Está en la página 1de 23

07/MAYO/2014

LICENCIA DE CONSTRUCCION DE PROYECTO POLLO MATON.


PROPIETARIO:
NOMBRE: _________________________________
TEL: ______________
DIRECCIN: ___________________________
FIRMA:_______________________

UBICACIN:
CALLE: AV. BENITO JUARES S/N
COLONIA: FRACC. PRIVADAS DE ANAHUAC.
MUNICIPIO: _ESCOBEDO, N.L.
EXP. CAT.: ___-029-034 Y 035
ASESOR ESTRUCTURAL:
NOMBRE: ING. ANTONIO RODARTE NAVARRO
CED. PROF.: No. 2925677
DIRECCIN: Zaragoza sur#1000 Condominio Acero, Despacho 905 , MONTERREY, N.L.
TELEFONO: 83-98-21-27


FIRMA:_______________________
MEMORIA DE CLCULO ESTRUCTURAL
EST-1214
DISEO ESTRUCTURAL

LOSA Y VIGAS

CONSIDERACIONES GENERALES
ESPECIFICACIONES DE MATERIALES
CONCRETO fc=200 Kg/cm2 A MENOS QUE SE ESPESIFIQUE LO CONTRARIO
ACERO fy=4200 Kg/cm2
POLIESTILENO 60X50X15 0 Kg/PZA.
I.- CARGAS GRAVITACIONALES
1.- LOSA DE AZOTEA COMIDA PARA LLEVAR 20.00 cm DE ESPESOR
ANCHO DE NERVADURA 15 cm
CARGAS VIVAS 100 Kg/M2

