CUADRO PARA EL CÁLCULO DE LA DEMANADA Aérea Subterránea X

3. 0 PROYECTO ELECTRICO: SENA 2 JULIO 08-2020 ESTRATO:5 ó 6

TRAMO LONGITUD AREA VA (m2) Dmax-KVA MOMENTO No FASES I AMP CALIBRE FP KG REGULACIÓN % (Kxmomento) PROTECCIÓN

K
m m2 KVAXm A =(KG/208/208)XFC PARCIAL TOTAL

POSTE a CAJA 3#2 F+1#2 N + 1#8D


8 22.138 177.104 3 61.448 0.95 59.2879 0.00137 0.242 0.242 3x80A
NÚMERO 1 CU-THHN
CAJA NÚMERO 1 a 3#2 F+1#2 N + 1#8D
7 22.138 154.966 3 61.448 0.95 59.2879 0.00137 0.212 0.454 3x80A
CAJA NÚMERO 2 CU-THHN
CAJA NÚMERO 2 a 3#2 F+1#2 N + 1#8D
5 22.138 110.960 3 61.448 CU-THHN 0.95 59.2879 0.00137 0.151 0.605 3x80A
TOTALIZADOR
TOTALIZADOR A 3#2 F+1#2 N + 1#8D
2.5 22.138 55.345 3 61.448 0.95 59.2879 0.00137 0.075 0.68 3x80A
BARRAJE CU-THHN

LOCAL 1 8 35 22 0.770 6.160 2 3.5 2#8 F+1#8 N + 1#8D 0.95 227.585 0.01057 0.065 0.745 2x30A
CU-THHN

LOCAL 2 15 50 22 1.100 16.500 2 5 2#8 F+1#8 N + 1#8D 0.95 227.585 0.01057 0.174 0.854 2x30A
CU-THHN
2#8 F+1#8 N + 1#8D
LOCAL 3 7 45 22 0.990 6.930 2 4.5 CU-THHN 0.95 227.585 0.01057 0.730 1.410 2x30A

2#8 F+1#8 N + 1#8D


LOCAL 4 2 60 22 1.320 2.640 2 6 CU-THHN 0.95 227.585 0.01057 0.027 0.707 2x30A

2#8 F+1#8 N + 1#8D


APTO 201 19 70 32 2.412 45.828 2 11.596 CU-THHN 0.95 227.585 0.01183 0.542 1.215 2x30A

2#8 F+1#8 N + 1#8D


APTO 202 22 80 32 2.508 55.176 2 12.057 CU-THHN 0.95 227.585 0.01183 0.652 1.332 2x30A

2#8 F+1#8 N + 1#8D


APTO 203 29 60 32 2.316 67.164 2 11.134 CU-THHN 0.95 227.585 0.01183 0.794 1.474 2x30A

2#8 F+1#8 N + 1#8D


APTO 204 25 79 32 2.498 62.450 2 12.009 CU-THHN 0.95 227.585 0.01183 0.738 1.418 2x30A

2#8 F+1#8 N + 1#8D


APTO 301 22 70 32 2.412 53.064 2 11.596 CU-THHN 0.95 227.585 0.01183 0.627 1.307 2x30A

2#8 F+1#8 N + 1#8D


APTO 302 25 80 32 2.508 62.700 2 12.057 CU-THHN 0.95 227.585 0.01183 0.741 1.421 2x30A

2#8 F+1#8 N + 1#8D


APTO 303 32 60 32 2.316 74.112 2 11.134 CU-THHN 0.95 27.585 0.01183 0.876 1.556 2x30A

2#8 F+1#8 N + 1#8D


APTO 304 28 79 32 2.498 69.944 2 12.009 CU-THHN 0.95 227.585 0.01183 0.827 1.507 2x30A

2#8 F+1#8 N + 1#8D


APTO 401 25 70 32 2.412 60.3 2 11.596 CU-THHN 0.95 227.585 0.01183 0.713 1.393 2x30A

2#8 F+1#8 N + 1#8D


APTO 402 28 80 32 2.502 70.224 2 12.057 CU-THHN 0.95 227.585 0.01183 0.830 1.510 2x30A

2#8 F+1#8 N + 1#8D


APTO 403 35 60 32 2.316 81.060 2 11.134 CU-THHN 0.95 227.585 0.01183 0.958 1.638 2x30A

2#8 F+1#8 N + 1#8D


APTO 404 31 79 32 2.498 77.4 2 12.009 CU-THHN 0.95 227.585 0.01183 0.916 1.596 2x30A

2#8 F+1#8 N + 1#8D


APTO 501 29 70 32 2.412 69.948 2 11.596 CU-THHN 0.95 227.585 0.01183 0.827 1.507 2x30A

2#8 F+1#8 N + 1#8D


APTO 502 31 80 32 2.508 77.748 2 12.057 CU-THHN 0.95 227.585 0.01183 0.919 1.599 2x30A

3#8 F+1#8 N + 1#8D


APTO 503 37 60 32 2.316 85.692 3 11.134 CU-THHN 0.95 227.585 0.00526 0.450 1.130 2x30A

3#8 F+1#8 N + 1#8D


APTO 504 34 79 32 2.528 84.932 3 12.009 CU-THHN 0.95 227.585 0,,00526 0.446 1.126 2x30A

3#4 F+1#4 N + 1#8D


SERVICIOS GENERALES 5 5.450 3 15.127 CU-THHN 0.95 92.4032 0.00213 0.058 0.738 3x50A
DEMANDA MAXIMA TOTAL: SR/FdiverR + SACR + SC/FdiverC + SACC

38.936 5.45 4.180

2.797 1.510

13.920 5.45 2.768 22.138