OBRA DE TOMA
TIPO PRESA DERIVADORA
1.- SECCION TRANVERSAL DEL RIO:

PERFIL TRANVERSAL
1200
1000
800
600
400
200
0
0.2 10.2 20.2

DATOS HIDRLOGICOS
Qmax : 322.81 m^3/s
Qmin : 326 l/s
Qd : 120.1 l/s
2.-CURVA DE DESCARGA:

Y A P R n So Q
0.1 0.12 1.3 0.09 0.02 0.02 #N/A
0.5 0.88 2.8 0.31 0.02 0.02 #N/A
1 4.23 8.5 0.50 0.02 0.02 #N/A
1.50 9.51 12.70 0.75 0.02 0.02 #N/A
2.00 16.44 15.40 1.07 0.02 0.02 #N/A
2.50 23.92 16.60 1.44 0.02 0.02 #N/A

CURVA DE DESCARGA
3
f(x) = 0.1202010957 x^1.7829849049
2.5 R² = 0.9821370024
2

1.5

0.5
Bmax =
0
0 1 2 3 4 5 6 7
1.5

0.5

0 Bmin =
0 1 2 3 4 5 6 7

Qmax = 322.81 m^3/s Ymax = 3.25 mts. 15 mts.


Qmin = 0.33 m^3/s Ymin = 0.16 mts. 5 mts.

3.-CALCULO DE LA SOCAVACION:

Q max
q q= 21.52 m^3/s/m [Caudal Unitario]
B max
1
q 2
 3
F= 4.7 [factor de LACEY] Ds = 6.236 mts.
Ds  1.35   
piedras pequeñas y gravas gruesas
F 
Dsa  Ds  Ksa Ksa = 1.5 [factor de ajuste] Dsa = 9.35 mts:
tramos rectos y curvas moderadas

ds  Dsa  Y max ds = 6.10 mts. [Altura de Socavacion a partir del lecho]

Ymax

ds

4.-CALCULO DE LA CARGA HIDRAULICA SOBRE EL AZUD:

V^2/(2*g)
1
Ho  q 2
 3
Hd Yc   

 g 

P Yc = 3.61 mts. [Tirante critico]

1.3  Yc  Ho  1.5  Yc

Asumo : Ho = 1.3 Yc Ho = 4.70 [Carga Hidraulica sobre el AZUD]

P= 3 mts. [Asumo]

V2 Q2
Ho Hd  Q  VA Q  V   B   Hd  P   Ho Hd  2
2 g B  (Hd  P)2  2  g
V2 Q2
Ho Hd  Q  VA Q  V   B   Hd  P   Ho Hd  2
2 g B  (Hd  P)2  2  g

Hd = 1.35 mts. [Energia en el punto aguas arriba]

5.- CALCULO DEL COEFICIENET DE DESCARGA.-

P = 1.3 mts.
P P
Ho = 4.70 mts.  Abaco  0.28 C= 2.2 [Coef. de descarga]
Ho Ho
3
L=B= 15 mts. Qv = 336.09 m^3/s
Qv  C  L  Ho 2

Qv = 336.09 > Qmax = 322.81 Ok !!! Cumple

6.-CALCULO DEL PERFIL AERODINAMICO.-

- Formula general para el perfil tipo CREAGER

K = 2 [Para paredes verticales]


n 1
X  K  Hd
n
Y
n= 1.85 [Para paredes verticales]

Xc = 0,283 Hd R2 = 0,234 Hd
X 1.85
Y Yc = 0,126 Hd R2 - R1 = 0,296 Hd
2  Hd 0.85 R1 = 0,530 Hd

Y X PERFIL AERODINAMICO
0 #N/A 0 0 0
0.02 #N/A 0 -0.02 1 0.55 2 3 4 5 6
0.05 #N/A -0.2 -0.05 0.9
0.1 #N/A -0.1 1.31
0.2 #N/A -0.4 -0.2 1.91
0.3 #N/A -0.3 2.38
0.4 #N/A -0.6 -0.4 2.78
0.5 #N/A -0.5 3.13
0.6 #N/A -0.8 -0.6 3.46
0.7 #N/A -0.7 3.76
0.8 #N/A -1 -0.8 4.04
0.9 #N/A -0.9 4.3
1.0 #N/A -1.2 -1 4.56
1.1 #N/A -1.1 4.8
1.2 #N/A -1.4 -1.2 5.03
1.3 #N/A -1.3 5.25
-1.3 0
Xc = 0.38205
Yc = 0.1701
R1 = 0.7155
R2 = 0.3159
R2-R1 = 0.3996

7.-DISEÑO DEL CUENCO DE DISIPACION.- Ymax=3,25 mts

V1  2  g  Y max V1 = 7.99 m/s Flujo Supercritico

Q
Q  V1  A1 Y1  Y1 = 2.70 mts. [Tirante aguas abjo del AZUD]
V1  B
V
F F= 1.55 > 1
g  Y1
Y2 1
Y1 2

  1 8  F2  1  Y2 = 4.72 mts.

