Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.

5 KV; Scenario: NUEVA RESISTIVIDAD]


Page 1

Ground Grid Performance


Report #1:
*******************************************************************************
************************************************
AUTOGRID PRO USER INPUT DATA REPORT
Creation Date/Time:
16 sep 2013/11:50:20
*******************************************************************************
************************************************
---------------------------------------------------------------Input Data Summary Reports
---------------------------------------------------------------System Data Summary
C:\Systems\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA A
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\User Input.rep
Requested Computation Reports and Plots
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA A
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\User Input.rep
---------------------------------------------------------------Graphics option chosen
---------------------------------------------------------------Computation Plots
Touch Voltages
Show All Values
Show Unsafe Values Above Selected Safety Threshold
Step Voltages
Show All Values
Show Unsafe Values Above Selected Safety Threshold
Electric Network Configuration
Soil Resistivity Measurement Interpretation
Fault Current Distribution
Section Span Currents
Shunt Tower Currents
Shunt Tower Potentials
One Terminal Plot
Terminal Number
...................
All Sections Selected

Configuration Plots
Grounding System Configuration
---------------------------------------------------------------Types of plot selected
---------------------------------------------------------------Computation Plots
2D Spot
2D Contour
3D Perspective
Configuration Plots

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 2

3D Perspective
Top View
End of Report #1
Report #2:
*******************************************************************************
************************************************
AUTOGRID PRO SYSTEM INPUT DATA REPORT
Creation Date/Time:
16 sep 2013/11:50:20
*******************************************************************************
************************************************
-----------------------------------------------------------------------------------------------------------------------------Project Summary
-----------------------------------------------------------------------------------------------------------------------------Run Identification .......................... NUEVA RESISTIVIDAD
System of Units ............................. Metric
Radius Measured in .......................... Meters
Frequency ................................... 60 Hz

-----------------------------------------------------------------------------------------------------------------------------Soil Structure (deduce soil structure from field resistivity measurements)


-----------------------------------------------------------------------------------------------------------------------------Measurement method...........................Wenner
Type of measurement..........................Resistance
Probe depth option...........................Account for Probe Depth
Measurement
Number

Spacing S
(Meters)

Apparent
Resistance
R (Ohms)

Depth of
Depth of
Current
Potential
Probes Do
Probes Di
(Meters)
(Meters)
-------------------------------------------------------------------------R1
0.3
850
0
0
R2
1
262.4
0
0
R3
2
123.15
0
0
R4
5
29.7
0
0
R5
7
13.8
0
0
R6
10
8.55
0
0
R7
15
7.2
0
0
R8
30
2.3
0
0

------------------------------------------------------------------------------------------------------------------------------

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 3

Network Fault Current Distribution


-----------------------------------------------------------------------------------------------------------------------------Average soil characteristics along electric lines:
Resistivity(Ohm-m) .......................... 100
Relative Permeability (p.u.) ................ 1
Central site definition:
Name ........................................
Ground Impedance (To be deduced from grounding computations)

-----------------------------------------------------------------------------------------------------------------------------Safety
-----------------------------------------------------------------------------------------------------------------------------Determine Safety Limits for Touch and Step Voltages
Safety Threshold for Touch Voltages ......... 1183.2 V
Safety Threshold for Step Voltages .......... 4138.3 V
Automatic Generation of Observation Points.
---------------------------------------------------------------The computation results are written in the following reports:
---------------------------------------------------------------Soil Resistivity Measurement Interpretation
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Soil Structure.rep
Ground Grid Perfomance
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Ground Grid Performance.rep
Safety Assessment
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Safety.rep
Report for Ampacity Function
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Ampacity.rep
Resistivity Comparison
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Resistivity Comparison.rep
List of Materials
C:\Users\ST02\Desktop\MALLA DE PUESTA A TIERRA 34.5KV\MALLA PUESTA
TIERRA 34.5 KV\NUEVA RESISTIVIDAD\Results\Bill of Materials.rep

A
A
A
A
A
A

End of Report #2
Report #3:
=========< R E S I S T I V I T Y

( SYSTEM INFORMATION SUMMARY ) >=========

Run ID......................................: NUEVA RESISTIVIDAD


System of Units ............................: Meters
Soil Type Selected..........................: Multi-Layer Horizontal
RMS error between measured and calculated...:
11.2231
in percent
resistivities (Note RMS=SQRT(average(Di**2)).

