Documentos de Académico
Documentos de Profesional
Documentos de Cultura
CFE CA-MT101
200
6
1000
15
15 ACOMETIDA CFE
11 12 13 3 9 10 4 5
1 2
LIMITE P RO PIED AD
BA N QU ET A O A RR O YO D E LA C ALLE
DIAGRAMA UNIFILAR
CFE
LOCALIZACIN
LINEA DE C F E
POSTE CFE
NOTAS.
1.-LOS MATERIALES QUE CONSTITUYEN LA ACO METIDA SE REPRESENTAN CON UNA LNEA PUNTEADA. 2.- EN ACOMETIDAS CUYA LONG ITUD SEA SUPERIOR A 5 m DENTRO DE LA PROPIEDAD DEL SOLICITANTE, CFE SLO PROPORCIONAR HASTA 5 m DENTRO DE DICHA PROPIEDAD, EL RESTO EST A CARG O DEL SOLICITANTE. 3.- LOS ELEMENTO S ELECTRO MEC NICOS (AISLADORES, HERRAJES ETC.) PARA LA RECE PCI N DE LA ACOMETIDA SERN A CARGO DEL S OLICITANTE.
SIN ESCALA
00 11 10
04 03 31 REV.
CFE CA-MT101
NUM. UNIDAD
MATERIALES Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE 6 7 8 9 10 11 12 13 14 15 PZA. PZA. PZA. PZA. PZA. PZA. PZA. PZA. PZA. Kg. Perno DR 16x457 Ojo RE Moldura RE Cruceta PT 200 Cruceta PT 250 Cortacircuitos fusible CCF 15- 100-110- 8000 Cortacircuitos fusible CCF 27-100-150-6000 Cortacircuitos fusible CCF 38-100-200-2000 Conector lnea viva LV13 Alambre CU 4 4 2 1 2 3 3 3 1 3 1 3 3 1 4 2 1 2 4 2 1 2
NOTAS: (*) El servicio se identificar mediante una Placa con dimensiones de 300x100 mm, la cual debe pintarse en color amarillo, con leyendas negras. (1) CFE definir el poste del cual se proporcionar la acometida, en caso de no existir, su instalacin ser con cargo al solicitante. (2) El equipo de medicin debe localizarse en el lmite de propiedad del solicitante. (3) En casos especiales de carga o valor de corto circuito, se establecer el calibre de conductor, as como el equipo de proteccin y de seccionalizacin adecuado. (4) Las retenidas no se incluyeron en la estructura, debiendo considerarlas en caso necesario, con cargo al solicitante. (5) Esta especificacin aplica tambin para los servicios que se encuentren en la misma acera del poste de CFE.
00 11 10
04 03 31 REV.
CFE CS-MT101
LMITE DE PROPIEDAD
11
8 5 6
ARROYO DE LA CALLE
ACOMETIDA
10 7 3 7
EMPOTRAMIENTO SEGN NORMA CFE 030004
1 2
5 m MXIMO
DIAGRAMA UNIFILAR
LOCALIZACIN
NOTAS.
1.- LOS MATERIALES QUE CONSTITUYEN LA ACOMETIDA SE REPRESENTAN CON UNA LNEA PUNTEADA. 2.- HASTA 10 m DE ACOMETIDA SERN CON CARGO A CFE, DE REQUERIRSE MAYOR LONGITUD, LA DIFERENCIA SER CON CARGO AL SOLICITANTE. 3.- LOS ELEMENTOS ELECTROMECNICOS (TERMINALES, SOPORTES, ETC.) PARA LA RECEPCIN DE LA ACOMETIDA SERN A CARGO DEL SOLICITANTE. 4.- LA OBRA CIVIL NECESARIA PARA LA INSTALACIN DE LA ACOMETIDA, SER CONSTRUIDA POR EL SOLICITANTE.
SIN ESCALA
00 11 10
04 03 31 REV.
