Está en la página 1de 15

INVESTIGACIN-Power & Energy Society - UNI

Reporte Grupo de Investigacin PES UNI


Tema principal de Investigacin:
Calidad de Energa Contaminacin debido a Desbalance de Voltaje.

1. GRUPO DE TRABAJO
Asesor: Ing. Bautista Ros, Juan Pablo
Investigadores:

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

2. LUGAR DE TRABAJO Y HORARIOS

Sala de Investigacin REIEEE UNI.


Residencia del joven Jorge Luis Cabrera

Sab. 8 12am
Vie 7pm Sab 8am

4 Sesiones
2 Sesiones

3. AUTOCAPACITACIONES REALIZADAS DENTRO DEL GRUPO.

Introduccin al DIgSILENT Program Language.


Introduccin a los Algoritmos Genticos.

4. HISTORIA DEL ARTE.


1.-A Robust Voltage Unbalance Allocation Methodology Based on the IEC/TR 61000-3-13 Guidelines - P.
Paranavithana
2-Propagation of Unbalance in Electric Power Systems - M. Chindri, A. Cziker, Anca Miron, H.Blan
3-Assessment of Voltage Unbalance - Annette von Jouanne
4-Discussions and Closures: Discussion of Assessment of Voltage Unbalance1 - R. C. Bansal, T. S. Bhatti,
and D. P. Kothari
5-On the Assessment of Voltage Unbalance - T. E. Seiphetlho, and A. P. J. Rens
6-A Review of Recent Investigations with Reference to IEC/TR 61000-3-13 on Voltage Unbalance
Emission Allocation - Prabodha Paranavithana
7-A Systematic Approach Towards Evaluating Voltage Unbalance Problem in Interconnected
Sub-transmission Networks: Separation of Contribution by Lines, Loads And Mitigation - Prabodha
Paranavithana
8-NORMA: IEC/TR 61000-3-13 - TECHNICAL REPORT Electromagnetic compatibility (EMC) Part 3-13:
Limits Assessment of emission limits for the connection of unbalanced installations to MV, HV and EHV
power systems

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


10- Artculo de algoritmos genticos
11-Analysis of Network Asymmetry of Interconnected 66kV Sub-transmission Systems in relation to
Voltage Unbalance - Prabodha Paranavithana, Sarath Perera and Danny Sutanto
12-Artculo de componentes simtricas
13-Location of Sources of Voltage Unbalance in an Interconnected Network - P. Paranavithana

5. CONCLUSIONES TERICAS.
La contaminacin de DV se da en todo nivel de tensin.
Los transformadores generan desbalance de voltaje debido a su tipo de conexin.
Las lneas de transmisin, por su asimetra, generan altos niveles de DV, con cargas
balanceadas.
Las cargas, monofsicas, bifsicas generan niveles de DV muy altos, con lneas
perfectamente transpuestas.
Existen niveles de DV usados en planeamiento, mencionados en la norma IEC/TR 61000-313.
Para lneas de transmisin, su nivel de DV con el que contribuye en el sistema depende ms
del punto de operacin en el que se encuentra la lnea, que de su impedancia mutua en
secuencia positiva y negativa.
Este grupo no se encuentra de acuerdo con lo propuesto por la Dra. Paranavithana, respecto
al desbalance por cargas. El grupo propuso dos mtodos distintos para hallar la contribucin
de cada carga al DV del sistema.

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


6. CONCLUSIONES PRCTICAS.
RESULTADO PRACTICO 1
Estudio de Desb. Voltaje en la linea Chilca Carabayllo 500kV
Estacin en Anlisis: Avenida mnima 2012

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Se recre el sistema con redes externas que son acordes al nivel de Corto circuito de cada barra a
la cual representa.
Asi mismo, la lnea Chilca_Carabayllo 500kV se model con el tipo de torre:

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI

El modelado de los conductores se muestra tal:

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


La disposicin geomtrica de las fases se muestra tal como:

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Se puede observar, que las matrices de resistencias y reactancias son NO TRIANGULARES, como
resultado de no tener transposicin esta lnea.

