Está en la página 1de 2

Lista de Parámetros Básicos ACS880

Cliente
Aplicación
Modelo
S/N

19: Operation mode


19.12: Ext1 control mode Speed

20: Start/stop/direction
20.01: Ext1 commands Fieldbus A
20.02: Ext1 start trigger type Level

22. Speed reference selection


22.11: Speed ref1 source FB A ref1

50: Fieldbus adapter (FBA)


50.01: FBA A ENABLE Option slot X
50.02: FBA A comm loss func Fault
50.03: FBA A comm loss t out 1
50.04: FBA A ref1 type Speed

51: FBA A settings


51.01: FBA A type PROFIBUS-DP
51.02: Node addres 10
51.03: Baut rate 1500
51.04: MSG type PPO6
51.05: Profile ABB DRIVES
51.06: T16 scale 99
51.08: Map selection 16bit

51.27: FBA A par refresh Refresh


51.31: D2FBA A comm status On-line

52. FBA A data in


52.01: FBA A data in 1 SW 16bit
52.02: FBA A data in 2 Act1 16bit
52.03: FBA A data in 3 10.2[16]
52.04: FBA A data in 4 4.1[16]
52.05: FBA A data in 5 1.7[16]
52.06: FBA A data in 6 1.14[16]
52.07: FBA A data in 7 1.10[16]
52.08: FBA A data in 8
52.09: FBA A data in 9

53.FBA A data out


53.01: FBA data out1 CW 16bit
53.02: FBA data out2 Ref1 16 bit

Nota: Después de culminar con la parametrización, ir al parámetro 51.27 y seleccionar refresh.


Luego el parámetro 51.31 cambia a On-line de manera automática.

Por ABB S.A.: …………………..……..………... Por el Cliente: …...……………..……………...

Fecha: de de 200_

GIVE YOU NEW LIFE TO YOUR DRIVE!