MANUAL CONFIGURACIÓN

ALARMAS EXTERNAS
Elaborado por: O&M ACCESO MÓVIL
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

INDICE

Contenido
INDICE.................................................................................................................................................. 2
1. CONFIGURACION EN BBU ERICSSON: ......................................................................................... 3
2. CONFIGURACION EN RECTIFICADOR HUAWEI: ........................................................................... 6
3. CONFIGURACION RECTIFICADOR ZTE ....................................................................................... 11

2
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

1. CONFIGURACION EN BBU ERICSSON:

I. En la banda base que cuenta con el siguiente conector realizar el cableado de la


siguiente manera:

Banda Base ALARMA


Posición 1 FALLO DE RED AC
Posición 2 FALLO DE RECTIFICADOR
Posición 3 PUERTA ABIERTA DE RECTIFICADOR
Posición 4 FALLA DE BREAKER DE EQUIPO
Posición 5 TEMPERATURA ALTA DE GABINETE
Posición 6 BAJO VOLTAJE DE BATERIAS
Posición 7 TEMPERATURA ALTA EN SALA
Posición 8 GRUPO ELECTROGENO ENCENDIDO

*La posición 7 y 8 es si el sitio se encuentra en sala y cuneta con grupo electrógeno si


la EBC es Outdoor bloquear la alarma.

Los colores son los siguientes:

3
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

Si el conector de la BBU es un RJ45 verificar lo siguiente:

II. Configuración en la BBU Ericsson.

En la configuración entrar con el comando hget alarmport y verificar lo siguiente:

4
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

Posición de
Configuración
alarmas
de normally
externas en
la BBU closed

De no encontrarse creadas las alarmas externas en la BBU ejecutar los siguientes


comandos:

cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7
cr Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8
------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 alarmSlogan FALLO DE RED AC
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 alarmSlogan FALLO DE RECTIFICADOR
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 alarmSlogan PUERTA ABIERTA DE RECTIFICADOR
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 alarmSlogan FALLA DE BREAKER DEL EQUIPO
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 alarmSlogan TEMPERATURA ALTA GABINETE
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 alarmSlogan BAJO VOLTAJE DE BATERIAS
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 alarmSlogan TEMPERATURA ALTA EN SALA
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 alarmSlogan GRUPO ELECTROGENO ENCENDIDO
------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 perceivedSeverity 4
-----------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 normallyOpen false
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 normallyOpen false
-------------------------------------------------------------------------------------------------------------
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=1 administrativeState 1

5
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=2 administrativeState 1


set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=3 administrativeState 1
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=4 administrativeState 1
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=5 administrativeState 1
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=6 administrativeState 1
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=7 administrativeState 0
set Equipment=1,FieldReplaceableUnit=SUP-1,alarmPort=8 administrativeState 0
El 0 es para bloquearlo si
la sala es outdoor

2. CONFIGURACION EN RECTIFICADOR HUAWEI:

RECTIFICADOR ALARMA
ALM1 FALLO DE RED AC
ALM3 FALLO DE RECTIFICADOR
ALM5 FALLA DE BREAKER
ALM6 BAJO VOLTAJE DE BATERIAS
ALM7 PUERTA ABIERTA DE RECTIFICADOR
ALM8 TEMPERATURA ALTA DE GABINETE

6
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

I. CONFIGURACION EN EL RECTIFICADOR HUAWEI V300

Entrar a las siguientes opciones, para configurar todas las alarmas cableadas en
Normally OPEN.

7
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

Parameters Settings

Alarm Parameters

Do Dry Contact

AlM1 Alarm Action

Open

8
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

II. CONFIGURACION EN EL RECTIFICADOR HUAWEI V200

Configuración de alarmas en el LCD

Entrar a las siguientes opciones, para configurar todas las alarmas cableadas en
Normally OPEN.

Settings

Alarm Settings

Site Summary

SD1 Action

Open

9
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

Configuración de alarmas en el LCD – Control

Entrar a las siguientes opciones, para configurar todos Control de alarmas cableadas
en Normally OPEN.

Control

Site Summary

SD1 Action

Open

10
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

3. CONFIGURACION RECTIFICADOR ZTE

I. Conectar 6 alarmas en las siguientes posiciones.

Posición Rectificador Nombre de Alarma

NC3-COM3 FALLO DE RED AC


NC4-COM4 FALLO DE MODULO DE RECTIFICADOR
NC2-COM2 PUERTA ABIERTA DE RECTIFICADOR
NC6-COM6 ALTA TEMPERATURA DE GABINETE
NC5-COM5 BAJO VOLTAJE DE BATERIAS
NC1-COM1 FALLO DE BREAKER

11
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

II. Configuración en el Display ZTE

Seguir los siguientes pasos.

Entrar a las siguientes opciones:

Las alarmas a configurar se encuentran en las siguientes categorías.

Nombre de Nombre de alarma Nombre de alarma ALARM RELAY


categoría de rectificador
alarma
AC ALM ATTR AC POWER OFF FALLO DE RED AC CRITICAL A3
SMR ALM ATTR SMR –COM FAILED FALLO DE MODULO DE RECTIFICADOR A4
MAJOR
ENV ALM ATTR DOOR ALARM PUERTA ABIERTA DE RECTIFICADOR A2
MINOR
SMR ALM ATTR SMR INTER T.H ALTA TEMPERATURA DE GABINETE A6
CRITICAL
DC ALM ATTR BATT. LOW VOLTAGE BAJO VOLTAJE DE BATERIAS A5
CRITICAL
DC ALM ATTR BATT.LOOP BRK FALLO DE BREAKER MAJOR A1

12
Elaborado Por: O&M ACCESO MÓVIL – Telefónica Del Perú
Versión 1.0

Todo lo que termine con .brk configurar en el relay A1 del rectificador ZTE.

Nota:
Configurar el resto de alarmas en NULL
Realizar las pruebas locales luego proceder con las pruebas llamar a O&M Acceso
Móvil.
De encontrar otra casuística comunicarse con personal de TDP O&M Acceso Móvil