Y3 = Ymax = 3.25 mts. e= 0.3 mts. [Espesor de la Losa]

[Longitud del Colchon Disipador]

Ls  5   Y 2  Y1 Ls = 10.14 mts.

8.-CALCULO DE LA ESTABILIDAD.-

0.38 #N/A
1.35

1.3

2.70
0.3

3.00
2.95

µ= 0.8 [Coef. de friccion ]

CARGAS VERTICALES :
PESO PROPIO :
γ HºCº = 2300 Kg/m^3

P1 = 1142.33 Kg/m

P2 = #N/A Kg/m

P3 = #N/A Kg/m

CARGA DE AGUA :
γ w = 1000 Kg/m^3

W1 = 515.77 Kg/m

W2 = #N/A Kg/m

SUPRESION :
γ suelo = 1800 Kg/m^3
C= 0.25 [Factor de Subpresion]

S1 = #N/A Kg/m

S2 = #N/A Kg/m
∑Fv = #N/A Kg/m

CARGAS HORIZONTALES :
EMPUJE DEL AGUA :
γ w = 1000 Kg/m^3

E1 = 3511.25 Kg/m

∑Fh = 3511.25 Kg/m

CSD 
Fv μ  1,5  1,1 CSD = #N/A #N/A 1.1 #N/A
Fh

8.2.- VERIFICACION AL VUELCO :

MEMENTOS VOLCADORES :

∑Mv = #N/A Kg m/m

MOMENTO ESTABILIZANTES :

∑Me = #N/A Kg m/m

CSV 
 Me  1,1 CSV = #N/A #N/A 1.1 #N/A
 Mv
9.- DISEÑO DE LA OBRA DE TOMA COMO ORIFICIO :

Qd = 0.120 m^3/s

Q  V  Aor V= 0.75 m/s [Vel. De Entrada] 0,5-1 m/s


por norma
Qd
Aor  Aor = 0.16 m^2
V

Aor  b  b b= 0.4 m

Ag  Kt  Kl  Aor
Ag  Kt  Kl  Aor Ag = 0.28 m^2

CALCULO DE PERDIDAS POR REJILLA :

2
 Aor   Aor 
K  1,45  0,45       K= 0.9
 Ag   Ag 
V2
hr  K  hr = 0.025 m
2g

CALCULO DE PERDIDAS POR ENTRADA :


Qd = 0.120 m^3/s
Cd = 0.8
Aor = 0.2

Q2
he  he = 0.036 m
Cd  Aor 2  2  g

10.-DISEÑO DE LA OBRA DE TOMA COMO VERTEDERO :


Qd = 0.120 m^3/s
K= 0.8
K! = 0.85
H= 0.3 m
C= 1.8

Q
L 3
L= 0.60 m

C H K K!
2

f = 0.3
s = 0.01875
b = 0.1
β = 1.79
α = 60

 s
LT  L   1  f    1    s LT = 0.9 m
 b
CALCULO DE PERDIDAS POR REJILLA :
V= 0.75 m/s

4
s 3
C  β    sen α C= 0.2
b 

V2
h  C  Δh = 0.005 m
2g
DISEÑO DEL CANAL TRAMO 1

DATOS:

Qd = 120 l/s
So = 0.005
n = 0.018 [Hormigón Ciclopeo]
Vmax = 3 m/s

1.-CALCULO DEL TIRANATE PARA UNA SECCION TIPO

2
2 1
1 B  2Y  1
 
2
2 1 3
Q   A  R  So 3 2
Q   2 Y2     So 2
n Y n  4Y 

Y= 0.25 mts.
0.49
B= 0.50 mts. constructivamente

2.-CALCULO DE LA VELOCIDAD EN EL CANAL

Q
V V= 0.96 m/s OK!!! Velocidad Autolimpiante
A

3.-CALCULO DEL NUMERO DE FROUD

V
F F= 0.61 < 1 FLUJO SUBCRITICO
gY
4.-DIMENCIONAMIENTO DEFINITIVO

Y
BL  BL = 0.08 mts.
3
B = 0.50 mts. [Base del Canal]
Y = 0.25 mts. [Tirante del Canal]
BL = 0.08 mts. [Borde Libre]
e = 0.20 mts. [Espesor del Canal]

= 0.08 m

= 0.25 m
= 0.20 m

DISEÑO DEL CANAL TRAMO 2

DATOS:

Qd = 100 l/s
So = 0.0028
n = 0.018 [Hormigón Ciclopeo]
Vmax = 3 m/s

1.-CALCULO DEL TIRANATE PARA UNA SECCION TIPO

2
2
1
1
B  2Y2
 1
1
 
3
Q   A  R  So 3 2 2 Q   2 Y2     So 2
n Y n  4Y 

Y= 0.26 mts.
0.52
B= 0.60 mts.

