ANEXO 1

CUADRO DE CARGAS
TABLERO TC
COND. [AWG]
CTO. LUM. TOMAS T.ESP. CARGA [W] F.P. P [VA] AMP. [A] 2 DESCRIP.
THHN - 90°C
1-3-5 RESERV.
2-4-6 1 7,460 0.8 9,325 24.48 10 3X30 MAQUINA1°
7 9 720 0.9 800 6.30 12 1X20 LUCES 2X40W
8-10 1 1,200 0.9 1,333 6.06 12 2X20 A/A 1°
9 6 960 0.9 1,067 8.40 12 1X20 TOMAS GALP.
11 8 200 0.9 222 1.75 12 1X20 LUCES OF.
12-14 1 1,200 0.9 1,333 6.06 12 1X20 A/A 2°
13 3 480 0.9 533 4.20 12 1X20 TOMAS |° P.
15 3 480 0.9 533 4.20 12 1X20 TOMAS 2° P.
16-18 1 2,238 0.8 2,798 12.72 12 2X20 MAQUINA
17 9 225 0.9 250 1.97 12 1X20 LUCES 2°
20-22-24 RESERV.
19-21-23 RESERV.
T. 26 13 3 15,163 0.88 17,231 45.22 8 3X50
D.M. 7,796 0.85 9,171 24.07 6 3x50

ANEXO 1

CUADRO DE CARGAS
TABLERO TC

COND. [AWG]
CTO. LUM. TOMAS T.ESP. CARGA [W] F.P. P [VA] AMP. [A] 2 DESCRIP.
THHN - 90°C
1-3-5 1 7,460 0.8 9,325 24.48 10 3X30 MAQUINA1°
2-4-6 1 7,460 0.8 9,325 24.48 10 3X30 MAQUINA2°
7 9 720 0.9 800 6.30 12 1X20 LUCES 2X40W
8-10 1 1,100 0.9 1,222 5.56 12 2X20 A/A 1°
9 6 960 0.9 1,067 8.40 12 1X20 TOMAS GALP.
11 8 200 0.9 222 1.75 12 1X20 LUCES OF.
12-14 1 1,100 0.9 1,222 5.56 12 1X20 A/A 2°
13 3 480 0.9 533 4.20 12 1X20 TOMAS |° P.
15 3 480 0.9 533 4.20 12 1X20 TOMAS 2° P.
16-18 1 2,238 0.8 2,798 12.72 12 2X20 MAQUINA
17 9 225 0.9 250 1.97 12 1X20 LUCES 2°
20-22-24 RESERV.
19-21-23 RESERV.
T. 26 13 4 22,423 0.87 25,693 67.44 8 3X50
D.M. 15,126 0.87 17,331 45.49 6 3x50
52.5
CUADRO REGULACION Y PERDID

MOMENTO TIPO
TRAMO DIST. [m] CARGA [KVA] COND. F.P.
[KVA-m] CONEX.
ACOMETIDA 15 17.80 267.00 6 0.85 FFFN
GULACION Y PERDIDAS

% %
FACTOR C. KG K CORR. [A] R [Ω/Km]
REGULAC. PERDIDAS
1 132.500 0.0027 0.7309 24.07 2.100 0.9847
CALCULO ACOMETIDA
DESDE CARGA CORR. CORRCC.
ITEM HASTA [AWG] F.P. [KVA] [A] CONDUCT. TEMP. [°C]
RED BT. 6
1 0.87 17.8 45.49 75 0.91
MEDIDOR (13,3 mm²)
CORRCC.
DUCTO CORREG. DUCTO
NO 68.25 1"Ø