CARGAS MUERTAS (ANALISIS DEL MODULO TIPICO)
i) POR PESO PROPIO
1.60 M
PERALTE 0.20 M
0.75 M
VOLUMEN TOTAL 0.240 M3
VOLUMEN DE ALIGERANTE 0.135 M3 3 0.6 0.5 0.15
VOLUMEN DE CONCRETO 0.105 M3
PESO DE ALIGERANTE 0.00 Kg
PESO DEL CONCRETO 241.50 Kg
CARGAS POR PESO PROPIO DEL MODULO TIPICO 241.50 Kg/MODULO TIPICO
CARGAS POR PESO PROPIO DEL MODULO TIPICO 150.94 Kg/M.L/MODULO TIPICO
ii) DE SERVICIO
IMPERMEHABILIZACION Y EMPASTE 120.00 Kg/M2
DUCTERIA Y CIELO FALSO 50.00 Kg/M2
TOTAL DE CARGAS MUERTAS DE SERVICIO POR M. TIPICO 127.50 Kg/M.L./MODULO TIPICO
TOTAL DE CARGAS MUERTAS POR MODULO TIPICO 278.44 Kg/M.L./MODULO TIPICO
CARGA DE DISEO AZOTEA 20.00 cm Esp.= Wu=1.6W.L. +1.2W.D. Wu = 454 Kg/M.L./M.TIPICO
Wu = 606 Kg/M2
LONG.M.TIPICO
ANCHO M.TIPICO ALIGERANTE MODULO TIPICO
CALCULO Y ANALISIS DE NERVADURA CARGADORA
NERVADURA N11
SECCION
b= 15 cm
h= 20 cm Wu= 454 Kg/M.L.
Wu= 454 Kg/M.L.
A , B
5.15 M
1169 Kg 1169 Kg
1169
V] 0 0
-1169
1505 Kg-m
0 0
ESFUERZOS EN LOSAS
CARGACLARO MOMENTOS DISTANCIAS
TRAMO Wu L M1 M max M2 V1 V2 M=0 M max M=O
(Kg) (MTS) (Kg-M) (Kg-M) (Kg-M) (Kg) (Kg) (MTS) (MTS) (MTS)
A-B 454 5.15 1505 1169 1169 0.00 2.58 5.15
REFUERZO EN LOSAS
b= 15 cm h= 20 cm fc= 200 Kg/cm2 fy= Kg/cm2
COEF. IND.
b d K REF. CALC. MIN, MAX. SELEX. CALC.
ACT. fc Fy CM CM adim. adim. % % % % CM2 3/8" 1/2" 5/8"
1505 200 4200 15 17 0.1929 0.2218 0.0106 0.0033 0.0150 0.0106 2.69 3.79 2.09 1.35
% CANT.
cm2 3/8" 1/2" 5/8"
-0.0044 -1.13 -1.59 -0.88 -0.57
CALCULO DEL REFUERZO POR CORTANTE
SECCION 15 X 20
DISTANCIA
(X) b d Vc VS
(METROS)
Kg Kg/cm2
cm cm Kg Kg
0.00 1169 200 15 17 1625 -536
5.15 1169 200 15 17 1625 -536
ESPAC.
NO REQUIERE
NO REQUIERE
ACERO POR COMPRESION
DIAMETRO
UTILIZANDO EL ANCHO DE NERVADURA PROPUESTO
Vu fc
SECCION CORT. RESIST.
CONCLUSION
CORTANTES
REFUERZO LOSA DE ENTREPISO
4200
Mu
DIMENS. ACERO REQ. POR TENSION
Kg/cm2 DIAMETRO
CALCULO Y ANALISIS DE NERVADURA CARGADORA
Wu= 454 Kg/M.T
NERVADURA N12
SECCION
b= 15 cm
h= 20 cm
100 KG/M.L.
Wu= 454.00 KG/M.L.
1 2
A B
5.15 m m
1134 Kg 1622
1134 418
100
2.65 m
V] 0
2.50 m
1416 kg-m
-1204 kg
M] 0 0
-181.2 kg-m
0.70
ESFUERZOS EN LOSAS
CARGACLARO MOMENTOS DISTANCIAS
TRAMO Wu L M1 M max M volado V1 V2 V3 M=0 M max M=O
(Kg) (MTS) (Kg-M) (Kg-M) (Kg-M) (Kg) (Kg) (MTS) (MTS) (MTS)
A-B 454 5.15 1416 181 1134 1204 418 0.00 2.50 5.85
REFUERZO EN LOSAS
b= 15 cm h= 20 cm fc= 200 Kg/cm2 fy= Kg/cm2
COEF. IND.
h b K REF. CALC. MIN, MAX. SELEX. CALC.
ACT. fc Fy cm cm adim. adim. % % % % CM2 3/8" 1/2" 5/8"
1416 200 4200 17 15 0.1815 0.207 0.0098 0.0033 0.0150 0.0098 2.51 3.53 1.94 1.25
181 200 4200 17 15 0.0232 0.024 0.0011 0.0033 0.0150 0.0033 0.84 1.19 0.65 0.42
% CANT.
cm2 3/8" 1/2" 5/8"
-0.005 -1.32 -1.85 -1.02 -0.66
-0.014 -3.54 -4.98 -2.74 -1.77
CALCULO DEL REFUERZO POR CORTANTE
SECCION 15 X 20
DISTANCIA
(X) b h Vc VS
(METROS) Kg Kg/cm2 cm cm Kg Kg 1/4" 3/8" D/2 60 DIAM.
0.00 1134 200 15 20 1911 -915 -60 -145 10 60 1/4 NO REQUIERE
5.15 418 200 15 20 1911 -1757 -31 -75 10 60 1/4 NO REQUIERE
5.15 1204 201 15 20 1916 -837 -65 -158 10 60 1/4 NO REQUIERE
CONCLUSION
Vu fc
SECCION CORT. RESIST. ESPACIAMIENTO (cm)
CALCULADO MIN. A.C.I.
DIAMETRO
ACERO POR COMPRESION
DIAMETRO
CORTANTES
REFUERZO LOSA DE ENTREPISO
4200
Mu
DIMENS. ACERO REQ. POR TENSION
Kg/cm2
CALCULO Y ANALISIS DE VIGA CARGADORA
VIGA V11

