SEMINARIO DE ESTRUCTURAS

COLUMNA 2D

VP. (0.4 X 0.5)


VP. (0.4 X 0.7)

7.50

.40

7.50

Pvl= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg
3

Pvc= 0.4mx0.5mx2400Kg/ m

x8.0mx3=16 128Kg

Plosa= 8.4mx2.95mx300Kg/ m

x2.55mx3=3 672Kg
2

x3=2 2302Kg

Ppiso terminado= 8.4mx2.95mx100Kg/ m


S/C= 8.4mx2.95mx350Kg/ m

1Tn

P= 82 073.4Kgx 1000 Kg

= 82.07Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

x3=7 434Kg

x3= 26 019Kg

Ptotal=82 073.4Kg

.70

AREA TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

.70
.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)


.70

.40

VP. (0.4 X 0.7)

4.50

VP. (0.4 X 0.5)

.40

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

5.40

VP. (0.4 X 0.7)

5.00

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

VP. (0.4 X 0.7)

4.50

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

5.40

8.40

VP. (0.4 X 0.5)

5.40

8.40

SEMINARIO DE ESTRUCTURAS

Az=

Pc x Factor de suelo
Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio

1.60

1.10= suelo blando

T = Az

(0.70.4)
=
2
T = Az

(T B)
2

.70

82.07 Tn x 1.05
=2.87 c m2
30 Tn

.60

2.87 c m2

.60

Az=

.40

1.90

Para el suelo de El Tambo, factor de suelo 1.05.

1.84 = 1.90m

(T B)
2

2.87 c m2

(0.70.4)
=
2

1.54 = 1.60m

2.90

Para el suelo de Chilca, factor de suelo 1.10.

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

(T B)
2

9.03 c m2

3.15 = 3.20m

(T B)
2

9.03 c m2

2.85 = 2.90m

1.25

.70

T = Az

.40

3.20

82.07 Tn x 1.10
2
=9.03 c m
10 Tn

1.25

Az=

SEMINARIO DE ESTRUCTURAS

COLUMNA 2A

VP. (0.4 X 0.5)


VP. (0.4 X 0.7)

7.50

.40

AREA TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg

7.50

.70

4.50
.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

.40

VP. (0.4 X 0.7)

.70
.40

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.7)

5.40

VP. (0.4 X 0.7)

5.00

VP. (0.4 X 0.7)

.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.5)

8.40

VP. (0.4 X 0.7)

4.50

8.40

VP. (0.4 X 0.7)

SEMINARIO DE ESTRUCTURAS
Pvl= 0.4mx0.7mx2400Kg/ m

Pvc= 0.4mx0.5mx2400Kg/ m

x8.0mx3=16 128Kg

Plosa= 8.4mx2.95mx300Kg/ m

x2.55mx3=3 672Kg
2

x3=22 302Kg

Ppiso terminado= 8.4mx2.95mx100Kg/ m


S/C= 8.4mx2.95mx350Kg/ m

x3=7 434Kg

x3= 26 019Kg

Ptotal=82 073.4Kg

1Tn

P= 82073.4Kgx 1000 Kg

= 82.07Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

Az=

Pc x Factor de suelo
Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando
1.60

Para el suelo de El Tambo, factor de suelo 1.05.

T = Az

(0.70.4)
=
2
T = Az

.60

.70

(T B)
2

.40

2.87 c m2

1.84 = 1.90m

(T B)
2

2.87 c m2

(0.70.4)
=
2

1.54 = 1.60m

1.90

82.07 Tn x 1.05
=2.87 c m2
30 Tn

.60

Az=

SEMINARIO DE ESTRUCTURAS
Para el suelo de Chilca, factor de suelo 1.10.

82.07 Tn x 1.10
2
=9.03 c m
10 Tn

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

.40

9.03 c m2

3.15 = 3.20m

(T B)
2

9.03 c m2

2.85 = 2.90m

COLUMNA 3C

1.25

3.20

(T B)
2

.70

T = Az

1.25

Az=

2.90

SEMINARIO DE ESTRUCTURAS

VP. (0.4 X 0.5)


VP. (0.4 X 0.7)

7.50

.40

7.50

Pvl= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg
3

Pvc= 0.4mx0.5mx2400Kg/ m

x4.1mx3=8 265.6Kg

Plosa= 4.5mx5.15mx300Kg/ m

x4.75mx3=6 840Kg
2

x3=20857.5Kg

Ppiso terminado= 4.5mx5.15mx100Kg/ m


S/C= 4.5mx5.15mx350Kg/ m

1Tn

P= 73 767.8Kgx 1000 Kg

= 73.77Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

x3=6 952.5Kg

x3= 24 333.8Kg

Ptotal=73 767.8Kg

.70

TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

4.50
.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)