2.-CALCULO DE LA VELOCIDAD EN EL CANAL

Q
V V= 0.64 m/s OK!!! Velocidad Autolimpiante
A
3.-CALCULO DEL NUMERO DE FROUD

V
F F= 0.40 < 1 FLUJO SUBCRITICO
gY

4.-DIMENCIONAMIENTO DEFINITIVO
BL = 0.09 mts.
Y
BL  BL = 0.1 mts. Asumo Constructivamente
3
B = 0.60 mts. [Base del Canal]
Y = 0.26 mts. [Tirante del Canal]
BL = 0.10 mts. [Borde Libre]
e = 0.20 mts. [Espesor del Canal]

= 0.10 m
= 0.26 m

= 0.2 m
DISEÑO DEL CANAL TRAMO 3

DATOS:

Qd = 100 l/s
So = 0.0019
n = 0.018 [Hormigón Ciclopeo]
Vmax = 3 m/s

1.-CALCULO DEL TIRANATE PARA UNA SECCION TIPO

2
2 1
1 B  2Y  1
 
2
Q   A  R  So 2 1 3
3 2
Q   2  Y2     So 2
n Y n  4Y 

Y= 0.28 mts.
0.56
B= 0.60 mts. constructivamente

2.-CALCULO DE LA VELOCIDAD EN EL CANAL

Q
V V= 0.60 m/s OK!!! Velocidad Autolimpiante
A

3.-CALCULO DEL NUMERO DE FROUD

V
F F= 0.36 < 1 FLUJO SUBCRITICO
gY
4.-DIMENCIONAMIENTO DEFINITIVO

Y
BL  BL = 0.09 mts.
3 BL = 0.1 mts. Asumo Constructivamente

B = 0.60 mts. [Base del Canal]


Y = 0.28 mts. [Tirante del Canal]
BL = 0.10 mts. [Borde Libre]
e = 0.20 mts. [Espesor del Canal]

= 0.10 m

= 0.28 m
= 0.20 m

DISEÑO DEL CANAL TRAMO 4

DATOS:

Qd = 100 l/s
So = 0.0019
n = 0.018 [Hormigón Ciclopeo]
Vmax = 3 m/s

1.-CALCULO DEL TIRANATE PARA UNA SECCION TIPO

2
2 1
1 B  2Y2
 1
1
 
3
Q   A  R  So 3 2 2 Q   2  Y2     So 2
n Y n  4Y 

Y= 0.26 mts.
0.52
B= 0.55 mts.

2.-CALCULO DE LA VELOCIDAD EN EL CANAL

Q
V V= 0.70 m/s OK!!! Velocidad Autolimpiante
A
3.-CALCULO DEL NUMERO DE FROUD

V
F F= 0.44 < 1 FLUJO SUBCRITICO
gY

4.-DIMENCIONAMIENTO DEFINITIVO
BL = 0.09 mts.
Y
BL  BL = 0.1 mts. Asumo Constructivamente
3
B = 0.55 mts. [Base del Canal]
Y = 0.26 mts. [Tirante del Canal]
BL = 0.10 mts. [Borde Libre]
e = 0.20 mts. [Espesor del Canal]

= 0.10 m
= 0.26 m

= 0.2 m
DISEÑO DEL DISIPADOR DE ENERGIA
CAIDA VERTICAL

DATOS :
PROGRESIVA 0+330 - 0+435
Qd = 120 l/s [Caudal de Diseño] 0.12
So = 0.002 m/m [Pendiente del canal]
H= 1 mts. [Desnivel de la Rapida]

1.-CALCULO DEL CANAL DE INGRESO :

2 1 2
1 B  2Y2
 1
2 1
 
3
Q   A  R 3  So 2 Q   2 Y2     So 2
n Y
n  4Y 

Y= 0.26 mts.