Wu MURO Y/O PRETIL= 100 Kg/M.L SECCION Wu1= 1169 Kg/M.T
Wu= 1622 Kg/M.T. b= 15 cm Wu2= 1622 Kg/M.T
M.T.= 0.75 M h= 40 cm Wu3= 1169 Kg/M.T
Wu= 1803 Kg/M.L Wu= 2407 Kg/M.L Wu= 1803 Kg/M.L
A B C D
4.88 M 4.78 M 5.85 M
3466 Kg 10715 Kg 12472 Kg 4194 Kg
J UNTA A B C D
TRAMO A-B B-A B-C C-B C-D D-C
CARGA 1802.67 1802.67 2406.67 2406.67 1802.67 1802.67
LONGITUD 4.88 4.88 4.78 4.78 5.85 5.85
RIGIDEZ RRELATIVA 0.15 0.20 0.21 0.21 0.17 0.13
FACTOR DE TRANSPORTE 0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE EMPOTRAMIENTO 3577.45 -3577.45 4582.37 -4582.37 5140.98 -5140.98
MOM. DE BALANCE -3577.45 -497.26 -507.66 -307.42 -251.19 5140.98
FACTOR DE TRANSPORTE
0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE TRANSPORTE -248.63 -1788.73 -153.71 -253.83 2570.49 -125.59
MOM. DE BALANCE 248.63 961.16 981.27 -1274.93 -1041.73 125.59
FACTOR DE TRANSPORTE
0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE TRANSPORTE 480.58 124.31 -637.46 490.64 62.80 -520.87
MOM. DE BALANCE -480.58 253.92 259.23 -304.57 -248.86 520.87
FACTOR DE TRANSPORTE
0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE TRANSPORTE 126.96 -240.29 -152.29 129.61 260.43 -124.43
MOM. DE BALANCE -126.96 194.26 198.32 -214.66 -175.39 124.43
FACTOR DE TRANSPORTE
0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE TRANSPORTE 97.13 -63.48 -107.33 99.16 62.22 -87.70
MOM. DE BALANCE -97.13 84.52 86.29 -88.81 -72.57 87.70
FACTOR DE TRANSPORTE
0.50 0.50 0.50 0.50 0.50 0.50
FACTOR DE DISTRIBUCION 1.00 0.49 0.51 0.55 0.45 1.00
MOM. DE TRANSPORTE 42.26 -48.56 -44.40 43.14 43.85 -36.28
MOM. DE BALANCE -42.26 46.00 46.97 -47.87 -39.12 36.28
MOM.RESULTANTE 0 -4552 4552 -6312 6312 0
ESFUERZOS EN VIGAS
CLARO MOMENTOS DISTANCIAS
L M1 M max M2 V1 V2 M=0 M max M=0
(MTS) (Kg-M) (Kg-M) (Kg-M) (Kg) (Kg) (MTS) (MTS) (MTS)
A-B 4.88 0 3332 -4552 3466 5331 0.00 1.92 3.85
B-C 4.78 4552 1470 -6312 5384 6120 1.13 2.24 3.34
C-D 5.85 6312 4878 0 6352 4194 1.20 3.52 5.85

DISEO POR FLEXION
b= 15 cm h= 40 cm fc= 200 Kg/cm2 fc= 4200 Kg/cm2
Mu COEF. IND.
Kg-M d b DO. REF. CALC. MIN, MAX. SELEC. CALC.
ACT. f'c fy CM CM S/U S/U % % % % CM2 3/8" 1/2" 5/8" 1"
4552 200 4200 37 15 0.1231 0.134 0.0064 0.0033 0.0150 0.0064 3.53 4.97 2.74 1.77 0.69
6312 200 4200 37 15 0.1708 0.193 0.0092 0.0033 0.0150 0.0092 5.09 7.17 3.95 2.54 1.00
3332 200 4200 37 15 0.0901 0.096 0.0045 0.0033 0.0150 0.0045 2.52 3.55 1.96 1.26 0.49
1470 200 4200 37 15 0.0398 0.041 0.0019 0.0033 0.0150 0.0033 1.83 2.58 1.42 0.92 0.36
4878 200 4200 37 15 0.1320 0.144 0.0069 0.0033 0.0150 0.0069 3.81 5.37 2.95 1.91 0.75
4552 200 4200 37 15 0.1231 0.134 0.0064 0.0033 0.0150 0.0064 3.53 4.97 2.74 1.77 0.69
6312 200 4200 37 15 0.1708 0.193 0.0092 0.0033 0.0150 0.0092 5.09 7.17 3.95 2.54 1.00
SELEX. CALC.
% cm2 3/8" 1/2" 5/8
-0.009 -4.79 -6.75 -3.72 -2.40
-0.006 -3.24 -4.56 -2.51 -1.62
-0.010 -5.80 -8.17 -4.50 -2.90
-0.013 -7.25 -10.21 -5.62 -3.62
-0.008 -4.51 -6.36 -3.50 -2.26
-0.009 -4.79 -6.75 -3.72 -2.40
-0.006 -3.24 -4.56 -2.51 -1.62
CALCULO DEL REFUERZO POR CORTANTE
SECCION 15 X 40
b d Vc VS
Kg Kg/cm2
cm cm Kg Kg 1/4" 3/8" D/2 60 DIAM.
3466 200 15 37 3536 -82 -1221 -2972 19 60 1/4 19
5384 200 15 37 3536 2174 46 113 19 60 1/4 19
6352 200 15 37 3536 3313 30 74 19 60 1/4 19
5331 200 15 37 3536 2112 48 116 19 60 1/4 19
6120 200 15 37 3536 3040 33 81 19 60 1/4 19
4194 200 15 37 3536 774 130 317 19 60 1/4 19
20
20
20
20
20
20
REFUERZO REQUERIDO
POR COMPRESION
DIAMETRO
Vu fc
SECCION CORT. RESIST. ESPACIAMIENTO (cm)
CALCULADO MIN. A.C.I. CONCLUSION
ESPACIAM. @
2407
1803
Kg/cm2
DIMENS. ACERO REQUERIDO POR TENSION
DIAMETRO
1803
TRAMO
CARGA CORTANTES
Wu
(Kg)
DISEO ESTRUCTURAL