.70

.40

VP. (0.4 X 0.7)

.70
.40

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.7)

5.40

VP. (0.4 X 0.7)

4.50

VP. (0.4 X 0.7)

AREA

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

5.40

5.00

8.40

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

8.40

VP. (0.4 X 0.7)

SEMINARIO DE ESTRUCTURAS

Az=

Pc x Fac tor de suelo


Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando

1.80

T = Az

(0.70.4)
=
2
T = Az

(T B)
2

.40

73.77 Tn x 1.05
=2.58 c m2
30 Tn
.55

Az=

.70

.55

1.50

Para el suelo de El Tambo, factor de suelo


1.05.

2.58 c m2

1.76 = 1.80m

(T B)
2

2.58 c m2

(0.70.4)
=
2

1.46 = 1.50m

3.00

Para el suelo de Chilca, factor de suelo 1.10.

73.77 Tn x 1.10
=8.1 c m2
10 Tn
1.15

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

(T B)
2

8.10 c m2

2.95 = 3.00m

(T B)
2

8.10 c m2

2.65 = 2.70m

.40

1.15

T = Az

.70

2.70

Az=

SEMINARIO DE ESTRUCTURAS

COLUMNA 1C

.40

AREA TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

.40

VP. (0.4 X 0.5)

.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

7.50

x9.7m=6 518.4Kg

7.50

4.50

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

.70
.40
5.00

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.7)

.70

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

.70

4.50

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

5.40

8.40

VP. (0.4 X 0.5)

5.40

8.40

VP. (0.4 X 0.7)

SEMINARIO DE ESTRUCTURAS
Pvl= 0.4mx0.7mx2400Kg/ m

Pvc= 0.4mx0.5mx2400Kg/ m

x4.1mx3=8 265.6Kg

Plosa= 4.5mx5.15mx300Kg/ m

x4.75mx3=6 840Kg
2

x3=20857.5Kg

Ppiso terminado= 4.5mx5.15mx100Kg/ m


S/C= 4.5mx5.15mx350Kg/ m

x3=6 952.5Kg

x3= 24 333.8Kg

Ptotal=73 767.8Kg

1Tn

P= 73 767.8Kgx 1000 Kg

= 73.77Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

Az=

Pc x Factor de suelo
Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando
1.80

Para el suelo de El Tambo, factor de suelo


1.05.

T = Az

(0.70.4)
=
2
T = Az

(T B)
2

.40

.70

2.58 c m2

1.76 = 1.80m

(T B)
2

2.58 c m2

(0.70.4)
=
2

1.46 = 1.50m

1.50

.55

73.77 Tn x 1.05
=2.58 c m2
30 Tn

.55

Az=

SEMINARIO DE ESTRUCTURAS

3.00

Para el suelo de Chilca, factor de suelo 1.10.

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

(T B)
2

8.10 c m2

2.95 = 3.00m

(T B)
2

8.10 c m2

2.65 = 2.70m

COLUMNA 1B

.70

.40

T = Az

1.15

2.70

73.77 Tn x 1.10
=8.1 c m2
10 Tn

1.15

Az=

SEMINARIO DE ESTRUCTURAS

.40

VP. (0.4 X 0.7)

7.50

.40

7.50

Pvl= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg
3

Pvc= 0.4mx0.5mx2400Kg/ m

x4.1mx3=8 265.6Kg

Plosa= 4.5mx5.15mx300Kg/ m

x4.75mx3=6 840Kg
2

x3=20857.5Kg

Ppiso terminado= 4.5mx5.15mx100Kg/ m


S/C= 4.5mx5.15mx350Kg/ m

1Tn

P= 73 767.8Kgx 1000 Kg

= 73.77Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

x3=6 952.5Kg

x3= 24 333.8Kg

Ptotal=73 767.8Kg

.70

AREA TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

4.50
.70

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)


.70

.40

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

.70

VP. (0.4 X 0.5)


VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.5)

VP. (0.4 X 0.7)

5.40

VP. (0.4 X 0.7)

4.50

VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.7)

5.00

8.40

VP. (0.4 X 0.5)

8.40

SEMINARIO DE ESTRUCTURAS

Az=

Pc x Factor de suelo
Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando
1.80

Para el suelo de El Tambo, factor de suelo


1.05.

T = Az

(0.70.4)
=
2
T = Az

(T B)
2

.70
.40

2.58 c m2

1.76 = 1.80m

(T B)
2

2.58 c m2

(0.70.4)
=
2

1.46 = 1.50m

Para el suelo de Chilca, factor de suelo 1.10.

