Tema 1: Circuitos trifásicos
Índice
Sistemas polifásicos
u (t ) = 2 ⋅ U ⋅ cos ω t
u1 (t ) = 2 ⋅ U ⋅ Cos ωt
u2 (t ) = 2 ⋅ U ⋅ Cos (ωt − ϕ )
u3 (t ) = 2 ⋅ U ⋅ Cos (ωt − 2ϕ )
un (t ) = 2 ⋅ U ⋅ Cos (ωt − (n − 1)ϕ )
n ⋅ ϕ = 360º
Generación de sistemas trifásicos
Fase
“Se denomina fase a cada una de las
partes del circuito en la que se genera,
transmite o utiliza una de las tensiones del
sistema”
u1 (t ) = 2 ⋅ U ⋅ Cos ωt
u2 (t ) = 2 ⋅ U ⋅ Cos (ωt − 120)
u3 (t ) = 2 ⋅ U ⋅ Cos (ωt − 240º ) = 2 ⋅ U ⋅ Cos (ωt + 120º )
Generación de sistemas trifásicos
U RN = U∠0º
U SN = U∠ − 120º
U TN = U∠120º
Generación de sistemas trifásicos
Fuentes en estrella
U RN = U∠0º
U SN = U∠ − 120º
U TN = U∠120º
Generación de sistemas trifásicos
Tensiones simples o de fase
“Es la tensión entre los bornes de cada uno de los generadores”
U RN = U∠0º
U SN = U∠ − 120º
U TN = U∠120º
− 1
= U F [1 + 2 cos120] = U F 1 + 2 ⋅ = 0
2
U RN + U SN + U TN = 0
Generación de sistemas trifásicos
Tensiones compuestas o de línea
“Es la tensión entre cada dos fases”
U RS = ?
U ST = ?
U TR = ?
U RS = ?
U ST = ?
U TR = ?
U RS = U RN 3∠30º U RS = U L ∠30º
U ST = U SN 3∠30º ⇒ U ST = U L ∠ − 90º
U TR = U TN 3∠30º U TR = U L ∠150º
U L = 3 ⋅U
Generación de sistemas trifásicos
Fuentes en triángulo
U RS = U∠0º UL =U
U ST = U∠ − 120º
U TR = U∠120º U RN + U SN + U TN = 0
Tema 2: Sistemas equilibrados
Índice
Definiciones
U RS = U L ∠30º
U ST = U L ∠ − 90º
U TR = U L ∠150º
U RN + U SN + U TN = 0
U L = 3 ⋅U
U RS = U∠0º
U ST = U∠ − 120º
U TR = U∠120º
UL =U
Sistemas equilibrados en estrella
Sistemas equilibrados en estrella con neutro
I 1 , I 2 , I 3 corrientes simples o de fase
Z A = Z1 + Z R ; Z B = Z 2 + Z S ; Z C = Z 3 + Z T
Z A = Z B = ZC = Z
U RN + U SN + U TN = 0
U RN + U SN + U TN
U N 'N = Z =0
1 3
+
ZN Z
U NN '
I1 + I 2 + I 3 = I N = =0
ZN
Sistemas equilibrados en estrella
Sistemas equilibrados en estrella sin neutro
U RN U SN U TN
+ +
ZA ZB ZC
U N 'N =
1 1 1 1
+ + +
Z N Z A Z B ZC
Z A = Z B = ZC = Z
U RN + U SN + U TN = 0
U RN U SN U TN
+ + U RN + U SN + U TN
ZA ZB ZC 1ª Ley de Kirchhoff
U N 'N = = Z =0
1 1 1 1 1 3 I1 + I 2 + I 3 = 0
+ + + +
Z N Z A Z B ZC ∞ Z
Sistemas equilibrados en estrella
Sistemas equilibrados en estrella sin neutro
U RN ' U RN U∠0º U
I1 = I R = = = = ∠ −ϕ
ZA ZA Z∠ϕ Z
U SN ' U SN U∠ − 120º U U
I2 = IS = = = = ∠ − 120º −ϕ IL = I ≡
ZB ZB Z∠ϕ Z Z
U TN ' U TN U∠120º U
I 3 = IT = = = = ∠120º −ϕ
ZC ZC Z∠ϕ Z
Sistemas equilibrados en estrella
Sistemas equilibrados en estrella (resumen)
U N 'N = 0
U RN + U SN + U TN = 0
I1 + I 2 + I 3 = I N = 0
U R 'N ' + U S 'N ' + U T 'N ' = 0
U
I1 = I R = ∠ −ϕ
U N 'N = 0 Z
U
I 2 = I S = ∠ − 120º −ϕ
I1 + I 2 + I 3 = 0 Z
U
I 3 = I T = ∠120º −ϕ
Z
Sistemas equilibrados en estrella
Ejemplo: en el sistema de la figura se sabe que la tensión de línea en la carga es 380 V.
