TEST REPORT REFERENCE NO.: PWO 215/13
LOT NO. 00-0/0513/0524, 0-0/0S13/0515, 1-0/0513/0568, 2-0/0513/0490, 3-O/0S1300358
REQUIREMENTS
TABLE 1- Dimension requirements in accordance with EN 60903:2003 & ASTM D120-09.
al Tics
Sie | eee eel ee Sune |
| In Crotch * [Others j
oF - = 030 280 PbO [ical eae
oot | 020 025 075 280 eS a]
0645051 | 1.90] a0 | 360] a8 |
cc a [es ge [mel | sealer ad
ss 27 es 9 es | ome | Os [ae
| ano maa | ase | ao s(n
| snes a sl [cs aon [aad
“inerchhicnes & nninom hick requrenens pind 9 ASTM renee ———|
The permissible variation in length shall be = 13mm for all classes.
< tas mci tikes am apn EN 650.2003 regres ny.
Class 00 maximum thickness 0.75mm applied to ASTM D120-09 requirements only.
TABLE2- AC Voltage requirements proof test current in accordance with EN 60903:2003 &
ASTM D120-09,
| Maximum proof test current **, mA rms ‘Withstand
case | Protest Glove length, mm te votage
of | voltage, aa
gloves | kVims 60 Hz AC Proof test voltage 50 Hz AC Proof test voltage Breakdown
voltage, KV
20 [300 | 0 | 460 | 200 | 30] «0 | a |” om
7
0 50 10 2 “4 | 6 67 10.0 7 13.3 10
7
2 [20 Was | 20a | 33] 150] 167 30
7
#0 wa wa [22 [2a a} 8 [200 90
*NA= Notaplebe
' For AC moisture absorption/proof test current shell not exceed the values specified in Table 2 by more than 2 mA
‘The proof test voltage is higher than the recommended maximum use voltage.
Page | of 6TEST REPORT REFERENCE NO.: PWO 215/13
LOT NO: 00-07/0513/0524, 0-070513/0515, 1-0/0513/0568, 2-0/0513/0490, 3-0/0513/0358
Sample description: Rubber insulating gloves of;
Class 00, 00-WOU-E28Y, Class 0, 00-UOU-E36Y,
Class 1, 00-XOU-E36Y, Class 2, 00-YOU-E36Y &
‘Class 3, 00-MOU-Q41Y
orange has been subjected to dimension measurements, physical properties
test and AC electrical tests at SOHz.
DIMENSIONS
Sampling test results in accordance with EN 60903:2003, clause 8.2.2 and & ASTM D120-09, section 17
Thickness
‘Sample. ength, mm___Palm, mm. Back, mm Crotch, mm
CLASS 00 270-280 0.68 - 0.75 0.68 — 0.74 0.34-0.48
CLASS 0 353 - 368 0.93 -1.01 0.95 -1.01 0.53 -0.69
‘CLASS 1 359-363 132-148 136-145 0.88 = 1.15
CLASS 2 360-365 2.05 -2.29 2.13 -2.29 1.40-2.12
CLASS3 405-410 -2.70-290 275-290 195-224
PHYSICAL PROPERTIES:
‘Sampling test results in accordance with EN 60903:2003, clause 5.2.1 & ASTM D120-09, section 19.2
Results Requirements Status
CLASS 00; Original.
1. Tensile strength, MPa Average: 27 min. 17 PASS
2. Elongation at break, % ‘Average: 993 min, 600 PASS
CLASS 00: Heat-aged for 168 hrs @ 70°C.
1. Tensile strength, % of original (26 MPa) 96% min, 80 PASS
2. Elongation at break, % (95596) 96% min. 80 PASS
Page 2 of 6TEST REPORT REFERENCE NO.: PWO 215/13
LOT NO. 00-0/0513/0524, 0-0/0513/0515, 1-0/0513/0568, 2-0/0513/0490, 3-O/0513/0358.
CLASS 0: Original,
3. Tensile strength, MPa ‘Average: 30 min. 17 PASS
4. Elongation at break, % Average: 1012 min, 600 PASS
CLASS 0: Heat-aged for 168 hrs @ 70°C.
3. Tensile strength, % of original (26 MPa) 87% min, 80 PASS
4. Blongation at break, % (957%) 94% rin, 80 PASS
CLASS 1: Original,
5. Tensile strength, MPa Average: 26 min. 17 PASS
6. Elongation at break, % ‘Average: 928 ‘min, 600 PASS
CLASS 1: Heat-aged for 168 hrs @ 70°C.
5. Tensile strength, % of original (26 MPa) 100% min. 80 PASS
6. Elongation at break, % (951%) 102% min, 80 PASS
CLASS 2: Original,
7. Tensile strength, MPa Average: 24 min, 17 PASS
8. Elongation at break, % Average: 962 ‘min, 600 PASS
CLASS 2: Heat-aged for 168 hrs @ 70°C.
7. Tensile strength, % of original (26 MPa) 108% min, 80 PASS
8. Elongation at break, % (951%) 99% min, 80 PASS:
CLASS 3: Original.
9. Tensile strength, MPa Average: 22 min, 17 PASS
10. Elongation at break, % Average: 915 min. 600 PASS
CLASS 3: Heat-aged for 168 hrs @ 70°C.
