Está en la página 1de 8
Printed in can == Nortec www.humidity.com Ottawa, Ontario, (618) 822. ESTIMATING THE HUMIDIFICATION LOAD Relative humidity, RH, is the percentage of moisture in a volume of air at a given temperature, compared to the maximum amount of moisture that the volume of air can hold at the same tempera- ture and atmospheric pressure. As air becomes warmer, it can absorb more moisture per unit volume. Therefore a quantity of air containing a specific amount of moisture will have different values of relative humidity as the temperature changes. Itis this process that causes dry air in buildings. As cold incoming air is heated, its relative humidity value drops. Therefore moisture must be added to attain an acceptable level of humidity within the building. object of this brochur Determining how much moisture must be added is the Table 2 on page 2 simplifies the calcula- tions which are described here in detail. Further information on humidity and temperature is located in form 1244. WB_OAD CALCULATION SUMMARY Factors to consider There to determine the humid cation load three basic values need 10 be known: A. The design conditions of the humidified space, ie., the tem- perature and humidity required. B. The conditions of the incoming, air, Le., the temperature and. humidity available. C. Incoming air volume and sec- ondary conditions that can affect, the humidification load, Data and calculations required to estimate humidification load are described in the tables on pages 2and 3 ‘A. Temperature and humidity required ‘The design temperature and humidi- ty of a space depends mostly upon the job being performed. Once the design temperature and humidity have been established, the required moisture can be found in gr/fv from Table 3. Remember always to take the worst case (highest temperature, highest humidity). Formula? For example: The press room of a printing plant should be kept at 76 - 80°F at 4396 — 47% RE ‘Therefore, the worst case is: 80", 479 RH. From Table 3 the required mois ture is: 1.04 ghd Xx 4M = 5:19 B. Temperature and humidity available ‘The outdoor conditions tell us the moisture available in the incoming air, Approximate values can be ‘obsained from Table 4, on page 4 and ‘combined with Table 3 to find the moisture available. Once again we must take the worst case (here, itis Jowest temperature, lowest humidity), As can be seen, the contribution of moisture from the outside air is almost zero. “Assume our printing plant is locat- ‘ed in Denver, Colorado. From Table 4 we see as the worst case: 10° F, 37% REL. From Table 3: 029 gr/R3 X37 RA. = 0.11 grit Combining this result with that of Moisture Required (A) we see that we will need: 5.19 ~ 0.11 = 5.08 ‘grains of moisture for every cubic foot of outside air brought in. C. Incoming air volume ‘The following outlines the steps necessary to determine the amount of outside air being brought into the humidified space and the correspon- ding amount of moisture required. ‘There are three basic means by which outside air is introduced into ‘a humidified space, ‘These are: 1. Through natural ventilation, ie, ‘opening and closing of doors ard ‘windows, and by infiltration through cracks and openings in the building construction, 2. Through mechanical ventilation, ice, the introduction of make-up air, or the exhausting of stale air by the building HVAC system. 3. Though the economizer section of the HVAC system — if this fea ture is included in the system, For maximum accuracy, all three should be estimated and the largest chosen. 1, Natural ventilation Using this method requires knowing the volume of the humidified space and the type of construction, A tightly constructed building will have at least one air change per hour. A loosely constructed build- ing will have at least one and one- half changes per hour, and this same building with a large amount of incoming or exiting trafic will have at least rwo air changes per hour. z= Nortec www.humidity.com Formula 3 ‘Assume our print shop has a floor area of 100! X 100' with a 20! ceil- ing with a large amount of traffic. ‘This gives us: 1007 X 100° 20° 2 = 400,000 3 /h; Using our example, the moisture required is: 400,000 X 5.08 = 290 Ibs/he 7000 grains 24. Make-up air Formula d Assume our print shop has a 15,000 CFM HVAC system and uses 10% make-up air during winter. ‘The amount of outside make-up air entering the HVAC system will, therefore, be 10% of 15,000 CFM = 1,500 CFM. Here, the moisture required will be: 1,500 X 5.08 X 60 min/e~ 65 Ibs/he 7,000 grains Table 1 Qutdoor/indoor relative humidity conversion chart we pesseTeev waa ss m [fi ti; tee eas SS oe [23 ts 6th bee 2 So pe [ist bss es oR SS eee ee or ees ie apm on te reels) ee ct ee a ara toe E wm Ji 2 3 5 6 9 1 13 17 2 om ” Bo |i 3 4 5 8 0 2 1 2 2 mr a tek ee ee te eee eee a ee el es Em li ies asec te a ee ee le ey ee a et 2 wom eee ee leaf: titi sect hes Bm lot bbb a hs 8S RS eae fn ee es eee ie ee Sm foi:iie 2s 3 8s 59 3 8m loot i i Fe sa ES SS Pepe Oe deka ad as m [oc oo oot 1 1 2 ee 8 m ]o oo 0 oo ood oo 20 1 OG IO IGS 20 22S SOD OS aH ASP SO