ESPECIFICACIN TCNICA
N ALTON08-540-D-ET-ME-01
INDUCED DRAFT FAN
NOMBRE
FIRMA
FECHA
PREPAR
MAYO 2007
REVIS
SERGIO ZUBAREW.
MAYO 2007
APROB
JUAN C. FERNNDEZ R.
MAYO 2007
REV
N
APROBACIN INGENIERO
DESCRIPCIN
Jefe
Disc.
Jefe
Proy.
Fecha
J.M.C.
J.C.F.
MAY. 2007
J.M.C.
J.C.F.
MAY. 2007
J.M.C.
J.C.F.
JUN. 2007
PROYECTO N
ALTON08
APROBACIN CLIENTE
Jefe
Disc.
Jefe
Proy.
Fecha
ARCHIVO N
ALTON08-540-D-ET-ME-01
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
CONTENIDO
1.0
SCOPE ...................................................................................................................... 2
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
GUARANTEES ........................................................................................................ 18
11.0
12.0
ATTACHMENTS
APPENDIX 1
APPENDIX 2
APPENDIX 3
APPENDIX 4
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
1.0
SCOPE
1.1
This Specification covers the design, manufacture and supply of two Induced
Draft Fans, furnished complete to the extent indicated in this specification and
on the attached Data Sheets.
1.2
1.3
Induced Draft Fans shall be complete with accessory equipment and shall
consist of, but not limited to, the following components, as required or specified
in the individual data sheets:
ITEM
N TAG
QTY
DESCRIPTION
Induced Draft Centrifugal fans, including: housing, wheel, shaft,
Special tools and spare parts required for start up for item 1 and 2.
Services
4
of
qualified
personnel
for
supervision
of
erection,
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
ITEM
XSTRATA COPPER
ALTONORTE
N TAG
QTY
DESCRIPTION
Centrifugal Fan Vibration Monitor with local LCD Display; Digital local
configuration
monitor
pushbuttons;
Analogue
output
signal
4 set
Alarm and Trip (DPDT 120 VAC, 5 A Output Contact). For vibration
and temperature high limit.
Four (4) accelerometer transducer one (1) speed sensor; one (1) axial
displace per Fan.
Temperature monitor for centrifugal fan and motor bearings; including
936
4 set
RTD set (4) with RTD channel monitor 4-20 mA analog output signal,
for each channel.
---
10
---
11
---
1.4
1.4.1
Fan inlet.
Outlet flange.
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
1.5
XSTRATA COPPER
ALTONORTE
Work Excluded
Gas ducting.
Earthing.
2.0
2.1
AMCA
ASME
ISO
ANSI
ASTM
CGA
AWS
AGMA
AFBMA
ISA
NEMA
NEC
IEEE
SEC
SSPC
Especificacin Tcnica
For Induced Draft Fan
2.2
XSTRATA COPPER
ALTONORTE
OSHA
MSHA
Should the Bidder be unable to comply with any of the Codes and Standards
above mentioned it shall so state in its proposal and shall provide copies in
English or Spanish, of alternate codes and standards it proposes to use. In
addition it shall provide proof that the applicable portion of the alternate code or
standard it proposes to use is equal, or superior, to the corresponding portions
of the listed codes and standards.
2.3
In the event that the Bidder should encounter a "deviation" between the listed
Codes and Standards (or his proposed Codes and Standards) and this
Specification, he shall attach to its proposal a description of the Codes and
Standards, which the Bidder considers to constitute a "deviation".
Notes Deviations shall be considered and the Buyer according to the merits and
applicability to the Project needs shall establish precedence of one document
over the other.
2.4
If
the
Manufacturer's
interpretations
suggest
conflict
between
this
3.0
OPERATING CONDITIONS
3.1
Induced Draft Fans will be installed in the Altonorte Smelting Plant facilities of
XSTRATA COPPER CHILE S.A., located in Antofagasta, Chile, and are part of
Project Sistema de Captacin y Limpieza de Gases Fugitivos .
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
3.2
XSTRATA COPPER
ALTONORTE
3.3
The manufacturer shall submit the basic calculations procedures used in the
determination of adequate size of fans for the specified operating conditions.