3.00

73.77 Tn x 1.10
=8.1 c m2
10 Tn

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

(T B)
2

8.10 c m2

1.15

.70

2.95 = 3.00m

(T B)
2

8.10 c m2

2.65 = 2.70m

2.70

.40

T = Az

1.15

Az=

1.50

.55

73.77 Tn x 1.05
=2.58 c m2
30 Tn

.55

Az=

SEMINARIO DE ESTRUCTURAS

COLUMNA 3B

VP. (0.4 X 0.7)


.40

7.50

4.50
.40

VP. (0.4 X 0.5)


VP. (0.4 X 0.5)
VP. (0.4 X 0.5)

.70

VP. (0.4 X 0.5)


7.50

.40

VP. (0.4 X 0.7)

VP. (0.4 X 0.7)

AREA
TRIBUTARIA

VP. (0.4 X 0.5)

VP. (0.4 X 0.5)


VP. (0.4 X 0.5)

5.40

VP. (0.4 X 0.7)

.70

VP. (0.4 X 0.7)

.70

5.00

4.50

VP. (0.4 X 0.7)

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

.70

8.40

VP. (0.4 X 0.7)

VP. (0.4 X 0.5)

5.40

5.40

8.40

SEMINARIO DE ESTRUCTURAS
Pc= 0.4mx0.7mx2400Kg/ m

Pvl= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg
3

Pvc= 0.4mx0.5mx2400Kg/ m

x4.1mx3=8 265.6Kg

Plosa= 4.5mx5.15mx300Kg/ m

x4.75mx3=6 840Kg
2

x3=20857.5Kg

Ppiso terminado= 4.5mx5.15mx100Kg/ m


S/C= 4.5mx5.15mx350Kg/ m

x3=6 952.5Kg

x3= 24 333.8Kg

Ptotal=73 767.8Kg

1Tn

P= 73 767.8Kgx 1000 Kg

= 73.77Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

Az=

Pc x Factor de suelo
Q admisible

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando
1.80

Para el suelo de El Tambo, factor de suelo 1.05.

(0.70.4)
=
2

(T B)
2

2.58 c m2

1.76 = 1.80m

.70
.40

T = Az

.55

1.50

73.77 Tn x 1.05
=2.58 c m2
30 Tn

.55

Az=

SEMINARIO DE ESTRUCTURAS

T = Az

(T B)
2

2.58 c m2

(0.70.4)
=
2

1.46 = 1.50m

3.00

Para el suelo de Chilca, factor de suelo 1.10.

73.77 Tn x 1.10
=8.1 c m2
10 Tn
1.15

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

8.10 c m2

2.95 = 3.00m

(T B)
2

8.10 c m2

2.65 = 2.70m

COLUMNA 2C

.40

.70

1.15

T = Az

(T B)
2

2.70

Az=

SEMINARIO DE ESTRUCTURAS

AREA TRIBUTARIA
Pc= 0.4mx0.7mx2400Kg/ m

Pvl= 0.4mx0.7mx2400Kg/ m

x9.7m=6 518.4Kg
3

Pvc= 0.4mx0.5mx2400Kg/ m

x7.5mx3=15120Kg

Plosa= 8.2mx5.3mx300Kg/ m

x4.9mx3=7056Kg

x3=39114Kg

Ppiso terminado= 8.2mx5.3mx100Kg/ m


S/C= 8.2mx5.3mx350Kg/ m

1Tn

= 126.48Tn

CALCULO DE DIMENSIONES DE ZAPATA


Dimensionamiento:

Az=

Pc x Factor de suelo
Q admisible

x3=13038Kg

x3= 45633Kg

Ptotal=126479.4Kg
P= 126479.4Kgx 1000 Kg

SEMINARIO DE ESTRUCTURAS

FACTORES DE SUELO
1.05= suelo duro
1.07= suelo intermedio
1.10= suelo blando

Para el suelo de El Tambo, factor de suelo 1.05.

Az=

126.48 Tn x 1.05
=4.43 m2
30 Tn

T = Az

(0.70.4)
=
2
T = Az

(T B)
2

4. 43 m2

2.26 = 2.30m

(T B)
2

4.43 m2

(0.70.4)
=
2

Para el suelo de Chilca, factor de suelo 1.10.

Az=

126.48 Tn x 1.10
2
=13.91m
10 Tn

T = Az

(0.70.4)
=
2
T = Az

(0.70.4)
=
2

(T B)
2

13.91m2

3.88 = 3.90m

(T B)
2

13.91m2

3.58 = 3.60m

1.96 = 2.00m