Outdoor temperature (Chart shows what the residual indoor LH, would be at 70°F under varying outdoor condone if proper humiaticaton system wore not installed inthe bulking. Studies indicate that he recommended RH should be between 40% and 60% for optimum benefits fo the occupants (Refer to Figure 1) 2B. Exhaust air Forma 5 Assume the print shop has a 1,000 (CEM fan to exhaust a drying room. Here the moisture required to humid- ify the drying room only will be: 1,000 x 5.08 x 60 min/he = 44 Ibs/hr 7,000 grains/Ib (Refer to Figure 1) 3. Economizer Cycle Care should be taken in sizing hhumiification load when an econo- mizer cycle is incorporated into @ building HVAC system. The purpose of an economizer cycle is to provide building cooling using outside ais, rather than the building refrigeration system when outside air conditions permit Table2 Load calevation summary sheet Determine the moisture equed inthe space (Table 3) Gain tom Tale 3 x infor = A grin SSacione Deternine the moist ove! of meoming a (Table*) ‘Gain tom Taio 4 x Outdoor = B gran? ‘Sor tnp Therefore: moisture o beaded: (reise) Mw A-8 _ . i ——orainsn? marina Detarning the volume fat tobe homie, Choose the largest vate 1. Natural vention: Volume x number of One ar changes 2. Exhast a CFM x 60 mine rine 3. Makeup ale CFM 60 mine Wn gc tine “Teefore: Gross humic ld = oad L = Mac ane 7000 ote: 7000 grins = * pours a "Note: VAG sytem uses economizer cyl, check lad using formula on page 3 == Wortec www.humidity.com Table 3 Note Moisture coment i ety popatona oR, sat: cote at 1008 x RAL Grains of Water Per Cubic Foot - Saturated Air (100% R.H.) “C Fonne “C “FOr “CF Grins °C “Frm °C “FGmins “C °F Gina 240 29 4 «0 286 © 58 Sar 76 975 35 5 1728 4 ZO 5 297 9 S60 77 1008 86 17BD 5 3033 0 308 16 60 $80 7% 1040 G7 1031 40 120 34.8 5 Sa" 61 600 79 10) 56 teas 25 3033 1210 78 332 2-620 27 6 110 BD 1030 st 100 eat "9 15 99 7 45 S48 6 Sat Bt 1140 38 100 1995 195 5030 7 2 124 35 Gt Ge2 2 78 101 20S Go 140 Seat 42s 186 Seo 10 65 Gas GS zn toe 2A 5 6404 4 50 195 383” 6S 707 BA 1243105 2171 66 150 7200 31 208 397 G7 73 20 85 Tear io 2m 18S BOT? a 213 10 §0 411 6s 757 86 Iazr 41 10S 2295 71 160 $049 B22 425 G8 7a0 G7 1967 | 106 2060 165 101.00 22 4a) 21 70 G10 88 408 fo? 2428 77 170 T1280 2% 238 a55 "| 71 age 69 tas) 108 2eg0 175 T2540 a8 247 472 72 B80 92 80 ase fon 2862 62 100 19020 37 25613 55 489 73 Bar St 1599 49 110 269 185 154.90 a3 206 505 74 GIS 82 1See 1M 2707 68 190 17070 w 278 523 20 75 945 sa Tem N12 278 195 188.60 iam 18 a7 Figure 1 Schematic of typicl print shop HVAC system age wr GENERAL ANT SPACE DAYS ROO £ YY = > 5] U Sager ose o Co “+4000 6FM \00crM | ce 00 or cd] gl ri ‘The economizer cycle senses and ‘compares outdoor air temperature and return air temperature during the cooling season, ‘When the HVAC system calls for cooling and the outdoor air tempera- ture is low enough — typically 55° or lower — the outside air and exhaust air dampers are positioned to provide the required supply air temperature to maintain cooling, and the recircu- lated air damper is positioned to maintain the required supply air vol ume. When the outdoor air tempera ture is higher than the supply air temperature required to maintain cooling but is lower than the return air temperature, the make-up air and exhaust air dampers are 100% open. ‘The recirculation air damper closes, and the building refrigeration system provides the portion of cooling load. that cannot be provided by outside air intake. From this it can be seen that it is possible to introduce 100% outside air into a building during the cooling Forma For example, if our print shop were using 100% outdoor air at 55 degrees and 40% RH, then the moisture required will be: 5.19 ~ 4.89 X 40% RED = 3.23 ax/t ‘Therefore, on 2 15,000 CFM system, the humidification load will be: 15,000 X_ 3.28 X 60 min/he =415 Ibs/he 7,000 grains /Tb In the above examples, the largest humidification load was due to the ‘economizer cycle at 415 Ibs/br. Cooling or refrigeration loads As air is cooled, it loses its ability to hold moisture. If itis cooled ‘enough, some of the moisture will ‘condense out. This is known as cooling load. Cooling load calcula- tions can be important for process applications or refrigeration applica- tions to product dehydration, Forma 7 ‘Assume that during the summer the HIVAC system is in the cooling mode. ‘The air leaving the cooling ‘coil is at 55°F and 90% RH. In ‘order to maintain the desired 47% [RH in the space, moisture must be addled using the Following formula: Desired 80°F 4796 RH =5.19 gr/f3 space Formula 1) 55° 90% = 489x090 = 4.40 g/d Grains 0 add = 0.79 go 15,000 x 0.79 x 60 min/br = 101.57 Ihs/he 7,000 grains/b Table 4 Design outdoor JANUARY JULY JANUARY JuLy conditions Relative Humidity Relative Humidity Relative Humidity Relative Humiity (RH) (%0R.H,) (% RH) (RA) 2 2 ox 2 site ty Me (ea eatae [cathe |. state cy LEP cee tat | © ma ot See lets Se Se ea oe a ee Ree eS GE OT BIE Ss sre i8 i Blk ee Sik 6 lel gale =a eee Sees seis Steklo) adaeel = ee eee eee ee a ee eee Pneamwalle tafe all Seales

También podría gustarte