Está en la página 1de 13

EJERCICIO 6.

1. Datos del Problema

Largo 21.50 m
Ancho 16.50 m
Área 354.75 m²
Columnas 0.50m x 0.50m
Columnas de Estudio A, B, C, D, E, F

Columnas Cargas (kN) Columnas


A 400 G
B 500 H
C 450 I
D 350 J
E 500 K
F 400 L

2. Carga Total de Columnas

Q (kN) 11000

5. Presión del Suelo

𝑞=𝑄/𝐴±(𝑀_𝑦 𝑥)/𝐼_𝑦 ± 𝑀_𝑥=𝑄𝑒_𝑦 𝑒_𝑥=𝑥^′ 𝑒_𝑦=𝑦^′ 𝑥^′=(𝑄_(1𝑥_1^′+) 𝑄_(2𝑥_2^′


(𝑀_𝑥 𝑦)/𝐼_𝑥 𝑀_𝑦=𝑄𝑒_𝑥 −𝐵/2 −𝐿/2 +) 𝑄_(3𝑥_3^′+)…)/𝑄

LOSA DE CIMENTACIÓN
A 354.750 m²
Ix 13665 m⁴
Iy 8048 m⁴
x' 7.814 m
ex -0.44 m
y' 10.85 m
ey 0.10 m
Mx 1050 kN-m
My -4800 kN-m

q= 31 -0.60 0.08
COLUMNA q
A 36.75
B 31.83
C 26.91
D 35.10
E 30.18
F 35.10
3. Coordenadas de Columnas x' e y' 4.

Columnas x y
A 0.25 21.25
B 8.25 21.25
C 16.25 21.25
D 16.25 0.25
Cargas (kN) E 8.25 0.25
1200 F 0.25 0.25
1500 G 16.25 7.25
1500 H 8.25 7.25
1200 I 0.25 7.25
1500 J 16.25 14.25
1500 K 8.25 14.25
L 0.25 14.25

_1^′+) 𝑄_(2𝑥_2^′ 𝑦^′=(𝑄_(1𝑦_1^′+) 𝑄_(2𝑦_2^′


^′+)…)/𝑄 +) 𝑄_(3𝑦_3^′+)…)/𝑄
Coordenadas de Columnas x e y

Columnas x y
A -8.25 10.75
B 0 10.75
C 8.25 10.75
D -8.25 -10.75
E 0 -10.75
F -8.25 -10.75
EJERCICIO 6.6

1. Datos del Problema

Tipo de Suelo Arenoso FRANJA B


Método Rígido Convencional F1 4.25
Largo (m) 21.5 m F2 8.00
Base (m) 16.5 m F3 4.25
f'c 20.7 MN/m²
fy 413.7 MN/m²
Factor de Carga 1.7
Ø 0.85

2. Presión del Suelo de cada Columna

COLUMNA q
A 36.75
B 31.83
C 26.91
D 35.10
E 30.18
F 35.10

3. Diagramas Cortante y Momento

PARA F1: PARA F2:

Base 4.25 m Base


Largo 21.50 m Largo

COLUMNA Q COLUMNA
A 400 kN B
L 1500 kN K
I 1500 kN H
F 400 kN E
TOTAL 3800 kN TOTAL

Presión promedio 35.93 kN/m² Presión promedio


Reacción Total del Suelo 3283 kN. Reacción Total del Su
Carga Promedio 3541.5 kN. Carga Promedio
q(prom. modificada) 38.758 kN/m² q(prom. modificada

Factor de Multiplicación 0.9320 Factor de Multiplicaci

COLUMNA Qmod COLUMNA


A 372.79 kN 3541.47 B
L 1397.95 kN 1770.7355 K
I 1397.95 kN H
F 372.79 kN E

Longitud Unitaria de la viga 164.72 kN/m Longitud Unitaria de la

4. Espesor de la losa

Franja F1
Qmáx 1500 kN

bo
U 1.5 +
2.55 MN 2d
d 0.68 m

recub. 76 mm
diam v 25 mm

h 0.8 m

5. Diagrama de Cortantes

F1 F2 F3
x (m) V x (m) V x (m)
0 0 0 0 0
0.25 41.19 0.25 54.26 0.25
0.25 -381.70 0.25 -529.00 0.25
7.25 821.65 7.25 990.17 7.25
7.25 -576.70 7.25 -759.58 7.25
14.25 576.70 14.25 759.58 14.25
14.25 -821.65 14.25 -990.17 14.25
21.25 331.70 21.25 529.00 21.25
21.25 -41.19 21.25 -54.26 21.25
21.50 0 21.50 0 21.50
6. Diagrama de Momentos

F1 F2 F3
x (m) M x (m) M x (m)
0 0 0 0 0
0.25 5.15 0.25 6.75 0.25
3.75 -326.55 3.75 -637.94 3.75
7.25 1127.57 7.25 1620.89 7.25
10.75 718.35 10.75 291.62 10.75
14.25 1727.57 14.25 1620.89 14.25
17.75 -326.55 17.75 -637.94 17.75
21.25 5.15 21.25 6.78 21.25
21.50 0 21.50 0 21.50

5. Refuerzo

Mmáx(+) 1727.57 kN-m


M' 406.5 Kn-m/m
Mu 691.0 Kn-m/m
a 23.51 As 0.0872758
As 0.0425 a 1.3574175
a 0.0677
As 2878 mm²/m
As prop. 2805.9 mm²

Mmáx(-) 1196.19 kN-m


M' 281.5 Kn-m/m
Mu 478.5 Kn-m/m
a 23.51 As 0.0604308
As 0.0425 a 1.3574175
a 0.0461
As 1960 mm²/m
As prop. 66.23 mm²

Acero Adicional

M' 66.2 Kn-m/m


Mu 112.6 Kn-m/m
a 23.51 As 0.014219
As 0.0425 a
a 0.0108
As 459 mm²/m
As prop. 502.00 mm²
L
21.50
21.50
21.50

PARA F3:

8.00 m Base 4.25 m


21.50 m Largo 21.50 m

Q COLUMNA Q
500 kN C 450 kN
1500 kN J 1200 kN
1500 kN G 1200 kN
500 kN D 350 kN
4000 kN TOTAL 3200 kN

Presión promedio 31.01 kN/m² Presión promedio


Reacción Total del Suelo 5333 kN. Reacción Total del Suelo
Carga Promedio 4666.7 kN. Carga Promedio
q(prom. modificada) 27.132 kN/m² q(prom. modificada)

Factor de Multiplicación 1.1667 Factor de Multiplicación

Qmod COLUMNA Qmod


583.33 kN 145.83 C 424.22 kN
1750.00 kN 72.916667 J 1131.25 kN
1750.00 kN G 1131.25 kN
583.33 kN D 329.95 kN

ongitud Unitaria de la viga 217.05 kN/m Longitud Unitaria de la viga

F3
V
0
32.45
-359.95
548.65
-497.79
410.81
-635.63
272.97
-32.30
0
F3
M
0
4.06
-495.00
664.56
-289.95
360.15
-1196.19
4.06
0
31.01 kN/m²
2833 kN.
3016.7 kN.
33.014 kN/m²

0.9427

140.31 kN/m