Z cond=√ R2 + X L2= ( 0.26 )2+ ( 7.021 X 10−3 ) =0.26
3e
e %= √ ( 100 )=
√ 3(1.0353) ( 100 )=0.8151 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm 2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=3.982 ( 2.5 )=9.955 A
Arrancador
Mpl2 P ( 5 ) (756)
IN= = =12 A
Primero √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
2
√
Z cond=√ R2 + X L2= ( 0.2588 )2 + ( 6.9881 X 10−3 ) =0.2588
3e
e %= √ ( 100 )=
√ 3(3.41616) ( 100 )=2.47 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5
Arrancador
Mpl
Segundo P ( 1.5 ) (756)
IN= = =3.62 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1
1 HP
2
I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 3.62 )( 1.1 ) =3.982 = 4 A
F=60 Hz
VL =220 V
I N X 1.25 4 (1.25) Cal #12
η= 0.90 I Cond mot = = =5.68 A
n F T F a (1) ( 0.88 ) (1)
F.P.=0.9
T=38 ׄ
n=1
Fa = 1
L= 48.7 m
R(Ω)= X LTabla5.6 ( 3051 )= 2 (305
48.7 )
=0.3193 Ω
2
√
Z cond=√ R2 + X L2= ( 0.3193 )2 + ( 8.6222 X 10−3 ) =0.3194
3e
e %= √ ( 100 )=
√ 3(1.2776) ( 100 )=1.0058 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=4 ( 2.5 )=10 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=4 ( 1.25 )=5
Arrancador
Mpl2 P ( 5 ) (756)
IN= = =12 A
segundo √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
2
√
Z cond=√ R2 + X L2= ( 0.2021 )2 + ( 8.4245 X 10−3 ) =0.2022
3e
e %= √ ( 100 )=
√ 3(2.66904) ( 100 ) =2.10 %
VL 220
Canalización
Con Fr = 40%
1
ACond =15.7 X 3=47.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A
Arrancador
MOI P ( 3 ) (756)
IN= = =7.25 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
3 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 7.25 ) (1.1 )=7.975 A
VL =220 V
η= 0.90 I N X 1.25 7.975(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ 1 2 ( 43.45 )
n=1 R(Ω)= X LTabla5.6 ( )
305
=
305
=0.2849 Ω
Fa = 1
L=43.45 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 43.45 ) =7.692786 X 10 −3
Ω
2
√
Z cond=√ R2 + X L2= ( 0.2849 )2 + ( 7.692786 X 10−3) =0.2850
3e
e %= √ ( 100 )=
√ 3(2.272875) ( 100 )=1.79 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=7.975 (2.5 )=20 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=7.975 ( 1.25 ) =9.96
Arrancador
MH Primero P ( 1 ) (756)
IN= = =2.417 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 2.417 ) ( 1.1 )=3.77 A
VL =220 V
η= 0.90 I N X 1.25 3.77(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 (305
40.5 )
=0.26557 Ω
Fa = 1
L=40.5 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 40.5 ) =7.17049 X 10 −3
Ω
2
√
Z cond=√ R2 + X L2= ( 0.26557 )2+ ( 7.17049 X 10−3 ) =0.2656
3e
e %= √ ( 100 )=
√ 3() ( 100 )=0.78 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125
Arrancador
2
√
Z cond=√ R2 + X L2= ( 0.24649 )2 + ( 6.65527 X 10−3 ) =0.24658
3e
e %= √ ( 100 )=
√ 3(0.93) ( 100 )=0.7321%
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125
I Rele SC =I N X 1.14=3.77 ( 1.14 ) =¿ 5.278
Arrancador
MH Tercero P ( 1 ) (756)
IN= = =2.417 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
