Está en la página 1de 2

DOCUMENTO BASE DE INGENIERA

HOJA DE DATOS RTD

Cdigo:

R-116

Pgina:

1 de 2

Revisin:

Tipo de
documento:

Registro

NOMBRE DEL PROYECTO:

REINGENIERA DE TRASLADO Y MONTAJE DEL SISTEMA DE REGULACIN Y MEDICIN DE GAS


N PROYECTO:

DOCUMENTO N:

PSTSC-PR-032-13

PST-03213-SCZ-PL-DI-HD-003

NDICE DE REVISIONES
REV.

DESCRIPCIN

REVISIN Y APROBACIN DEL CLIENTE

APROBADO PARA CONSTRUCCIN

Fecha:

Rev. A

Rev. 0

20/03/13

15/04/13

Preparado por:

J.Guerrero

J.Guerrero

Revisado por:

G. Montao

G. Montao

Aprobado por:

ADM SAO

ADM SAO

REA:

PLANTA ADM SAO

REV:

N:
ADM SAO S.A.
PROYECTO:

PST-03213-SCZ-PL-DI-HD-003

REINGENIERA DE TRASLADO Y MONTAJE DEL SISTEMA DE


REGULACIN Y MEDICIN DE GAS

0
HOJA:

2 de 2

TITULO:

HOJA DE DATOS RTD

PROCESS DATA

GENERAL DATA

TAG NUMBER

SITE

QUANTITY

LOCATION

SERVICE

6
7

MANUFACTURER
MODEL

P&ID NUMBER

FLUID

10

FLOW (Nm3/Hra)

11

PRESSURE (Psig)

TE-1102 TW-1102
Planta ADM SAO
2
4"-.0.237-B(G-1)-1008
4"-0.237"-B(G-1)-1009
Temperature Measurement
Rosemount
1067

PST-03213-SCZ-PL-PP-PR-001
Gas
MAXIMUM
NORMAL

3050
-

MINIMUM

1160

MAXIMUM

OPERATING

148

MINIMUM

80

MAXIMUM

95

NORMAL

77

12

TEMPERATURE
(F)

13

SPECIFIC GRAVITY RANGE

14

16

ACCURACY
PROCESS TEMPERATURE SENSOR RANGE
(F)
TYPE

RTD

TW

17

CONNECTION

3/4"

3/4"

18

MATERIAL

Platinum

SS316

19

LENGTH

STD

(U) 2.5"

20

MOUNTING

In Line

21

WIRE CONNECTION

4 Wire

22

CONDUIT CONNECTION

23

CLASSIFICATION

24

EXPLOSION PROOF

25

TAGGING

26

CALIBRATION

MINIMUM

SPECIFICATION

15

OTHER

1097

60
0,62
0,1 C
320,8 ... 1112 F

1/2" NPT
IP 66
Required
SS 316
Required

Reference Documents:

PST-03213-SCZ-PL-PP-PR-001 P&ID del Sistema de Medicin y Regulacin


Notes:
1) Vendor must include a Certificate of Conformance
2) Vendor must include catalogues
3) Vendor must include certificate of hazardous locations Class I, Division 1, Groups C & D, Explosion Proof.

Sistema de Gestin de Calidad