Está en la página 1de 1

T

CA
-5
CA
-2
C

F1
A-
1

2 X WS 70mm2 extraflexible

BB 960Ah -48VDCI

CS
-3
F1
T

2 X WS 70mm2 extraflexible

BB 960Ah -48VDCII
T
CS-2

T
CA
3x60A -4
CS-9
CA-1 AIRE ACONDICIONADO - PRECISION 1
IC60N 3-1x16mm² NH + 1x16mm² NH(N) +1x16mm² THW(T)

3x60A
CA-2 AIRE ACONDICIONADO - PRECISION 2
3x80A IC60N 3-1x16mm² NH + 1x16mm² NH(N) +1x16mm² THW(T)

3x40A
CS-2

CA-3 AIRE ACONDICIONADO


IC40N 3-1x10mm² NH + 1x10mm² NH(N) +1x10mm² THW(T)

3x40A
CS-
1

CA-4 RESERVA SIN CABLEADO


C
A

IC40N
-3

2x30A
CS

CA-5 AIRE ACONDICIONADO - CONFORT 1


-9

IC30N 1x6mm² NH + 1x6mm² NH(N) +1x6mm² THW(T)

CA-6 RESERVA SIN EQUIPAR 1F+1N

2x10A 2x10A
CS-1 TOMACORRIENTES SALA DE FUERZA
IK60N 1x4mm² NH + 1x4mm² NH(N) +1x2.5mm² NH(T)
30mA

2x10A 2x10A
CS-2 TOMACORRIENTES SALA DE ENERGÍA
IK60N 1x4mm² NH + 1x4mm² NH(N) +1x2.5mm² NH(T)
30mA
T

2x20A 2x10A 2x10A


T

CS-3 TOMACORRIENTES SALA DE EQUIPOS


IK60N 30mA 1x4mm² NH + 1x4mm² NH(N) +1x2.5mm² NH(T)

2x10A
CS-4 ILUMINACIÓN SALA DE FUERZA
T

IK60N 1x2.5mm² NH + 1x2.5mm² NH(N)

2x10A
CS-5 ILUMINACIÓN SALA DE ENERGÍA
IK60N 1x2.5mm² NH + 1x2.5mm² NH(N)

2x10A
CS-6 ILUMINACIÓN SALA DE EQUIPOS
IK60N 1x2.5mm² NH + 1x2.5mm² NH(N)

2x10A
CS-7 ILUMINACIÓN CUARTO DE ADMINISTRACIÓN CENTRALIZADA
CS

1x2.5mm² NH + 1x2.5mm² NH(N)


-9

IK60N

2x10A
CS-8 ILUMINACIÓN PASILLOS, DEPÓSITO Y SS.HH.
IK60N 1x2.5mm² NH + 1x2.5mm² NH(N)

2x10A 2x10A
CS-9 TOMACORRIENTES PATIO
IK60N 1x4mm² NH + 1x4mm² NH(N) +1x2.5mm² NH(T)
30mA

CS-10 RESERVA SIN EQUIPAR 1F + 1N


CS

TIERRA
-1

Para los circuitos CS 9,10 y CA 6 se considera un espacio


monofasico disponible para albergar un ITM de la familia
IK60N.
T

T
TELECOMUNICACIONES
PROGRAMA NACIONAL DE

DE EMERGENCIA
PLANTA DEL PRIMER

IE-06
NIVEL ALUMBRADO Y LUCES
TM
PRONATEL