LAYOUT DE CONECTIVIDAD DEL CABLEADO ESTRUCTURADO

ISP ISP ISP ISP


“A” “B” “A” “B”

CUARTO DE CUARTO DE
ENTRADA ENTRADA
1 1 Cassete 1 Cassete 1 Cassete 1 Cassete
2
FO SM FO SM FO SM FO SM
MPO24 “A” MPO24 “B” MPO24 “A” MPO24 “B”

12 Patch Cord 12 Patch Cord 12 Patch Cord 12 Patch Cord


Duplex FO SM Duplex FO SM Duplex FO SM Duplex FO SM

2 Cassete FO SM MPO24
1 Cassete 1 Cassete 1 Cassete 1 Cassete
24 Patch Cord Duplex FO SM
FO SM FO SM FO SM FO SM
MPO24 “A” MPO24 “B” MPO24 “A” MPO24 “B”

12 Patch Cord 12 Patch Cord 12 Patch Cord 12 Patch Cord


Duplex FO SM Duplex FO SM Duplex FO SM Duplex FO SM

LEYENDA DE CABLES:
30 Cables UTP Cat6A
1 Cable Troncal FO MM MPO12
1 Cable Troncal FO SM MPO24

CENTRO DE DATOS

MDA 1 MDA 2

4 Cassete FO SM MPO24 4 Cassete FO SM MPO24


48 Patch Cord Duplex FO SM 48 Patch Cord Duplex FO SM

6 Cassete FO MM MPO12 6 Cassete FO MM MPO12


24 Patch Cord Duplex FO MM 2 Cassete FO SM MPO24 24 Patch Cord Duplex FO MM
24 Patch Cord Duplex FO SM

HDA 1A HDA 1B HDA 2A HDA 2B HDA 3A HDA 3B

EDA11 EDA12 EDA13 EDA14 EDA15 EDA21 EDA22 EDA23 EDA24 EDA25 EDA31 EDA32 EDA33 EDA34 EDA35

Considerando que cada gabinete EDA tiene 15 servidores, entonces:

POR CADA RACK EDA: POR CADA RACK HDA:

Por cada Servidor, se requiere 2 cables UTP Cat6A <> En 15 servidores: 30 UTP Cat6A Llegan 150 cables UTP Cat6A
Entonces, se necesita: Entonces, se necesita:
- 1 Patch Panel “A” de 48ptos y 1 Patch Panel “B” de 48ptos - 4 Patch Panel “A” de 48ptos y 4 Patch Panel “B” de 48ptos
- 60 patch cord UTP Cat6A (30 “A” y 30 “B”) - 4 Switch de Borde “A” de 48ptos y 4 Switch de Borde “B” de 48ptos
- 8 patch cord duplex FO MM (4 para conexión desde switch de borde “A” hacia switch de distribución “A” y 4
para “B”)
- 2 Cassete FO MM MPO12 (1 “A” y 1 “B”)