La carga de cada fase es 10∟45ºΩ, la impedancia de línea es ZL=(1+j)Ω/fase y la
secuencia de fases es directa (R-S-T). Tomando como referencia UR’N’ en la carga,
determinar:
U RS = U RN 3∠30º = 434.9∠30º
U TR = U TN 3∠30º = 434.9∠150º
Sistemas equilibrados en estrella
Ejemplo: en el sistema de la figura se sabe que la tensión de línea en la carga es 380 V.
La carga de cada fase es 10∟45ºΩ, la impedancia de línea es ZL=(1+j)Ω/fase y la
secuencia de fases es directa (R-S-T). Tomando como referencia UR’N’ en la carga,
determinar:
U RS = U RN 3∠30º = 434.9∠30º
U ST = U SN 3∠30º = 434.9∠ − 90º
U TR = U TN 3∠30º = 434.9∠150º
I R + I S + IT = 0
I R = I R2 'S ' + I T2'R ' − 2 ⋅ I R 'S ' ⋅ I T 'R ' cos(I R 'S ' , I T 'R ' )
2
−1
I L2 = 2 ⋅ I 2 − 2 ⋅ I 2 cos(120º ) = 2 ⋅ I 2 − 2 ⋅ I 2 ⋅ = 3⋅ I 2
IR ≡ IL 2
Z A = Z1 + Z R ; Z B = Z 2 + Z S ; Z C = Z 3 + Z T
U RN U SN U TN
+ +
ZA ZB ZC
U N 'N =
1 1 1 1
+ + +
Z N Z A Z B ZC
U RN U SN U TN U RN U SN U TN
+ + + +
ZA ZB ZC ZA ZB ZC
U N 'N = = =0
1 1
+ +
1
+
1 ∞
0 Z A Z B ZC
I1 + I 2 + I 3 = I N ≠ 0
Sistemas desequilibrados en estrella
U RN U SN U TN
+ +
ZA ZB ZC
U N 'N =
1 1 1 1
+ + +
Z N Z A Z B ZC
U RN U SN U TN U RN U SN U TN
+ + + + 1ª Ley de Kirchhoff
ZA ZB ZC ZA ZB ZC
U N 'N = = ≠0
1 1 1 1 1 1 1 I1 + I 2 + I 3 = 0
+ + + + +
∞ Z A Z B ZC Z A Z B ZC
Sistemas desequilibrados en estrella
Ejemplo: se dispone de la red de la figura, cuyos valores son: tensión de línea del
generador 230V; ZL=ZN=10 Ω; ZR=20j Ω; ZS=-10j Ω; ZT=15 Ω.
10.1∠ − 76.03º
U N 'N = = 48∠ − 78.77 º
0.21∠2.73º
Sistemas desequilibrados en estrella
Ejemplo: se dispone de la red de la figura, cuyos valores son: tensión de línea del
generador 230V; ZL=ZN=10 Ω; ZR=20j Ω; ZS=-10j Ω; ZT=15 Ω.
U RN = 132.8∠0º V
Recordamos: U SN = 132.8∠ − 120º V
U TN = 132.8∠120º V
Sistemas desequilibrados en estrella
Ejemplo: se dispone de la red de la figura, cuyos valores son: tensión de línea del
generador 230V; ZL=ZN=10 Ω; ZR=20j Ω; ZS=-10j Ω; ZT=15 Ω.
U RN ' 132.8∠0º
I1 = = = 5.94∠ − 63.43º A
Z L + Z R 22.36∠63.43º
U TN ' 132.8∠120º
I3 = = = 5.31∠120º A
Z L + ZT 25∠0º
Sistemas desequilibrados en estrella
Ejemplo: se dispone de la red de la figura, cuyos valores son: tensión de línea del
generador 230V; ZL=ZN=10 Ω; ZR=20j Ω; ZS=-10j Ω; ZT=15 Ω.