B= 0.52 mts. 0.6

2.-CALCULO DE LA ENERGIA EN EL CANAL DE INGRESO :

V2
V= 0.89 m/s E1  Y  E1 = 0.30 mts.
2g

3.-CALCULO DE LA SECCION DE CONTROL :

Caso de seccion Rectangular 1


 Qd  2 3 Qd 2
Vc 2
1
Qd E 1   2  
E 1  Yc   q2  3
q  B1  g   1 2

2g Yc      Qd  3 2
B1
g   B1   2    2  g
  B1  g  
 
1
 Qd 2  3 Qd 2
Vc 2
1

E1   2   
q  2 Qd
 B1  g  1 2
3
E 1  Yc  Yc    q  
2g B1   Qd   2 3
g   B1   2    2  g
  B1  g  
 

B1 = 0.43 mts. Asumo 0.45

Yc = 0.20 mts. Vc = 1.40

0.20

4.-CALCULO DE LA LONGITUD DE TRANSICION :

α = 22.5 º [Angulo de Transicion]


B = 0.6 mts. [Ancho del Canal]
B1 = 0.45 mts. [Ancho de la Rapida]

B  B1
LT 
2  tan g  α 
LT = 0.18 mts. LT = 0.20 mts.

5.-CALCULO DE LA LONGITUD Y LA PROFUNDIDAD DEL COLCHON DISIPADOR :

Qd= 120.00 l/s [Caudal de Diseño]


h= 1.33 mts. [Altura de Caida del Agua]
B= 0.43 mts. [Base del Canal]
^
�=�^�/
(𝑩^𝟐∗𝒈∗𝒉^𝟑 ) D= 0.00335

�=𝒉∗(𝟏𝟐,𝟔∗�^(𝟎,𝟐𝟕)−𝟐,𝟕∗�^(𝟎,� L= 3.287 mts.


𝟐𝟓)) Asumo Constructivamente
L= 3.300 mts.

OTRO CRITERIO

Tiemo de Caida del Chorro de Agua


�=√((𝟐∗(∆𝒛+𝒆))/𝒈)
�=√((𝟐∗(∆𝒛+𝒆))/𝒈)
t= 0.52 s

Distancia Horizontal Recorrida por el Chorro

𝑿�=𝑽𝒄∗�
Xn= 0.73 mts.

Longitud del Colchon

�=𝟐∗𝑿�
L= 1.46 mts.
Constructivamente Asumo
L= 1.50 mts.
Para la construccion de la longitud del colchon adopataremos el resultado que obtuvimos aplicando el primer metodo

L= 3.500 mts.
DISEÑO DEL DESARENADOR
DATOS :
Qd = 0.12 m^3/s
B= 0.50 mts. ancho del canal (canal diseñado)
b= 1 mts. ancho de la camara de sedimentacion

1.-DIAMETRO DE LA PARTICULA, VELOCIDAD DE SEDIMENTACION :

D= 0.2 mm Vs = 2.16 cm/s


tabla15,3 -pag200 -pronar
2.-CALCULO DE LA VELOCIDA DE ESCURRIMIENTO :

D= 0.2 mm [Diametro de la Particula Asumida]


a= 44 [Coef. de Decantacion] tabla-15,2 -pag199 -pronar

Vd  a  D Vd = 0.20 m/s

3.-CALCULO DE LA ALTURA DE LA CAMARA DE SEDIMENTACION :


1.63978318
Qd
H 
Vd  b H= 0.61 mts.

4.-CALCULO DEL TIEMPO DE RETENCION :

H
ts  ts = 28.23 seg.
Vs

5.-CALCULO DE LA LONGITUD MINIMA DE LA CAMARA :

K= 1.25 [Coef. de Seguridad] tabla-15,4-pag201-pronar

L  K  Vd  ts L= 7 mts.

6.-CALCULO DE LA LONGITUD DE TRANSICION :

α = 12.5 º [Angulo de Transicion]


B=T2 0.50 mts.
b=T1 1 mts.

b B
LT 
2  tan g  α 
b B
LT 
2  tan g  α 
LT = 0.90 mts.

LT = 0.90 mts. [Asumo por fines Constructivos]


DISEÑO DEL PUENTE CANAL

DATOS :

Qd = 120 l/s
n = 0.018
Sc = 0.0075 m/m [Pendiente del Puente Canal]
So = 0.005 m/m [Pendiente del Canal de Entrada ]
L = 44.22 mts. [Longitud del Puente Canal]

B1 = 0.5 mts. B4 = 0.5 mts.


Seccion 1 Seccion 4
Y1 = 0.25 mts. Y4 = 0.25 mts.

B2 = 0.3 mts. B3 = 0.3 mts.


Seccion 2 Seccion 3
Y2 = ? mts. Y3 = ? mts.

