and load factor shall be extracted from 24 hours load profile or a reference load profile. The load
profile is a record of how load varies along a day of fault-free (undisturbed) operation. The average load is the
mean value of the 24 hours load profile; the load factor at any time is the quotient between instantaneous and
maximum load.

Load/Maximum Load Load Factor m

Time in Hours

Ratio Load to maximum load in %

Ratio of average to maximum load

24 H Load -Cycle and Load factor Calculation (Example)


Table 5. Acronyms for Designation (Preliminar)

Cables are designated with:


- On acronym according material shortcuts as in following table.
- Number of conductors x conductor cross section in mm2.
- Conductor shape and type.
- Rated voltage in kV

Cable according to this standard


Aluminium conductor
Cooper conductor

Paper insulation
Lead sheath
Aluminium sheath
Corrosion protection
PVC outer jacket
PVC outer jacket with reinforced wall thickness
Round conductor
Stranded conductor

Table 6. Rated Current. Cables Laid in Earth

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 7. Rated Current. Cables Laid in Air

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 8. Rated Current. Cables Laid in Earth

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 9. Rated Current. Cables Laid in Air

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 10. Rated Current. Cables Laid in Earth

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes
Table 11. Rated Current. Cables Laid in Air

Insulation Material Impregnated Paper


Permissible
operating temper.

Type designation

Configuration

Cross Section Cooper conductor rated current Aluminium conductor rated


in Amperes current in Amperes

Table 12. Load Factor Definitions

Rated currents are calculated based upon a load profile which is often found in power distribution networks. Such
profiles are characterized with their 24 hours of maximum load and its load factor (see 24 hours cycle diagram).

Maximum load and load factor shall be extracted from 24 hours load profile or a reference load profile. The load
profile is a record of how load varies along a day of fault-free (undisturbed) operation. The average load is the
mean value of the 24 hours load profile; the load factor at any time is the quotient between instantaneous and
maximum load.

Load/Maximum Load Load Factor m

Time in Hours

Ratio Load to maximum load in %

Ratio of average to maximum load

24 H Load -Cycle and Load factor Calculation (Example)


Table 11. Rated Current. Cables Laid in Earth

Material Insulation
Impregnated Paper

Permissible
Operating Temper.

Type Designation 1)

Configuration

Cross Section Cooper conductor. Rated Aluminium conductor. Rated


current in A current in A

Rated current for types with different outer jacket are the same
Table 12. Rated Current. Cables Laid in Air

Material Insulation
Impregnated Paper

Permissible
Operating Temper.

Type Designation 1)

Configuration

Cross Section Cooper conductor. Rated Aluminium conductor. Rated


current in A current in A

Rated current for types with different outer jacket are the same
Tabla IV

Descripción F
Caso general 0,7
Alambre de pantalla aislados no
0,5
embebidos en el material
Cable relleno con aceite 1
INEDON
INGENIERÍA ELÉCTRICA 903-HM150-E01-GUD-152
Rev. 0
CÁLCULO DE ALIMENTADORES SEGÚN NORMA IEC

ANEXO III: IMPEDANCIAS TIPICAS DE CABLES

903-HM150-E01-GUD-152_REV0.DOCX 39 de 39 INEDON