Está en la página 1de 2

SOLO CHILLER

Equations

SOLO SISTEMA CHILLER, CALCULO DEL SISTEMA DE ENFRIAMIENTO REFRIGERADO, EN LAS CONDI-
CIONES MAS EXIGENTES, O SEA CUANDO Ta=26◦
Q = 120 (1)

T w1 = 15 (2)

T w2 = 10 (3)

DATOS DEL EVAPORADOR


U e = 0, 8 Kw/m2◦ C (4)

T e = T w2 − 5 eSPECIFICADO PARA SITUACION MAXIMA (5)

T amax = 24 (6)

T c = 5 + 1, 4 · T amax ESPECIFICADO PARA TODAS LAS CONDICIONES DE OPERACION DEL CHILLER (7)
(T w1 − T e) − (T w2 − T e)
LM T De =   (8)
ln TT w2−T
w1−T e
e

Q = U e · Ae · LM T De (9)

Q = mr · ER (10)

ER = h2 − h1 (11)

TERMODINAMICA DEL CICLO


R$ = ‘R134a’ (12)

h4 = h (R$; T = T c; x = 0) (13)

h1 = h4 (14)

pc = P (R$; T = T c; x = 0) (15)

pe = P (R$; T = T e; x = 0) (16)

h2 = h (R$; T = T e; x = 1) (17)

s2 = s (R$; T = T e; x = 1) (18)

denv = ρ (R$; T = T e; x = 1) (19)

denl = ρ (R$; T = T c; x = 0) (20)

h3 = h (R$; p = P c; s = s2) (21)

T 3 = T (R$; p = pc; s = s2) (22)

Cp = cp (R$; p = pc; s = s2) (23)

1
Cv = cv (R$; p = pc; s = s2) (24)

CONDENSADOR
Qc = mr · (h3 − h4) (25)

Qc = mac · Cpac · (T ac2 − T amax) (26)

Cpac = cp (Airha ; T = T amax; P = 101) (27)

Qc = U c·Ac·LM T Dc SE DETERMINA EL VALOR DEL AREA DEL CONDENSADOR PARA LA SITUACION MAXIMA(28)

(T c − T ac2) − (T c − T amax)
LM T Dc =   (29)
ln TTc−T
c−T ac2
amax

U c = 0, 5 (30)

Gac = 62000 (31)

mac = Gac · den24 /3600 (32)

den24 = ρ (Airha ; T = T amax; P = 101) (33)

P otc = 10 Kw (34)

COMPRESOR
n = Cp/Cv (35)
1/n
rel = (pc/pe) (36)

Et = 1 − 0, 08 · (rel − 1) (37)

mr = denv · V f is · Et DETERMINA EL FLUJO VOLUMETRICO DEL COMPRESOR Vfis (38)

W c = mr · (h3 − h2) (39)

SOLUCION
Ac=25,19 Ae=20,79 Gac=62000 LMTDc=10,91 LMTDe=7,213 mac=20,39 mr=0,8154

Potc =10 Q=120 Qc=137,4 T3=42,22 Tac2=30,69 Tamax=24 Tc=38,6 Te=5

Tw1=15 Tw2=10 Uc=0,5 Ue=0,8 Vfis=0,05288 Wc=17,42

También podría gustarte