DPS Para Media Tension

Calculo de subestaciones
Barra principal
Seleccin de DPS

Y-T

34,5 KV

220 KV

10%

Metor sobre nivel del mar:

Ke

= 3
=
1 =

2 =

Km

Y-T

oY

1.4

1.73

Liquido

Aire

0.83

0.73

1 Seg

10 Seg

2H

Kt

1.15

1.07

0.97

Ko

0.8

MEDIA TENSION

UR

2000

ALTA TENSION

DPS Para Alta Tension

Un =

34.5

kV

Un =

220

kV

Um =

37.95

kV

Um =

242

kV

COV =

23.0

kV

COV =

139.9

kV

TOV =

32.2

kV

TOV =

242.0

kV

UR1 =

28.8

kV

UR1 =

174.9

kV

UR2 =

28.0

kV

UR2 =

210.4

kV

Catalogo

33

kV

228

kV

UR

Catalogo

NPR

108.7

10 kA - (8/20s)

NPR

519

10 kA - (8/20s)

NPM

76.8

0,5 kA - (30/60s)

NPM

445

1 kA - (30/60s)

BIL Rango I

Calculo de subestaciones - Barra principal


Coodinacion de Aislamiento

Metor sobre nivel del mar:

Ke

Ki

1.25

Ka

1.28

KM

1.15

Y-T

oY

1.4

1.73

Liquido

Aire

Km

0.83

0.73

Ko

0.8

MEDIA TENSION

2000

ALTA TENSION

Un =

34.5

kV

Un =

220

kV

Um =

37.95

kV

Um =

242

kV

Catalogo

33

kV

Catalogo

228

kV

BIL y BLS Rango II


UR

BIL
BIL

NPR

108.7

10 kA - (8/20s)

NPR

519

10 kA - (8/20s)

NPM

76.8

0,5 kA - (30/60s)

NPM

445

1 kA - (30/60s)

Calculado

Normalzado

BLS

Calculado

173.54

kV

250

kV

182.50

kV

BIL
BIL

Calculado

Normalzado

BLS

Calculado

828.57

kV

850

kV

620.50

kV

kV

BLS

Norma F-F =

NA

kV

NA

kV

BLS

Norma F-T =

NA

kV

NA

Cumple

BLS/NPM

NA

Cumple

BLS

Norma F-F =

NA

BLS

Norma F-T =

BLS/NPM

UR

Nota: No se determina BLS porque la


tension pertenece al rango I.

Nota: No se determina BLS porque la tension


pertenece al rango I.