CFE CS-MT101
NUM. UNIDAD
DESCRIPCIN CORTA
MATERIALES PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DE CFE: 1 m Cable AL (1/0)-XLP 30 30 30 2 Kg. Cable CU 2 2 2 2 3 Kg. Cable de cobre Cu 8 3 3 3 Indicador de falla 200 4 PZA. 3 3 3 MATERIAL Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE 5 PZA. Fusible tipo codo FI-200 3 3 6 PZA. Conectador tipo codo MT 200-OCC 3 3 7 PZA. Adaptador 200 (para aterrizar pantallas) 6 6 8 PZA. Conectador tipo mltiple MT-200-OCC 2 3 3 9 PZA. Registro de media tensin 1 1 10 m Banco de ductos para media tensin 10 10 11 PZA. Boquilla estacionaria sencilla MT-200 3 3
3 3 6 3 1 10 3
NOTAS: CFE definir el poste del cual se proporcionar el servicio, en caso de no existir, su instalacin ser con cargo al solicitante. (2) El equipo de medicin debe localizarse en el lmite de propiedad del solicitante. (3) En casos especiales de carga o valor de corto circuito, se establecer el calibre de conductor, as como el -equipo de proteccin y de seccionalizacin que resulte adecuado. (4) La obra especifica entre el punto de conexin y el registro de la acometida son cargo al solicitante (1)
00 11 10
04 03 31 REV.
CFE CS-MT101B
8 9 12 13 14 25 15 16 17 7 1 2 3 26 11
5 4
LMITE DE PROPIEDAD
10
ACOMETIDA
24
22 21 20
23 9
18
EMPOTRAMIENTO
5m
19
DIAGRAMA UNIFILAR
LOCALIZACIN
SOLICITANTE
CFE
SOLICITANTE
CFE
LMITE DE PROPIEDAD
LMITE DE PROPIEDAD
NOTAS.
1.- LOS MATERIALES QUE CONSTITUYEN LA ACOMETIDA SE REPRESENTAN CON UNA LNEA PUNTEADA. 2.- 20 m DE ACOMETIDA SERN CON CARGO A CFE, DE REQUERIRSE MAYOR LONGITUD, LA DIFERENCIA SER CON CARGO AL SOLICITANTE. 3.- LOS ELEMENTOS ELECTROMECNICOS (TERMINALES, SOPORTES, ETC.) PARA LA RECEPCIN DE LA ACOMETIDA SERN A CARGO DEL SOLICITANTE. 4.- LA OBRA CIVIL NECESARIA PARA LA INSTALACIN DE LA ACOMETIDA, SER CONSTRUIDA POR EL SOLICITANTE. 5.- ESTA ESPECIFICIN ES APLICABLE CUANDO LA LONGITUD ENTRE LA ESTRUCTURA DE TRANSICIN Y EL LMITE DE PROPIEDAD NO SEA MAYOR DE OCHO METROS
SIN ESCALA
00 11 10
04 03 31 REV.
CFE CS-MT101B
MATERIALES PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DE CFE: 1 PZA Terminal MT premoldeada 15-1/0 3 2 PZA Terminal MT premoldeada 25-1/0 3 3 PZA Terminal MT premoldeada 35-1/0 3 4 m Cable AL(1/0)- XLP 60 60 60 5 Kg. Cable Cu 2 4 4 4 6 Kg. Cable de cobre Cu 8 1 1 1 7 PZA Conector zapata a compresin 3 3 3 MATERIAL Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE Conector lnea viva LV13 8 PZA 3 3 3 9 Kg. Alambre de Cu 4 2 2 2 10 PZA Sello cinta termocontractil 1 1 1 11 PZA Perno DR 16x457 4 4 4 12 PZA Apartarrayo ASOM-II-25-10 3 13 PZA Apartarrayo ASOM-II-25-18 3 14 PZA Apartarrayo ASOM-II-25-21 3 Cortacircuitos fusible CCF 15- 100-110- 8000 15 PZA 3 Cortacircuitos fusible CCF 27-100-150-6000 16 PZA 3 Cortacircuitos fusible CCF 38-100-200-2000 17 PZA 3 18 PZA Conectador MET-16 1 1 1 19 PZA Electrodo para tierra ACE-16 1 1 1 20 PZA Registro de media tensin 1 1 1 m Banco de ductos para media tensin 21 20 20 20 22 m Fleje de acero 3 3 3 23 PZA Grapa para fleje 3 3 3 24 PZA Tubo conduit de 101,6 mm de dimetro 9 9 9 25 PZA Cruceta PT 200 2 2 26 PZA Cruceta PT 250 2 NOTAS: (*) (1) El servicio se identificar mediante una Placa con dimensiones de 300x100 mm, la cual debe pintarse en color amarillo, con leyendas negras.
CFE definir el poste del cual se proporcionar la acometida, en caso de no existir, su instalacin ser con cargo al solicitante. (2) El equipo de medicin debe localizarse en el lmite de propiedad del solicitante. (3) En casos especiales de carga o valor de corto circuito, se establecer el calibre de conductor, as como el -equipo de proteccin y de seccionalizacin que resulte adecuado.