1.- CALCULO DE LA VELOCIDAD :

Q
V4  V4 = 0.96 m/s
A

2.-CALCULO DEL NUMERO DE FROUD :

V4
F4  F4 = 0.61 < 1 Flujo Subcritico OK !!!!
g  Y4
3.-CALCULO DE LA TRANSICION DE ENTRADA :
T = 0.5 mts. [Espejo de agua en el canal]
T b
LT 
2  Tang  β 
T b
LT  b = 0.3 mts. [Ancho en el Puente]
2  Tang  β  β = 22.5 [Angulo de Transicion]

LT = 0.241421 mts.

LT = 1 mts. [Asumo por fines Contructivos]

4.-CALCULO DEL TIRANTE EN LA SECCION 3 :

Sc = 0.0075 m/m
LT = 1 mts.
Ks = 0.5 [Ceficiente de perdida por Salida en Linea Recta]

V3
2
V4
2
 V3 2  V4 2 
S 3 4  L T  Y3   Y4   Ks   

2g 2g  2g 

Y3 = 0.3 mts. V= 1.33333333

5.-CALCULO DEL NUMERO DE FROUD EN LA SECCION 3 :

V3
F3  F3 = 0.78 < 0.8 Flujo Subcritico OK !!!!
g  Y3

9.-CALCULO DEL TIRANTE EN LA SECCION 2 :

2
 
V3  0,7937  n   V2  V3  
2 2
V2
Sc  L  Y2   Y3     L
2g 2  g  2
R 2  R 3  3 

Y2 = 0.23 mts.

10.-CALCULO DEL TIRANTE EN LA SECCION 1 :


Sc = 0.0075 m/m
LT = 1 mts.
Ke = 0.5 [Ceficiente de perdida por Entrada en Linea Recta]

V1
2
V2
2
 V2 2  V12 
S12  L T  Y1   Y2   Ke   

2g 2g  2  g 
V1
2
V
2
 V 2  V12 
S12  L T  Y1   Y2  2  Ke   2 

2g 2g  2  g 

Y1 = 0.21 mts.

11.-DIMENSIONAMIENTO FINAL :

Y1 = 0.21
Y2 = 0.23

Y3 = 0.3 Y4 = 0.25
DISEÑO DEL DISIPADOR DE ENERGIA
RAPIDA

DATOS :
PROGRESIVA 0+330 - 0+435
Qd = 100 l/s [Caudal de Diseño]
So = 0.0019 m/m [Pendiente del canal]
H= 7.25 mts. [Desnivel de la Rapida] > 2,5 que permite la norma por eso se hace esta obra
L= 65 mts. [Longitrud de la Rapida] pag-124-pronar

1.-CALCULO DEL CANAL DE INGRESO :

2 1 2
1 B  2Y2
 1
2 1
 
3
Q   A  R 3  So 2 Q   2 Y2     So 2
n Y
n  4Y 

Y= 0.28 mts.

B= 0.60 mts.

2.-CALCULO DE LA ENERGIA EN EL CANAL DE INGRESO :

V2
V= 0.60 m/s E1  Y  E1 = 0.30 mts.
2g

3.-CALCULO DE LA SECCION DE CONTROL :

Caso de seccion Rectangular 1


 Qd  2 3 Qd 2
Vc 2
1
Qd E 1   2  
E 1  Yc   q2  3
q  B1  g   1 2

2g Yc      Qd  3 2
B1
g   B1   2    2  g
  B1  g  
 
1
 Qd 2  3 Qd 2
Vc 2
1

E1   2   
q 
2 Qd
 B1  g  1 2
3
E 1  Yc  Yc    q  
2g B1   Qd   2 3
g   B1   2    2  g
  B1  g  
 

B1 = 0.36 mts. Asumo 0.4

Yc = 0.20 mts.

0.20

4.-CALCULO DE LA LONGITUD DE TRANSICION :

α = 22.5 º [Angulo de Transicion]


B = 0.6 mts. [Ancho del Canal]
B1 = 0.4 mts. [Ancho de la Rapida]

B  B1
LT 
2  tan g  α  LT = 0.24 mts. LT = 0.25 mts.

