Motores

Mpl Primero P ( 1.5 ) (756)


IN= = =3.62 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1
1 HP
2 I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 3.62 )( 1.1 ) =3.982
F=60 Hz
VL =220 V I N X 1.25 3.982(1.25) Cal #12
I Cond mot = = =5.65 A
η= 0.90 n F T F a (1) ( 0.88 ) (1)
F.P.=0.9
T=38 ׄ R(Ω)= X LTabla5.6 ( 3051 )= 2(39.66)
305
=0.26 Ω
n=1
Fa = 1 1 0.054 ( 39.66 )
L= 39.66 m
X L (Ω)=X LTabla 5.6 ( )
305
=
305
=7.021 X 10−3 Ω

2

Z cond=√ R2 + X L2= ( 0.26 )2+ ( 7.021 X 10−3 ) =0.26

e=Z cond I N =0.26 (3.982 ) =1.03532V

3e
e %= √ ( 100 )=
√ 3(1.0353) ( 100 )=0.8151 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm 2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=3.982 ( 2.5 )=9.955 A

I N < I Prot < I Cond=3.982<20<30 ITM= 3X30 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12


Relevador de sobrecarga
I Rele S C =I N X 1.25=3.982 ( 1.25 ) =4.97

I Rele SC =I N X 1.14=3.982 ( 1.14 )=5.57

La capacidad nominal de un valor de un intervalo de 4 y 5

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A

Mpl2 P ( 5 ) (756)
IN= = =12 A
Primero √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)

5 HP I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 12 )( 1.1 ) =13.2 A


F=60 Hz
VL =220 V I N X 1.25 13.2(1.25) Cal #12
I Cond mot = = =18.75 A
η= 0.90 n F T F a (1) ( 0.88 ) (1)
F.P.=0.9
T=38 ׄ R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 39.47
305
)
=0.2588Ω
n=1
Fa = 1
L=39.47m
X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 39.47 ) =6.9881 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.2588 )2 + ( 6.9881 X 10−3 ) =0.2588

e=Z cond I N =0.2588 ( 13.2 ) =3.41616V

3e
e %= √ ( 100 )=
√ 3(3.41616) ( 100 )=2.47 %
VL 220

Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A

I N < I Prot < I Cond=13.2<20<30 ITM= 3X30 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5

I Rele SC =I N X 1.14=13.2 ( 1.14 )=18.48

La capacidad nominal de un valor de un intervalo de 16 y 18

Arrancador

Para 220 V (230 V nominales)

Tamaño 0 CRB= 64 Corriente Nominal = 18 A

Mpl
Segundo P ( 1.5 ) (756)
IN= = =3.62 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1
1 HP
2
I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 3.62 )( 1.1 ) =3.982 = 4 A
F=60 Hz
VL =220 V
I N X 1.25 4 (1.25) Cal #12
η= 0.90 I Cond mot = = =5.68 A
n F T F a (1) ( 0.88 ) (1)
F.P.=0.9
T=38 ׄ
n=1
Fa = 1
L= 48.7 m
R(Ω)= X LTabla5.6 ( 3051 )= 2 (305
48.7 )
=0.3193 Ω

X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 48.7) =8.6222 X 10


−3

2

Z cond=√ R2 + X L2= ( 0.3193 )2 + ( 8.6222 X 10−3 ) =0.3194

e=Z cond I N =0.3194 ( 4 )=1.2776 V

3e
e %= √ ( 100 )=
√ 3(1.2776) ( 100 )=1.0058 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=4 ( 2.5 )=10 A

I N < I Prot < I Cond=4<20< 30 ITM= 3X30 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=4 ( 1.25 )=5

I Rele SC =I N X 1.14=4 (1.14 )=5.6

La capacidad nominal de un valor de un intervalo de 5 y 5.6

Arrancador

Para 220 V (230 V nominales)


Tamaño 00 CRB= 40 Corriente Nominal = 9 A

Mpl2 P ( 5 ) (756)
IN= = =12 A
segundo √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)

5 HP I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 12 )( 1.1 ) =13.2 A


F=60 Hz
VL =220 V I N X 1.25 13.2(1.25) Cal #10
I Cond mot = = =18.75 A
η= 0.90 n F T F a (1) ( 0.88 ) (1)
F.P.=0.9
T=38 ׄ R(Ω)= X LTabla5.6 ( 3051 )= 1.2305
( 51.39 )
=0.2021 Ω
n=1
Fa = 1 1 0.050 ( 51.39 )
L=51.39m
X L (Ω)=X LTabla 5.6 ( )
305
=
305
=8.4245 X 10−3 Ω