This information shall accompany the Manufacturer's proposal.
3.4
3.4.1
Fans will handle fugitives gases generated by a Noranda furnace and three
Peirce Smith Converters. Entrance gas volumes, pressure and temperature are
included in attached DATA SHEETS.
3.5
All the units and all other component parts of the same function shall be
interchangeable.
3.6
3.7
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
4.0
DESIGN CHARACTERISTICS
4.1
General
4.1.1
The centrifugal fan shall be of the manufacturer's standard heavy duty design,
suitable for the service specified. All equipment and components included in the
supply must be of proven design, modern and reliable prototypes will not be
accepted. Standard replacement parts shall be readily available.
Bidders will provide a full list of similar supplies done for this type of projects, if
this requirement will not be done the quotation could be not considered.
4.1.2
The draft fans shall be a complete unit, ready for erection on foundations
provided by others.
4.1.3
4.1.4
Fans shall be in accordance with the requirements of this specification and the
attached Data Sheet.
4.1.5
Fans shall be designed to minimize the generation of noise and shall comply
with the noise limits as specified in the AMCA Standards N 300-67 Test Code
for Sound Rating and in the data sheets.
4.1.6
4.1.7
For each Centrifugal Fan the supplier shall provide a Vibration and Temperature
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
Four (4) accelerometer transducers per Fan shall be installed in bearing block in
manufacturer facility. Monitoring Modules shall be supply and output signal for
remote monitoring (DCS) (4-20mA) small be included.
4.1.8
For each centrifugal fan a RTD set for bearing block temperature shall be
installed in manufacturer facility. Each RTD shall be send to temperature
monitoring module, output signal 4-20 mA to remote monitoring (DCS) small be
provided.
4.2
Fan Housing
4.2.1
Fan housing shall be provided with standard threaded drain connection, with cap
or plug, in the bottom of the scroll.
4.2.2
4.2.3
4.2.4
A cleaning inspection door shall be provided on the fan housing. The door shall
be gasketed and held in place with quick-release latches.
4.2.5
Suction and discharge connection of the fan shall be flanged and drilled for
bolted connections. The suction shall be of the venturi bell type.
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
4.2.6
XSTRATA COPPER
ALTONORTE
Housing shall be provided with steel clips welded to the outside of the fan
housing and inlet boxes to support Owner's furnished insulation. Vendor shall
recommend non-asbestos type insulation and shall include installation
procedures and necessary drawings for that purpose.
4.3
Fan wheel
4.3.1
4.3.2
Fans shall be of the centrifugal backward wheel type, designed with deep radial
tip blades to insure maximum life due to the abrasive characteristics of the dust
in gases.
Side plates shall be parallel. Side plate inlet ring shall be machined in order to
contribute for high efficiency performance.
The process gas contains dust and there are possibilities of dust build up at the
wheel.
Therefore
it
is
mandatory
to
avoid
internally
and
externally
4.3.3
Fan wheel shall be carbon steel fabrication with minimum thickness of 8 mm.
4.3.4
Fan shall be designed so that the first critical speed shall be at least 1,25 times
the maximum speed of the fan.
INCA S.A.
Ingenieros Consultores
Especificacin Tcnica
For Induced Draft Fan
4.3.5
XSTRATA COPPER
ALTONORTE
The entire fan wheel assembly shall be statically and dynamically balanced at
full operating speed. The balance of the wheel shall be in accordance with the
standards of the Air Moving and Conditioning Association Inc., (AMCA).
4.4
4.4.1
Suitable shaft seals shall be used to prevent gas leakage around the fan shaft.
Seals shall be readily removable and replaceable labyrinth type.
4.4.2
Bearings shall be antifriction, self aligning type with high grade seals, rated for a
life of 100.000 hours as minimum. Bearings shall be full split housing for troublefree assembly and disassembly.
Shaft shall be mounted with at least two independent outboard bearings and
bearings supports.
4.4.3
Fans operating in hot service shall be provided with shaft coolers and
appropriate bearing lubrication systems to suit the specified conditions.
