Configuracin y Cableado de Alarmas Externas ERICSSON - Rectificadores
Configuracin y Cableado de Alarmas Externas ERICSSON - Rectificadores
ALARMAS EXTERNAS
Elaborado por: O&M ACCESO MÓVIL
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
INDICE
Contenido
INDICE.................................................................................................................................................. 2
1. CONFIGURACION EN BBU ERICSSON: ......................................................................................... 3
2. CONFIGURACION EN RECTIFICADOR HUAWEI: ........................................................................... 6
3. CONFIGURACION RECTIFICADOR ZTE ....................................................................................... 11
2
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
3
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
4
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Posición de
Configuración
alarmas
de normally
externas en
la BBU closed
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8
------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 alarmSlogan FALLO DE RED AC
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 alarmSlogan FALLO DE RECTIFICADOR
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 alarmSlogan PUERTA ABIERTA DE RECTIFICADOR
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 alarmSlogan FALLA DE BREAKER DEL EQUIPO
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 alarmSlogan TEMPERATURA ALTA GABINETE
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 alarmSlogan BAJO VOLTAJE DE BATERIAS
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 alarmSlogan TEMPERATURA ALTA EN SALA
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 alarmSlogan GRUPO ELECTROGENO ENCENDIDO
------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 perceivedSeverity 4
-----------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 normallyOpen false
-------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 administrativeState 1
5
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
RECTIFICADOR ALARMA
ALM1 FALLO DE RED AC
ALM3 FALLO DE RECTIFICADOR
ALM5 FALLA DE BREAKER
ALM6 BAJO VOLTAJE DE BATERIAS
ALM7 PUERTA ABIERTA DE RECTIFICADOR
ALM8 TEMPERATURA ALTA DE GABINETE
6
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Entrar a las siguientes opciones, para configurar todas las alarmas cableadas en
Normally OPEN.
7
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Parameters Settings
Alarm Parameters
Do Dry Contact
Open
8
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Entrar a las siguientes opciones, para configurar todas las alarmas cableadas en
Normally OPEN.
Settings
Alarm Settings
Site Summary
SD1 Action
Open
9
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Entrar a las siguientes opciones, para configurar todos Control de alarmas cableadas
en Normally OPEN.
Control
Site Summary
SD1 Action
Open
10
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
11
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
12
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0
Todo lo que termine con .brk configurar en el relay A1 del rectificador ZTE.
Nota:
Configurar el resto de alarmas en NULL
Realizar las pruebas locales luego proceder con las pruebas llamar a O&M Acceso
Móvil.
De encontrar otra casuística comunicarse con personal de TDP O&M Acceso Móvil
13