1 HP
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 2.417 ) ( 1.1 )=3.77 A
VL =220 V
η= 0.90 I N X 1.25 3.77(1.25) Cal #12
I Cond mot = = =11.33 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 34.67
305
)
=0.2273Ω
Fa = 1
L=34.67 m 1 0.054 ( 34.67 )
X L (Ω)=X LTabla 5.6 ( )
305
=
305
=6.1383 X 10−3 Ω
2
√
Z cond=√ R2 + X L2= ( 0.2273 )2 + ( 6.1383 X 10−3 ) =0.2273
3e
e %= √ ( 100 )=
√ 3(0.2273) ( 100 )=0.67 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=3.77 ( 2.5 )=9.425 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=3.77 ( 1.25 )=4.7125
Arrancador
MSA
IN=
P
=
( 12 )(756) =1.2085 A
1 √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
HP
2
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 1.2085 ) (1.1 ) =1.32935 A
VL =220 V
η= 0.90 I N X 1.25 1.32935(1.25) Cal #12
I Cond mot = = =1.88 A
F.P.=0.9 n FT Fa (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R(Ω)= X LTabla5.6 ( 3051 )= 2 ( 29.96
305
)
=0.1964 Ω
Fa = 1
L=29.96 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 29.96 ) =5.3043 X 10 −3
Ω
2
√
Z cond=√ R2 + X L2= ( 0.1964 )2+ ( 5.3043 X 10−3 ) =0.1964
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=1.32935 ( 2.5 )=3.323375 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=1.32935 ( 1.25 )=1.66
Arrancador
5 HP P ( 5 ) (756)
F=60 Hz IN= = =12 A
√3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
VL =220 V
η= 0.90 I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 12 )( 1.1 ) =13.2 A
F.P.=0.9
T=38 ׄ
n=1
Fa = 1
L=27.91 m
I N X 1.25 13.2(1.25)
I Cond mot = = =18.75 A Cal #12
n F T F a (1) ( 0.88 ) (1)
2
√
Z cond=√ R2 + X L2= ( 0.1830 )2 + ( 4.9414 X 10−3 ) =0.1830
3e
e %= √ ( 100 )=
√ 3(2.5156) ( 100 )=1.90 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5
Arrancador
Para 220 V (230 V nominales)
MSA Segundo
IN=
P
=
( 12 )(756) =1.2085 A
1 √3 VL F T F a √ 3 ( 220 ) ( 0.9 ) (0.9)
HP
2
F=60 Hz I N =I N ( FP ) Nota :0.9( 0.9−1=1.1) I N =( 1.2085 ) (1.1 ) =1.33 A
VL =220 V
η= 0.90 I N X 1.25 1.33(1.25) Cal #12
I Cond mot = = =1.88 A
F.P.=0.9 n F T F a (1) ( 0.88 ) (1)
T=38 ׄ
n=1 R ( Ω )= X LTabla5.6 ( 3051 )= 2(305
19.4 )
=0.1272Ω
Fa = 1
L=19.4 m X L (Ω)=X LTabla 5.6 ( 3051 )= 0.054305( 19.4 ) =3.43475 X 10 −3
Ω
2
√
Z cond=√ R2 + X L2= ( 0.1272 )2 + ( 3.43475 X 10−3 ) =0.1272
3e
e %= √ ( 100 )=
√ 3(0.169476) ( 100 ) =0.1332%
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=1.32935 ( 2.5 )=3.323375 A
I N < I Prot < I Cond=1.32935<15< 30 ITM= 3X15 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=1.32935 ( 1.25 )=1.66
Arrancador
2
√
Z cond=√ R2 + X L2= ( 0.114 )2 + ( 3.075 X 10−3 ) =0.1114
3e
e %= √ ( 100 )=
√ 3(1.548) ( 100 )=1.18 %
VL 220
Canalización
Con Fr = 40%
1
ACond =11.7 X 3=35.10 mm2 Tubo (conduit) de 16 mm
2
Interruptor
I Max =I N X 2.5=13.2 ( 2.5 )=33 A
Relevador de sobrecarga
I Rele SC =I N X 1.25=13.2 ( 1.25 )=16.5
Arrancador
Zona 1: Esterilización de
Botellas
Lámpara StarcoatTM T8 32 W
A= 176.621 m2
E=
n=
I=