4.4.4
4.4.5
4.4.6
4.4.7
INCA S.A.
Ingenieros Consultores
10
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
4.5
Drive
4.5.1
The fan shall be furnished with direct drive. Nominal fan motor speed is 1.000
rpm and will be with use AC frequency converter M.T.. Motor and AC frequency
converter shall be included.
4.5.2
Vendor shall be responsible for the compatibility of the complete drive train and
its components.
4.5.3
The Vendor shall furnish a common base plate with machine pads for the fan,
drive and pillow blocks. Provision shall be made for moving the shaft pillow
blocks to permit alignment of the wheel.
4.5.4
Each moving part shall be provided with a guard for covering and protecting.
The lubrication guard shall have inspection doors adequate for operation and
maintenance.
5.0
5.1
Motors
The motors shall be designed, manufactured and tested in accordance with the
especification N ALTON08-000-D-ET-EL-06 Rev A.
5.2
For start, stop and speed control are included a frecuency variable control drive,
will be in accordance with the specification N ALTON08-000-D-ET-EL-05-Rev
B.
INCA S.A.
Ingenieros Consultores
11
Especificacin Tcnica
For Induced Draft Fan
5.3
XSTRATA COPPER
ALTONORTE
Monitoring system shall include field sensors for bearing vibration and
temperature sensors and:
Vibration modules with led local indication and analog output signal for
each channel.
Temperature modules with led local indication and analog output signal for
each channel.
Digital Output signal (contact voltage free) for alarm and trip for each channel
and general trip summary signal shall be included.
Electronics modules shall be mounteo in 19 rack that include power supply and
strip terminal block rack and output terminal block shall be mounte in a stand
alone panel nema 12 for local panel control and monitoring fuctions.
6.0
6.1
6.1.1
Vendor shall furnish general arrangement drawings and Catalogs showing the
equipment main components with all their technical characteristics and details.
6.1.2
INCA S.A.
Ingenieros Consultores
12
Especificacin Tcnica
For Induced Draft Fan
6.1.3
XSTRATA COPPER
ALTONORTE
Vendor shall fill out all blank spaces on all Data Sheets attached hereto, as
applicable. Where requested data is inappropriate or inapplicable, or Vendor
cannot comply with it, suitable notations shall be made stating so.
6.1.4
GENERAL
Engineering Schedules
Estimate and Schedule Time for equipment and accessories for erection
and estimated man-hours required for erection. Maximum dimensions and
loads for transporting and erection.
PROCESS
Performance Curves
MECHANICAL
DRIVE
13
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
6.2
6.2.1
The final certified drawing will be in Polyester. Cad drawings will be submitted in
CD.
6.2.2
6.2.3
The following is a detailed list of drawing and document that shall be submitted
after purchase.
INCA S.A.
Ingenieros Consultores
14
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
GENERAL
Engineering Schedules
Specification Lists
Packaging Description
PROCESS
Performance Curves.
MECHANICAL
General arrangements.
Mounting Details.
Material lists.
INCA S.A.
Ingenieros Consultores
15
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
STRUCTURAL
6.2.4
INSTRUMENT
ELECTRICAL
7.0
ENGINEERING SERVICES
7.1
Vendor shall provide all services to manage supervise and coordinate the
design, detailing, fabrication, procurement and supply of the draft fans and
accessory equipment.
16
Especificacin Tcnica
For Induced Draft Fan
8.0
XSTRATA COPPER
ALTONORTE
DELIVERY TIME
9.0
Vendor shall establish an inspection procedure for all items in order to assure
that quality meets standards.
9.1
9.2
Owner reserves the right to have the equipment inspected at any time during the
course of fabrication or construction. Vendor shall notify the Owner at
designated times when inspections can be made.
9.3
17
Especificacin Tcnica
For Induced Draft Fan
9.4
XSTRATA COPPER
ALTONORTE
All pieces of equipment shall be given manufacturer's standard shop tests and
inspections to assure that the product is free from structural and mechanical
defects and is in accordance with design specifications. The Owner shall have
the right to inspect the X-ray films of the welded joints where applicable and
witness other non destructive tests, as dye penetrating, magnetic particle,
ultrasonic, etc.