2

Z cond=√ R2 + X L2= ( 0.2021 )2 + ( 8.4245 X 10−3 ) =0.2022

e=Z cond I N =0.2022 ( 13.2 )=2.66904 V

3e
e %= √ ( 100 )=
√ 3(2.66904) ( 100 ) =2.10 %
VL 220

Canalización

Con Fr = 40%
1
ACond =15.7 X 3=47.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A

I N < I Prot < I Cond=13.2<30<30 ITM= 3X30 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12


Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5

I Rele SC =I N X 1.14=13.2 ( 1.14 )=18.48

La capacidad nominal de un valor de un intervalo de 16 y 18

Arrancador

Para 220 V (230 V nominales)

Tamaño 0 CRB= 64 Corriente Nominal = 18 A

MOI P ( 3 ) (756)
IN= = =7.25 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
3 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 7.25 ) (1.1 )=7.975 A
VL =220 V
η= 0.90 I N X 1.25 7.975(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ 1 2 ( 43.45 )
n=1 R(Ω)= X LTabla5.6 ( )
305
=
305
=0.2849 Ω
Fa = 1
L=43.45 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 43.45 ) =7.692786 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.2849 )2 + ( 7.692786 X 10−3) =0.2850

e=Z cond I N =0.2850 ( 7.975 ) =2.272875V

3e
e %= √ ( 100 )=
√ 3(2.272875) ( 100 )=1.79 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=7.975 (2.5 )=20 A

I N < I Prot < I Con d=7.975< 25<30 ITM= 3X25 A

Cal. Para puesta a tierra ITM= 25 A Cal #10 = Id #10

Relevador de sobrecarga
I Rele SC =I N X 1.25=7.975 ( 1.25 ) =9.96

I Rele SC =I N X 1.14=7.975 (1.14 )=11.165

La capacidad nominal de un valor de un intervalo de 10 y 1

Arrancador

Para 220 V (230 V nominales)

Tamaño 0 CRB= 70 Corriente Nominal = 18 A

MH Primero P ( 1 ) (756)
IN= = =2.417 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 2.417 ) ( 1.1 )=3.77 A
VL =220 V
η= 0.90 I N X 1.25 3.77(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 (305
40.5 )
=0.26557 Ω
Fa = 1
L=40.5 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 40.5 ) =7.17049 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.26557 )2+ ( 7.17049 X 10−3 ) =0.2656

e=Z cond I N =0.2656 (3.77 )=1.001312V

3e
e %= √ ( 100 )=
√ 3() ( 100 )=0.78 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A

I N < I Prot < I Cond=3.77< 20<30 ITM= 3X20 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125

I Rele SC =I N X 1.14=3.77 ( 1.14 ) =¿ 5.278

La capacidad nominal de un valor de un intervalo de 4 y 5

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A


MH Segundo P ( 1 ) (756)
IN= = =2.417 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 2.417 ) ( 1.1 )=3.77 A
VL =220 V
η= 0.90 I N X 1.25 3.77(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 37.59
305
)
=0.24649Ω
Fa = 1
L=37.59 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 37.59 ) =6.65527 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.24649 )2 + ( 6.65527 X 10−3 ) =0.24658

e=Z cond I N =0.24658 ( 3.77 )=0.93 V

3e
e %= √ ( 100 )=
√ 3(0.93) ( 100 )=0.7321%
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A

I N < I Prot < I Cond=3.77< 20<30 ITM= 3X20 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125
I Rele SC =I N X 1.14=3.77 ( 1.14 ) =¿ 5.278

La capacidad nominal de un valor de un intervalo de 4 y 5

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A

MH Tercero P ( 1 ) (756)
IN= = =2.417 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 2.417 ) ( 1.1 )=3.77 A
VL =220 V
η= 0.90 I N X 1.25 3.77(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 34.67
305
)
=0.2273Ω
Fa = 1
L=34.67 m 1 0.054 ( 34.67 )
X L (Ω)=X LTabla 5.6 ( )
305
=
305
=6.1383 X 10−3 Ω

2

Z cond=√ R2 + X L2= ( 0.2273 )2 + ( 6.1383 X 10−3 ) =0.2273

e=Z cond I N =0.24658 ( 3.77 )=0.93 V

3e
e %= √ ( 100 )=
√ 3(0.2273) ( 100 )=0.67 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A

I N < I Prot < I Cond=3.77< 20<30 ITM= 3X20 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125

I Rele SC =I N X 1.14=3.77 ( 1.14 ) =¿ 5.278

La capacidad nominal de un valor de un intervalo de 4 y 5

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A

MSA
IN=
P
=
( 12 )(756) =1.2085 A
1 √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
HP
2
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 1.2085 ) (1.1 ) =1.32935 A
VL =220 V
η= 0.90 I N X 1.25 1.32935(1.25) Cal #12
I Cond mot = = =1.88 A
F.P.=0.9 n FT Fa (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 29.96
305
)
=0.1964 Ω
Fa = 1
L=29.96 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 29.96 ) =5.3043 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.1964 )2+ ( 5.3043 X 10−3 ) =0.1964

e=Z cond I N =0.1964 ( 1.32935 )=0.2610 V


3e
e %= √ ( 100 )=
√ 3(0.2610) ( 100 )=0.2054 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=1.32935 ( 2.5 )=3.323375 A