CUBIERTA M ETALICA

DISENO ESTRUCTURAL
DISEO ESTRUCTURAL DE UNA NAVE INDUSTRIAL
LARGO = 15.60 M CONDICIONES
ANCHO = 12.85 M CONDICIONES
4 MARCOS @ 4.90 M PROPUESTO
14 POLINES @ 1.20 M PROPUESTO
ALT. VERTICAL 3.50 M PROPUESTO
ALT. CUMBRERA 0.65 M PROPUESTO
LAMINA GALVANIZADA CALIBRE 24 SECCIN 4 SOPORTADA POR LARGUEROS @ 1.20 M
CLARO LM= 1.20 M PROPUESTO
CARGA VIVA SOBRE LA CUBIERTA DE UNA PENDIENTE MAYOR AL 5%
WL= 40 Kg/M2
CARGA POR PESO PROPIO DE LA LAMINA
WL= 5.75 Kg/M2
LARGUEROS @ 1.20 A BASE DE CANAL APOYADOS SOBRE
EL MARCO PRINCIPAL @ 4.90 METROS
PROPIEDADES DE LA SECCION
SECCION
OK
PESO = 4.57 KG/M.L.
AREA = 5.79 CM2
PERALTE = 10.16 CM
ANCHO 5.08 CM
ESPESOR = 2.66 MM
I x = 92.18 CM4
Sx = 18.15 CM3
rx = 3.99 CM
I y = 19.37 CM4 SEGUN DATOS DEL FABRICANTE
Sy = 5.92 CM3
ry = 1.83 CM
Fy= 2530 Kg/cm2
E= 2039000 Kg/cm2
CARGA SOBRE LOS LARGUEROS
Wlamina (Kg/m.l.) 6.9
W viva (Kg/m.l.) 48
W larguero (Kg/m.l.) 4.57
W diseo (Kg/m.l.) 59.47
4 MONTEN 12
CARGA PARA ANALISIS DE LARGUEROS APOYADO SOBRE LOS MARCOS PRINCIPALES
W=59.47
Wy 59.17
Wx 5.99
6.46
6.43
ESFUERZOS EN LARGUEROS @ 1.20 METROS POR CARGA VERTICAL
CARGA CLARO MOMENTOS DISTANCIAS
Wu L M1 M max M2 V1 V2 M=0 M max M=0
(Kg) (MTS) (Kg-M) (Kg-M) (Kg-M) (Kg) (Kg) (MTS) (MTS) (MTS)
A-B 59.17 4.90 0.00 110.43 -150.18 114.31 175.61 0.00 1.93 3.86
B-C 59.17 4.90 150.18 48.27 -109.60 153.24 136.68 1.31 2.59 3.87
C-D 59.17 4.90 109.60 61.45 -122.78 142.27 147.65 0.96 2.40 3.85
D-E 59.17 4.90 122.78 61.45 -109.60 147.65 142.27 1.05 2.50 3.94
E-F 59.17 4.90 109.60 48.27 -150.18 136.68 153.24 1.03 2.31 3.59
F-G 59.17 4.90 150.18 110.43 0.00 175.61 114.31 1.04 2.97 4.90
ESFUERZO FLEXIONANTE (Fb ACT)=MC/I KG/CM2 0.6Fy KG/CM2
ESFUERZO FLEXIONANTE (Fb ACT)= 827.63 KG/CM2 1518.00 KG/CM2 SI CUMPLE
CARGA CORTANTE ACT= 175.61 KG 0.4 Fy
ESFUERZO CORTANTE ACT= 30.33 KG/CM2 1012.00 KG/CM2 SI CUMPLE
DEFLEXION ACTUANTE=5WL4/384EI 0.98 cm
0.95 cm 0.98 cm SI CUMPLE
TRAMO
<Fb PERM.=
CORTANTES
0
.