Z1 ⋅ Z 3 Z1 ⋅ Z 2 Z 2 ⋅ Z3
Z1 ' = Z2 ' = Z3 ' =
Z1 + Z 2 + Z 3 Z1 + Z 2 + Z 3 Z1 + Z 2 + Z 3
U RN U SN U TN U RN U SN U TN
+ + + +
ZA ZB ZC ZA ZB ZC
U N 'N = =
1 1 1 1 1 1 1
+ + + + +
∞ Z A Z B ZC Z A Z B ZC
U RN − U N ' N = U RN ' I R = U RN ' / Z A U R 'S ' = U R ' N ' − U S ' N ' = I R Z '1 − I S Z ' 2
U SN − U N ' N = U SN ' ⇒ I S = U SN ' / Z B U S 'T ' = U S ' N ' − U T ' N ' = I S Z ' 2 − I T Z '3
U TN − U N ' N = U TN ' I T = U TN ' / Z C U T ' R ' = U T ' N ' − U R ' N ' = I T Z '3 − I R Z '1
Sistemas desequilibrados en triángulo
Tensiones en la carga
I R 'S ' = U R 'S ' / Z R 'S '
I S 'T ' = U S 'T ' / Z S 'T '
I T 'R' = U T 'R ' / Z T 'R '
Potencia
Medida de potencia
El generador sólo proporcionará la potencia total demandada por todas las cargas.
Esto quiere decir que el balance energético se podría analizar desde el consumo en
vez del suministro.
Sea un sistema polifásico de p-hilos (n<p), siendo r el hilo de referencia al que están
conectadas todas las cargas, la potencia aparente total será:
S T = S1 + S 2 + + S n = U 1r I 1* + U 2 r I 2* + + U nr I n* (n sumandos)
S 3 = U RN I R* + U SN I S* + U TN I T* (3 sumandos)
Potencia en sistemas trifásicos
Definición de potencia
S = U RN I R* + U SN I S* + U TN I T* ≡ P + jQ
{ } { } {
P = Re U RN I R* + Re U SN I S* + Re U TN I T* }
{ } { } {
Q = Im U RN I R* + Im U SN I S* + Im U TN I T* }
P = PR + PS + PT
Q = QR + QS + QT
S = P2 + Q2
Potencia en sistemas trifásicos
Definición de potencia
Trifásico a tres hilos
S = U RT I R* + U ST I S*
Demostración:
S = U RS I RS
*
+ U ST I ST
*
+ U TR I TR
*
= (−U ST − U TR ) I RS
*
+ U ST I ST
*
+ U TR I TR
*
= (U RT − U ST ) I RS
*
+ U ST I ST
*
+ U TR I TR
*
=
U RS + U ST + U TR = 0
= (U RT − U ST ) I RS
*
+ U ST I ST
*
− U RT I TR
*
= U RT ( I RS
*
− I TR
*
) + U ST ( I ST
*
− I RS
*
) = U RT ( I RS − I TR )* + U ST ( I ST − I RS )* =
= U RT I R * + U ST I S *
Potencia en sistemas trifásicos
Potencia de sistemas equilibrados
Cargas en estrella
P = P + P + P = 3 U I cos ϕ
R S T
Q = QR + QS + QT = 3 U I senϕ
S = P 2 + Q 2 = 3 ⋅U I
IL = I
U L = 3 ⋅U
UL
P = 3⋅ I L cos ϕ = 3 ⋅ U L I L cos ϕ
3
Q = 3 ⋅ U L I L senϕ
S = 3 ⋅U L I L
Potencia en sistemas trifásicos
Potencia de sistemas equilibrados
Cargas en triángulo
P = 3 ⋅ U I cos ϕ
Q = 3 ⋅ U I senϕ
S = P 2 + Q 2 = 3 ⋅U I
UL =U
IL = 3 ⋅ I
IL
P = 3 ⋅U L cos ϕ = 3 ⋅ U L I L cos ϕ
3
Q = 3 ⋅ U L I L senϕ
S = 3 ⋅U L I L
Potencia en sistemas trifásicos
Potencia de sistemas equilibrados
P = 3 ⋅ U I cos ϕ = 3 ⋅ U L I L cos ϕ
Q = 3 ⋅ U I senϕ = 3 ⋅ U L I L senϕ
S = 3 ⋅U I = 3 ⋅U L I L
Potencia en sistemas trifásicos
Potencia de sistemas desequilibrados
Cargas en estrella
Z R = RR + jX R = Z R ∠ϕ R
Z S = RS + jX S = Z S ∠ϕ S
Z T = RT + jX T = Z T ∠ϕ T
PR = U RN I R cos ϕ R = R R I R2