I N < I Prot < I Cond=1.32935<15< 30 ITM= 3X15 A

Cal. Para puesta a tierra ITM= 15 A Cal #14 = Id #14

Relevador de sobrecarga
I Rele SC =I N X 1.25=1.32935 ( 1.25 )=1.66

I Rele SC =I N X 1.14=1.32935 (1.14 )=¿ 1.86

La capacidad nominal de un valor de un intervalo de 1 y 2

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A


Mpl2 Tercero

5 HP P ( 5 ) (756)
F=60 Hz IN= = =12 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
VL =220 V
η= 0.90 I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 12 )( 1.1 ) =13.2 A
F.P.=0.9
T=38 ׄ
n=1
Fa = 1
L=27.91 m
I N X 1.25 13.2(1.25)
I Cond mot = = =18.75 A Cal #12
n F T F a (1) ( 0.88 ) (1)

R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 27.91


305
)
=0.1830 Ω

X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 27.91 ) =4.9414 X 10


−3

2

Z cond=√ R2 + X L2= ( 0.1830 )2 + ( 4.9414 X 10−3 ) =0.1830

e=Z cond I N =0.1830 ( 13.2 ) =2.5156V

3e
e %= √ ( 100 )=
√ 3(2.5156) ( 100 )=1.90 %
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A

I N < I Prot < I Cond=13.2<20<30 ITM= 3X20 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5

I Rele SC =I N X 1.14=13.2 ( 1.14 )=¿ 18.48

La capacidad nominal de un valor de un intervalo de 1 y 2

Arrancador
Para 220 V (230 V nominales)

Tamaño 0 CRB= 64 Corriente Nominal = 18 A

MSA Segundo
IN=
P
=
( 12 )(756) =1.2085 A
1 √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
HP
2
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 1.2085 ) (1.1 ) =1.33 A
VL =220 V
η= 0.90 I N X 1.25 1.33(1.25) Cal #12
I Cond mot = = =1.88 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R ( Ω )= X LTabla5.6 ( 3051 )= 2(305
19.4 )
=0.1272Ω
Fa = 1
L=19.4 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 19.4 ) =3.43475 X 10 −3

2

Z cond=√ R2 + X L2= ( 0.1272 )2 + ( 3.43475 X 10−3 ) =0.1272

e=Z cond I N =0.1272 ( 1.33 )=0.169476V

3e
e %= √ ( 100 )=
√ 3(0.169476) ( 100 ) =0.1332%
VL 220

Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=1.32935 ( 2.5 )=3.323375 A
I N < I Prot < I Cond=1.32935<15< 30 ITM= 3X15 A

Cal. Para puesta a tierra ITM= 15 A Cal #14 = Id #14

Relevador de sobrecarga
I Rele SC =I N X 1.25=1.32935 ( 1.25 )=1.66

I Rele SC =I N X 1.14=1.32935 (1.14 )=¿ 1.86

La capacidad nominal de un valor de un intervalo de 1 y 2

Arrancador

Para 220 V (230 V nominales)

Tamaño 00 CRB= 40 Corriente Nominal = 9 A

Mpl2 Cuarto P ( 5 ) (756)


IN= = =12 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
5 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 12 )( 1.1 ) =13.2 A
VL =220 V
η= 0.90 I N X 1.25 13.2(1.25) Cal #12
I Cond mot = = =18.75 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 17.37
305
)
=0.114 Ω
Fa = 1
L=17.37 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 17.37 ) =3.075 X 10
−3

2

Z cond=√ R2 + X L2= ( 0.114 )2 + ( 3.075 X 10−3 ) =0.1114

e=Z cond I N =0.1114 (13.2 ) =1.548V

3e
e %= √ ( 100 )=
√ 3(1.548) ( 100 )=1.18 %
VL 220
Canalización

Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2

Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A

I N < I Prot < I Cond=13.2<20<30 ITM= 3X20 A

Cal. Para puesta a tierra ITM= 20 A Cal #12 = Id #12

Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5

I Rel e SC =I N X 1.14=13.2 ( 1.14 )=¿ 18.48

La capacidad nominal de un valor de un intervalo de 1 y 2

Arrancador

Para 220 V (230 V nominales)

Tamaño 0 CRB= 64 Corriente Nominal = 18 A


Cálculo de Luminarias

Zona 1: Esterilización de
Botellas
Lámpara StarcoatTM T8 32 W
A= 176.621 m2
E=
n=
I=