Está en la página 1de 4

CALCULO DE LA RED DOMICILIARIA DE AGUA POTABLE

TRAMO CAUDAL CAUDAL LONG N N N N LONG LONG J J


INSTALADO MAX PROB DIAM VELOC REAL CODO TEE TEE VALV EQUIV TOTAL UNIT TOT
(l/m) (l/m) (mm) (m/s) (m) DIR LAT/BIL GLO (m) (m) (m/m) (mca)

1-2 164 58.4 32 1.21 7.4 1.0 1.0 1.61 9.01 0.0588 0.53
2-3 144 53.4 25 1.82 7.7 1.0 2.0 3.77 11.47 0.1626 1.87
3-4 75 34.1 19 2.01 1.0 1.0 1.09 2.09 0.2728 0.57
4-5 33 25.0 19 1.47 3.0 1.0 1.0 1.0 6.55 9.55 0.1586 1.51
5-6 15 15.0 19 0.88 2.0 3.0 1.0 6.56 8.56 0.0648 0.56

CELDAS RESALTADAS EN AMARILLO: DATOS QUE DEBE PROPORCIONAR EL USUARIO


PRIMERA COTA PIEZOMETRICA INICIAL = COTA DE TERRENO EN SOLERA FRENTE AL MEDIDOR + PRESIN RED PBLICA (14mca)
LE
PIEZOMET PIEZOMET COTA PRESION
INICIAL FINAL ARTEF DISPONIB
(m) (m) (m) (mca)

114.00 113.47 100.20 13.27


113.47 111.60 100.20 11.40
111.60 111.03 100.20 10.83
111.03 109.52 102.85 6.67
109.52 108.96 104.65 4.31
CALCULO DE LA RED DOMICILIARIA DE AGUA POTABLE CALIENTE
TRAMO CAUDAL CAUDAL LONG N N N N LONG LONG J J
INSTALADO MAX PROB DIAM VELOC REAL CODO TEE TEE VALV EQUIV TOTAL UNIT TOT
(l/m) (l/m) (mm) (m/s) (m) DIR LAT/BIL GLO (m) (m) (m/m) (mca)

1-2 114 45.5 25 1.55 1.5 1.0 1.0 1.0 9.02 10.52 0.0988 1.04
2-3 65 30.9 19 1.82 1.0 1.0 1.09 2.09 0.1848 0.39
3-4 23 23.0 19 1.35 3.0 1.0 1.0 1.0 6.55 9.55 0.1104 1.05
4-5 15 15.0 19 0.88 2.0 3.0 1.0 6.56 8.56 0.0522 0.45

CELDAS RESALTADAS EN AMARILLO: DATOS QUE DEBE PROPORCIONAR EL USUARIO


LIENTE
PIEZOMET PIEZOMET COTA PRESION
INICIAL FINAL ARTEF DISPONIB
(m) (m) (m) (mca)

111.60 110.56 100.30 10.26


110.56 110.17 100.30 9.87
110.17 109.12 102.85 6.27
109.12 108.67 104.65 4.02