6
5
0
<Fb PERM.=
<V PERM.=
<V PERM.=
<V PERM.=
<Def. PERM.=
CARGA TRIBUTERIA SOBRE EL MARCO PRINCIPAL
W.L.= 40 Kg/M2
Wlamina= 5.75 Kg/M2
W.larg.= 4.57 Kg/M2
W.total= 50.32 Kg/M2
ancho trib.= 4.90 M
W.S= 246.568 Kg/M.L.
Wpp seccin marco= 27.48 Kg/M.L.
Wd= 274.05 Kg/M.L.
polin @= 1.20 M
Carga @ poln= 328.86 Kg
ANALISIS DEL MARCO PRINCIPAL
P= 328.86 KG
P/2= 164.4288
0.650
3.500
15.60 METROS
Ra= 2138 Kg
7.- CALCULO DE ESFUERZOS PERMISIBLES Y ACTUANTES EN EL MARCO PRINCIPAL
UTILIZANDO UN PERFIL DE CANAL DOBLE ( 2 MT ).
PROPIEDADES DE LA SECCION SEGUN DATOS DEL FABRICANTE
SECCION
OK = 2.2363
PESO = 27.48 KG/M.L. = 0.1857
AREA = 34.78 CM2 A= 16.155
PERALTE = 30.48 CM B= 6.7429
ANCHO 17.78 CM C= 32.747
ESPESOR = 3.42 MM
I x = 4666.48 CM4 M2= -4607.39 Kg-m
Sx = 306.19948 CM3 M3= 2873.49 Kg-m
rx = 11.583 CM V1= 2137.57 Kg
I y = 1834.889 CM4 H5= 1316.40 Kg
Sy = 206.399 CM3
ry = 7.263 CM
Fy= 2530 Kg/cm2
E= 209000 Kg/cm2
Ra = 2137.57 KG POR ESTATICA
12 CAJ ON 10
V max. = 2137.57 KG CORTANTE MAXIMO ACTUANTE
Fv ACT.= 205.06 KG/CM2 ESFUERZO CORTANTE ACTUANTE
Seccin compacta s: b/2t= 25.99 < 1590/Fy^0.5=31.61
h/tw= 44.56 < 2150/Fy^0.5=42.74
ENTONCES EL ESFUERZO CORTANTE PERMISIBLE ES:
Fv=0.4Fy
Fv=1012 KG/CM2
COMO F V ACT = 205.06 ES MENOR QUE Fv PERM= 1012 SI CUMPLE
MOMENTO MAXIMO ACTUANTE (AL CENTRO DEL CLARO CON MARCO SIMPLE)
M max. = 4607.39 KG -M MOMENTO FLEXIONANTE MAXIMO
Fb ACT. = 1504.70 KG/CM2 ESFUERZO ACTUANTE A LA FLEXION
Fb ACT. < Fb PERM.
1505 < 1518 SI CUMPLE
REVISION DE COLUMNA METALICA
SECCION
TUBO 16" x 0.25"
PESO = 62.65 KG/M.L.
AREA = 79.81 CM2
DIAMETRO= 40.60 CM
ESPESOR = 6.35 MM
I x = 15969.60 CM4 SEGUN DATOS DEL FABRICANTE
Sx = 785.90 CM3
rx = 14.15 CM
Fy= 2530 Kg/cm2
E= 2039000 Kg/cm2
ESFUERZO ACTUANTE
CARGA TOTAL CC
< =
Fa
Kg cm2 Kg/cm2 cm cm kg/cm
SECCION ESF. ACT. K
126.13 1517.8
L r KL/r
ESF. ACT. ESF. PERM.
3084 79.81 19.32 1.00
Kg/cm2 Kg/cm2
19.32 1517.84 SI CUMPLE
0.28 3.950 14.15
DISEO ESTRUCTURAL