9. Tensile strength, % of original (21 MPa) 95% min, 80 PASS
10. Elongation at break, % (818%) 89% min, 80 PASS
Page 3 of 6TEST REPORT REFERENCE NO.: PWO 215/13
LOT NO. 00-0/0513/0524, 0-0/0513/0515, 1-070513/0568, 2-0/0513/0490, 3-O/0S13/0358——
AC PROOF TEST
Sampling test results in accordance with EN 60903:2003, clause 8.4.2 & ASTM D120.09, section 18.4.2
‘The gloves, right side out was filled with tap water and immersed in water to a specified depth from the
cuff. The water level during the test shall be the same inside and outside the glove. A metal rod was
lowered inside the glove as one electrodes and a metal rod placed in the water tank outside the glove as
the other electrode.
A voltage was applied to the electrodes at an increasing rate of 1000V/s until specified voltage for cach
class of glove was reached. The specified voltage was applied for a period of 3 minutes after which the
voltage was lowered to 0 V.
Sample Status
CLASS 00: 2.5 KV, max. leakage allowed 6.7 mA.
19-23 mA PASS
CLASS 0: 5.0 KV, max, leakage allowed 10.0 mA
36-42 mA PASS
CLASS 1: 10.0 KV, max. leakage allowed 11.7 mA.
49-58mA PASS
CLASS 2: 20.0 KV, max. leakage allowed 13.3 mA
5.6-6.0mA PASS
CLASS 3: 30.0 KV, max. leakage allowed 16.7 mA
74-82 mA PASS
AC WITHSTAND TEST / BREAKDOWN TEST
‘Sampling test results in accordance with EN 60903:2003, clause 8.4.2.2 & ASTM D120-09, section.
18.43.
The gloves, right side out was filled with tap water and immersed in water to a specified depth from the
cuff. The water level during the test shall be the same inside and outside the glove. A metal rod was
lowered inside the glove as one electrodes and a metal rod placed in the water tank outside the glove as
* the other electrode, A voltage was applied to the electrodes at an increasing rate of 1000V/s until
specified voltage for each class of glove was reached.
Page 4 of 6TEST REPORT REFERENCE NO.: PWO 215/13
TOT NO. 00-0/0513/0524, 0-O/SI3HSTS, 1-0/0513/0568, 2-070513/0490, 3-0/0513/0358
Applied. V A¢ Status
CLASS 00 S.0KV PASS
CLASS 0 10.0KV PASS
CLASS 1 20.0KV PASS
CLASS 2 30.0KV PASS
CLASS3 40.0KV PASS
AC MOISTURE ABSORPTION / PROOF TEST
‘Sampling test results in accordance with EN 60903:2003, clause 8.4.1 & ASTM D120-09, section 18.4.4.
‘The gloves, right side out was filled with tap water and immersed in water to a specified depth from the
cuft The gloves were soaked for a period of 16 hours. Then, the gloves shall be tested to AC proof test.
‘The voltage was applied to the electrodes at an increasing rate of 1000V/ until specified voltage for each
clase of glove was reached. The specified voltage was applied for a period of 3 minutes after which the
voltage was lowered 10 0 V.
‘Sample sults Status
CLASS 00: 2.5 KV, max. leakage allowed 8.7 mA
23-27mA PASS
CLASS 0: 5.0 KV, max. leakage allowed 12.0 mA
75-91 mA PASS
CLASS 1: 10.0 KV, max. leakage allowed 13.7 mA.
9.5-11.0mA PASS
CLASS 2: 20.0 KV, max. leakage allowed 15.3 mA
71-82 mA PASS
CLASS 3: 30.0 KV, max. leakage allowed 18.7 mA
85-99 mA PASS
Page 5 of 6TEST REPORT REFERENCE NO.: PWO 215/13
LOT NO.: 00-0/0513/0524, 0-0/0513/0515, 1-0/0513/0568, 2-0/0513/0490, 3-0/0513/0358.
AC AGEING FE TEST
‘Sampling test results in accordance with EN 60903:2003, clause 8.5.
‘The gloves shall be place in an air oven for 168 hours at 70°C. Then, the gloves shall be tested to AC
proof test. A voltage was applied to the electrodes at an increasing rate of 1000V/s until specified voltage
for each class of glove was reached. The specified voltage was applied for a period of 3 minutes after
which the voltage was lowered to 0 V.
‘Sample __Results__Status
CLASS 00: 2.5 KV, max. leakage allowed 6.7 mA
23-24mA PASS
CLASS
: 5.0 KV, max. leakage allowed 10.0 mA.
4.0-4.2 mA PASS
CLASS 1: 10.0 KV, max. leakage allowed 11.7 mA
5.0-S8mA PASS
CLASS 2: 20.0 KY, max. leakage allowed 13.3 mA
63-6.6mA PASS
CLASS 3: 30.0 KV, max. leakage allowed 16.7 mA
7.7-8.0mA. PASS
Prepared by: : payee LL Ae
Name: Norwaltida Yusof Name: CBLam
Designation: Senior QA/QC Executive Designation: QA Manager
Page 6 of 6