PS = U SN I S cos ϕ S = RS I S2
PT = U TN I T cos ϕ T = RT I T2
QR = U RN I R senϕ R = X R I R2
QS = U SN I S senϕ S = X S I S2
QT = U TN I T senϕ T = X T I T2
Potencia en sistemas trifásicos
Potencia de sistemas desequilibrados
Cargas en estrella
P = PR + PS + PT
Q = QR + QS + QT
S = P2 + Q2
S = S R + S S + ST
Q
tan ϕ =
cos ϕ ⇒ P
P
cos ϕ =
S
Potencia en sistemas trifásicos
Potencia de sistemas desequilibrados
Cargas en triángulo Z = R RS + jX RS = Z RS ∠ϕ RS
RS
Z ST = RST + jX ST = Z ST ∠ϕ ST
Z TR = RTR + jX TR = Z TR ∠ϕ TR
PRS = U RS I RS cos ϕ RS = RRS I RS
2
QRS = U RS I RS senϕ RS = X RS I RS
2
QST = U ST I ST senϕ ST = X ST I ST
2
QTR = U TR I TR senϕ TR = X TR I TR
2
Potencia en sistemas trifásicos
Potencia de sistemas desequilibrados
Cargas en triángulo
P = UI cos ϕ = U ⋅ I
“La potencia activa se puede
expresar como un producto
escalar de dos vectores”
P = ∑ Pk
Medida de potencia
Potencia activa
Sistema equilibrado con neutro
P = ∑ Pk
P = 3W
Medida de potencia
Potencia activa
Sistema desequilibrado con neutro
P = ∑ Pk
P = W1 + W2 + W3
Medida de potencia
Potencia activa
Sistema equilibrado sin neutro
P = ∑ Pk P = 3W
Medida de potencia
Potencia activa
Sistema desequilibrado sin neutro
Para cargas en triángulo y estrella se conectan 3 vatímetros
P = ∑ Pk P = W1 + W2 + W3
Si el neutro no es accesible se crea un neutro artificial
P = W1 + W2 + W3
Medida de potencia
Potencia activa
Método de Aron (método de los dos vatímetros)
Para sistemas sin neutro (equilibrados y desequilibrados)
P = W1 + W2
Medida de potencia
Potencia activa
Método de Aron (método de los dos vatímetros)
Demostración (para sistemas equilibrados):
(clase 9ª pag.4)
W1 = U RT ⋅ I R = U L I L cos(30 − ϕ )
W2 = U ST ⋅ I S = U L I L cos(30 + ϕ )
W1 + W2 = U L I L [cos(30 − ϕ ) + cos(30 + ϕ )] =
= U L I L 2 ⋅ cos 30 cos ϕ = 3U L I L cos ϕ
P = W1 + W2 = 3U L I L cos ϕ
Medida de potencia
Potencia reactiva
Medida con varímetros
W1 = U RT ⋅ I R = U L I L cos(30 − ϕ )
⇒ W1 − W2 = U L I L senϕ ⇒
W2 = U ST ⋅ I S = U L I L cos(30 + ϕ )
⇒ Q = 3 (W1 − W2 )
Medida de potencia
Potencia reactiva (EQUILIBRADOS)
Medida con dos vatímetros: método de Aron
Q = 3 (W1 − W2 ) Q 3 (W1 − W2 )
⇒ tan ϕ = =
P = W1 + W2 P W1 + W2
Medida de potencia
Potencia reactiva (EQUILIBRADOS)
Medida con dos vatímetros: método de Aron
Q = 3 (W1 − W2 )
P = W1 + W2
Medida de potencia
Potencia reactiva (DESEQUILIBRADOS)
Medida con tres vatímetros
W1 + W2 + W3
Q=
3
Medida de potencia
Ejemplo: se dispone de una red trifásica cuya tensión de línea es de 380 V a la que hay
tres cargas equilibradas:
Determinar la lectura de los dos vatímetros que midan correctamente las potencias
activa y reactiva absorbidas por la instalación
736 ⋅10
P1 = = 8652.9 W
0.85
P2 = 6000 W P = 27152.9 W
10000
P3 = = 12500 W
0.80