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON EQUIPO TIPO PEDESTAL PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT102
E S Q U E M A F S IC O (V IS T O D E P E R F IL )
S E C C IO N A D O R C O N V A (S ) P R O T E G ID A(S )
G A B IN E T E
T C 'S Y TP 'S
BANQ U ETA9 O JA R D IN 1 1
8
S U B E S T A C I N P A R T IC U LA R
A C O M E T ID A AN ILLO D E C .F .E .
4 3
R E G IS T R O
5 m
D IA G R A M A U N IF ILA R
LO C A LIZ A C I N
11
LN E A D E C F E
S
1 6
A C O M E TIDA
10
F1 F2 F3
10
F1 F2 F3
11 4
LM IT E D E P R O P IE D A D
S E C C IO N A D O R
12
1 2 6
EM
LM IT E D E P R O P IE D A D
TC TP
EM
NOTAS.
A L A S .E . P A R T ICU LA R
1 .- L O S M A T E R IA L E S Q U E IN C L U Y E N L A A C O M E T ID A S E R E P R E S E N T A N C O N U N A L N E A P U N T E A D A . 2 .- E L E Q U IP O D E S E C C IO N A M IE N T O P R IM A R IO C O N P R O T E C C I N S E R IN S T A L A D O D E A C U E R D O A L A S N E C E S ID A D E S D E L A C A R G A P O R E L S O L IC IT A N T E Y C E D ID O A C F E . 3 .- H A S T A 1 0 m D E A C O M E T ID A S E R N C O N C A R G O A C .F .E ., D E R E Q U E R IR S E M A Y O R L O N G IT U D , L A D IF E R E N C IA S E R C O N C A R G O A L S O L IC IT A N T E . 4 .- L O S E L E M E N T O S E L E C T R O M E C N IC O S (T E R M IN A L E S , S O P O R T E S , E T C .) P A R A L A R E C E P C I N D E L A A C O M E T ID A S E R N A C A R G O D E L S O L IC IT A N T E . 5 .- L A O B R A C IV IL N E C E S A R IA P A R A L A IN S T A L A C I N D E L A A C O M E T ID A , S E R C O N S T R U ID A P O R E L S O L IC IT A N T E .
S IN E S C ALA
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON EQUIPO TIPO PEDESTAL PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT102
NUM. UNIDAD
DESCRIPCIN CORTA
13 23 33 MATERIALES PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DE CFE: Conectador tipo codo MT 200-OCC 1 PZA 3 3 3 Adaptador 200 (para aterrizar pantallas) 2 PZA 3 3 3 Cable CU 2 3 Kg 2 2 2 Cable AL (1/0)-XLP 4 m 30 30 30 5 kg Cable de cobre Cu 8 1 1 1 Indicador de falla 200 6 PZA 3 3 3 MATERIAL Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE Banco de ductos para media tensin 7 m 10 10 10 8 9 10 11 12 NOTAS: (1) El equipo de medicin debe localizarse en el lmite de propiedad del solicitante. PZA PZA PZA PZA PZA Base para seccionador y registros Conectador tipo codo MT 200-OCC Adaptador 200 (para aterrizar pantallas) Indicador de falla 200 Seccionador en SF6 con proteccin electrnica 1 6 6 3 1 1 6 6 3 1 1 6 6 3 1
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON EQUIPO TIPO SUMERGIBLE PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT103
3000
1600
9 11
F1 F2 F3
1 10
6
F1 F2 F3
SUBESTACIN PARTICULAR
5
SECCIONADOR
4 3
REG ISTRO
ACOMETIDA
5m
DIAGRAMA UNIFILAR
LOCALIZACIN
A LA S.E.
TC TP
E.M.
EM
11 6
LM ITE DE PROPIEDAD
BVEDA
ACOMETIDA
LNEA DE CFE
9
4 11 10
F1 F2 F3
S
Seccionador sumergible en SF 6 con proteccin electrnica intercalado en la red existente. 12
LMITE DE PROPIEDAD
9 1 2 6
F1 F2 F3
5 7
SECCIO NADOR
NOTAS.