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 4

Layer
Number
======
1
2
3

<--- LAYER CHARACTERISTICS -->


Resistivity
Thickness
(ohm-m)
(Meters)
============== ==============
infinite
infinite
1678.116
2.508663
474.6207
infinite

Reflection
Coefficient
(p.u.)
============
0.0
-1.0000
-0.55905

Resistivity
Contrast
Ratio
============
1.0
0.16781E-16
0.28283

**WARNING** MORE THAN ONE SOIL MODEL CAN PRODUCE SIMILAR APPARENT RESISTIVITY
MEASUREMENT CURVES. IF YOU USE THE DEFAULT STEEPEST-DESCENT
METHOD,
THEN YOU WILL MOST OFTEN OBTAIN DECENT AGREEMENT BETWEEN MEASURED
VALUES AND THE COMPUTED CURVE, WITH A REALISTIC SOIL MODEL;
HOWEVER,
THE FIT MAY OCCASIONALLY BE SUB-OPTIMAL. IN SUCH CASES, THE
MARQUARDT
METHOD WILL USUALLY YIELD AN EXCELLENT FIT, BUT MAY SOMETIMES
SUGGEST
EXTREME RESISTIVITY VALUES. NOTE THAT DIFFERENT SOIL MODELS WILL
USUALLY
YIELD SIMILAR RESULTS FOR YOUR GROUNDING SYSTEM MODELS (I.E., GPR,
TOUCH &
STEP VOLTAGES), PROVIDED THAT THE GROUNDING SYSTEM IS LOCATED
CLOSE TO
THE EARTH SURFACE. IF IN DOUBT, CHECK YOUR RESULTS WITH BOTH SOIL
MODELS.
End of Report #3
Report #4:
****************************************************************
Resistivity Comparison
Creation Date/Time:
16 sep 2013/11:50:21
****************************************************************

Comparison of Measured & Computed Apparent Resistivities


========================================================

POINT
=====
1
2
3
4
5
6
7
8

C1-C2 SPACING
(meters)
=============
0.900000
3.00000
6.00000
15.0000
21.0000
30.0000
45.0000
90.0000

APPARENT RESISTIVITY
MEASURED
COMPUTED
========
========
1602.
1677.
1649.
1642.
1548.
1477.
933.1
865.4
607.0
668.8
537.2
551.8
678.6
500.9
433.5
480.2

DISCREPANCY
Di (percent)
===========
4.66
0.41
4.56
7.25
10.19
2.72
26.18
10.76
=========
Average discrepancy:
8.34%

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 5

RMS ERROR BETWEEN MEASURED AND CALCULATED RESISTIVITIES :


11.22 percent
*NOTE* RMS = SQRT( average(Di**2) )
End of Report #4
Report #5:
****************************************************************
List of Materials
Creation Date/Time:
16 sep 2013/11:50:21
****************************************************************
Interconnection / Bonding Nodes .......................
Extent of Grounding System ............................
Surface Layer Thickness ...............................
Volume of Insulating Layer ............................
Wet Resistivity of Insulating Surface Layer ...........

550
4536 (Square Meters)
10 (Centimeters)
453.6 (Cubic meters)
2500 (Ohm-m)

Grounding System Data


Number of Rods
Length (m)
Diameter (m)
---------------------------------------------------------------10
2.4
0.032258
12
2.4
0.02
Number of Grid Conductors
Length (m)
Diameter (m)
---------------------------------------------------------------2
25
0.0134112
1
10
0.0134112
8
16
0.0134112
26
54
0.0134112
3
9
0.0134112
3
20
0.0134112
11
84
0.0134112
8
58
0.0134112
Total Length of Grid Conductors (m)
Diameter (m)
---------------------------------------------------------------3067
0.0134112
24
0.032258
28.8
0.02

End of Report #5
Report #6:
Date of run (Start) = lunes,16 septiembre 2013
Starting Time = 11:50:21 a.m.

