CONVENCIONES

BANDEJA PORTACABLES LUMINARIA INDUSTRIAL


METALICA CERRADA HIGH BAY 400W IP67
40X10CMS

3-TBT2
TRASNFORMADOR TIPO SECO LUMINARIA INDUSTRIAL
250 KVA BAJA-BAJA 440/220V TIPO APLIQUE 20W IP67

TUNEL ENTRE ELEVADORES EL-1 y EL-2


3-TBT2 TABLERO ELECTRICO DE LUMINARIA INDUSTRIAL
DISTRIBUCION T8 - 2X32W IP67

PROYECTOR EXTERIOR
CAJA DE PASO METALICA
40*40*20 CMS LED 75W ASOZULIA
3-TBT2

PROYECTO:
CAJA DE PASO METÁLICA
Bandeja Portacables TIPO INTEMPERIE IP65
Caja de Paso Metalica Metalica Cerrada 30x10cms
40x40x20 cms 30*30*15 CMS
Alt. Instalacion: 16.75 mts
3-TBT2 MOLINO Y PLANTA DE SECADO DE ARROZ DE
1-TBT2 1-TBT2
4,6-TBT2 ASOZULIA
1-TBT2

3-TSGBT

3-TSGBT

3-TSGBT
A TBT2
CAJA DE PASO EN CONCRETO
A TBT2 30*30*30 CMS

EL-2
MUNICIPIO SAN JOSÉ DE CÚCUTA

SILO SP-3
1Ø3/4" EMT
(2#12F+1#12N+1#12T) 14,16-TSGBT
AWG/THHN/Cu NORTE DE SANTANDER
C O L O M B I A
TUBERIA METALICA EMT

OBSERVACIONES:
TUBERIA PVC TIPO PESADO
Bandeja Portacables SUBTERRANEA
Metalica Cerrada 30x10cms
4,6-TBT2 Alt. Instalacion: 16.75 mts

TOMACORRIENTE NEMA
5-15R TIPO INDUSTRIAL

Bandeja Portacables Bandeja Portacables


Metalica Cerrada 30x10cms Metalica Cerrada 30x10cms
Alt. Instalacion: 16.75 mts Alt. Instalacion: 16.75 mts TOMACORRIENTE BIFASICA
1-TBT2 220V

TBT2

Cuarto Tecnico

1Ø1" EMT
(3#8F+1#8N+1#8T)
1Ø1" EMT
(3#8F+1#8N+1#8T)
Tableros Electricos
Bodega Trilla
14,16-TSGBT
OBSERVACIONES
AWG/THHN/Cu AWG/THHN/Cu 2,4-TSGBT

5-TSGBT
NOTAS: DONDE NO SE INDIQUE LO CONTRARIO:
1- La tubería será conduit EMT Ø 1/2" tipo pesado.
1-TBT2

1-TBT2

1-TBT2

1-TSGBT

TF-BT
TSGBT

1-TSGBT

1-TSGBT
14,16-TSGBT

2-Todos los conductores seran de Cu AWG Nº 12 aislamiento 600V-THHN 90º C


3-Todos los tomas a 0.30 mts sobre el nivel del piso acabado.
4-Todos los interruptores a 1.20 mts sobre el nivel del piso acabado.
5- Los apliques a 2.10 mts sobre el nivel del piso acabado.
6- En todos los circuitos se llevara un conductor de cobre aislado de color verde
para conexión a tierra desde el tablero de circuitos y se atornillara
a cada caja metálica deacuerdo a la protección como de 15A / AWG Nº14, de
20A/AWG Nº12, de 30A/AWG Nº 10 y de 40 a 70A/AWG Nº 8.
7- En todas las zonas húmedas los tomas instalados de uso no permanente y en
tomas exteriores a una altura menor de 1.20 m serán tomas especiales GFCI.
JUAN CARLOS SAYAGO ORTEGA
INGENIERO CIVIL-DISEÑO HIDROSANITARIO
Mat. Prof. # 54202-43863 NTS

SAMUEL MEDINA JAIMES


INGENIERO ESTRUCTURAL
Mat. Prof. # 54202-46109 NTS

ALVARO ANTONIO RUIZ TARAZONA


INGENIERO ELECTROMECANICO
Mat. Prof. # CN250-130614
MODIFICACIONES

RUBÉN DARIO ORTIZ OÑORO


ARQUITECTO
Mat. Prof. #A21372016-1090372245

ANDRÉS FELIPE ROZO TORRES


INGENIERO CIVIL
Mat. Prof. #54202-370724

RUBEN DARIO FERNANDEZ CARDENAS


VIENE DE TABLERO SERV. INGENIERO CIVIL
VIENE DE TABLERO GENERALES BODEGA DE Mat. Prof. #54202-55424
CARGAS DE TRILLA APROBÓ
EMERGENCIAS