1.- LOS MATERIALES QUE INCLUYEN LA ACOMETIDA SE REPRESENTAN CON UNA LNEA PUNTEADA. 2.- EL EQUIPO DE SECCIONAMIENTO PRIMARIO CON PROTECCIN SER INSTALADO DE ACUERDO A LAS NECESIDADES DE LA CARGA POR EL SOLICITANTE Y CEDIDA A CFE. 3.- HASTA 10 m DE ACOMETIDA SERN CON CARGO A C.F.E., DE REQUERIRSE MAYOR LONGITUD, LA DIFERENCIA SER CON CARGO AL SOLICITANTE. 4.- LOS ELEMENTOS ELECTROMECNICOS (TERMINALES, HERRAJES, ETC.) PARA LA RECEPCIN DE LA ACOMETIDA SERN A CARGO DEL SOLICITANTE. 5.- LA OBRA CIVIL NECESARIA PARA LA INSTALACIN DE LA ACOMETIDA, SER CONSTRUIDA POR EL SOLICITANTE. SIN ESCALA
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON EQUIPO TIPO SUMERGIBLE PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT103
NUM. UNIDAD
DESCRIPCIN CORTA
MATERIALES PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DE CFE Conectador tipo codo MT 200 A OCC 1 PZA 3 3 3 Adaptador 200 (para aterrizar pantallas) 2 PZA 3 3 3 Cable CU 2 3 Kg. 2 2 2 Cable AL (1/0)-XLP 4 m 30 30 30 5 Kg. Cable de cobre Cu 8 1 1 1 Indicador de falla 200 6 PZA 3 3 3 MATERIAL Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE Bveda para seccionador 7 PZA 1 1 1 Banco de ductos para media tensin 8 m 10 10 10 Conectador tipo codo MT 200-OCC 9 PZA 6 6 6 Adaptador 200 (para aterrizar pantallas) 10 PZA 6 6 6 Indicador de falla 200 11 PZA 3 3 3 12 PZA Seccionador en SF6 con proteccin electrnica 1 1 1
NOTAS:
(1)
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON CONECTORES MLTIPLES PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT104
3000
1600
12
9 10 5 10
LMITE DE PROPIEDAD
3 6 4 6 10
5m REGISTRO
ACOMETIDA
11 2
DIAGRAMA UNIFILAR
TRANSFORMADOR PARTICULAR
12
10
(J-3)
5
3 3 11
11
RED DE C.F.E. (ANILLO SUBT.)
1
RED DE C.F.E. (ANILLO SUBT.) ACOMETIDA A SUBESTACIN PARTICULAR
5 10
NOTAS.
1.- LOS MATERIALES QUE INCLUYEN LA ACOMETIDA SE REPRESENTAN CON UNA LNEA PUNTEADA. 2.- 5 m DE ACOMETIDA SERN CON CARGO A C.F.E., DE REQUERIRSE MAYOR LONGITUD, LA DIFERENCIA SER CON CARGO AL SOLICITANTE. 3.- LOS ELEMENTOS ELECTROMECNICOS (TERMINALES, SOPORTES, ETC.) PARA LA RECEPCIN DE LA ACOMETIDA SERN A CARGO DEL SOLICITANTE 4.- LA OBRA CIVIL NECESARIA PARA LA INSTALACIN DE LA ACOMETIDA, SER CONSTRUIDA POR EL SOLICITANTE. SIN ESCALA ACOTACIONES EN mm
00 11 10
04 03 31 REV.
ACOMETIDA SUBTERRNEA CON CONECTORES MLTIPLES PARA SERVICIO TRIFSICO EN MEDIA TENSIN
CFE CS-MT104
NUM. UNIDAD
CANTIDAD: (Tensin kV) 13 23 33 MATERIALES PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DE CFE 1 m Cable AL (1/0)-XLP 15 15 15 2 kg Cable CU 2 2 2 2 3 kg Cable de cobre Cu 8 3 3 3 Indicador de falla 200 4 PZA 3 3 3 DESCRIPCIN CORTA MATERIAL Y EQUIPO PARA LA INSTALACIN DE LA ACOMETIDA A CARGO DEL SOLICITANTE 5 6 7 8 9 10 11 12 PZA PZA PZA PZA m PZA PZA PZA Fusible tipo codo FI-200 Adaptador 200 (para aterrizar pantallas) Conectador tipo mltiple MT-200-OCC 3 Registro de media tensin Banco de ductos para media tensin Conectador tipo codo MT 200 A OCC Indicador de falla 200 Boquilla estacionaria sencilla MT-200 3 6 3 1 5 6 3 3 3 6 3 1 5 6 3 3 3 6 3 1 5 6 3 3
NOTAS: (1) El equipo de medicin debe localizarse en el lmite de propiedad del solicitante (2) Este tipo de acometidas ser utilizado para servicios con cargas hasta de 500 kW en un nivel de tensin de 13.8 kV, 800 kW para 23 kV, y 1200 kW para 33 kV.
00 11 10