5.-CALCULO DE TIRANTES :

Ecuacion General de Tramos Fijos 2


 
SE1  SE 2  V n 
So  X  E1  E 2  S E  X SE  SE   2 
2  3 
R 
 
2
 
2

V
2
V 
1  V n 
2
 V2  n  
So  X  Y1  1  Y2  2     1 2   2    X
2g 2  g 2  R 3  R 3  
 1   2  

6.-CALCULO DEL BORDE LIBRE :

BL  0,61  0,0371  V  Y

Y BL H
0.20 0.63 0.83 BL = 0.9 asumo
0.08 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73
0.09 0.64 0.73

7.-CALCULO DE LA LONGITUD Y LA PROFUNDIDAD DEL COLCHON DISIPADOR :

Y1 = 0.09 mts. [Tirante en el que las Energias se igualan]


Y = 0.28 mts. [Tirante del Canal de Entrada]
B= 0.36 mts. [Base del Canal]
V
F F= 0.64 < 1 Flujo Subcritico
g  Y1

2
Y1 2  Qd Y12
Y2    
2 g  Y1  B 2
4 Y2 = 0.383 mts.

e  1,15  Y 2  Yn e= 0.16 mts.

Ls  5   Y 2  Y1 Ls = 1.48 mts. Constructivamente


Ls = 1.50 mts.
8.-DIMENSIONAMIENTO FINAL :
0.28
0.20

0.2 0.38 0.28


0.09

1.48
Q 0.1
b 0.4
Z 0
S 0.1115
n 0.018

x Dx S Dx Y A P R R^2/3
0 0 6.5 0.7248 0.2000 0.0800 0.8000 0.1000 0.2154
1 6.5 6.5 0.7248 0.0828 0.0331 0.5657 0.0586 0.1508
2 13 6.5 0.7248 0.0881 0.0352 0.5762 0.0612 0.1552
3 19.5 6.5 0.7248 0.0871 0.0348 0.5741 0.0607 0.1544
4 26 6.5 0.7248 0.0872 0.0349 0.5745 0.0607 0.1545
5 32.5 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545
6 39 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545
7 45.5 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545
8 52 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545
9 58.5 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545
10 65 6.5 0.7248 0.0872 0.0349 0.5744 0.0607 0.1545

V V^2/2g E S Dx+E Se Se prom Se prom* Dx E+Se prom Dx


1.2500 0.0796 0.2796 1.0044 0.0109 - - -
3.0184 0.4644 0.5472 1.2719 0.1298 0.0703 0.4572 1.0044
2.8373 0.4103 0.4984 1.2232 0.1082 0.1190 0.7735 1.2719
2.8712 0.4202 0.5072 1.2320 0.1121 0.1101 0.7159 1.2232
2.8655 0.4185 0.5057 1.2305 0.1114 0.1117 0.7263 1.2320
2.8664 0.4188 0.5060 1.2307 0.1115 0.1115 0.7245 1.2305
2.8663 0.4187 0.5060 1.2307 0.1115 0.1115 0.7248 1.2308
2.8663 0.4187 0.5060 1.2307 0.1115 0.1115 0.7247 1.2307
2.8663 0.4187 0.5060 1.2307 0.1115 0.1115 0.7247 1.2307
2.8663 0.4187 0.5060 1.2307 0.1115 0.1115 0.7247 1.2307
2.8663 0.4187 0.5060 1.2307 0.1115 0.1115 0.7247 1.2307

C
0 0
Y1 = 0.087 mts. 1 0.9689
2 0.8502
3 0.8714
4 0.8678
5 0.8684
6 0.8683
7 0.8683
8 0.8683
9 0.8683
10 0.8683
DISEÑO DEL DISIPADOR DE ENERGIA
RAPIDAS ESCALONADAS
UBICACIÓN 3 + 475 : 3 + 600

1+ 100

1 + 096

1.-CALCULO DE LA PENDIENTE MAXIMA :


Qd = 0.100 m^3/s [Caudal de Diseño]
B = 0.600 mts. [Ancho del Canal de Ingraso]
h = 0.700 mts. [Altura del Escalon Asumo]

1
 q 2
 3
Yc = 0.14 mts.
Yc   

 g 

1
h  0,09  h  13
    (h/L) max = 93.97 %
 L  max  Yc 

2.-CALCULO DEL ANCHO MINIMO DE CADA ESCALON :

h= 0.7 mts. [Altura del Escalon Asumo]


(h/L) = 0.94 [Pendiente del Escalon]

h
L L= 0.745 mts.
h 
 
L 

Qd  h 18
b  b= 0.60 mts.
0 ,027  g  L19 ,5
Qd  h 18
b 
0 ,027  g  L19 ,5

3.-DIMENSIONAMIENTO FINAL :