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 6

>>Safety Calculation Table


System Frequency....................................:
System X/R..........................................:
Surface Layer Thickness.............................:
Number of Surface Layer Resistivities...............:
Starting Surface Layer Resistivity..................:
Incremental Surface Layer Resistivity...............:
Equivalent Sub-Surface Layer Resistivity........... .:

60.000(Hertz)
20.000
10.000(cm)
10
2500.0(ohm-m)
100.00(ohm-m)
1678.1(ohm-m)

Body Resistance Calculation.........................:


Body Resistance Exceeded by.........................:
Percent of Hand-to-Hand Resistance..................:
Fibrillation Current Calculation....................:
Foot Resistance Calculation.........................:
User Defined Extra Foot Resistance..................:

IEC
95%
75.000 %
IEEE Std.80-2000 (50kg)
IEEE Std.80-2000
0.0000 ohms

==============================================================================
Fault Clearing Time (sec) |
0.125
|
0.250
|
0.500
|
+----------------------------+---------------+---------------+---------------+
Decrement Factor
|
1.192 |
1.101 |
1.052 |
Fibrillation Current (amps)|
0.328 |
0.232 |
0.164 |
Body Resistance
(ohms)|
719.82 |
756.33 |
796.90 |
==============================================================================
==========================================================================
|
Fault Clearing Time
|
|
Surface |-----------------+-----------------+-----------------| Foot |
Layer |
0.125 sec.
|
0.250 sec.
|
0.500 sec.
| Resist |
Resist |-----------------|-----------------|-----------------| ance |
ivity | Step | Touch | Step | Touch | Step | Touch | 1 Foot |
(ohm-m) |Voltage |Voltage |Voltage |Voltage |Voltage |Voltage | (ohms) |
|(Volts) |(Volts) |(Volts) |(Volts) |(Volts) |(Volts) |
|
==========================================================================
2500.0| 4138.3| 1183.2| 3175.5|
913.4| 2356.9|
682.5| 7156.7|
|---------+--------+--------+--------+--------+--------+--------+--------+
2600.0| 4263.5| 1214.5| 3271.3|
937.4| 2427.9|
700.2| 7384.2|
|---------+--------+--------+--------+--------+--------+--------+--------+
2700.0| 4388.3| 1245.7| 3366.9|
961.3| 2498.6|
717.9| 7610.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
2800.0| 4512.7| 1276.8| 3462.1|
985.1| 2569.1|
735.5| 7836.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
2900.0| 4636.8| 1307.8| 3557.1| 1008.8| 2639.4|
753.1| 8062.1|
|---------+--------+--------+--------+--------+--------+--------+--------+
3000.0| 4760.5| 1338.7| 3651.7| 1032.5| 2709.5|
770.6| 8286.8|
|---------+--------+--------+--------+--------+--------+--------+--------+
3100.0| 4883.8| 1369.6| 3746.2| 1056.1| 2779.4|
788.1| 8510.9|
|---------+--------+--------+--------+--------+--------+--------+--------+
3200.0| 5006.9| 1400.3| 3840.4| 1079.6| 2849.1|
805.5| 8734.5|
|---------+--------+--------+--------+--------+--------+--------+--------+
3300.0| 5129.7| 1431.0| 3934.4| 1103.1| 2918.7|
822.9| 8957.5|
|---------+--------+--------+--------+--------+--------+--------+--------+
3400.0| 5252.3| 1461.7| 4028.2| 1126.6| 2988.2|
840.3| 9180.1|
|---------+--------+--------+--------+--------+--------+--------+--------+
* Note * Listed values account for short duration asymmetric waveform
decrement factor listed at the top of each column.