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


RESULTADOS
Del flujo de carga trifsico, se puede obtener el aporte de DESBALANCE DE VOLTAJE que
aporta la lnea Chilca_Carabayllo 500kV a cada una de las barras del sistema:

Barra

U1 - kV

U2 - kV

U0 kV

VUF%

Chilca_220
Chilca_Nueva_220
Chilca_500
Carabayllo_500
Zapallal_Nueva_220
Planicie_220
Zapallal_220
Orcotuna_220

127.017
127.017
292.342
292.074
127.51
127.442
127.059
127.298

0.128
0.128
0.645
0.63
0.161
0.143
0.139
0.046

0.095
0.095
0.061
0.076
0.029
0.065
0.019
0.003

0.100773912
0.100773912
0.220632
0.215698761
0.126264607
0.112207906
0.109397996
0.036135682

VUF%
0.25
0.2
0.15
0.1
VUF%
0.05
0

CONCLUSIN
Esta lnea de transmisin, aporta un considerable nivel de desbalance, pero no lo suficiente para
poder considerarlo peligroso o daino para la red de transmisin. Sin embargo, se debe realizar el
anlisis cuando la lnea de transmisin tenga mayor cargabilidad y asi mismo, cuando se hayan
construido los dems proyectos de 500kV.
Asesor: Ing. Bautista Ros, Juan Pablo
-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


RESULTADO PRACTICO 2
Se cre un sistema de distribucin de 22.9kV, en el cual se sometera a prueba dos propuestas del
grupo para hallar la contribucin de desbalance de voltaje por cada una de las cargas.
A continuacin se presentan los datos correspondientes a la red:

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Se tiene la siguiente informacin de cargas.
Ph
1:Act.Pow.
MW
0.5
0
0.8
0.3
0
0.5

Ph
1:React.Pow.
Mvar
0.1643421
0
0.98
0.97
0
0.1976127

Ph
1:App.Pow.
MVA
0.5263158
0
1.265069
1.015332
0
0.5376344

Ph 1:I
kA
0.03980811
0
0.09568402
0.07679509
0
0.0406642

Ph
1:Pow.Fact.

Ph
1:cos(phi)

0.95
0
0.6323764
0.2954697
0
0.9299999

ind.
ind.
ind.
ind.
ind.
ind.

Ph
2:Act.Pow.
MW
0
0.7
0.8
0.9
0
0.5

Ph
2:React.Pow.
Mvar
0
0.93
0.98
0.97
0
0.1976127

Ph
2:App.Pow.
MVA
0
1.164002
1.265069
1.323216
0
0.5376344

Ph 2:I
kA
0
0.08803974
0.09568402
0.100082
0
0.0406642

Ph
2:Pow.Fact.

Ph
2:cos(phi)

0
0.6013737
0.6323764
0.6801611
0
0.9299999

ind.
ind.
ind.
ind.
ind.
ind.

Ph
3:Act.Pow.
MW
0
0
0.8
0
0.3
0.5

Ph
3:React.Pow.
Mvar
0
0
0.98
0
0.08750007
0.1976127

Ph
3:App.Pow.
MVA
0
0
1.265069
0
0.3125
0.5376344

Ph 3:I
kA
0
0
0.09568402
0
0.02363607
0.0406642

Ph
3:Pow.Fact.

Ph
3:cos(phi)

0
0
0.6323764
0
0.9599999
0.9299999

ind.
ind.
ind.
ind.
ind.
ind.

Respecto a los datos de lneas de transmisin, se consideraron perfectamente transpuestas y no


tienen ninguna influencia en los resultados de desbalance de tensin.

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Mtodo de Carga Solitaria
VUF% -Original
U1
Ang U1
U2
Ang U2

Subestacin
13.221
0
0.297
1.413

Nodo1
13.023
0.149
0.323
-3.551

Nodo2
12.835
0.316
0.352
-6.011

Nodo3
12.672
0.453
0.357
-7.442

Nodo4
12.586
0.494
0.361
-8.837

Nodo5
12.546
0.446
0.356
-8.292

Nodo6
12.512
0.408
0.356
-8.289

VUF%
Ang VUF% -Degrees

2.24642614
1.413

2.48022729
-3.7

2.742500974
-6.327

2.817234848
-7.895

2.868266328
-9.331

2.837557787
-8.738

2.845268542
-8.697

U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0.087
-54.419
0.658044021
-54.419
-0.949790709
0.382885096
-0.535183087

Nodo1
13.221
-0.014
0.094
-59.384
0.710990092
-59.37
-1.036201959
0.362243795
-0.61178946

Nodo3
13.221
-0.015
0.094
-59.385
0.710990092
-59.37
-1.036201959
0.362243795
-0.61178946

Nodo4
13.221
-0.016
0.094
-59.385
0.710990092
-59.369
-1.036184506
0.362254473
-0.611783137