0.7
0.6

0.7
DISEÑO DEL VERTEDERO

DATOS :
Qd = 0.1 m^3/s [Caudal de Diseño] tirante para 0,22 m3/s
Qv = 0.120 m^3/s [Asumo Caudal que se Vierte] 0.34 m
Y= 0.34 mts. [Altura del Canal]
B= 0.70 mts. [Base del Canal] tirante para 0,1 m3/s
n= 0.018 [Coef. de Rugosidad de Mannig] 0.25 m
L= ? mts. [Longitud de la Cresta del Vertedero]
So = 0.003 m/m [Pendiente del Canal]

1.-CALCULO DEL CAUDAL CON TIRANTE NORMAL :

2 1
1
Q   A  R 3  So 2 Q= 0.22 m^3/s
n

2.-VERIFICACION DEL TIPO DE REGIMEN:


Q
q q= 0.314 m^3/s/m
B
1
 q2 3 Yc = 0.216 mts.
Yc   
 g 
Y1 = 0.34 mts. > Yc = 0.216 mts. OK !!!!

3.-DETERMINACION DEL TIRANTE AGUAS ABAJO :


Qmax = 0.100 m^3/s
2 1
1
Q   A  R 3  So 2 Y4 = 0.25 mts.
n
4.-VERIFICACION DEL TIPO DE REGIMEN AGUAS ABAJO DEL VERTEDERO:

Q
q q2 = 0.143 m^3/s/m
B
1
 q2 3
Yc 4    Yc 4 = 0.128 mts.
 g 
Y4 = 0.25 mts. > Yc4 = 0.128 mts. OK !!!!

5.-CALCULO DEL TIRANTE AL COMIENZO DEL VERTEDERO :

E2  E4 V22 V42
Y2   Y4  Y2 = 0.22 mts.
2g 2g
6.-CALCULO DE LA CRESTA DEL VERTEDERO :

Qv = 0.12 m^3/s/m [Caudal que se Vierte]


Cd = 1.9 [Coef. de Descarga 1,9 Borde Rectangular]
s = 0.1
^
 
 y S 
 1 1 
5 Qv Y 4 S
L   
2 3 5
 L 1.77673235 mts.
 Cd*(y1 S)2  y1 S 2 

1 
 1.8
 
 Y4 S  

7.-DIMENSIONAMIENTO FINAL :

0.34 0.25

0.22
DISEÑO DEL SIFON INVERTIDO
UBICACIÓN (1+455 : 1+530 )

DATOS :
Qd = 0.1 m^3/s
B = 0.6 mts.
Y = 0.28 mts.
Cota A = 1274 m.s.n.m.
Cota B = 1257.7 m.s.n.m.
L = 1261.2044 mts. [Longitud de la Tuberia ]
ΔZ = 16.3 mts. [Desnivel entre los Puntos de Entrada y salida]
1.-CALCULO DEL AREA DE LA SECCION TRANSVERSAL DEL DUCTO :

Vd = 2 m/s Velocidad en el Ducto [1,5 - 3 m/s] por norma - pagina 111- pronar

Qd
Ad  Ad = 0.050 m^2
Vd

2.-CALCULO DEL DIAMETRO DE LA TUBERIA :

π  d2
Ad  d= 0.2523 mts.
4
d= 9.9 plg [Asumo] 10.0 pulg
d= 254.000 mm

Q
Vd  Vd = 1.97 m/s
Ad

3.-PERDIDA DE CARGA POR LA REJILLA DE ENTRADA :

eb = 0.0095 mts. [Espesor de las Barras] 3/8"


Sb = 0.04 mts.
Sb = 0.05 mts. [Espaciamiento de las Barras] Asumimos Constructivamente
φ = 75 º [Angulo de inclinacion de la Regilla]
F = 1.79 [Factor de forma]

4
e  Vc 2
3
h r e  F   b    sen φ hre = 0.00341 mts.
 sb  2g

3.-CALCULO DE LA LONGITUD DE TRANSICION :

T D
LT  LT = 0.4177 mts.
2  Tan  α 
LT = 0.5000 mts.

5.-PERDIDA POR TRANSICION EN LA ENTRADA :

Vd = 1.97 m/s [Velocidad en la Tuberia]


Vc = 0.60 m/s [Velocidad en el Canal de Ingreso]

h te 

0,4  Vd 2  Vc 2  hte = 0.07218 mts.
2g

6.-NIVEL DE AGUA SOBRE EL PUNTO B :

Cota : 1274.28 m.s.n.m.

NA B  Cota  h r e  h te NA B = 1274.204 m.s.n.m.

7.-PROYECCION VERTICAL DEL DIAMETRO :

d= 254.000 mm [Diametro del Conducto]


β1 = 5.15 º [Angulo de Inclinacion de la Tuberia de Ingreso]

D
D PE 
cos β 1  D PE = 0.255 mts.