COLUM NAS
columnas cortas lu/h < = 10 y/o lu/r < 40
PEDESTALES
COLUMN. P.U. Fy Es CANT. DIAM. As ls calc. b min max selex. fc Ec b h Ag lc rec
TIPO Ton. Kg/cm Kg/cm Pzas. " cm cm
4
% % % % % Kg/cm Kg/cm cm cm cm cm
4
cm
1 25 4220 2E+06 6 5/8 11.88 29339 0.0074 0.0203 0.01 0.08 0.0100 200 213546 40 40 1600 213333 3
l
u
/
h
<

=
1
0
1
0
<
l
u
/
h
<


=

4
0
4
0

<

l
u
/
h
Corta Larga M.L.
lu lu/h lu/r At lt n 1 0.1fcAg Pb Po Pomax. Pn m1b m2b Ft Pn Pn Pn P.U.
cm cm
4
% % % Ton. Ton-m Ton-m Ton Ton Ton Ton.
150 4 50 101.52 242673 10 0.85 32 81 224 179 36 0 0 45 66 63 1508 25
COLUMNAS
COLUMN. P.U. Fy Es CANT. DIAM. As ls calc. b min max selex. fc Ec b h Ag lc rec
TIPO Ton. Kg/cm Kg/cm Pzas. " cm cm
4
% % % % % Kg/cm Kg/cm cm cm cm cm
4
cm
1 15 4220 2E+06 6 5/8 11.88 2056 0.0264 0.0203 0.01 0.08 0.0100 200 213546 15 30 450 33750 3
Corta Larga M.L.
lu lu/h lu/r At lt n 1 0.1fcAg Pb Po Pomax. Pn m1b m2b Ft Pn Pn Pn P.U.
cm cm
4
% % % Ton. Ton-m Ton-m Ton Ton Ton Ton.
285 10 95 101.52 35806 10 0.85 9 23 87 70 21 0 0 45 30 24 62 15
seleccin
Ton
66
seleccin
Ton
30
DISEO ESTRUCTURAL





CIM ENTACIN
DISEO DE ZAPATAS AISLADAS CRITICAS DE CENTRO
TIPO P.U. C.M.S. C.V.S S.C. P.Vol. Cap. Carga
Kg Kg Kg Kg/M2 Kg/M3 Kg/M2
ZC-1 0.40 0.40 15000 6000 3882 500 1800 10000
TIPO h de Despl. S.C.Total Cap.Net.T. Long. calc. b (prop.) Long. Prop. Req. Prop.
Metros Kg/M2 Kg/M2 Metros Metros Metros (M2) (M2)
ZC-1 1.30 2840.00 7160 1.15 1.20 1.20 1.38 1.44 Ok
Reacc. T. Vu Req. Prop. Efectivo MU ANCHO f c
Kg/M2 Kg M CM cm Kg-CM CM Kg/cm2
ZC-1 10417 4689 0.06 20.00 10.00 500000 120 200 Ok
Coef. Indice Req.
De Ref. De Ref. Calculado Minimo Maximo Selec. ( cm2 ) 1/2" 5/8" 3/4
0.2315 0.2764 0.0132 0.0033 0.0150 0.0132 15.80 10 15 21
ZC-1
1.20 X 1.20 X 0.20
CUADRICULA DE VARILLA
EN LECHO INFERIOR
5/8 " @ 15 cm
Acero de Refuerzo Acero
% DE REFUERZO ESPACIAMIENTO ( cm )
Cargas de servicio
Dim. De Pedestal
( Metros )
Dimensiones
Peralte de Zapata
Elevacin de Zapata
b
h
h