Nodo5
13.221
-0.016
0.094
-59.385
0.710990092
-59.369
-1.036184506
0.362254473
-0.611783137

Nodo6
13.221
-0.016
0.094
-59.385
0.710990092
-59.369
-1.036184506
0.362254473
-0.611783137

U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0.195
30.815
1.474926254
30.815
0.5378232
1.266704749
0.755557101

Nodo1
13.198
0.032
0.212
25.85
1.606303985
25.818
0.450609099
1.445965932
0.699567737

Nodo3
13.175
0.064
0.23
21.64
1.74573055
21.576
0.376572233
1.623408269
0.641966312

Nodo4
13.175
0.064
0.23
21.64
1.74573055
21.576
0.376572233
1.623408269
0.641966312

Nodo5
13.176
0.063
0.23
21.639
1.745598057
21.576
0.376572233
1.62328506
0.64191759

Nodo6
13.176
0.063
0.23
21.639
1.745598057
21.576
0.376572233
1.62328506
0.64191759

U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0
0
0
0
0
0
0

Nodo1
13.145
0.09
0
0
0
-0.09
-0.001570796
0
0

Nodo3
12.993
0.274
0
0
0
-0.274
-0.004782202
0
0

Nodo4
12.993
0.274
0
0
0
-0.274
-0.004782202
0
0

Nodo5
12.993
0.274
0
0
0
-0.274
-0.004782202
0
0

Nodo6
12.993
0.274
0
0
0
-0.274
-0.004782202
0
0

U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0.123
-10.942
0.930338098
-10.942
-0.190973923
0.913424399
-0.176592314

Nodo1
13.178
0.079
0.134
-15.907
1.016846259
-15.986
-0.279008329
0.977523817
-0.280041964

Nodo3
13.09
0.24
0.158
-23.695
1.207028266
-23.935
-0.417744549
1.10323144
-0.489691356

Nodo4
13.047
0.321
0.17
-26.752
1.302981528
-27.073
-0.47251298
1.160210428
-0.59301992

Nodo5
13.047
0.321
0.17
-26.752
1.302981528
-27.073
-0.47251298
1.160210428
-0.59301992

Nodo6
13.047
0.321
0.17
-26.752
1.302981528
-27.073
-0.47251298
1.160210428
-0.59301992

U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0.052
-172.414
0.393313668
-172.414
-3.009191925
-0.389871316
-0.051923004

Nodo1
13.215
-0.01
0.056
-177.379
0.423760878
-177.369
-3.095672988
-0.423314182
-0.01945212

Nodo3
13.203
-0.029
0.066
174.833
0.499886389
174.862
3.051917585
-0.497877788
0.04476729

Nodo4
13.197
-0.038
0.071
171.776
0.538001061
171.814
2.99871995
-0.532519392
0.076604428

Nodo5
13.191
-0.047
0.077
169.148
0.583731332
169.195
2.953009778
-0.573382292
0.109430411

Nodo6
13.191
-0.047
0.077
169.148
0.583731332
169.195
2.953009778
-0.573382292
0.109430411

VUF% -Load1
Nodo2
13.221
-0.015
0.094
-59.384
0.710990092
-59.369
-1.036184506
0.362254473
-0.611783137

VUF% -Load2
Nodo2
13.175
0.064
0.23
21.64
1.74573055
21.576
0.376572233
1.623408269
0.641966312

VUF% -Load3
Nodo2
13.069
0.182
0
0
0
-0.182
-0.003176499
0
0

VUF% -Load4
Nodo2
13.134
0.159
0.145
-20.116
1.104004873
-20.275
-0.3538655
1.035600981
-0.382566814

VUF% -Load5
Nodo2
13.209
-0.019
0.061
178.411
0.461806344
178.43
3.114190931
-0.46163298
0.012652706

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


VUF% -Load6
U1
Ang U1
U2
Ang U2
VUF%
Ang VUF% - Degrees
Ang VUF% - Radians
Real_VUF%
Imag_VUF%

Subestacin
13.221
0
0
0
0
0
0
0
0

Nodo1
13.189
-0.035
0
0
0
0.035
0.000610865
0
0

Nodo2
13.156
-0.069
0
0
0
0.069
0.001204277
0
0

Nodo3
13.124
-0.104
0
0
0
0.104
0.001815142
0
0

Nodo4
13.091
-0.138
0
0
0
0.138
0.002408554
0
0

Nodo5
13.059
-0.173
0
0
0
0.173
0.00301942
0
0

Nodo6
13.026
-0.208
0
0
0
0.208
0.003630285
0
0

Se puede obtener los siguientes resultados:


3.5
3
2.5
V
2
U
F 1.5
%

Datos de Flujo de Carga

Metodo de Carga Solitaria

0.5
0

Terminales

Angulo en grados sexagesimales

2
0
-2
Datos de Flujo de Carga

-4

Metodo de Carga Solitaria


-6
-8
-10
-12

Terminales

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Mtodo de Sustraccin de Carga
A continuacin se muestran los resultados de la aplicacin de este mtodo.
Sistema Completo
Barra
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
subestacion
1
0 0.02249586
1.413217
0
1
0.9850045
0.1491162 0.02442923
-3.551325
0
2
0.9708024
0.3159584 0.02662124
-6.0107
0
3
0.9584244
0.4529698 0.02697262
-7.441673
0
4
0.9519549
0.4937827 0.02733554
-8.836556
0
5
0.9489216
0.4458186 0.02690695
-8.291999
0
6
0.9463574
0.4081692 0.02690861
-8.289159
0

0
0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-real
VUF%-imag
2.249586
1.413217
2.248901737
0.055481064
2.48011354
-3.7004412
2.474942807
-0.16006651
2.74218935
-6.3266584
2.725488842
-0.302180398
2.81426683
-7.8946428
2.787594084
-0.386544987
2.87151629
-9.3303387
2.833526147
-0.465548451
2.8355293
-8.7378176
2.802619673
-0.430754427
2.84338771
-8.6973282
2.810691422
-0.42996209

Sistema Sin C1
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.98582
0.1621944 0.02133614
11.85828
0
2
0.9716466
0.3292535 0.02316088
7.648421
0
3
0.9592854
0.465993 0.02333795
5.797926
0
4
0.9528273
0.5066977 0.02353579
3.981669
0
5
0.9497934
0.4587484 0.02317335
4.836737
0
6
0.9472317
0.4211705 0.02317495
4.836699
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
2.16430383
11.6960856
0.355577149
-0.598815037
2.38367324
7.3191675
0.361238058
-0.60585185
2.43284741
5.331933
0.365273454
-0.612618612
2.4701003
3.4749713
0.367967444
-0.615267443
2.4398306
4.3779886
0.369908129
-0.617001295
2.44659781
4.4155285
0.371355305
-0.618323821

Sistema Sin C2
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.9868694
0.1148303 0.01310042
-45.33018
0
2
0.9745372
0.2464475 0.01375091
-46.74305
0
3
0.9622088
0.3815694 0.01440898
-48.02746
0
4
0.9557652
0.4212168 0.01507452
-49.20297
0
5
0.9527396
0.3741453 0.01457953
-49.49906
0
6
0.9501859
0.3367994 0.01457895
-49.49842
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
1.32747251
-45.4450103
1.543596743
0.78586043
1.41101951
-46.9894975
1.762986707
0.729597529
1.49748994
-48.4090294
1.793547746
0.733431801
1.57722001
-49.6241868
1.811805598
0.735996423
1.53027438
-49.8732053
1.816386484
0.739324105
1.53432607
-49.8352194
1.821069418
0.742558607

Sistema Sin C3
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.9910778
0.05692473 0.02407634
-3.938835
0
2
0.9829381
0.1278589 0.02623322
-6.381534
0
3
0.9765928
0.1664747 0.02657202
-7.809622
0
4
0.9702464
0.2057263 0.02692686
-9.200787
0
5
0.9672706
0.1595666 0.02650588
-8.658917
0
6
0.9647554
0.1233335
0.0265074
-8.656267
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
2.42930878
-3.99575973
0.051539168
0.009214157
2.66885778
-6.5093929
0.073836425
0.000377588
2.72089043
-7.9760967
0.093025431
-0.008994346
2.77525998
-9.4065133
0.09558346
-0.011965196
2.74027558
-8.8184836
0.094736959
-0.010657493
2.74757726
-8.7796005
0.095308106
-0.010588439

Sistema Sin C4
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.9885983
0.06653281 0.01393178
3.256207
0
2
0.9779818
0.1481788 0.01532305
2.0323
0
3
0.9691471
0.1976562 0.01495893
3.314769
0
4
0.966153
0.1513614 0.01460135
4.66316
0
5
0.963158
0.104909 0.01425223
6.078558
0
6
0.960632
0.06836769 0.01425281
6.078317
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
1.4092458
3.18967419
1.067880201
-0.238479152
1.56680319
1.8841212
1.159532723
-0.353694055
1.54351491
3.1171128
1.246362843
-0.470476771
1.51128755
4.5117986
1.326921842
-0.584432954
1.47973957
5.973649
1.330915295
-0.584752492
1.48369095
6.00994931
1.335155244
-0.585306251