8.-CALCULO DEL PORCENTAJE DE AHOGAMIENTO :

a% = 45 % [Porcentaje de Ahogamiento (10% - 50%)]


NA B = 1274.204 m.s.n.m.
D PE = 0.255 mts.

 a% 
CotaB  NA B  DPE  1  
 100 
 a% 
CotaB  NA B  DPE  1   Cota B = 1274.064 m.s.n.m.
 100 

a  NA B  Cota B  D PE a= 0.115 mts.

9.-PERDIDA POR ENTRADA EN EL DUCTO :

Vd = 1.97 m/s [Velocidad en la Tuberia]


Ke = 0.5 [Coef. de Perdida por Entrada] tabla 8,2-pag113-pronar
aristas con angulos rectos

Vd 2
he  Ke he = 0.099 mts.
2g

10.-PERDIDAS LOCALIZADAS :

Vd = 1.97 m/s
Coeficientes de Perdidas de Carga por Accesorios
K1 = 0.9 [Codos de Radio Corto] n= 7
K2 = 2.5 [Valvula de Retencion] n= 1
K3 = 0.6 [Codos de Radio Largo] n= 1

∑Km = 9.4

Vd 2
hm  k m  2  g ∑hm = 1.866 mts.

11.-PERDIDAS POR FRICCION :

Vd = 1.97 m/s
ε = 1.50E-06 m [Rugosidad Absluta PVC] tabla 8,5 pvc
d = 254.000 mm [Diametro]
T= 15º C [Temperatura del Agua]
ν = 1.15E-06 m^2/s [Viscosidad Cinematica]
Ld = 1261.2044 mts. [Longitud del la Tuberia]

d  Vd
Re  Re = 4.36E+05
ν

 ε 
1  2,51 
 2  Log d   f= 1.36E-02
f  3,71 Re  f 
 
 
 ε 
1  2,51 
 2  Log d  
f  3,71 Re  f 
 
 

Ld  Vd 2
hf  f  hf = 13.405 mts.
d 2g

12.-PERDIDA POR SALIDA :


Vd = 1.97 m/s [Velocidad en el Conducto]
Ve = Vsalida = 0.60 m/s [Velocidad de Salida al Canal]

�_𝐬= (�_�−�_� )
^�/(𝟐∗𝐠) hs = 0.10 mts.

13.-PERDIDA DE CARGA POR REJILLA :

eb = 0.0094 mts. [Espesor de las Barras] 3/8"


Sb = 0.1 mts. [Espaciamiento de las Barras]
φ = 75 º [Angulo de inclinacion de la Regilla]
F = 1.79 [Factor de forma]
Vs = 0.60 m/s [Velocidad de Salida al Canal]

4
e  3 VS 2
h re  F   b    sen φ hre = 0.001 mts.
 sb  2g

14.-PERDIDA DE CARGA TOTAL :

 hT  h re  h te  h e  h f   h m  h s  h r e ∑hT = 15.54 mts.

∑hT = 15.54 mts. < ΔZ = 16.3 mts. Ok !!! Cumple

15.-CALCULO DE LA COTA DE SOLERA :


hT = 15.54 mts. [Perdida total de Carga]
Cota A = 1274 m.s.n.m.

Cota F  Cota A  1,1  hT Cota F = 1256.90 mts.

16.CALCULO DE LA COTA DE SALIDA :


YF = 0.28 mts.
Cota NA F  Cota F  YF  hrs Cota NA F = 1257.18 m.s.n.m.

17.-CALCULO DEL NIVEL DE AGUA EN EL PUNTO E :

Cota NA E  Cota NA F  h S Cota NA E = 1257.28 m.s.n.m.

18.-CALCULO DEL AHOGAMIENTO DE SALIDA :

d= 254 mm

d
as  as = 0.04 mts.
6

19.-CALCULO DE LA COTA DEL PUNTO E :


d= 254 mm
β= 1.92 º [Angulo de Deflexion de Salida del Sifon]

d
Dps 
cos β 
Dps = 0.25 mts.

𝐲−𝐃𝐩𝐬 < �/𝟔


0.03 < 0.0423 Ok !!! Cumple

Cota E  Cota NA E  Dps  as Cota E = 1256.99 m.s.n.m.


DISEÑO DEL PUENTE COLGANTE

Qd 0.1
n 0.01 para PVC
s 0.007
y 0,8*D
d ???

Entrando en el Cuadro 1.1 de la Pag. 26 del Libro Hidraulica de Canales de Maximo Villon

Iterando obtenemos que

D 0.2969 mts.
11.6889764 plg

Asumo 12 plg

y 0.2375 mts.