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 7

End of Report #6
Report #7:

DATE OF RUN (Start)= DAY 16 / Month


STARTING TIME= 11:50:21:39
===========< G R O U N D I N G

9 / Year 2013

( SYSTEM INFORMATION SUMMARY ) >===========

Run ID......................................:
System of Units ............................:
Earth Potential Calculations................:
Type of Electrodes Considered...............:
Soil Type Selected..........................:
SPLITS/FCDIST Scaling Factor................:

NUEVA RESISTIVIDAD
Metric
Single Electrode Case
Main Electrode ONLY
Multi-Layer Horizontal
1.0000

1
1
MULTI-LAYER EARTH CHARACTERISTICS USED BY PROGRAM

LAYER
No.
----1
2
3

TYPE

REFLECTION
COEFFICIENT
------ ------------Air
0.00000
Soil -0.999990
Soil -0.559054

RESISTIVITY
THICKNESS
(ohm-meter)
(METERS)
------------- ------------0.100000E+21
Infinite
1678.12
2.50866
474.621
Infinite

1
CONFIGURATION OF MAIN ELECTRODE
===============================
Original Electrical Current Flowing In Electrode..:
Current Scaling Factor (SPLITS/FCDIST/specified)..:
Adjusted Electrical Current Flowing In Electrode..:
Number of Conductors in Electrode.................:
Resistance of Electrode System....................:
SUBDIVISION
===========
Grand Total of Conductors After Subdivision.:
Total Current Flowing In Main Electrode......:
Total Buried Length of Main Electrode........:

1000.0
1.0000
1000.0
84
3.9025

amperes
ohms

1082
1000.0
3119.8

amperes
meters

EARTH POTENTIAL COMPUTATIONS


============================
Main Electrode Potential Rise (GPR).....:

amperes

3902.5

volts

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 8

End of Report #7
Report #8:
---------------------------------------------------------------Report for Ampacity Function
Creation Date/Time:
16 sep 2013/11:50:21
---------------------------------------------------------------CDEGS Conductor Ampacity Calculation (per IEEE Standard 80)
---------------------------------------------------------------Computation Results
---------------------------------------------------------------Use 250C if mechanical considerations do not allow annealing for the
conductor(e.g., connections of abovegroung conductors), no matter how the
connections are made. Also for pressure type connections if no temperature data
is available:
Minimum Conductor Size:
====================
76.4531 MCM
38.7300 mm
0.1382 in (radius)
3.5112 mm (radius)
Use 450C for brazed conductors:
Minimum Conductor Size:
====================
61.6733 MCM
31.2428 mm
0.1242 in (radius)
3.1536 mm (radius)
Other temperatures may apply for pressured type conductors
Use fusing temperature of conductor otherwise (e.g., direct-buried conductors
with exothermic welded joints):
1083.0000 C (fusing temperature)
Minimum Conductor Size:
====================
47.8421 MCM
24.2361 mm
0.1094 in (radius)
2.7776 mm (radius)
Input Data:
====================
Symmetrical RMS Current Magnitude: 9.4 kA
Maximum Fault Duration: 0.5 s
Ambient Temperature: 20 C
Conductor Type: Copper, annealed soft drawn (100% conductivity)
Decrement Factor: 1.0517

Auto Grid Pro [Project: MALLA PUESTA A TIERRA 34.5 KV; Scenario: NUEVA RESISTIVIDAD]
Page 9

X/R: 20
Frequency: 60 Hz
Material Constants of Conductor:
====================
Name: Copper, annealed soft drawn (100% conductivity)
Reference Temperature for Material Constants: 20 C
Thermal Coefficient of Resistivity at Reference Temperature: 0.00393 1/C
Fusing Temperature of Conductor: 1083 C
Resistivity of Conductor at Reference Temperature: 1.72 mWcm
Thermal Capacity per Unit Volume: 3.42 J/cm C
---------------------------------------------------------------End of Report #8