Está en la página 1de 14

PERDIDA DE CARGA DIAMETRO DE C

SECCION CAUDAL ELEGIDA


DIAMETRO CALCULADO
Q K D5 D
(ft3/min) (m3/h) (-) (in5) (in)
A-1 600 1019.4 2.019 88314.0625 9.8
A-2 400 679.6 2.019 39250.6944 8.3
A-B 1000 1699.0 2.019 245316.84 12.0
C-3 500 849.5 2.019 61329.21 9.1
C-4 500 849.5 2.019 61329.21 9.1
C-D 2000 3398.0 2.019 981267.361 15.8
E-5 500 849.5 2.019 61329.21 9.1
E-6 500 849.5 2.019 61329.21 9.1
E-F 3000 5097.0 2.019 2207851.56 18.6
G-7 600 1019.4 2.019 88314.0625 9.8
G-8 500 849.5 2.019 61329.21 9.1
G-H 4100 6965.9 2.019 4123776.08 21.0
DIAMETRO DE CONDUCTO PRESION DINAMICA DEL
AREA VELOCIDAD
IAMETRO CALCULADO DIAMETRO REDONDEADO CONDUCTO
D D A v VP
2 2
(mm) (in) (mm) (ft ) (m ) (fpm) (m/s) (in WC)
247.8 10 254 0.545 0.0507 1100 5.6 0.075
210.7 8 203.2 0.349 0.0324 1146 5.8 0.082
303.9 12 304.8 0.785 0.0730 1273 6.5 0.101
230.3 9 228.6 0.442 0.0410 1132 5.7 0.080
230.3 9 228.6 0.442 0.0410 1132 5.7 0.080
401.0 16 406.4 1.396 0.1297 1432 7.3 0.128
230.3 9 228.6 0.442 0.0410 1132 5.7 0.080
230.3 9 228.6 0.442 0.0410 1132 5.7 0.080
471.7 19 482.6 1.969 0.1829 1524 7.7 0.145
247.8 10 254 0.545 0.0507 1100 5.6 0.075
230.3 9 228.6 0.442 0.0410 1132 5.7 0.080
534.4 21 533.4 2.405 0.2235 1705 8.7 0.181
PRESION DINAMICA DEL LONGITUD DE PERDIDA
CONDUCTO CONDUCTO
VP L 12 L/D
(Pa) (ft) (m) (-) (in wc) (mm cw)
19 20 6.096 24.0 0.035 0.897
20 16 4.877 24.0 0.038 0.973
25 28 8.534 28.0 0.055 1.401
20 24 7.315 32.0 0.050 1.265
20 18 5.486 24.0 0.037 0.949
32 32 9.754 24.0 0.060 1.520
20 22 6.706 29.3 0.046 1.160
20 24 7.315 32.0 0.050 1.265
36 20 6.096 12.6 0.036 0.905
19 20 6.096 24.0 0.035 0.897
20 20 6.096 26.7 0.042 1.054
45 24 7.315 13.7 0.048 1.230
Constante K para varias perdidas

F
K

F
K
onstante K para varias perdidas por friccion (F) en WC por 100 pies de longitud de conducto

(wc/100ft) 0 0.1 0.2 0.3 0.4 0.5 1


(-) 0 1.427 2.019 2.474 2.857 3.194 4.517

(wc/100ft) 2 3 4 5 6 7
(-) 6.388 7.823 9.032 10.1 11.06 11.9
PORCENTAJE PORCENTAJE DE AREA DE CONDUCTO

1 2
2 3.5
3 5.5
4 7
5 9
6 10.5
7 11.5
8 13
9 14.5
10 16.5
11 17.5
12 18.5
13 19.5
14 20.5
15 21.5
16 23
17 24
18 25
19 26
20 27
21 28
22 29.5
23 30.5
24 31.5
25 32.5
26 33.5
27 34.5
28 35.5
29 36.5
30 37.5
31 39
32 40
33 41
34 42
35 43
36 44
37 45
38 46
39 47
40 48
41 49
42 50
43 51
44 52
45 53
46 54
47 55
48 56
49 57
50 58
51 59
52 60
53 61
54 62
55 63
56 64
57 65
58 65.5
59 66.5
60 67.5
61 68
62 69
63 70
64 71
65 71.5
66 72.5
67 73.5
68 74.5
69 75.5
70 76.5
71 77
72 78
73 79
74 80
75 80.5
76 81
77 82
78 83
79 84
80 84.5
81 85.5
82 86
83 87
84 87.5
85 88.5
86 89.5
87 90
88 90.5
89 91.5
90 92
91 93
92 94
93 94.5
94 95
95 96
96 96.5
97 97.5
98 98
99 99
100 100

DATOS INICIALES

TIPO DE INSTALACION: Oficina publica


CAUDAL TOTAL DE AIRE Q (m3/h) 9000

VELOCIDAD INICIAL DE COLECTOR PRINCIPAL v (m/s) 9


SECCION DE COLECTOR PRINCIPAL A (m2) 0.28
FACTOR DE CONTROL-ROZAMIENTO EN
APLICACIÓN FACTOR DE CONTROL DEL NIVEL DE RUIDO Conductos principales
(Conductos principales) Suministro Retorno
Residencias 3 5 4
Apartamentos
Dormitorios de hotel 5 7.5 6.5
Dormitorios de hospital
Oficinas particulares
Despachos de directores 6 10 7.5
Bibliotecas
Salas de cine y teatro
4 6.5 5.5
Auditorios
Oficinas publicas
Restaurantes de primera categoria
7.5 10 7.5
Comercios de primera categoria
Bancos
Comercios de categoria media
9 10 7.5
Cafeterias
Locales industriales 12.5 15 9
ELEGIR DE TABLA 6
DIMENSIONES DE COLECTOR PRINCIPAL
DAMETRO
RECTANGULAR
EQUIVALENTE
ANCHO ALTO DIAMETRO
a b D
(mm) (mm) (mm)
540 540 600

PERDIDA POR ROZAMIENTO EN


CONDUCTO REDONDO
ONTROL-ROZAMIENTO EN CONDUCTO
Conductos derivados
Suministro Retorno
3 3

6 5

8 6

5 4

8 6

8 6
11 7.5