1xNo. 6 AWG/THHN/Cu - Fase 1xNo. 8 AWG/THHN/Cu - Fase


ESCALA:
1xNo. 6 AWG/THHN/Cu - Neutro 1xNo. 8 AWG/THHN/Cu - Neutro INDICADAS
8 AWG/THHN/Cu - SPT 8 AWG/THHN/Cu - SPT
1Ø1 1/4" PVC 1Ø1" EMT FECHA : MARZO DE 2021
T

TOTALIZADOR 3x50A. TOTALIZADOR 3x40A.


PRINCIPAL 50KA. PRINCIPAL 25KA.
T

ESPECIFICACIONES DE LOS MATERIALES:


T

T
T

1xNo. 6 AWG/THHN/Cu - Fase 1xNo. 8 AWG/THHN/Cu - Fase CONCRETO


T

1xNo. 6 AWG/THHN/Cu - Neutro 1xNo. 8 AWG/THHN/Cu - Neutro


8 AWG/THHN/Cu - SPT 8 AWG/THHN/Cu - SPT
T

T T CONCRETO F'C= 210 KG/CM. 21MPA


8 Cu 8 Cu
N N RESISTENCIA DEL CONCRETO A LOS 28 DIAS
F F
ACERO
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
10 AWG/THHN/Cu - Fase
10 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
10 AWG/THHN/Cu - Fase
10 AWG/THHN/Cu - N
8 AWG/THHN/Cu - Fase
8 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - Fase
12 AWG/THHN/Cu - N REFUERZO VARILLA Ø>= # 5 FY= 4200 KG/CM 420MPA
12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 8 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT
REFUERZO VARILLA Ø>= # 4 FY= 4200 KG/CM 420MPA
REFUERZO VARILLA Ø<= # 3 FY= 2400 KG/CM 240MPA
1x20A. 2x20A. 1x20A. 1x20A. 2x32A. 2x20A. 2x32A. 3x40A. 2x20A. 1x20A. 2x20A. 1x20A. 1x20A.
10KA. 10KA. 10KA. 10KA. 10KA. 10KA. 10KA. 25KA. 10KA. 10KA. 10KA. 10KA. 10KA. SOLDADURA E-7018,NORMAS AWS
PERFILES ESTRUCTURALES TIPO ACESCO GRADO 50

12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 10 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 10 AWG/THHN/Cu - Fase 8 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase 12 AWG/THHN/Cu - Fase
SISTEMA DE RESISTENCIA SÍSMICA: MUNICIPIO DE EL ZULIA
12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 10 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 8 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N 12 AWG/THHN/Cu - N
12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT 12 AWG/THHN/Cu - SPT
8 AWG/THHN/Cu - SPT
1Ø1" EMT
Grado de capacidad de
Disipacion de energia = DES

ZONA DE AMENAZA SÍSMICA: ALTA


CÓDIGO MUNICIPIO NSR-10: 54261

1 2-4 3 5 6-8 7-9 10-12 11-13-15 14-16 17-18 1 4-6 3 5 2-7-8 CONTIENE:
9-10-11-12
ILUMINACION EXTERIOR
ILUMINACION BODEGA

ILUMINACION BODEGA

BODEGA TRILLA 2 - TBT2


A.A. CUARTO TECNICO

ILUMINACION TUNEL
TOMAS 220V MTTO
CUARTO TÉCNICO

Salidas Tomas Bodega


SERV. GENERALES
TOMAS BODEGA

TOMAS BODEGA

TOMAS BODEGA

MANTENIMIENTO
TOMA BIFASICO
BODEGA TRILLA

TOMAS/LUCES

TABLERO DIST.

TOMAS TUNEL

de Trilla, Diagrama Unifilar,


RESERVAS

RESERVAS
BODEGA

SECADO

SECADO
LADO A
TRILLA 1

TRILLA 2

LADO B

TRILLA

Cuadro de Cargas
DIAGRAMA UNIFILAR TABLERO SERVICIOS DIAGRAMA UNIFILAR TABLERO SERVICIOS
GENERALES BODEGA TRILLA - (TD-SGBT) GENERALES SILOS - (TBT2) NUMERO

CODIGO PLANO
TIPO
CODIGO PROYECTO PLANO PLANO ESCALA PLANO

BODEGA DE TRILLA - TOMAS EL12 1 IND