Medida de potencia
Ejemplo: se dispone de una red trifásica cuya tensión de línea es de 380 V a la que hay
tres cargas equilibradas:
Determinar la lectura de los dos vatímetros que midan correctamente las potencias
activa y reactiva absorbidas por la instalación
Determinar la lectura de los dos vatímetros que midan correctamente las potencias
activa y reactiva absorbidas por la instalación
P = 27152.94 W
Q = 13565.81 VAr
P = W1 + W2 W1 = 17492.6 W
⇒
Q = 3 (W1 − W2 ) W2 = 9660.4 W
Corrección del factor de potencia
Batería de condensadores en estrella
cos ϕ 2
QC = P ⋅ [tan ϕ1 − tan ϕ 2 ]
QC = 3 ⋅ U L I RC
P = 3 ⋅ U L I R1 cos ϕ1
3 ⋅ U L I RC = 3 ⋅ U L I R1 cos ϕ1 [tan ϕ1 − tan ϕ 2 ]
I RC = I R1 cos ϕ1 [tan ϕ1 − tan ϕ 2 ]
Corrección del factor de potencia
Batería de condensadores en estrella
cos ϕ 2
U L2
QC = 3Qc = 3 ⋅ U ωC = 3 ⋅
2
ωC = U L2ωC
3
Q 3 ⋅ U L I RC 3 ⋅ I RC I RC IC
C = 2C = = = ≡
U Lω U L2ω U Lω Uω Uω
IC
CΥ =
Uω
Corrección del factor de potencia
Batería de condensadores en triángulo
U
QC = 3Qc = 3 ⋅ UI C sen 90º = 3 ⋅ UI C = 3 ⋅ U = 3 ⋅ U L2ωC
XC
QC
QC = 3 ⋅ U L2ωC ∆ ⇒ C ∆ =
3 ⋅ U L2ω
QC 13507.64
C∆ = = = 99.25µF
3 ⋅ U Lω 3 ⋅ 380 ⋅ 2π ⋅ 50
2 2
P = 27151.45 W 27151.45 = W1 + W2
Q = 13507.64 VAr 13507.64 = 3 (W1 − W2 )
Corrección del factor de potencia
Ejemplo: Calcular la potencia reactiva y capacidad por fase de una batería de
condensadores, conectados en triángulo, para que eleve el factor de potencia a la
unidad, así como la lectura de los vatímetros que midan correctamente las potencias
activa y reactiva de una instalación trifásica equilibrada.
Datos: P=27151.45 W; UL=380 V; cosφ1=0.895.
P = 27151.45 W 27151.45 = W1 + W2
Q = 13507.64 VAr 13507.64 = 3 (W1 − W2 )
W1 = 17475.04 W
W2 = 9676.40 W
Corrección del factor de potencia
Ejemplo: Calcular la potencia reactiva y capacidad por fase de una batería de
condensadores, conectados en triángulo, para que eleve el factor de potencia a la
unidad, así como la lectura de los vatímetros que midan correctamente las potencias
activa y reactiva de una instalación trifásica equilibrada.
Datos: P=27151.45 W; UL=380 V; cosφ1=0.895.
P = 27151.45 W 27151.45 = W1 + W2
Q = 0 VAr 0 = 3 (W1 − W2 )
W1 = 13575.73 W
W2 = 13575.73 W
Bibliografía
1. F. Aznar, A. Espín y F. Gil. “Electrotecnia básica para ingenieros”. 2ª Ed. Universidad
de Granada, 2012.
2. J. Fraile Mora. “Electromagnetismo y circuitos eléctricos”. 4ª Ed. McGraw-Hill, 2005.
3. A. Pastor Gutiérrez, J. Ortega Jiménez, V. M. Parra Prieto y A. Pérez Coyto.
“Circuitos Eléctricos” Vol. I. Editorial de la Universidad Nacional de Educación a
Distancia, 2005.
4. J. Fraile Mora. “Problemas de circuitos eléctricos”. Pearson, 2013.
5. M. R. Spiegel, L. Abellanas. “Fórmulas y tablas de matemática aplicada”. McGraw-
Hill, 1997.