D
e
s
p
l
.
Acero
de
Refuerzo
Planta de Zapata
b
l
CALCULO Y ANALISIS DE VIGA DE CONTRACIMIENTO
VIGA VC-1 Wu= 1246 Kg/M.T SECCION
Wu MURO Y/O PRETIL= 750 Kg/M.L b= 30 cm
h= 40 cm
Wu= 1246 Kg/M.L.
1 , 3
8.00 M
4982 Kg 4982 Kg
4982
V] 0 0
-4982
Kg-m
M] 0 0
9965
ESFUERZOS EN VIGA
CARGA CLARO MOMENTOS DISTANCIAS
TRAMO Wu L M1 M max M2 V1 V2 M=0 M max M=O
(Kg) (MTS) (Kg-M) (Kg-M) (Kg-M) (Kg) (Kg) (MTS) (MTS) (MTS)
A-B 1246 8.00 9965 4982 4982 0.00 4.00 8.00
REFUERZO EN VIGAS
. 30 cm h= 40 cm fc= 200 Kg/cm2 fy= Kg/cm2
COEF. IND.
b d K REF. CALC. MIN, MAX. SELEX. CALC.
ACT. fc Fy CM CM adim. adim. % % % % CM2 3/8" 1/2" 5/8" 1"
9965 200 4200 30 30 0.2050 0.2385 0.0114 0.0033 0.0150 0.0114 10.22 14.40 7.92 5.11 2.00
% CANT.
cm2 3/8" 1/2" 5/8" 1"
-0.0036 -3.28 -4.62 -2.54 -1.64 -0.64
CALCULO DEL REFUERZO POR CORTANTE
SECCION 30 X 40
DISTANCIA
(X) b d Vc VS
(METROS) Kg Kg/cm2 cm cm Kg Kg 1/4" 3/8" D/2 60 DIAM.
0.00 4982 200 30 37 7072 -2458 -41 -100 19 60 1/4
8.00 4982 200 30 37 7072 -2458 -41 -100 19 60 1/4
CONCLUSION
ESPAC.
20
20
ACERO POR COMPRESION
DIAMETRO
ESPACIAMIENTO (cm)
CALCULADO MIN. A.C.I.
Vu fc
SECCION CORT. RESIST.
CORTANTES
REFUERZO VIGA DE CONTRACIMIENTO
4200
Mu
DIMENS. ACERO REQ. POR TENSION
Kg/cm2 DIAMETRO
GRUPO RODARTE
Diseo Arquitectnico, Topografa, Clculo Estructural, Construccin
Y Presupuesto, Tramite De Construccin y Uso de Suelo, Perito
Responsable y Perito en el Poder Judicial del Estado.



Av. Zaragoza #1000 sur, Condominio Acero, Desp. #905, Centro de Monterrey N.L.
Cel. 044 811 044 1441, Tel.- 83 98 21 27;

Monterrey, N. L. a 07 de J unio del 2014.

SECRETARIA DE DESARROLLO URBANO Y OBRAS PUBLICAS DEL
MUNICIPIO DE ESCOBEDO, N.L.

P R E S E N T E:


Referente al proyecto LICENCIA DE CONSTRUCCION PARA LOCAL POLLO
MATON, que se ubicar en predio propiedad de, En predio
identificado con Expediente Catastral ____029-034 Y 035, en la colonia FRACC.
PRIVADAS DE ANHUAC, en el municipio de ESCOBEDO, NUEVO LEON.

Manifiesto que he elaborado la memoria de clculo estructural y elaborado los
planos correspondientes a vigas, columnas, losas y zapatas.

Las revisiones se realizaron de acuerdo al reglamento de las construcciones de
obras pblicas de la ciudad de Monterrey as como el A.C.I.318-2001 de las
construcciones de concreto.

As mismo firmo cada una de las pginas que componen la memoria de
clculo estructural anexando copia de mi cdula profesional.


De acuerdo a mi leal saber y entender agradeciendo de antemano y sin ms
por el momento quedo de ustedes para cualquier duda o aclaracin:








ING. ANTONIO RODARTE NAVARRO
CED. PROF: No. 2925677
GRUPO RODARTE
Diseo Arquitectnico, Topografa, Clculo Estructural, Construccin
Y Presupuesto, Tramite De Construccin y Uso de Suelo, Perito
Responsable y Perito en el Poder Judicial del Estado.



Av. Zaragoza #1000 sur, Condominio Acero, Desp. #905, Centro de Monterrey N.L.
Cel. 044 811 044 1441, Tel.- 83 98 21 27;




Cdula profesional para memoria de clculo de CONSTRUCCION DE UN LOCAL PARA
PROYECTO POLLO MATON que se ubicar en FRACC.PRIVADAS DE ANAHUAC, con
expediente catastral ____029- 034 Y 035, en el municipio de ESCOBEDO, N. L.
































Me deslindo de responsabilidad por el mal uso que se le pueda dar a este documento, as
como tambin a su involucracin en un trmite distinto al descrito anteriormente.

También podría gustarte