Vendor shall submit, immediately after his inspection has been performed, a
record of all test procedures and a test report.
9.5
The two weeks trial run after completed installation shall be performed under the
supervision of the Vendor. During the trial run the Vendor's representative shall
train the operating and maintenance personnel of the Purchaser. The number of
men to be provided and the basis of charges for their services shall be stated.
When the plant is in normal operating condition and the timing is agreeable to
both Purchaser and Vendor, a test run shall be performed. The guarantee run
shall be performed after the test run and shall meet the values guarantee on
data sheets.
10.0
GUARANTEES
10.1
All equipment shall be sized and constructed so that the draft fans shall be
capable of operating at full load as set out in this specification and attached Data
Sheets, without being overloaded.
INCA S.A.
Ingenieros Consultores
18
Especificacin Tcnica
For Induced Draft Fan
10.2
XSTRATA COPPER
ALTONORTE
The material used and the quality of work must be first class and shall be
previously approved by the Owner. No re-used materials or components will be
allowed.
10.3
10.4
The Vendor is also responsible for the equipment and materials delivered by his
sub-suppliers.
10.5
The mechanical guarantee shall be 24 months from the approval of test run and
acceptance by the Owner.
10.6
The length of the performance guarantee test will be 48 hr. and following
performance shall be guaranteed:
During that time; the capacity, pressure, power, efficiency, velocity and sound
level of the fans will agree with those figures specified and offered by Vendor.
The Vendor shall decide in good cooperation with the owner the moment when
the 48 hr. performance guarantee test will begin after the Vendor has had the
opportunity to make pretest, which he considers necessary.
10.7
When the first performance guarantee test of 48 hr. does not succeed for
reasons under vendor responsibility, the vendor shall have the right to make
adjustments and start the test again during the one week test period, at his own
expenses.
If guaranteed figures have not been reached during one month test period due
to Vendor's reasons, the Vendor shall make the repairs and adjustments he
INCA S.A.
Ingenieros Consultores
19
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
considers necessary and the date of new capacity guarantee test of 48 hr. shall
be agreed together between vendor and Owner.
11.0
11.1
11.2
All openings in the equipment shall be sealed to exclude foreign matter during
shipment and storage. Pipe couplings shall be provided with pipe plugs or tight
metal caps to protect the threads, and flanges shall be provided with wooden
covers bolted in place to protect the flange face.
11.3
All items shall be provided with adequate lifting lugs to facilitate unloading and
handling prior to erection and shall be properly braced and supported during the
handling and the shipment.
11.4
Subassemblies shall be kept to a minimum. Disassembled units shall be matchmarked for ready reassemble, crated for protection against exposure of damage
in transit or storage, with markings for identification. Uncrating, inspection and
installation instructions shall be included with each crate. Special erection jigs,
or tools, fragile, vulnerable, loose or small parts shall be crated separately with
proper identification and instructions included.
11.5
20
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
sealed thick polyethylene aluminum coated foil bags and the moist air evacuated
and filled with dry air. Bags filled with hygroscopic substance have to be
included inside and a moisture indicator installed on the cover to show the
condition of the packing.
12.0
Vendor shall list and supply all special tools and spare parts required for
erection and start up.
The Vendor shall list spare parts one year operation. The manufacturers
numbers, not by Vendors Numbers, shall identify parts.
INCA S.A.
Ingenieros Consultores
21
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
ATTACHMENT
INCA S.A.
Ingenieros Consultores
22
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
APPENDIX 1
INDUCED DRAFT FAN DATA SHEETS N 1
INCA S.A.
Ingenieros Consultores
23
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
APPENDIX 2
VENDOR DATA REQUIREMENTS.
INCA S.A.
Ingenieros Consultores
24
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
APPENDIX 3
ELECTRICAL MOTOR SPECIFICATION.
INCA S.A.
Ingenieros Consultores
25
Especificacin Tcnica
For Induced Draft Fan
XSTRATA COPPER
ALTONORTE
APPENDIX 4
FRECUENCY CONVERTER SPECIFICATION.
INCA S.A.
Ingenieros Consultores
26