Sistema Sin C5
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.9854842
0.1592584 0.02881727
-1.895897
0
2
0.9717611
0.3361691 0.03140828
-4.633008
0
3
0.9598704
0.4832291
0.0321766
-6.333883
0
4
0.9538799
0.5344836 0.03296505
-7.955305
0
5
0.9513233
0.4970937
0.0329676
-7.952032
0
6
0.9487657
0.4596325
0.0329701
-7.948629
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
2.92417372
-2.0551554
-0.447349993
-0.055201145
3.23209892
-4.9691771
-0.49446204
-0.022216584
3.35218171
-6.8171121
-0.540888041
0.011360741
3.45589104
-8.4897886
-0.584495898
0.044655609
3.4654465
-8.4491257
-0.625215355
0.078427723
3.47505185
-8.4082615
-0.627007995
0.078179697

Sistema Sin C6
u1-mod-p.u. u1-deg
u2-mod-p.u. u2-deg
u0-mod-p.u. u0-deg
1
0.9876663
0.1828381 0.02427191
-3.556187
0
2
0.9761275
0.3832924 0.02644955
-6.00857
0
3
0.9664058
0.5541818 0.02679662
-7.437319
0
4
0.9625458
0.6304696 0.02715527
-8.830245
0
5
0.9620842
0.620134 0.02673016
-8.29458
0
6
0.9620849
0.6200691 0.02673018
-8.294645
0

0
0
0
0
0
0

VUF%-mod VUF%-deg
VUF%-dif-real VUF%-dif-imag
2.45750108
-3.7390251
0.022672682
0.000192026
2.7096409
-6.3918624
0.032691769
-0.00052207
2.77281241
-7.9915008
0.041709275
-0.001051402
2.82119251
-9.4607146
0.050705987
-0.00182534
2.77835973
-8.914714
0.057822243
-0.00020842
2.77835979
-8.9147141
0.065893935
0.00058393

Barra

Barra

Barra

Barra

Barra

Barra

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


Finalmente-Total diferencia VUF%
real
ima
mod
deg
1
2.59391595
-0.097228721 2.59573754 -2.14669747
2 2.895823641
-0.252309442 2.90679456 -4.97968031
3 2.999030708
-0.348348591 3.01919392 -6.62562405
4 3.068488433
-0.432838901 3.098866047 -8.02936652
5 3.044553756
-0.394867871 3.070053453 -7.39002739
6 3.061774013
-0.392896278 3.086879913 -7.31262407

Barra

Barra

Error
real
ima
Mod
1 0.11897314
0.062837789
0.134548119
2 0.1703348
0.049870957
0.177485369
3 0.21143662
0.038196396
0.214859048
4 0.23496229
0.032709549
0.237228139
5 0.24193408
0.035886556
0.244581162
6 0.25108259
0.037065813
0.253803748

3.5

2.5

VUF% de Flujo de Carga


VUF% Metodo Sustraccion de
Carga

1.5

0.5

0
1

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos

INVESTIGACIN-Power & Energy Society - UNI


0
1

-1

Angulo en Grados Sexagesimales

-2
-3
-4
-5
-6

VUF% Angulo Flujo de Carga


VUF% Angulo- Metodo de
Sustraccion de Carga

-7
-8
-9
-10

7. Observaciones y/o Temas Pendientes


El Ing. Bautista Ros, est en busca de una red que cuente con lneas no transpuestas,
desbalance por cargas y un parque motor. La idea bsica es poder reducir las prdidas por
contaminacin de desbalance de voltaje, en los motores trifsicos, y as, aumentar la calidad
de energa para la distribuidora duea de la red.
Consultar al Ing. Bautista Ros, cual mtodo usar para cuantificar el aporte de VUF% por
cargas desbalanceadas, o bien el Metodo de Carga Solitaria, o bien el Metodo de
Sustraccin de Carga.
Resta cuantificar las prdidas en motores trifsicos, debido al DV.
Diseo del algoritmo para luego ser programado en DPL.

Asesor: Ing. Bautista Ros, Juan Pablo


-

Cabrera Chirre, Jorge Luis


Morales Tello, Carlos Alonso
Palma Gutierrez, Jose Carlos